Professional Documents
Culture Documents
Kirloskar KG645 - User Manual For Genset Controller PDF
Kirloskar KG645 - User Manual For Genset Controller PDF
KG645
Kirloskar
Genset Controller
User Manual
www.kirloskar.com
Page 1 of 123
KG645 CONTROLLER MANUAL
Table of Contents
KG-645 Genset Controller
1 Introduction ..................................................................................................................................... 5
1.1 Key Highlights of the Product ............................................................................................................................ 5
2 Specifications ................................................................................................................................... 6
2.1 Terminals............................................................................................................................................................ 6
2.2 Power Supply Specifications .............................................................................................................................. 7
3 Inputs .............................................................................................................................................. 8
3.1 Generator Voltages And Frequency Measurements.......................................................................................... 8
3.2 Generator Current Measurement ...................................................................................................................... 8
3.3 Mains Voltage And Frequency Measurements .................................................................................................. 8
3.4 Digital Inputs ...................................................................................................................................................... 9
3.5 Analogue Inputs ...............................................................................................................................................10
3.6 Sensor Common...............................................................................................................................................11
3.7 Magnetic Pick Up Input....................................................................................................................................11
3.8 D+ Charge Alt ...................................................................................................................................................12
4 Outputs.......................................................................................................................................... 12
4.1 Digital Outputs .................................................................................................................................................12
4.2 Actuator Outputs .............................................................................................................................................13
5 Communication Ports ..................................................................................................................... 13
6 Installation ..................................................................................................................................... 14
6.1 Dimensions ......................................................................................................................................................14
6.2 Mounting on panel ..........................................................................................................................................15
6.3 Terminal Description ........................................................................................................................................16
6.4 Typical Wiring Diagram ....................................................................................................................................18
7 Module Display .............................................................................................................................. 20
7.1 Power on screen ..............................................................................................................................................20
7.2 Monitoring Mode.............................................................................................................................................20
8 Description of Control keys ............................................................................................................. 27
8.1 Mode Selection diagram ..................................................................................................................................27
8.2 Functions of Control keys.................................................................................................................................28
9 Configuration Mode ....................................................................................................................... 29
9.1 Configurable Parameters .................................................................................................................................30
10 Module Operation in Manual Mode……………………………………………………….…………………………………….46
11 Module Operation in Auto Mode .................................................................................................. 46
11.1 Auto Mains Failure (AMF) ..............................................................................................................................46
11.2 Remote start/stop ..........................................................................................................................................47
12 Paralleling support / Speed bias mode .......................................................................................... 47
12.1 Paralleling concept.........................................................................................................................................47
12.2 Configuration in KG-645.................................................................................................................................48
13 Module Operation In Test Mode ................................................................................................... 49
14 Deep Sleep Mode ......................................................................................................................... 49
15 Alarms ......................................................................................................................................... 49
16 Troubleshooting ........................................................................................................................... 53
Communication Protocol
17 Introduction ................................................................................................................................. 56
18 MODBUS Based Protocol .............................................................................................................. 56
18.1 Connection Details .........................................................................................................................................56
18.2 Supported Functions......................................................................................................................................56
Page 2 of 123
KG645 CONTROLLER MANUAL
Expansion Module
19 Introduction ................................................................................................................................. 66
19.1 Expansion Module Integration ......................................................................................................................67
KG-645 – Configuration Utility
20 Introduction ................................................................................................................................. 68
21 Installation Instructions ................................................................................................................ 68
21.1 System Requirements ....................................................................................................................................68
21.2 Installation Process for KG 645 - Configuration Utility...................................................................................68
21.3 Installation Process for USB Driver ................................................................................................................69
22 Usage Instructions ........................................................................................................................ 75
22.1 Starting with KG 645 - Configuration Utility ..................................................................................................75
22.2 Working with KG 645 - Configuration Utility .................................................................................................76
22.3 Establishing Connection with Controller .......................................................................................................76
22.4 Editing Parameters .........................................................................................................................................76
22.5 Tools ...............................................................................................................................................................77
23 Interpretation of Parameters ........................................................................................................ 83
23.1 Module...........................................................................................................................................................83
23.2 Digital Inputs ..................................................................................................................................................85
23.3 Analog Inputs .................................................................................................................................................87
23.4 Outputs ..........................................................................................................................................................94
23.5 Timers ............................................................................................................................................................97
23.6 Generator.....................................................................................................................................................100
23.7 Mains ...........................................................................................................................................................105
23.8 Engine ..........................................................................................................................................................107
23.9 Maintenance ................................................................................................................................................112
23.10 Rotary Actuator..........................................................................................................................................113
23.11 Expansion Module .....................................................................................................................................117
KG-645 – EOL Flashing Utility
24 Menu Bar ................................................................................................................................... 121
25 Writing Configuration To Device.................................................................................................. 122
Page 3 of 123
KG645 CONTROLLER MANUAL
Page 4 of 123
KG645 CONTROLLER MANUAL
1 Introduction
This document presents information necessary for operating KOEL's KG-645 genset controller. It also provides
the user with the necessary background for using KG-645 genset controller in an application that involves
communication of the genset controller with an external system such as a server or a remote data
communication system.
KOEL's KG-645 is a modern and feature rich genset controller with user-friendly HMI and full graphics LCD. The
KG-645 controller comes bundled with highly versatile software & extensive I/O's and thereby supports a wide
variety of industry standard features in diesel/gasoline engine gensets. The KG-645 controller's smart software
offers flexibility to configure each individual input and output for a specific function or application. KG-645
controller also offers unique feature such as electronic governing for engines with mechanical fuel systems. With
the Rotary Actuator as an add-on for air/fuel charge control, these controllers can subsume the electronic
governing duty for the engine and offer tight speed governing performance. The KG-645 can be configured
through Windows PC utility (Refer section KG 645 - Configuration Utility). Also, all parameters can be configured
using the keypad of the genset controller.
Page 5 of 123
KG645 CONTROLLER MANUAL
2 Specifications
2.1 Terminals
The KG-645 hosts two types of terminal blocks as shown in figure 3 and figure 4 below.
Connector type/ Male (On genset Female (Mating) Male (On genset Female (Mating)
Manufacturer controller) controller)
Degson Phoenix
(Degson Electronics Co. Ltd.) (Phoenix Contact (I) Pvt. Ltd.)
2-Pin 2EDGVC-5.08-02P-14- 2EDGK-5.08-02P-14- 1755516 1754449
00AH 00AH
4-Pin 2EDGVC-5.08-04P-24- 2EDGK-5.08-04P-24- NA NA
00AH 00AH
Figure 4: Representative photograph for 8-pin female (mating) connector of 3.5 mm pitch
Page 6 of 123
KG645 CONTROLLER MANUAL
Connector type/ Male (On genset Female (Mating) Male (On genset Female (Mating)
Manufacturer controller) controller)
Degson Phoenix
(Degson Electronics Co. Ltd.) (Phoenix Contact (I) Pvt. Ltd.)
4-Pin 15EDGVC-3.5-04P-14- 15EDGK-3.5-04P-14- 1843622 1840382
00AH 00AH
6-Pin 15EDGVC-3.5-06P-14- 15EDGK-3.5-06P-14- 1843648 1840405
00AH 00AH
8-Pin 15EDGVC-3.5-08P-14- 15EDGK-3.5-08P-14- 1843664 1840421
00AH 00AH
10-Pin 15EDGVC-3.5-10P-14- 15EDGK-3.5-10P-14- 1843680 1840447
00AH 00AH
3 Inputs
Page 7 of 123
KG645 CONTROLLER MANUAL
For 1 phase genset application, it is mandatory to connect the genset phase and
neutral cables to the genset controller's phase R and Neutral terminals respectively.
Page 8 of 123
KG645 CONTROLLER MANUAL
For 1 phase application, it is mandatory to connect the mains phase and neutral
cables to the genset controller's phase R and Neutral terminals respectively.
Page 9 of 123
KG645 CONTROLLER MANUAL
This input can be configured to accept input from lube oil pressure sensor or canopy temperature sensor or lube
oil temperature sensor.
Page 10 of 123
KG645 CONTROLLER MANUAL
While generating genset paralleling application, this input can be configured to accept a 0-5 V-DC speed bias signal
generated by a load sharing module (LSM).
Important Note: The sensor common point (SCP) terminal (Pin # 41) should be directly connected
to the point of engine body which is a common reference point for all the analog sensors. The wire
used for the SCP connection should not be shared with any other connection. The SCP connection
should not be taken from genset control panel ground because this will let sharing of it with other
connections. The connection should be done with a single wire being connected from pin# 41 to
the engine body.
Page 11 of 123
KG645 CONTROLLER MANUAL
The Magnetic Pick Up (MPU) is an inductive sensor fitted on the engine flywheel for the engine speed sensing. The output
of MPU is a sine-wave signal.
4 Outputs
Page 12 of 123
KG645 CONTROLLER MANUAL
Actuator outputs are used only for rotary Actuator, if installed. The rotary Actuator is a 4-wire actuator that is
used for creating an electronic governing application in case of a mechanical fuel system engine. In diesel engines,
the rotary Actuator's shaft output gets mechanically connected to the stop lever or the throttle lever of an in-
line or rotary fuel injection pump. In case of petrol or natural gas engines, the rotary Actuator's shaft output gets
connected to the throttle/charge control valve.
Figure 5: Representing Actuator connector pin out when viewed from the terminal insertion side
The following table provides the connection details while connecting Actuator with KG-645 controller.
5 Communication Ports
Used to flash the firmware
USB USB 2.0 Type B for connection between controller and PC running KG
645 - Configuration Utility
RS485 Used for data communication
Controller terminal number for 15, 16
RS485
Used for communication between controller and the input/output
CAN expansion module* (Refer section 18)
Controller terminal number for CAN 13, 14
For further details please refer section Communication Protocol For KG-645 (section 16).
Page 13 of 123
KG645 CONTROLLER MANUAL
6 Installation
6.1 Dimensions
Figure 6: Dimensions of the KG-645 genset controller
Recommended mounting panel cut-out dimensions: 118 mm X 93 mm
Page 14 of 123
KG645 CONTROLLER MANUAL
Figure 7: Representative drawing of Fixing clip and screw supplied along with controller
Figure 8: Representative drawing of controller mounting on the panel using the fixing clips
• Insert the fixing clip into the slot provided on the side of the controller.
• Pull the fixing clips backwards (towards the back of the module). Ensure that the fixing clip is properly
fitted inside the slot provided on the controller.
• Fix the screws and tighten the screw (turn clockwise) to mount the controller properly into the panel.
Ensure that the screw will be always perpendicular to the panel surface. The maximum tightening torque
is 0.19 N-m.
Page 15 of 123
KG645 CONTROLLER MANUAL
Page 16 of 123
KG645 CONTROLLER MANUAL
Page 17 of 123
KG645 CONTROLLER MANUAL
Figure 10: Representative drawing of KG-645 genset controller when used in the 3-phase Manual Control Panel
Page 18 of 123
KG645 CONTROLLER MANUAL
1-phase Manual Control Application on engine with Analog current LOP sensor configuration and Analog resistive
CANOPY Temperature sensor configuration.
Figure 13: Representative drawing of KG-645 genset controller when used in the 1-phase Manual Control Panel
Page 19 of 123
KG645 CONTROLLER MANUAL
7 Module Display
Following section describes the layout of screens.
Generator screens
Mains screens
Engine screens
Page 20 of 123
KG645 CONTROLLER MANUAL
Test mode
Off mode
Page 21 of 123
KG645 CONTROLLER MANUAL
(This screen will be visible in Auto mode) (This screen will be visible in Manual mode)
(This screen will be visible in Manual mode) (This screen will be visible in Manual mode)
Page 22 of 123
KG645 CONTROLLER MANUAL
(This screen will be visible only if output related to genset (The “Y” and “B” phase will be visible only if config-
and mains contactor are configured) ured for 3 phase genset)
(The “Y” and “B” phase will be visible only if configured (The “Y” and “B” phase will be visible only if config-
for 3 phase genset) ured for 3 phase genset)
Screen 17: GENERATOR KVAr LOAD Screen 18: GENERATOR POWER FACTOR
(The “Y” and “B” phase will be visible only if configured (The “Y” and “B” phase will be visible only if config-
for 3 phase genset) ured for 3 phase genset)
Page 23 of 123
KG645 CONTROLLER MANUAL
MAINS SCREENS
Screen 21: MAINS Screen 22: MAINS
(This screen will be visible if “Mains monitoring” is enabled and mains is not available or unhealthy. The “Y” &
“B” phase will be visible only if configured for 3 phase mains. )
Page 24 of 123
KG645 CONTROLLER MANUAL
ENGINE SCREENS
Screen 24: ENGINE BATTERY Screen 25: CANOPY TEMPERATURE
Screen 26: ENGINE TEMPERATURE Screen 27: ENGINE LUB OIL PRESSURE
(This screen will be visible only if “Engine tempera- (This screen will be visible only if “Lube Oil Pressure”
ture” sensor is configured) sensor is configured)
Screen 28: ENGINE REMAINING FUEL Screen 29:EXPANSION MODULE ANALO SENSOR 1
(This screen will be visible only if “Fuel Level” sensor (This screen will be visible only if Expansion module is
is configured) enabled and
“AN EX-S1” is configured as “Pressure Sensor”)
Page 25 of 123
KG645 CONTROLLER MANUAL
(This screen will be visible only if “Lube Oil Temperature” sensor is configured)
Page 26 of 123
KG645 CONTROLLER MANUAL
Menu
Navigation
UP key
Menu
Navigation AUTO/MANU
DOWN key AL/
TEST mode
select key
STOP key
START key
Page 27 of 123
KG645 CONTROLLER MANUAL
Page 28 of 123
KG645 CONTROLLER MANUAL
9 Configuration Mode
To configure the controller please follow the below mentioned instructions.
Enter into the configuration mode (Refer section 8).
Screen 34: Configuration Mode Screen 35: Configuration mode: Authentication Page
To enter into edit mode press “START” key. If you wish to read the configuration press “STOP” key.
To access the configuration menu, please enter your 4-Digit PIN here using ''Navigation UP/DOWN” keys. Once
you enter into the “EDIT” mode scroll to the parameter that you wish to edit and press “START” key to edit the
parameter. At this moment the parameter will start blinking and you can change the parameter value using “UP”
and “DOWN” keys (Refer section 9.1 for configuring parameters).
After selecting the required value press “START” key to save parameter or “STOP” key to discard the value. After
completion of parameter configuration, exit from configuration mode. Before existing from configuration mode
controller will show you the following screen.
Page 29 of 123
KG645 CONTROLLER MANUAL
Page 30 of 123
KG645 CONTROLLER MANUAL
Level 0 Level 1 (On screen) Level 2 (On screen) Possible Value (On screen)
DIG IN D Source (SOURCE) Refer Table 2
Polarity (POLARITY) Close To Activate, Open To
Activate
Action (ACTION) None, Warning, Electrical Trip,
Shutdown
Activation (ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
Activation delay (ACTIVATION DELAY) 1 – 60 sec
DIG IN E Source (SOURCE) Refer Table 2
Polarity (POLARITY) Close To Activate, Open To
Activate
Action (ACTION) None, Warning, Electrical Trip,
Shutdown
Activation (ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
Activation delay (ACTIVATION DELAY) 1 – 60 sec
ENG TEMP/DIG G Sensor selection (SENSOR SELECTION) Not used, Dig In G, Anlg In Eng
Temp
(Digital) Source ((DIG) SOURCE) Refer Table 2
(Digital) Polarity ((DIG) POLARITY) Close To Activate, Open To
Activate
(Digital) Action ((DIG) ACTION) None, Warning, Electrical Trip,
Shutdown
(Digital) Activation ((DIG) ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
(Digital) Activation delay ((DIG) 1 – 60 sec
ACTIVATION DELAY)
Shutdown (SHUTDOWN) Disable, Enable
Shutdown threshold (SHUTDOWN 26 – 200 °C
THRESHOLD)
Warning (WARNING) Disable, Enable
Warning threshold (WARNING 25 – 199 °C
THRESHOLD)
Open circuit alarm (OPEN CKT ALARM) None, Warning, Electrical Trip,
Shutdown
Engine Temperature Sensor Calibration Refer Table 3
Fuel LVL/DIG H Sensor selection (SENSOR SELECTION) Not used, Dig In H, Anlg In Fuel
LVL
(Digital) Source ((DIG) SOURCE) Refer Table 2
(Digital) Polarity ((DIG) POLARITY) Close To Activate, Open To
Activate
(Digital) Action ((DIG) ACTION) None, Warning, Electrical Trip,
Page 31 of 123
KG645 CONTROLLER MANUAL
Level 0 Level 1 (On screen) Level 2 (On screen) Possible Value (On screen)
Shutdown
(Digital) Activation ((DIG) ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
(Digital) Activation delay ((DIG) 1 – 60 sec
ACTIVATION DELAY)
Shutdown (SHUTDOWN) Disable, Enable
Shutdown threshold (SHUTDOWN 0 – 50 %
THRESHOLD)
Warning (WARNING) Disable, Enable
Warning threshold (WARNING 2 – 55 %
THRESHOLD)
Fuel tank capacity (FUEL TANK CAPACITY) 0 – 1000 Litres
Fuel theft alarm (FUEL THEFT ALARM) Disable, Enable
Fuel theft threshold (FUEL THEFT 0 – 100 % per hour
THRESHOLD)
Fuel Consumption (FUEL CONSUMPTION) 0.0 – 100.0 Litres per hour
Fuel in liters (FUEL IN LITERS) Disable, Enable
Fuel Level Sensor Calibration Refer Table 4
Analog Sensor S1 Sensor selection (SENSOR SELECTION (pin Not used, LOP Sensor
(AN S1 (4 to 20 23))
mA))
Shutdown (SHUTDOWN) Disable, Enable
Shutdown threshold (SHUTDOWN 0.0 – 4.8 Bar
THRESHOLD)
Warning (WARNING) Disable, Enable
Warning threshold (WARNING 0.2 – 5.0 Bar
THRESHOLD)
Circuit fault alarm (CKT FAULT ALARM) None, Warning, Electrical Trip,
Shutdown
LOP (4 to 20mA) Sensor Calibration Refer Table 5
Analog Sensor S2 Sensor selection (SENSOR SELECTION (pin Not used, Dig In F, Anlg In
(AN S2 RES/DIG F) 26)) Canopy Temp, Anlg In Lube Oil
Temp, Anlg In LOP
(Digital) Source ((DIG) SOURCE) Refer Table 2
(Digital) Polarity ((DIG) POLARITY) Close To Activate, Open To
Activate
(Digital) Action ((DIG) ACTION) None, Warning, Electrical Trip,
Shutdown
(Digital) Activation ((DIG) ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
(Digital) Activation delay ((DIG) 1 – 60 sec
ACTIVATION DELAY)
Shutdown (SHUTDOWN) Disable, Enable
Page 32 of 123
KG645 CONTROLLER MANUAL
Level 0 Level 1 (On screen) Level 2 (On screen) Possible Value (On screen)
Shutdown threshold (SHUTDOWN 0.0 – 4.8 Bar (for LOP) /
THRESHOLD) 26 – 200 °C (for Canopy Temp
/ Lube Oil Temp)
Warning (WARNING) Disable, Enable
Warning threshold (WARNING 0.0 – 5.0 Bar (for LOP) /
THRESHOLD) 25 – 199 °C (for Canopy Temp /
Lube Oil Temp)
Open circuit alarm (OPEN CKT ALARM) None, Warning, Electrical Trip,
Shutdown
Canopy Temp Sensor Calibration/Lube Oil Refer Table 6
Temperature Sensor Calibration
LOP (Resistive) Sensor Calibration Refer Table 7 (for LOP)
Outputs OUT A Source (SOURCE) Refer Table 8
On activation (ON ACTIVATION) De-energise, Energise
OUT B Source (SOURCE) Refer Table 8
On activation (ON ACTIVATION) De-energise, Energise
OUT C Source (SOURCE) Refer Table 8
On activation (ON ACTIVATION) De-energise, Energise
OUT D Source (SOURCE) Refer Table 8
On activation (ON ACTIVATION) De-energise, Energise
OUT E Source (SOURCE) Refer Table 8
On activation (ON ACTIVATION) De-energise, Energise
OUT F Source (SOURCE) Refer Table 8
On activation (ON ACTIVATION) De-energise, Energise
Timers Cranking timer Crank hold time (CRANK HOLD TIME) 1 – 15 sec
Crank rest time (CRANK REST TIME) 2 – 60 sec
Crank start delay (CRANK START DELAY) 0 – 30 sec
General timer Safety monitor start delay (SAFETY 10 – 60 sec
MONITOR DELAY)
Mains detect delay (MAINS DETECT 1 – 30 sec
DELAY)
Alternator detect delay (ALT DETECT 1 – 30 sec
DELAY)
Warm up delay (WARM UP DELAY) 0 – 60 sec
Return to mains delay (RETN -TO-MAINS 0 – 600 sec
DELAY)
Engine cooling time (ENG COOL TIME) 0 – 300 sec
Stop action time (STOP ACTION TIME) 10 – 120 sec
Load transfer delay (LOAD TRANSFER 0 – 60 sec
DELAY)
Page 33 of 123
KG645 CONTROLLER MANUAL
Level 0 Level 1 (On screen) Level 2 (On screen) Possible Value (On screen)
Power save mode delay (PWR SAVE MODE 5 – 1800 sec
DELAY)
Screen changeover time (SCRN 1 – 1800 sec
CHNGOVER TIME)
Deep sleep mode delay (DEEP SLP MODE 5 – 1800 sec
DELAY)
Sounder alarm timer (SOUNDER ALARM 1 – 300 sec
TIMER)
Test mode timer (TEST MODE TIMER) 1 – 720 Min
Page 34 of 123
KG645 CONTROLLER MANUAL
Level 0 Level 1 (On screen) Level 2 (On screen) Possible Value (On screen)
(FREQ MONITOR) Under frequency shutdown threshold (UF 0.0 – 59.0 Hz
SHUTDOWN THRESHOLD)
Under frequency warning (UNDER FREQ Disable, Enable
WARNING)
Under frequency warning threshold (UF 1.0 – 60.0 Hz
WARNING THRESHOLD)
Over frequency shutdown (OVER FREQ Disable, Enable
SHUTDOWN)
Over frequency shutdown threshold (OF 26.0 – 70.0 Hz
SHUTDOWN THRESHOLD)
Over frequency warning (OVER FREQ Disable, Enable
WARNING)
Over frequency warning threshold (OF 25.0 – 69.0 Hz
WARNING THRESHOLD)
Current monitoring CT ratio (CT RATIO) 1 – 8000
(CURR MONITOR)
Over current threshold (OVER CURR 5 – 10000 A
THRESHOLD)
Over current delay (OVER CURR DELAY) 1 – 600 sec
Over current action (OVER CURR ACTION) None, Warning, Electrical Trip,
Shutdown
Unbalanced load action (UNBAL LOAD None, Warning, Electrical trip,
ACTION) Shutdown
Unbalanced load threshold (UNBAL LOAD 5 – 200 %
THRESHOLD)
Unbalanced load delay (UNBAL LOAD 1– 600 sec
DELAY)
RESERVED NA
Load monitoring Generator rating (GEN RATING) 1.0 – 800.0 kW
(LOAD MONITOR)
Over load threshold (OVERLOAD 50 – 150 %
THRESHOLD)
Overload monitoring delay (OVERLOAD 1 – 600 sec
MON DELAY)
Overload action (OVERLOAD ACTION) None, Warning, Electrical trip,
Shutdown
Mains Mains Mains monitoring (MAINS MONITORING) Disable, Enable
Configuration
Mains AC system (MAINS AC SYSTEM) 1 Phase, 3 Phase
(MAINS CONFIG)
Phase reversal detect (PHASE REVERSAL Disable, Enable
DETECT)
Phase reversal action (PHASE REVERSAL None, Notification
ACTION)
Under voltage Enable (ENABLE) No, Yes
monitoring
Trip (TRIP) 48 – 398 V Ph-N
Page 35 of 123
KG645 CONTROLLER MANUAL
Level 0 Level 1 (On screen) Level 2 (On screen) Possible Value (On screen)
(UNDER VOLT Return (RETURN) 50 – 400 V Ph-N
MON)
Over voltage Enable (ENABLE) No, Yes
monitoring
Trip (TRIP) 102 – 800 V Ph-N
(OVER VOLT MON)
Return (RETURN) 100 – 798 V Ph-N
Under frequency Enable (ENABLE) No, Yes
monitoring
Trip (TRIP) 27.0 – 67.0 Hz
(UNDER FREQ
MON) Return (RETURN) 28.0 – 68.0 Hz
Over frequency Enable (ENABLE) No, Yes
monitoring
Trip (TRIP) 30.0 – 70.0 Hz
(OVER FREQ MON)
Return (RETURN) 29.0 – 69.0 Hz
Engine Crank disconnect Start attempts (START ATTEMPTS) 1–9
(CRANK
Disconnect on oil pressure (DISCONN ON Disable, Enable
DISCONNECT)
LOP SENS)
Disconnect oil pressure (DISCONN LOP 0.5 – 10.0 Bar
SENS)
Reserved (RESERVED) NA
Disconnect on oil pressure switch Disable, Enable
(DISCONN ON LLOP SW)
LLOP switch transient time (LLOP SW 0.0 – 3.0 Sec
TRANS TIME)
Alternator frequency (ALT FREQUENCY) 0 – 70 Hz
Engine speed (ENGINE SPEED) 0 – 4000 RPM
Disconnect on charging alternator voltage Disable, Enable
(DISCONN ON CHG ALT VOLT)
Charging alternator threshold (CHG ALT 5.0 – 30.0 Volt
THRESHOLD)
Speed monitoring Speed sense source (SPEED SENSE Magnetic pickup, Alternator
(SPEED MONITOR) SOURCE) frequency (Alt Freq)
Flywheel teeth (FLYWHEEL TEETH) 1– 300
Under speed shutdown (UNDER SPEED Disable, Enable
SHUTDOWN)
Under speed threshold (UNDER SPEED 0 – 3600 RPM
THRESHOLD)
Under speed delay (UNDER SPEED DELAY) 1– 60 Sec
Over speed level 1 threshold (OVER SPEED 800 – 4000 RPM
THRESHOLD)
Over speed delay (OVER SPEED DELAY) 1 – 60 Sec
Over speed level 2 threshold (Gross OS 100 – 200 %
THRESHOLD)
Page 36 of 123
KG645 CONTROLLER MANUAL
Level 0 Level 1 (On screen) Level 2 (On screen) Possible Value (On screen)
Healthy speed threshold (HEALTHY SPEED 300 – 4000 RPM
THRES)
Battery monitoring Low volt action (LOW VOLT ACTION) None, Warning, Electrical Trip,
(BATTERY Shutdown
MONITOR)
Low volt threshold (LOW VOLT 8.0 – 24.0 V
THRESHOLD)
Low volt delay (LOW VOLT DELAY) 5 – 1800 Sec
High volt action (HIGH VOLT ACTION) None, Warning, Electrical Trip,
Shutdown
High volt threshold (HIGH VOLT 12.0 – 36.0 V
THRESHOLD)
High volt delay (HIGH VOLT DELAY) 5 – 1800 Sec
Charge alternator Fail action (FAIL ACTION) None, Warning, Electrical Trip,
monitoring Shutdown
(CHARGE ALT
Fail threshold (FAIL THRESHOLD) 4.0 – 28.0 V
MON)
Fail delay (FAIL DELAY) 5 – 60 Sec
Preheat Preheat timer (PREHEAT TIMER) 1 – 60 Sec
(PREHEAT)
Engine Temperature limit (ENG TEMP Disable, Enable
LIMIT)
Engine Temperature limit (ENG TEMP 0 – 300 °C
LIMIT)
Maintenan Maintenance Action (ACTION) Notification, Warning
ce alarm (MAINT
Due at engine hours (DUE AT ENGINE 10 – 65000 hrs
ALARM)
HOURS)
Alarm due date Current day onwards
(ALARM DUE DATE)
Rotary General Actuator application (ACTUATOR APPLN) As E-Governor, As Start/Stop
Actuator (GENERAL) Device
}
Actuator speed (ACTUATOR SPEED) 1 – 10 x25 Hz
Actuator direction (ACTUATOR Clockwise, Anti–Clockwise
DIRECTION)
Engine start Cranking steps (CRANKING STEPS) 10 – 5000
strategy (ENG
Reserved parameter NA
START STRGY)
Reserved parameter NA
Reserved parameter NA
Init low speed delay (INIT LOW SPEED 0 – 180 Sec
DELAY)
Init low speed (INIT LOW SPEED) 500 – 1800 RPM
CRANK SENSE SPEED 20 – 2800 RPM
Ramp up time (RAMP UP TIME) 1 – 180 Sec
Reserved parameter NA
Page 37 of 123
KG645 CONTROLLER MANUAL
Level 0 Level 1 (On screen) Level 2 (On screen) Possible Value (On screen)
Reserved parameter NA
Reserved parameter NA
Reserved parameter NA
Generator E- Speed set point select (SPEED SET POINT Fixed (0% droop), Speed bias
governor SELECT) Inp (0-5V), Load based droop
configuration
Droop (DROOP) 0–4%
(GEN EGOV CNFG)
Target speed (TARGET SPEED) 500 – 4000 RPM
Proportional gain (PROPORTIONAL GAIN) 0 – 1000
Integral gain (INTEGRAL GAIN) 0 – 2000
Derivative gain (DERIVATIVE GAIN) 0 – 1000
Friction set off (FRICTION SETOFF) 0 – 1000
Gain schedule trigger (GAIN SCHEDULE 0.0 – 100.0 % RPM error
TRIGGER)
Loading factor (LOADING FACTOR) 0 – 1000
Unloading factor (UNLOADING FACTOR) 0 – 1000
Engine E-governor Target speed (TARGET SPEED) 500 – 4000 RPM
configuration
Proportional gain (PROPORTIONAL GAIN) 0 – 1000
(ENG EGOV CNFG)
Integral gain (INTEGRAL GAIN) 0 – 2000
Derivative gain (DERIVATIVE GAIN) 0 – 1000
Friction set off (FRICTION SETOFF) 0 – 1000
Gain schedule trigger (GAIN SCHEDULE 0.0 – 100.0 % RPM error
TRIGGER)
Loading factor (LOADING FACTOR) 0 – 1000
Unloading factor (UNLOADING FACTOR) 0 – 1000
Start/stop device Running steps (RUNNING STEPS) 0 – 500
configuration
(STR/STP DEVICE
CNFG)
Expansion DIG IN EX-A Source (SOURCE) Refer Table 2
digital
Polarity (POLARITY) Close To Activate, Open To
inputs (EXP
Activate
DIG
INPUTS) Action (ACTION) None, Warning, Electrical Trip,
Shutdown
Activation (ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
Activation delay (ACTIVATION DELAY) 1 – 60 sec
DIG IN EX-B Source (SOURCE) Refer Table 2
Polarity (POLARITY) Close To Activate, Open To
Activate
Action (ACTION) None, Warning, Electrical Trip,
Page 38 of 123
KG645 CONTROLLER MANUAL
Level 0 Level 1 (On screen) Level 2 (On screen) Possible Value (On screen)
Shutdown
Activation (ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
Activation delay (ACTIVATION DELAY) 1 – 60 sec
DIG IN EX-C Source (SOURCE) Refer Table 2
Polarity (POLARITY) Close To Activate, Open To
Activate
Action (ACTION) None, Warning, Electrical Trip,
Shutdown
Activation (ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
Activation delay (ACTIVATION DELAY) 1 – 60 sec
DIG IN EX-D Source (SOURCE) Refer Table 2
Polarity (POLARITY) Close To Activate, Open To
Activate
Action (ACTION) None, Warning, Electrical Trip,
Shutdown
Activation (ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
Activation delay (ACTIVATION DELAY) 1 – 60 sec
DIG IN EX-E Source (SOURCE) Refer Table 2
Polarity (POLARITY) Close To Activate, Open To
Activate
Action (ACTION) None, Warning, Electrical Trip,
Shutdown
Activation (ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
Activation delay (ACTIVATION DELAY) 1 – 60 sec
Expansion AN EX-S1/DIG EX-F Sensor selection (SENSOR SELECTION) Not used, Dig In EX-F, Pressure
analogue sensor, Temperature sensor
inputs (EXP
(Digital) Source ((DIG) SOURCE) Refer Table 2
ANLG
INPUTS) (Digital) Polarity ((DIG) POLARITY) Close To Activate, Open To
Activate
(Digital) Action ((DIG) ACTION) None, Warning, Electrical Trip,
Shutdown
(Digital) Activation ((DIG) ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
(Digital) Activation delay ((DIG) 1 – 60 sec
ACTIVATION DELAY)
Action None, Warning, Electrical Trip,
Shutdown
Threshold (THRESHOLD) 0.0 – 10.0 Bar (for Pressure) /
Page 39 of 123
KG645 CONTROLLER MANUAL
Level 0 Level 1 (On screen) Level 2 (On screen) Possible Value (On screen)
-5.0 – 1000.0 °C (for
Temperature)
Threshold type Less Than Threshold, Greater
Than Threshold
Open circuit alarm (OPEN CKT ALARM) None, Warning, Electrical Trip,
Shutdown
Pressure Sensor Calibration / Refer Table 7 (for Pressure) /
Temperature Sensor Calibration Refer Table 9 (for Temperature)
AN EX-S2/DIG EX-G Sensor selection (SENSOR SELECTION) Not used, Dig In EX-G, Pressure
sensor, Temperature sensor
(Digital) Source ((DIG) SOURCE) Refer Table 2
(Digital) Polarity ((DIG) POLARITY) Close To Activate, Open To
Activate
(Digital) Action ((DIG) ACTION) None, Warning, Electrical Trip,
Shutdown
(Digital) Activation ((DIG) ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
(Digital) Activation delay ((DIG) 1 – 60 sec
ACTIVATION DELAY)
Action None, Warning, Electrical Trip,
Shutdown
Threshold (THRESHOLD) 0.0 – 10.0 Bar (for Pressure) /
-5.0 – 1000.0 °C (for
Temperature)
Threshold type Less Than Threshold, Greater
Than Threshold
Open circuit alarm (OPEN CKT ALARM) None, Warning, Electrical Trip,
Shutdown
Pressure Sensor Calibration / Refer Table 7 (for Pressure) /
Temperature Sensor Calibration Refer Table 9 (for Temperature)
AN EX-S3/DIG EX-H Sensor selection (SENSOR SELECTION) Not used, Dig In EX-H, Pressure
sensor, Temperature sensor
(Digital) Source ((DIG) SOURCE) Refer Table 2
(Digital) Polarity ((DIG) POLARITY) Close To Activate, Open To
Activate
(Digital) Action ((DIG) ACTION) None, Warning, Electrical Trip,
Shutdown
(Digital) Activation ((DIG) ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
(Digital) Activation delay ((DIG) 1 – 60 sec
ACTIVATION DELAY)
Action None, Warning, Electrical Trip,
Page 40 of 123
KG645 CONTROLLER MANUAL
Level 0 Level 1 (On screen) Level 2 (On screen) Possible Value (On screen)
Shutdown
Threshold (THRESHOLD) 0.0 – 10.0 Bar (for Pressure) /
-5.0 – 1000.0 °C (for
Temperature)
Threshold type Less Than Threshold, Greater
Than Threshold
Open circuit alarm (OPEN CKT ALARM) None, Warning, Electrical Trip,
Shutdown
Pressure Sensor Calibration / Refer Table 7 (for Pressure) /
Temperature Sensor Calibration Refer Table 9 (for Temperature)
AN EX-S4/DIG EX-I Sensor selection (SENSOR SELECTION) Not used, Dig In EX-I, Pressure
sensor, Temperature sensor
(Digital) Source ((DIG) SOURCE) Refer Table 2
(Digital) Polarity ((DIG) POLARITY) Close To Activate, Open To
Activate
(Digital) Action ((DIG) ACTION) None, Warning, Electrical Trip,
Shutdown
(Digital) Activation ((DIG) ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
(Digital) Activation delay ((DIG) 1– 60 sec
ACTIVATION DELAY)
Action None, Warning, Electrical Trip,
Shutdown
Threshold (THRESHOLD) 0.0 – 10.0 Bar (for Pressure) /
-5.0 – 1000.0 °C (for
Temperature)
Threshold type Less Than Threshold, Greater
Than Threshold
Open circuit alarm (OPEN CKT ALARM) None, Warning, Electrical Trip,
Shutdown
Pressure Sensor Calibration / Refer Table 7 (for Pressure) /
Temperature Sensor Calibration Refer Table 9 (for Temperature)
AN EX-S5/DIG EX-J Sensor selection (SENSOR SELECTION) Not used, Dig In EX-J, Pressure
sensor, Temperature sensor
(Digital) Source ((DIG) SOURCE) Refer Table 2
(Digital) Polarity ((DIG) POLARITY) Close To Activate, Open To
Activate
(Digital) Action ((DIG) ACTION) None, Warning, Electrical Trip,
Shutdown
(Digital) Activation ((DIG) ACTIVATION) Never, From Engine Start,
From Monitoring On, Always
(Digital) Activation delay ((DIG) 0 – 60 sec
Page 41 of 123
KG645 CONTROLLER MANUAL
Level 0 Level 1 (On screen) Level 2 (On screen) Possible Value (On screen)
ACTIVATION DELAY)
Action None, Warning, Electrical Trip,
Shutdown
Threshold (THRESHOLD) 0.0 – 10.0 Bar (for Pressure) /
-5.0 – 1000.0 °C (for
Temperature)
Threshold type Less Than Threshold, Greater
Than Threshold
Open circuit alarm (OPEN CKT ALARM) None, Warning, Electrical Trip,
Shutdown
Pressure Sensor Calibration / Refer Table 7 (for Pressure) /
Temperature Sensor Calibration Refer Table 9 (for Temperature)
Expansion OUT EX-A Source (SOURCE) Refer Table 8
digital
Polarity (POLARITY) De-energise, Energise
outputs
(EXP OUT EX-B Source (SOURCE) Refer Table 8
OUTPUTS) Polarity (POLARITY) De-energise, Energise
OUT EX-C Source (SOURCE) Refer Table 8
Polarity (POLARITY) De-energise, Energise
OUT EX-D Source (SOURCE) Refer Table 8
Polarity (POLARITY) De-energise, Energise
OUT EX-E Source (SOURCE) Refer Table 8
Polarity (POLARITY) De-energise, Energise
Password Password 1 #### 0 – 9 for each digit
Password 2 #### 0 – 9 for each digit
Page 42 of 123
KG645 CONTROLLER MANUAL
Page 43 of 123
KG645 CONTROLLER MANUAL
Page 44 of 123
KG645 CONTROLLER MANUAL
Page 45 of 123
KG645 CONTROLLER MANUAL
*All the expansion module relevant parameters will be applicable, if KG-645 is connected to expansion module.
Page 46 of 123
KG645 CONTROLLER MANUAL
During Crank Hold Time, if the mains voltage recovers or any stop command or shutdown alarm occurs controller
will not issue start command. To start the genset it is necessary to clear all the alarms manually and put the
controller in Auto mode again.
Once the Mains Monitoring is disabled, then enable option will not appear in configuration menu. To enable the
Mains Monitoring again, enable and configure at least one parameter from mains voltage or frequency
monitoring.
Mains healthy condition will be decided by mains under/over voltage/frequency thresholds. If the Under Voltage
monitoring is disabled, controller will display MAINS HEALTHY condition for Under Voltage condition also.
Controller will detect unhealthy condition of enabled parameters only.
Page 47 of 123
KG645 CONTROLLER MANUAL
frequency of the alternator output, the speed must be controlled until the genset is paralleled with the grid or
other genset with the help of electronic governor. A Load Sharing Module controls the speed and the voltage of
the genset by controlling the AVR and E-governor of the gesnet. To control these two devices the LSM provides
the DC analog voltage signal to the both devices. The analog voltage signal is generally in the range of 0-5 V.
Page 48 of 123
KG645 CONTROLLER MANUAL
15 Alarms
KG-645 controller allows to configure several Shutdown/Electrical trip, Warning and Notification alarms such as
Low Oil Pressure shutdown, Over Load warning and many more.
An alarm condition occurs when the preconfigured parameter is out of preset level. On initiation of an alarm,
the Alarm LED will start blinking and Sounder alarm will be activated if configured. The controller will display
name of alarms along with count on ALARMS screen and the nature of alarm on STATUS screen. For
acknowledging the alarms, press “UP+DOWN” key (in case of sounder alarm). All the alarms will be activated at
the end of Safety Monitoring Delay duration. The controller will not issue the start command if any of alarm left
unacknowledged.
Page 49 of 123
KG645 CONTROLLER MANUAL
Sr. Action
Alarms Causes
No. Options
Indicates that the oil pressure measured is below the
Shutdown
1 Low Oil Pressure preset threshold. This condition is detected only when
Warning
engine is off.
Indicates that the oil pressure measured is below the Shutdown
Low Oil Pressure
2 preset threshold. This condition is detected only when Electrical Trip
(Switch)
engine is off. Warning
Shutdown
3 Oil Pressure Ckt Open The oil pressure sensor is detected as not being present Electrical Trip
Warning
Indicates that the engine temperature is above the preset Shutdown
4 High Eng Temp
threshold. This condition is detected only when engine is on. Warning
Shutdown
High Eng Temp Indicates that the engine temperature is above the preset
5 Electrical Trip
(Switch) threshold. This condition is detected only when engine is on.
Warning
Shutdown
Eng Temp/ pin24-Ckt
6 The temperature sensor is detected as not being present Electrical Trip
Opn
Warning
Indicates that the amount of fuel level is below the preset Shutdown
7 Low Fuel level
threshold. This condition is detected only when engine is on. Warning
Shutdown
Indicates that the amount of fuel level is below the preset
8 Low Fuel level (Switch) Electrical Trip
threshold. This condition is detected only when engine is on.
Warning
9 Fuel Theft The fuel consumption has exceeded the preset threshold Warning
Shutdown
Low Water Level Indicates that radiator water level is below the preset
10 Electrical Trip
Switch threshold
Warning
High Canopy Indicates that canopy temperature is above the preset Shutdown
11
Temperature threshold Warning
Shutdown
High Canopy Indicates that canopy temperature is above the preset
12 Electrical Trip
Temperature (Switch) threshold
Warning
Shutdown
The canopy temperature sensor is detected as not being
13 Canopy Temp Ckt Open Electrical Trip
present
Warning
Shutdown
Anlg S1/ pin23-Ckt Opn
14 Analog sensor S1 is detected as not being present Electrical Trip
/ Gnd
Warning
Shutdown
Anlg S2 / pin26-Ckt
15 Analog sensor S2 is detected as not being present Electrical Trip
Open
Warning
Auxiliary Input (for Shutdown
Configured auxiliary input has triggered longer than preset
16 eg.Aux_A) /user Electrical Trip
duration
defined name Warning
Page 50 of 123
KG645 CONTROLLER MANUAL
Sr. Action
Alarms Causes
No. Options
When emergency stop switch is pressed and immediate
17 Emergency Stop shutdown is required. This condition is detected in both Shutdown
conditions- engine on and off.
It is detected that genset is still running after sending stop
18 Fail To Stop Shutdown
command
Indicates that genset has not started after the preset
19 Fail To Start Shutdown
number of Start Attempts
Indicates that genset (R) Phase voltage has exceeded the Shutdown
20 R Phase Over Voltage
preset over voltage threshold. Warning
Indicates that genset (Y) Phase voltage has exceeded the Shutdown
21 Y Phase Over Voltage
preset over voltage threshold Warning
Indicates that genset (B) Phase voltage has exceeded the Shutdown
22 B Phase Over Voltage
preset over voltage threshold Warning
Indicates that geset (R) Phase voltage has fallen below Shutdown
23 R Phase Under Voltage
preset under voltage threshold. Warning
Indicates that geset (Y) Phase voltage has fallen below Shutdown
24 Y Phase Under Voltage
preset under voltage threshold Warning
Indicates that geset (B) Phase voltage has fallen below Shutdown
25 B Phase Under Voltage
preset under voltage threshold Warning
Shutdown
26 DG Phase Reversed Alternator phase sequence (R-Y-B) is not correct Electrical Trip
Warning
27 Mains Phase Reversed Indicates the mains unhealthy condition Notification
Indicates that genset output frequency has exceeded the Shutdown
28 Over Frequency
preset threshold Warning
Indicates that genset output frequency has fallen below the Shutdown
29 Under Frequency
preset threshold Warning
Shutdown
Indicates that genset current has exceeded the preset
30 Over Current Electrical Trip
shutdown threshold
Warning
Shutdown
Anlg S1 / pin23-Over Indicates that analog sensor S1 current input has exceeded
31 Electrical Trip
Curr threshold (25mA)
Warning
Shutdown
Indicates that the measured kW load rating has exceeded
32 Over Load Electrical Trip
the preset threshold
Warning
Shutdown
Load on any phase is greater or less than other phases by a
33 Unbalanced Load Electrical Trip
threshold value
Warning
Indicates that genset speed has exceeded the preset over
34 Over Speed speed threshold. Genset will shutdown after Over Speed Shutdown
Delay.
Indicates that genset speed has exceeded the preset Gross
35 Gross Over Speed Shutdown
Over Speed Threshold. Genset will shutdown immediately
Page 51 of 123
KG645 CONTROLLER MANUAL
Sr. Action
Alarms Causes
No. Options
without any delay.
36 Under Speed The engine speed has fallen below the preset RPM Shutdown
Shutdown
The charge alternator voltage has dropped below the preset
37 Charge Fail Electrical Trip
threshold
Warning
38 No Speed Signal Indicates that speed sensor connections are absent Shutdown
Shutdown
Indicates that there is failure of the V-belt, which is driving
39 V Belt Broken Electrical Trip
the charging alternator
Warning
Shutdown
40 Battery Under Voltage The battery voltage has fallen below the preset threshold Electrical Trip
Warning
Shutdown
41 Battery Over Voltage The battery voltage has exceeded the preset threshold Electrical Trip
Warning
This indicates that alternator voltage have not crossed 50 V-
42 Alt Voltage Lost Shutdown
RMS within 2 seconds after crank disconnect event
High Oil Press Lube oil pressure is detected above the crank disconnect
43 Warning
Detected threshold when the engine is off.
This indicates that engine speed have not crossed preset
44 Engine Speed Fault Healthy Speed Threshold within 2 seconds from the crank Shutdown
disconnect event
Controller has detected engine speed even when the start
45 Eng Speed Detected Warning
command is not issued.
Indicates that engine running hours has exceeded the preset
Notification
46 Maintenance Due hours limit or maintenance due date has occurred and filter
Warning
servicing is required.
Indicates that lube oil temperature is above the preset Shutdown
47 High Lube Oil Temp
threshold Warning
Expansion module is enabled in the controller configuration
48 Exp Module Comm but controller is not receiving any response from the Notification
Error* expansion module.
Auxiliary Input* (for Shutdown
The user configured digital input from expansion module is
49 eg.Aux_XA) /user Electrical Trip
activated longer than the preset duration
defined name) Warning
Shutdown
Anx S1/S2/S3/S4/S5 Analog sensor EX-(S1/S2/S3/S4/S5) from expansion module
50 Electrical Trip
Ckt Opn* is detected as not being present
Warning
Note: Only warning alarms will get auto cleared.
Page 52 of 123
KG645 CONTROLLER MANUAL
16 Troubleshooting
This section explains the common faults, their possible causes and remedial actions.
Sr.
Fault Remedial Actions
No.
Possible Issues in MANUAL Mode
1 The controller does not power ON. • Check the battery voltage.
• Check the fuse on the battery supply.
• Check continuity between battery +ve and
controller terminal # 2.
• Check continuity between battery ground
and controller terminal # 1.
2 The controller fails to crank-start the engine. • Check the battery voltage.
• Enter the “configuration mode” in
controller and verify the configuration for
the “START” output. Also, check that
“START” output is working correctly by
measuring its voltage o/p.
• Enter the “configuration mode” in
controller and verify the configuration of
“CRANK DISCONNECT” method.
• Verify the configuration of “LLOP SWITCH”
polarity. Also, ensure that the lube oil
pressure switch & sensor are working OK.
Check their wiring.
3 The “Emergency Stop” alarm comes up even • Check if the “Emergency Stop” switch is
when the “Emergency Stop” is not pressed. working OK. Check its wiring also.
• Enter the “configuration mode” in
controller and verify the configuration of
“EMERGENCY STOP” polarity.
4 The controller generates unnecessary • Check the respective switch/sensor and
“Shutdown Alarms” or “Warning Alarms” wiring.
• Enter the “configuration mode” in the
controller and verify the respective
threshold configuration.
5 The controller reports “Charge Fail” alarm. • To check if the controller's charging
alternator terminal is working or not:
disconnect the charging alternator wiring
to the controller's terminal # 7. Short the
terminal # 7 to the ground through a DC
ammeter. Crank-start the engine. The DC
ammeter should indicate the current in the
range 200 - 400 mA for ~30 seconds. If yes,
the controller's charging alternator
terminal is working OK.
• Disconnect and re-connect the charging
alternator ind connection to the
controller's terminal # 7.
• Check if the charging alternator is working
OK or not.
6 The controller issues unnecessary “crank-start” • Ensure that the controller's o/p terminal is
Page 53 of 123
KG645 CONTROLLER MANUAL
Sr.
Fault Remedial Actions
No.
command immediately after power on. not directly connected to the starter relay.
The controller's o/p should be given to an
intermediate relay which should in-turn
power the starter relay. The controller can
get permanently damaged and will need to
be replaced if this precaution is not taken.
• Check start-relay connection with the
suitable controller terminal.
• Enter the “configuration mode” in the
controller and verify the configuration for
the “START RELAY” o/p polarity.
7 The engine runs, but the controller shows • Check if the MPU signal (if used), and main
genset to be “OFF”. alternator voltage signal (R phase) are
received by the controller terminals.
• Check if the LOP and LLOP are working OK.
Also check their wiring to the controller.
8 The controller displays incorrect PF value or kW • Check wiring of the respective alternator
or load current. phase voltage and the CT to the controller.
• Check the CT ratio (if kW or current
reading is faulty).
9 The controller displays incorrect mains voltage • Check the wiring of the respective phase to
or incorrect main alternator voltage. the controller.
• If the problem is not resolved, replace the
controller and try again.
10 Controller displays incorrect reading for any of • Check respective sensor and its wiring.
LOP, Fuel Level, Temp sensors. • Enter the “configuration mode” in the
controller and verify the calibration for the
respective sensor in configuration.
11 The controller displays incorrect engine RPM. • Check the MPU connection and
configuration (if enabled).
• Check wiring of the main alternator’s R-
phase and neutral to the controller.
12 The controller screen freezes or hangs up. • Reset the controller power.
Page 54 of 123
KG645 CONTROLLER MANUAL
Page 55 of 123
KG645 CONTROLLER MANUAL
Page 56 of 123
KG645 CONTROLLER MANUAL
4 Number of registers to write – high byte Number of registers to write must be between
5 Number of registers to write – low byte 1 to 255
6 Number of data bytes to follow (n)
7 Value at first register
. .
. .
. .
6+n Value at last register
7+n/8+n Error check CRC
Page 57 of 123
KG645 CONTROLLER MANUAL
Page 58 of 123
KG645 CONTROLLER MANUAL
Page 59 of 123
KG645 CONTROLLER MANUAL
Register Scale
Value Unit/Interpretation Bits/ Sign
Offset Factor
30 Generator B apparent power 0.1 KVA Unsigned
31 Generator total apparent power 0.1 KVA Unsigned
32 Generator R reactive power 0.1 KVAr Unsigned
33 Generator Y reactive power 0.1 KVAr Unsigned
34 Generator B reactive power 0.1 KVAr Unsigned
35 Generator total reactive power 0.1 KVAr Unsigned
36 Generator power factor R 0.01 -- Unsigned
37 Generator power factor Y 0.01 -- Unsigned
38 Generator power factor B 0.01 -- Unsigned
39 Generator average power factor 0.01 -- Unsigned
40– 41 Generator cumulative energy 0.1 KWh Unsigned
42 – 43 Generator cumulative apparent energy 0.1 KVAh Unsigned
44 – 45 Generator cumulative reactive energy 0.1 KVArh Unsigned
46 Mains R-N voltage 0.1 V Unsigned
47 Mains Y-N voltage 0.1 V Unsigned
48 Mains B-N voltage 0.1 V Unsigned
49 Mains R-Y voltage 0.1 V Unsigned
50 Mains Y-B voltage 0.1 V Unsigned
51 Mains B-R voltage 0.1 V Unsigned
52 Mains R frequency 0.1 Hz Unsigned
53 Mains Y frequency 0.1 Hz Unsigned
54 Mains B frequency 0.1 Hz Unsigned
55 Alarm 1 -- --
Low oil pressure -- -- 13/16-16/16
High coolant temperature -- -- 9/16-12/16
Low fuel level -- -- 5/16-8/16
Radiator Water level -- -- 1/16-4/16
56 Alarm 2 -- --
Under speed -- -- 13/16-16/16
Over speed -- -- 9/16-12/16
Fail to start -- -- 5/16-8/16
Fail to stop -- -- 1/16-4/16
57 Alarm 3 -- --
Reserved -- -- 13/16-16/16
Reserved -- -- 9/16-12/16
Generator low frequency -- -- 5/16-8/16
Page 60 of 123
KG645 CONTROLLER MANUAL
Register Scale
Value Unit/Interpretation Bits/ Sign
Offset Factor
Generator high frequency -- -- 1/16-4/16
58 Alarm 4 -- --
Generator high current -- -- 13/16-16/16
Generator overload -- -- 9/16-12/16
Unbalanced load -- -- 5/16-8/16
Emergency stop -- -- 1/16-4/16
59 Alarm 5 -- --
Charge fail -- -- 13/16-16/16
Filter maintenance -- -- 9/16-12/16
Reserved -- -- 5/16-8/16
Reserved -- -- 1/16-4/16
60 Alarm 6 -- --
Battery low voltage -- -- 13/16-16/16
Battery high voltage -- --
Analog sensor 1/ pin23 circuit open -- -- 5/16-8/16
Engine temperature circuit open -- -- 1/16-4/16
61 Alarm 7 -- --
Fuel theft -- -- 13/16-16/16
No speed signal -- -- 9/16-12/16
Analog sensor 2/ pin26 circuit open -- -- 5/16-8/16
Analog sensor 1 over current -- -- 1/16-4/16
62 Alarm 8 -- --
Auxiliary Input A -- -- 13/16-16/16
Auxiliary Input B -- -- 9/16-12/16
Auxiliary Input C -- -- 5/16-8/16
Auxiliary Input D -- -- 1/16-4/16
63 Alarm 9 -- --
Auxiliary Input E -- -- 13/16-16/16
Auxiliary Input F -- -- 9/16-12/16
Auxiliary Input G -- -- 5/16-8/16
Auxiliary Input H -- -- 1/16-4/16
64 Alarm 10 -- --
Gen R phase low volt -- -- 13/16-16/16
Gen R phase high volt -- -- 9/16-12/16
Gen Y phase low volt -- -- 5/16-8/16
Gen Y phase high volt -- -- 1/16-4/16
Page 61 of 123
KG645 CONTROLLER MANUAL
Register Scale
Value Unit/Interpretation Bits/ Sign
Offset Factor
65 Alarm 11 -- --
Gen B phase low volt -- -- 13/16-16/16
Gen B phase high volt -- -- 9/16-12/16
DG phase rotation -- -- 5/16-8/16
Mains phase rotation -- -- 1/16-4/16
66 Alarm 12 -- --
High canopy temperature -- -- 13/16-16/16
V belt broken -- -- 9/16-12/16
Analogue EX-S1 circuit open* -- -- 5/16-8/16
Analogue EX-S2 circuit open* -- -- 1/16-4/16
67 Alarm 13 -- --
Analogue EX-S3 circuit open* -- -- 13/16-16/16
Analogue EX-S4 circuit open* -- -- 9/16-12/16
Analogue EX-S5 circuit open* -- -- 5/16-8/16
Auxiliary Input EX-A* -- -- 1/16-4/16
68 Alarm 14 -- --
Auxiliary Input EX-B* -- -- 13/16-16/16
Auxiliary Input EX-XC* -- -- 9/16-12/16
Auxiliary Input EX-XD* -- -- 5/16-8/16
Auxiliary Input EX-XE* -- -- 1/16-4/16
69 Alarm 15 -- --
Auxiliary Input EX-F* -- -- 13/16-16/16
Auxiliary Input EX-G* -- -- 9/16-12/16
Auxiliary Input EX-H* -- -- 5/16-8/16
Auxiliary Input EX-I* -- -- 1/16-4/16
70 Alarm 16 -- --
Auxiliary Input EX-J* -- -- 13/16-16/16
Analog sensor 1/pin23 circuit ground -- -- 9/16-12/16
Alternator voltage lost -- -- 5/16-8/16
Engine Speed detected -- -- 1/16-4/16
71 Exp Module I/O Diagnostics* -- --
Digital Input EX-A* -- -- 16/16
Digital Input EX-B* -- -- 15/16
Digital Input EX-C* -- -- 14/16
Digital Input EX-D* -- -- 13/16
Digital Input EX-E* -- -- 12/16
Page 62 of 123
KG645 CONTROLLER MANUAL
Register Scale
Value Unit/Interpretation Bits/ Sign
Offset Factor
Digital Input EX-F* -- -- 11/16
Digital Input EX-G* -- -- 10/16
Digital Input EX-H* -- -- 9/16
Digital Input EX-I* -- -- 8/16
Digital Input EX-J* -- -- 7/16
Digital Output A* -- -- 6/16
Digital Output B* -- -- 5/16
Digital Output C* -- -- 4/16
Digital Output D* -- -- 3/16
Digital Output E* -- -- 2/16
Expansion module comm error* -- -- 1/16
72 Input Output Diagnostics -- --
Digital Input A -- -- 16/16
Digital Input B -- -- 15/16
Digital Input C -- -- 14/16
Digital Input D -- -- 13/16
Digital Input E -- -- 12/16
Digital Input F -- -- 11/16
Digital Input G -- -- 10/16
Digital Input H -- -- 9/16
Digital Output A -- -- 8/16
Digital Output B -- -- 7/16
Digital Output C -- -- 6/16
Digital Output D -- -- 5/16
Digital Output E -- -- 4/16
Digital Output F -- -- 3/16
Unimplemented -- -- 2/16
Unimplemented -- -- 1/16
73 DG Status -- --
Load on DG -- TRUE (1), FALSE (0) 16/16
Running (1), Stopped
Current DG Status -- 15/16
(0)
DG Stopped normally -- TRUE (1), FALSE (0) 14/16
DG Stopped with fault -- TRUE (1), FALSE (0) 13/16
DG Mode -- Auto (1), Manual(0) 12/16
Common shutdown -- 11/16
Common electric trip -- 10/16
Page 63 of 123
KG645 CONTROLLER MANUAL
Register Scale
Value Unit/Interpretation Bits/ Sign
Offset Factor
Common warning -- 9/16
Common notification -- 8/16
Unimplemented -- -- 7/16-1/16
One of the following:
DG Started (1)
DG Stopped (2)
DG already On (3)
74 Command Status -- Unsigned
DG already Off (4)
DG in manual mode
(5)
DG Not started (6)
75 Alarm 17 -- --
High oil pressure detected -- -- 13/16-16/16
Engine Speed Fault -- -- 9/16-12/16
Lube Oil Temperature -- -- 5/16-8/16
Reserved -- -- 1/16-4/16
Actual value = Observed value on MODBUS interface multiplied with scale factor.
Actual value ** Value of the configured sensor will be shown at a time from Analog Sensor S2.
Page 64 of 123
KG645 CONTROLLER MANUAL
The interpretation of alarm status (registers 54-69 and 74 in Table 16) is as shown in Table 18.
Page 65 of 123
KG645 CONTROLLER MANUAL
Expansion Module
19 Introduction
The input/output expansion module can be used in conjunction with KG-645 genset controller to provide additional 5
digital inputs, 5 analog inputs and 5 digital outputs. These inputs/outputs have the same specification as given in
sections 3.4 , 3.5 and 4.1.
Expansion module have two diagnostic LED's as shown in figure 20. Green LED indicates power status of the module
and red LED blinks when data communication between KG-645 controller and expansion module is active. Refer
section 9.1 and 22.11 for configuration details of module.
Figure 21: Representing the expansion module connector when viewed from the terminal insertion side
The following table provides the details for connecting expansion module with KG-645 genset controller.
Page 66 of 123
KG645 CONTROLLER MANUAL
7 Not used NA
Page 67 of 123
KG645 CONTROLLER MANUAL
21 Installation Instructions
Page 68 of 123
KG645 CONTROLLER MANUAL
A progress bar will show installation completion progress. On completion of installation, a window will be shown as
below. Click Finish.
Page 69 of 123
KG645 CONTROLLER MANUAL
Once the controller enters into the Programming mode, go to Device Manager→Other devices→GCUSMPL.
Page 70 of 123
KG645 CONTROLLER MANUAL
Page 71 of 123
KG645 CONTROLLER MANUAL
III. Choose “Browse my computer for driver software” to select the correct driver software.
IV. For driver installation on 64-bit Windows system, choose a driver path as “C:\Program Files(x86)\KG-645
Configuration Utility\USB Driver” and then click Next.
Page 72 of 123
KG645 CONTROLLER MANUAL
V. On successful installation of USB driver, a confirmation screen will be shown as below. Click Close.
Page 73 of 123
KG645 CONTROLLER MANUAL
VI. Ensure the successful driver installation by checking the entry of “GCxx” under the “Ports” option in Device
Manager.
After successful installation of configuration utility and USB driver, if KG-645 controller is not
detected at PC port, then disable serial or virtual serial port (if any used) of PC.
Page 74 of 123
KG645 CONTROLLER MANUAL
22 Usage Instructions
The screen prompts the user to select between two options as follows.
• Open a config file: Editing a configuration previously saved to disk by clicking “Open a config file” and
browsing to the file.
• Other options: Creating a new configuration. Click on text “START” on next screen, to start with
configuration.
Page 75 of 123
KG645 CONTROLLER MANUAL
Increment/Decrement
Arrows
Text
entry
Box Slider
Check Box
Page 76 of 123
KG645 CONTROLLER MANUAL
• Check box
Check box is typically used to enable/disable a feature.
• Text entry box
A value can be directly entered in a text entry box.
• Increment/Decrement arrows
Increment/Decrement arrows can be used to progressively increase/decrease the corresponding value.
• Slider
A slider can be dragged to change the corresponding parameter value.
22.5 Tools
KG 645 - Configuration Utility allows a set of actions to be performed in addition to editing and saving the
configurations. These actions can be accessed under the Tools menu as shown in following screenshot. These
actions are enabled only if an active connection with a controller is detected.
Page 77 of 123
KG645 CONTROLLER MANUAL
The user can confirm that these values of parameters are correct. To modify these values, Edit Configuration option
should be chosen to go back to the parameter editing page. To write the values, choose Write Configuration To
Device option. Following pop-up window will be shown.
Page 78 of 123
KG645 CONTROLLER MANUAL
Select Read From Device option. The configuration will be read from the controller and appropriately populated
in the uility. A confirmation window will be shown as below.
Page 79 of 123
KG645 CONTROLLER MANUAL
Page 80 of 123
KG645 CONTROLLER MANUAL
Then click Update. The firmware on the controller will be updated. A progress bar will show status of updation.
Page 81 of 123
KG645 CONTROLLER MANUAL
Page 82 of 123
KG645 CONTROLLER MANUAL
It is necessary, first to check date and time of your computer system are correct. On selecting Yes option,
computer system's current date and time will be updated in the controller.
23 Interpretation of Parameters
This section describes interpretation of parameters which are accessed via configuration utility.
23.1 Module
The Module allows configuration of a set of module-wide parameters.
Select Module to start GCU
configuration
Page 83 of 123
KG645 CONTROLLER MANUAL
23.1.1 General
Parameter Interpretation
Allows to enter a text string to identify configuration as a Profile. This ID will be
Profile Name
displayed on Active Profile screen of the controller.
The controller enters into this mode, on application of battery supply. Available
Power On Mode
options are Manual and Auto mode.
Enables or disables lamp test sequence. If enabled, all LEDs on front fascia of the
Power On Lamp Test
controller will illuminate for 3 seconds.
Enables or disables Deep Sleep mode. If enabled, the controller enters into low-
Deep Sleep Mode power mode after Deep Sleep Mode Delay duration (Refer section 22.5.2 for delay
setting).
Enables or disables Expansion module. This enables the Expansion Box option
Expansion Mode*
(Refer section 22.11) to configure expansion module parameters.
Table 19: General
23.1.2Display
Parameter Interpretation
Contrast Decides the percentage contrast of LCD display.
Enables or disables power save feature for LCD display backlit. If enabled, the
Power Save Mode backlit of LCD display will be switched OFF after Power Save Mode Delay duration
(Refer section 22.5.2 for delay setting).
Table 20: Display
Page 84 of 123
KG645 CONTROLLER MANUAL
23.1.3RS485 Communication
Parameter Interpretation
Decides the communication function to be performed by the controller.
Available options:
None: No communication function will be performed.
Communication Mode
MODBUS: The controller will communicate through the RS485 port using
MODBUS protocol. The relevant parameters such as MODBUS Slave ID and
Baudrate will be activated.
MODBUS Slave ID MODBUS slave ID you wish to communicate with.
MODBUS Baudrate MODBUS baudrate (bits per second) you wish to connect at.
Parity bit provides the simple error checking for transmitted data. The available
Parity Bit types of parity checking are as follows:
None, Even, Odd
Table 21: RS485 Communication
Page 85 of 123
KG645 CONTROLLER MANUAL
Parameter Interpretation
Decides how the digital input will be interpreted by the controller. The input
Source
can be assigned as one of a set of Digital Input Source (Refer section 22.2.1).
It is enabled only if the Source is selected as User configured. The text string
entered here will be displayed on LCD screen when corresponding user
Name
configured input is activated. The text string is also used as the event
description for the corresponding input event in the event log.
Allows to select polarity of the digital input. Available options:
Close to Activate: The input will be interpreted as active if the input is
Polarity grounded.
Open to Activate: The input will be interpreted as active if the input is not
grounded.
It is enabled if the Source is selected as User configured or switch or High
Canopy Temperature. Allows to select the action taken by the controller when
the input is found to be active. Available options:
None: No action will be taken.
Action
Warning: A warning will be displayed without affecting the operation of genset.
Electric Trip: The genset will be first unloaded by deactivating the contactor
before genset being stopped.
Shutdown: Genset will be shutdown.
It is enabled only if the Source is selected as User configured or switch or High
Canopy Temperature. Decides when to start monitoring of the digital input.
Available options:
Never: The input will never monitored.
Activation
From Engine Start: The input will be monitored from the start of genset.
From Monitoring On: The input will be monitored when the engine and
alternator safety monitoring begins.
Always: The input will always monitored.
Allows to select duration in seconds, for which the input active condition
Activation Delay
should persist before which preconfigured action will be taken.
Table 22: Digital Input A
Refer Table 22 for configuration of Digital Input A, Digital Input B, Digital Input C, Digital Input D and Digital Input
Page 86 of 123
KG645 CONTROLLER MANUAL
Page 87 of 123
KG645 CONTROLLER MANUAL
Parameter Interpretation
Decides how the input will be interpreted. Available options:
Use Input As Not used: The input will not be used.
Lube Oil Pressure Sensor: The input will be used as LOP (4 – 20 mA) sensor.
Low Level Shutdown Enables or disables low oil pressure shutdown detection.
Low Level Shutdown Allows to select the threshold on the oil pressure value below which selected
Threshold action for Low Oil Pressure condition will be triggered.
Low Level Warning Enables or disables low oil pressure warning detection.
Low Level Warning Allows to select the threshold on the oil pressure value below which selected
Threshold action for Low Oil Pressure condition will be triggered.
Allows to select alarm action on detection of following fault conditions:
1. Oil pressure open circuit/ground (Anlg S1 / pin23 - Ckt Opn/Gnd)
2. Analog sensor S1 over current (Anlg S1 / pin23 - Overcurrent)
When any of these conditions is detected, an alarm will be triggered. Available
options:
Oil Pressure Circuit Fault
None: No action will be taken.
Warning: A warning will be displayed without affecting the operation of genset.
Electric Trip: The genset will be first unloaded by deactivating the contactor
before genset being stopped.
Shutdown: Genset will be shutdown.
A table that defines relation between the sensor value and corresponding
Sensor Calibration Table
physical quantity.
Table 24: Analog Sensor S1 (4–20 mA)
Page 88 of 123
KG645 CONTROLLER MANUAL
At any given time, user can select either Lube Oil Pressure (4-20mA) current sensor
Lube Oil Pressure resistive sensor or Speed bias input (0-5 V) in Generator Egov Configura-
tion.
Parameter Interpretation
Decides how the input will be interpreted. Available options:
Not used: The input will not be used.
Digital Input F: The selected sensor input will be used as digital input. The
parameters identical to digital inputs will be displayed and the input can
configured in the same way as that of digital input being configured (Refer
section 22.2.1).
Use Input As
Canopy Temperature Sensor: The input will be used as analog input for canopy
temperature sensor (resistive).
Lube Oil Temperature Sensor: The input will be used as analog input for lube
oil temperature sensor (resistive).
Lube Oil Pressure Sensor: The input will be used as analog input for lube oil
pressure sensor (resistive).
High Level Shutdown Enables or disables shutdown for high canopy temperature value
Threshold on canopy temperature value above which shutdown will be
Shutdown Threshold
triggered
High Level Warning Enables or disables warning for high canopy temperature value
Warning Threshold Threshold on canopy temperature value above which warning will be triggered
Page 89 of 123
KG645 CONTROLLER MANUAL
Parameter Interpretation
When the S2 sensor circuit open condition is detected, an alarm will be
triggered. Available options:
None: No action will be taken.
Warning: A warning will be displayed without affecting the operation of
S2 Sensor Circuit Fault
genset.
Electric Trip: The genset will be first unloaded by deactivating the contactor
before genset being stopped.
Shutdown: Genset will be shutdown.
A table that defines relation between the sensor value and corresponding
Sensor Calibration Table
physical quantity.
Analog Sensor S2 (Resistive) can be configured as Lube Oil Pressure Sensor (resistive) on enabling in all
conditions except:
• If the Lube Oil Pressure sensor is configured to Analog Sensor S1 (4-20 mA)
• Speed Bias Input (0-5 V) is configured in Generator Egov Configuration
Following is an example showing, Analog Sensor S2 (Resistive) configured as Lube Oil Pressure Sensor(resistive).
Following is an example showing, Analog Sensor S2 (Resistive) configured as Lube Oil Temperature
Sensor(resistive).
Page 90 of 123
KG645 CONTROLLER MANUAL
Parameter Interpretation
Decides how the input will be interpreted. Available options:
Not used: The input will not be used.
Digital Input G: The selected sensor input will be used as digital input. The
parameters identical to digital inputs will be displayed and the input can
Use Input As
configured in the same way as that of digital input being configured (Refer
section 22.2.1).
Engine Temperature Sensor: The input will be used as analog sensor
(resistive).
High Temp Shutdown Enables or disables shutdown for high engine temperature value
Page 91 of 123
KG645 CONTROLLER MANUAL
Parameter Interpretation
Threshold Threshold on engine temperature value above which shutdown will be triggered
High Temp Warning Enables or disables warning for high engine temperature value
Threshold Threshold on engine temperature value above which warning will be triggered
Allows to select the action taken by the controller if engine temperature sensor is
detected as open circuit (Eng Temp / pin24 - Ckt Opn). Available options:
None: No action will be taken.
Engine Temp Circuit Fault Warning: A warning will be displayed without affecting the operation of genset.
Electric Trip: The genset will be first unloaded by deactivating the contactor
before genset being stopped.
Shutdown: Genset will be shutdown.
A table that defines relation between the sensor value and corresponding
Sensor Calibration Table
physical quantity.
Table 26: Engine Temperature Sensing (Resistive)
Parameter Interpretation
Decides how the input will be interpreted. Available options:
Not Used: The input will not be used.
Digital Input H: The selected sensor input will be used as digital input. The
Use Input As parameters identical to digital inputs will be displayed and the input can
configured in the same way as that of digital input being configured (Refer
section 22.2.1).
Fuel Level Sensor: The input will be used as analog sensor (resistive).
Page 92 of 123
KG645 CONTROLLER MANUAL
Parameter Interpretation
Enables or disables an engine shutdown by the controller if Low Fuel Level
Low Fuel Level Shutdown
condition is detected.
Allows to select the threshold on fuel level value below which Low Fuel
Shutdown Threshold
Level shutdown alarm will be triggered.
Enables or disables warning generation by the controller if Low Fuel Level
Low Fuel Level Warning
condition is detected.
Allows to select the threshold on fuel level value below which Low Fuel
Warning Threshold
Level warning will be triggered.
Fuel Theft Warning Enables or disables Fuel Theft warning alarm.
Allows to select the threshold on percentage fuel consumption per hour,
Fuel Theft Threshold
above which Fuel Theft alarm will be triggered.
Fuel Consumption Fuel consumption in litres per hour.
Display Fuel in Liters If enabled, fuel level will be displayed in liters on screen.
A table that defines relation between the sensor value and corresponding
Sensor Calibration Table
physical quantity.
Table 27: Fuel Level Sensing (Resistive)
Analog Sensor S2, Engine Temperature Sensing and Fuel Level Sensing can be configured as Digital Inputs (Refer
section 22.2 and 22.2.1).
Following is the screenshot of configuration utility representing configuration of Fuel Level sensor as a digital
switch.
Page 93 of 123
KG645 CONTROLLER MANUAL
23.4 Outputs
The Outputs allows configuration of digital outputs.
Parameter Interpretation
Allows to select the output as one of the set of Digital Output Source (Refer
Source
section 22.4.1). Alternatively, the outputs can be disabled.
Allows to select activation polarity of selected output. Available options:
De-energise: The output will be disconnected from battery positive supply if the
On Activation corresponding source condition is active.
Energise: The output will be connected to battery positive supply if the
corresponding source condition is active.
Table 28: Outputs
Page 94 of 123
KG645 CONTROLLER MANUAL
Interpretation
Digital Output Source
Active when... Inactive when...
Mains is detected as healthy or mains
Mains Failure Mains is detected as not healthy.
monitoring is disabled.
Any warning or shutdown or electric
Common Alarm No alarm is pending.
trip alarm is pending.
Common Electric Trip Any electric trip alarm is pending. No electric trip alarm is pending.
Common Shutdown Any shutdown alarm is pending. No shutdown alarm is pending.
Common Warning Any warning alarm is pending. No warning alarm is pending.
Cooling Down Cooling down timer is active. Cooling down timer is not active.
Digital Input A Digital Input A is active. Digital Input A is not active.
Digital Input B Digital Input B is active. Digital Input B is not active.
Digital Input C Digital Input C is active. Digital Input C is not active.
Digital Input D Digital Input D is active. Digital Input D is not active.
Digital Input E Digital Input E is active. Digital Input E is not active.
Digital Input F (Analog S2
Digital Input F is active. Digital Input F is not active.
Input)
Digital Input G (Analog
Digital Input G is active. Digital Input G is not active.
Input Eng Temp)
Digital Input H (Analog
Digital Input H is active. Digital Input H is not active.
Input Fuel LVL)
Emergency stop input is active. This
Emergency Stop output will be active (if configured) in Emergency stop input is not active.
both conditions- engine on and off.
An engine stop command is being An engine stop command is not being
Stop Solenoid
issued. issued.
Fail To Start Fail To Start alarm is pending. Fail To Start alarm is not pending.
Fail To Stop Fail To Stop alarm is pending. Fail To Stop alarm is not pending.
Fuel Relay Engine needs to be running. Engine need not to be running.
Genset voltage and frequency are Genset voltage and frequency are not
Gen Available
within acceptable limits. within acceptable limits.
Genset R Phase Over Voltage shutdown Genset R Phase Over Voltage
R Phase OV Shutdown
alarm is pending. shutdown alarm is not pending.
Genset R Phase Under Voltage Genset R Phase Under Voltage
R Phase UV Shutdown
shutdown alarm is pending. shutdown alarm is not pending.
Genset Y Phase Over Voltage shutdown Genset Y Phase Over Voltage
Y Phase OV Shutdown
alarm is pending. shutdown alarm is not pending.
Genset Y Phase Under Voltage Genset Y Phase Under Voltage
Y Phase UV Shutdown
shutdown alarm is pending. shutdown alarm is not pending.
Page 95 of 123
KG645 CONTROLLER MANUAL
Interpretation
Digital Output Source
Active when... Inactive when...
Genset B Phase Over Voltage shutdown Genset B Phase Over Voltage
B Phase OV Shutdown
alarm is pending. shutdown alarm is not pending.
Genset B Phase Under Voltage Genset B Phase Over Voltage
B Phase UV Shutdown
shutdown alarm is pending. shutdown alarm is not pending.
Genset Over Current alarm is not
Gen Over Current Genset Over Current alarm is pending.
pending.
High Engine Temperature output is High Engine Temperature output is
High Engine Temperature
active. not active.
Low Fuel LVL Low Fuel level alarm is pending. Low Fuel level alarm is not pending.
Low Oil Pressure alarm is not
Low LOP Low Oil Pressure alarm is pending.
pending.
Mains voltage is not detected to be
Mains High Volt Mains voltage is detected to be high.
high.
Mains voltage is not detected to be
Mains Low Volt Mains voltage is detected to be low.
low.
Oil pressure circuit is detected to be Oil pressure circuit is not detected to
Oil Pressure Open Circuit
open. be open.
Open Gen Contactor Genset contactor is to be open. Genset contactor is not to be open.
Open Mains Contactor Mains contactor is to be open. Mains contactor is not to be open.
Over Frequency shutdown alarm is Over Frequency shutdown alarm is
Over Freq Shutdown
pending. not pending.
Over Speed shutdown alarm is not
Over Speed Shutdown Over Speed shutdown alarm is pending.
pending.
Gross Over Speed Gross Over Speed Shutdown alarm is Gross Over Speed Shutdown alarm is
Shutdown pending. not pending.
Start Relay Cranking command is active. Cranking command is not active.
Temperature circuit is detected to be Temperature circuit is not detected to
Temp Sensor Open Circuit
open. be open.
Under Frequency shutdown alarm is Under Frequency shutdown alarm is
Under Freq Shutdown
pending. not pending.
Under Speed shutdown alarm is Under Speed shutdown alarm is not
Under Speed Shutdown
pending. pending.
Maintenance Due alarm is not
Maintenance Due Maintenance Due alarm is pending.
pending.
Stop Mode Controller is in Stop mode. Controller is not in Stop mode.
Auto Mode Controller is in Auto mode. Controller is not in Auto mode.
Manual Mode Controller is in Manual mode. Controller is not in Manual mode.
Reserved NA NA
Page 96 of 123
KG645 CONTROLLER MANUAL
Interpretation
Digital Output Source
Active when... Inactive when...
Preheat output is to be active as per Preheat output is not to be active as
Preheat Output
preheating setting. per preheating setting.
Digital Input XA* Digital Input XA is active. Digital Input XA is not active.
Digital Input XB* Digital Input XB is active. Digital Input XB is not active.
Digital Input XC* Digital Input XC is active. Digital Input XC is not active.
Digital Input XD* Digital Input XD is active. Digital Input XD is not active.
Digital Input XE* Digital Input XE is active. Digital Input XE is not active.
Digital Input XF (ANX S1
Digital Input XF is active. Digital Input XF is not active.
RES)*
Digital Input XG (ANX S2
Digital Input XG is active. Digital Input XG is not active.
RES)*
Digital Input XH (ANX S3
Digital Input XH is active. Digital Input XH is not active.
RES)*
Digital Input XI (ANX S4
Digital Input XI is active. Digital Input XI is not active.
RES)*
Digital Input XJ (ANX S5
Digital Input XJ is active. Digital Input XJ is not active.
RES)*
Communication between genset Communication between genset
Expansion Module
controller and expansion module is controller and expansion module is
Available*
active. not active.
Table 29: Digital Output Source
23.5 Timers
23.5.1 Cranking
Page 97 of 123
KG645 CONTROLLER MANUAL
Parameter Interpretation
Crank Hold Time The crank output will be active upto this time during cranking.
Crank Rest Time The time between two crank commands.
Crank Start Delay Gets executed only when no output is configured for the engine preheat function.
Table 30: Cranking
23.5.2 General
Parameter Interpretation
Decides the time from engine on for which engine and alternator safety
parameters will be ignored. This timer should be selected sufficiently large so
Safety Monitoring Delay
that no false alarms will be triggered due to transient during genset start-up
procedure.
The time in which a deviation in mains parameters (voltage, frequency) outside
Mains Detect Delay the preconfigured range is allowed before corresponding alarm being
triggered.
The time in which a deviation in genset parameters (voltage, frequency)
Alternator Detect Delay outside the preconfigured range is allowed before corresponding alarm being
triggered.
Page 98 of 123
KG645 CONTROLLER MANUAL
Parameter Interpretation
The delay between (1) Alternator's developing healthy voltage and frequency,
Warm-Up delay and (2) the load being transferred onto the alternator by suitably actuating
contactors.
A delay between the detection of healthy mains return and issuing genset Stop
Return To Mains Delay
command in Auto mode operation of genset.
The time between issuing Stop command and the beginning of actual stopping
Engine Cooling Time sequence. This timer will be skipped in case of shutdown alarms, emergency
stop and repeated “STOP” key input
This timer will start after receiving stop command. After completion of this
Stop Action Time timer, if LOP or engine speed is detected below threshold, then genset will
declared as completely off, otherwise Fail To Stop alarm will be triggered.
The time between one of the genset or mains contactor being opened and the
Load Transfer Delay other contactor being closed during a power transfer event between the
genset and mains.
The time in which, if no activity is detected and engine is OFF, the backlit of
Power Save Mode Delay LCD display will be switched OFF. Go on page Module to enable Power Save
Mode (Refer section 22.1.2).
The time after which a display screen will shift to the next screen. When this
time is set to 0, then screen will not scroll automatically. User will have to scroll
Screen Changeover Time
all the screens excluding ALARMS screen using “UP”/“DOWN” keys. ALARMS
screen will pop up on detection of any alarm.
The time in which, if no activity is detected and engine is OFF, the controller
Deep Sleep Mode Delay enters into Deep Sleep mode. Go on page Module to enable Deep Sleep Mode
(Refer section 22.1.1).
On initiation of an alarm, audible alarm will sound (if configured) upto this
Sounder Alarm Timer
time.
The controller will remain in Test mode, for the preconfigured Test Mode
Test Mode Timer Duration. This timer expires only when engine is running, otherwise controller
remains in this mode for infinite time.
Table 31: General
Page 99 of 123
KG645 CONTROLLER MANUAL
23.6 Generator
The genset specific parameters are divided into sections as shown below.
23.6.1Alternator Configuration
Parameter Interpretation
Allows to select engine operation with or without the alternator. If the
Alternator Present alternator is not fitted, all the relevant parameters will be ignored and disabled.
This will be considered as an engine-only operation.
Number Of Poles Allows to select the number of poles of alternator.
AC System Allows to select AC System as 3 Phase or 1 Phase.
Min Healthy Voltage A threshold above which genset is considered healthy for taking electrical load.
Min Healthy Frequency A threshold above which genset is considered healthy for taking electrical load.
If enabled, the alternator phase sequence (R-Y-B) will be checked. This option
Phase Reversal Detection
will be enabled if AC System is configured as 3 Phase.
Allows to select the action taken by the controller if the alternator phase
reversal condition occurs. Available options:
None: No action will be taken.
Phase Reversal Action Warning: A warning will be displayed.
Electric Trip: The genset will be first unloaded by deactivating the contactor
before the genset being stopped.
Shutdown: Genset will be shutdown.
This alarm will generate if alternator voltage does not cross 50 V-RMS within 2
Alt Voltage Lost Shutdown
seconds after crank disconnect event
Parameter Interpretation
An option to actuate genset and mains contactors if configured as outputs in
Auto Load Transfer the manual mode. If disabled, it is necessary to manually put the load on
genset.
Table 32: Alternator Configuration
Parameter Interpretation
Under-voltage Shutdown Enables or disables Under Voltage shutdown alarm.
Under Voltage Shutdown The voltage value below which the Under Voltage shutdown alarm will be
Threshold triggered.
Under-voltage Warning Enables or disables Under Voltage warning alarm.
Under Voltage Warning The voltage value below which the Under Voltage warning alarm will be
Threshold triggered.
Over-voltage Shutdown Enables or disables Over Voltage shutdown alarm.
Over Voltage Shutdown The voltage value above which the Over Voltage shutdown alarm will be
Threshold triggered.
Over-voltage Warning Enables or disables Over Voltage warning alarm.
Over Voltage Warning The voltage value above which the Over Voltage warning alarm will be
Threshold triggered.
Table 33: Voltage Monitoring
23.6.3Frequency Monitoring
These parameters will be enabled, if the Alternator Present parameter is selected as Yes (Refer section 22.6.1).
Parameter Interpretation
Under-frequency Shutdown Enables or disables Under Frequency shutdown alarm.
Under Frequency Shutdown The frequency value below which the Under Frequency shutdown alarm will be
Threshold triggered.
Under-frequency Warning Enables or disables Under Frequency warning alarm.
Under Frequency Warning The frequency value below which the Under Frequency warning alarm will be
Threshold triggered.
Over-frequency Shutdown Enables or disables Over Frequency shutdown alarm.
Over Frequency Shutdown The frequency value above which the Over Frequency shutdown alarm will be
Threshold triggered.
Over-frequency Warning Enables or disables Over Frequency warning alarm.
Over Frequency Warning The frequency value above which the Over Frequency warning alarm will be
Threshold triggered.
Table 34: Frequency Monitoring
Parameter Interpretation
The primary-side factor for interpretation of CT ratio. The controller assumes
CT Ratio
that the secondary-side factor is 5.
Over-current Threshold The current value above which the Over Current alarm will be triggered.
The time for which a value higher than the preset Over Current Threshold value
Over-current Delay
is allowed before the Over Current alarm being triggered.
Allows to select the action when Over Current condition is detected.
Available options:
None: No action will be taken.
Over-current Action Warning: A warning will be displayed without affecting the operation of genset.
Electric Trip: The genset will be first unloaded by deactivating the contactor
before the genset being stopped.
Shutdown: Genset will be shutdown.
Allows to select the action if an unbalanced load is detected in AC System
configured as 3 Phase. Available options:
None: No action will be taken.
Unbalanced Load Action Warning: A warning will be displayed without affecting the operation of genset.
Electric Trip: The genset will be first unloaded by deactivating the contactor
before the genset being stopped.
Shutdown: Genset will be shutdown.
The threshold on load unbalance, in percentage of per-phase full load. The
unbalance load action will be triggered when
Unbalanced Load Threshold {[(Max kW from R, Y, B)– (Min kW from R, Y, B)] / [Max kW load allowed per
phase assuming 100 % rated load]} * 100 is greater than configured unbalanced
load threshold
The time for which an unbalanced load condition is monitored before the
Unbalanced Load Delay
corresponding action will be taken.
Parameter Interpretation
Decides the genset rating in kW.
This value must be specified as a total load rating
Generator Rating and NOT as per phase load rating.
The load value (as a percentage of full load) above which the selected action for
Over-load Threshold
Over Load alarm will be triggered.
The time for which a value higher than the preset Overload Threshold value is
Over-load Mon Delay
allowed before the Over Load alarm being triggered.
Allows to select the action when Over Load alarm is detected.
Available options:
None: No action will be taken.
Over-load Action Warning: A warning will be displayed without affecting the operation of genset.
Electric Trip: The genset will be first unloaded by deactivating the contactor
before genset being stopped.
Shutdown: Genset will be shutdown.
23.7 Mains
The Mains configuration is divided into sections as shown below.
23.7.1Mains Configuration
Parameter Interpretation
When enabled it displays status of mains on the Mains monitoring screen.
Mains Monitoring
Enables or disables Auto Mains Failure (AMF) mode.
Mains AC System Allows to select Mains AC system as 1 Phase or 3 Phase.
Phase Reversal If enabled, the mains phase sequence (R-Y-B) will be checked.
Allows to select the action taken by the controller. In AMF mode, if the mains
phase reversal condition occurs then genset will start. Available options:
Phase Reversal Action
None: No action will be taken.
Notification: A notification text will be displayed.
Table 37: Mains Configuration
23.7.2Voltage Monitoring
Parameter Interpretation
Enables or disables mains under voltage monitoring. If enabled, the controller
Under Voltage
monitors the mains under voltage condition.
The voltage value below which an under voltage condition for mains is
Under Voltage Trip
detected.
The minimum voltage which must be reached for the mains voltage to be
Under Voltage Return considered healthy. This value is used when an unhealthy mains condition has
been detected.
Enables or disables mains over voltage monitoring. If enabled, the controller
Over Voltage
monitors the mains over voltage condition.
The maximum value for the mains voltage to be considered healthy. This value
Over Voltage Return
is used when an unhealthy mains condition has been detected.
Over Voltage Trip The voltage value above which an over voltage condition for mains is detected.
Table 38: Voltage Monitoring
23.7.3Frequency Monitoring
Parameter Interpretation
Enables or disables mains under frequency monitoring. If enabled, the
Under Frequency
controller monitors the mains under frequency condition.
The frequency value below which an under frequency condition for mains is
Under Frequency Trip
detected.
The minimum frequency which must be reached for the mains frequency to be
Under Frequency Return considered healthy. This value is used when an unhealthy mains condition has
been detected.
Enables or disables mains over frequency monitoring. If enabled, the controller
Over Frequency
monitors the mains over frequency condition.
The maximum value for the mains frequency to be considered healthy. This
Over Frequency Return
value is used when an unhealthy mains condition has been detected.
Parameter Interpretation
The frequency value above which an over frequency condition for mains is
Over Frequency Trip
detected.
Table 39: Frequency Monitoring
23.8 Engine
The engine specific parameters are divided into sections as shown below.
Parameter Interpretation
Allows to select maximum number of start sequences before Fail To Start alarm is
Start Attempts
triggered.
Decides if the oil pressure value is used for crank disconnect operation. If enabled,
Disconnect on LOP Sensor
crank will be disconnected if oil pressure is sensed to be more than a threshold.
The threshold value for the oil pressure above which the cranking command will
Disconnect Pressure Threshold
be withdrawn. This parameter is relevant only if Disconnect on LOP is enabled.
Decides if the oil pressure switch condition is used for withdrawing the crank
Disconnect on LOP Switch command. If enabled, the crank command will be withdrawn as soon as oil
pressure switch stops indicating that oil pressure is low.
Parameter Interpretation
The time for which the oil pressure switch condition should be consistently shown
as Low Oil Pressure before the corresponding crank command withdrawal. Note
LLOP Switch Transient Time that if some other source for crank command withdrawal (such as engine speed
more than Engine Speed Threshold) is reached before this time, then crank is
withdrawn before this time.
Alternator Frequency Threshold on alternator frequency above which the crank command will be
Threshold withdrawn.
Allows to select the engine speed above which crank command will be
withdrawn.
Parameter Interpretation
Allows to select electrical signal to be use for measurement of engine speed.
Available options:
Engine Speed Sense Source Magnetic pickup: Engine speed will be sensed from Magnetic Pickup Unit
(MPU).
Alternator frequency: Engine speed will be sensed from alternator frequency.
Allows to select the number of teeth on flywheel ring gear. This option is
Flywheel Teeth
enabled, if Engine Speed Sense Source is selected as MPU.
Under-speed Shutdown Enables or disables Under Speed shutdown alarm.
Under-speed Threshold The engine speed below which Under Speed alarm will be triggered.
The time for which an engine speed value lower than Under Speed Threshold is
Under-speed Delay
allowed before Under Speed shutdown alarm being triggered.
Over-speed Threshold The engine speed in RPM above which Over Speed alarm will be triggered.
The time for which an engine speed value higher than the preset Over Speed
Over-speed Delay
Threshold is allowed before Over Speed shutdown alarm being triggered.
The percentage speed above Over Speed Threshold to sense the speed very
Gross Over-speed Threshold fast, especially during ramp up and to trip the engine on detecting high speed.
It will shutdown engine immediately.
Minimum engine speed that the genset must achieve within 2 seconds from
Healthy-speed Threshold
crank disconnect event.
Table 41: Speed Monitoring
23.8.3Battery Monitoring
Parameter Interpretation
Allows to select the action if the Low Battery Voltage condition is detected.
Available options:
None: No action will be taken.
Low Battery Voltage Action Warning: A warning will be displayed without affecting the operation of genset.
Electric Trip: The genset will be first unloaded by deactivating the contactor
before genset being stopped.
Shutdown: Genset will be shutdown.
Low Battery Voltage The value of battery voltage below which the Battery Under Voltage alarm will
Threshold be triggered.
The time for which battery voltage value lower than Low Battery Voltage
Low Battery Voltage Delay
Threshold is allowed before the Battery Under Voltage alarm being triggered.
Allows to select the action if the High Battery Voltage condition is detected.
Available options:
None: No action will be taken.
High Battery Voltage Action Warning: A warning will be displayed without affecting the operation of genset.
Electric Trip: The genset will be first unloaded by deactivating the contactor
before genset being stopped.
Shutdown: Genset will be shutdown.
High Battery Voltage The value of battery voltage above which the Battery Over Voltage alarm will
Threshold be triggered.
The time for which battery voltage value higher than High Battery Voltage
High Battery Voltage Delay
Threshold is allowed before the Battery Over Voltage alarm being triggered.
Table 42: Battery Monitoring
Parameter Interpretation
Allows to select the action if the charging alternator fail (Charge Fail) condition is
detected. Available options:
None: No action will be taken.
Charging Alternator Fail
Warning: A warning will be displayed without affecting the operation of genset.
Action
Electric Trip: The genset will be first unloaded by deactivating the contactor
before genset being stopped.
Shutdown: Genset will be shutdown.
Charging Alternator Fail The voltage at the charge alternator fail input terminal, below which the Charge
Threshold Fail alarm will be triggered.
The time for which voltage value (at charge alternator fail input terminal) lower
Charging Alternator Fail
than Charging Alternator Fail Threshold is allowed before the Charge Fail alarm
Delay
being triggered.
Table 43: Charging Alternator Monitoring
23.8.5 Preheat
To enable the Preheat, configure one of the digital output as the Preheat Output (Refer section 22.4).
Parameter Interpretation
Preheat Timer is used for engine smoke reduction and better cold start. The
Preheat Timer Preheat Output will be active for this duration. If this timer is configured, Crank
Start Delay will not considered.
Engine Temperature Limit Temperature Enable decides whether the coolant temperature is used for
controlling the Preheat Output. If enabled, the Preheat output is deactivated
Engine Temperature when the coolant temperature is sensed to be higher than the Temperature
Limit.
Table 44: Preheat
23.9 Maintenance
Parameter Interpretation
Alarm action on logged engine hours or service due date, which ever occurs
first. Available options:
Alarm Action
Notification: Notification text will be displayed on LCD screen.
Warning: A warning will be displayed without affecting the operation of
genset.
Due At Engine Hours Maintenance Due alarm will be triggered when the engine has run for more
than specified number of hours or if maintenance service due date
Alarm Due Date occurred, whichever happens first.
23.10.1 General
Parameter Interpretation
Allows to select the Actuator application. Available options:
Actuator Application
As E-Governor or As Start/Stop Device
Actuator frequency multiplying factor. The frequency at which Actuator
Actuator Speed
controls the engine.
Allows to select the Actuator direction to stop the engine. This direction
depends on the engine design. The Actuator is viewed from the shaft side.
Available options:
Actuator Direction
Clockwise: Actuator will rotate in clockwise direction to stop the engine.
Anti clockwise: Actuator will rotate in anti-clockwise direction to stop the
engine.
Table 46: General
Parameter Interpretation
Cranking Steps Number of pulses issued to the Actuator.
Time for which engine stays at low idle speed (used for ramping-for smoke
Initial Low Speed Delay
reduction)
Initial Low Speed Low Idle Speed
The speed governor recognizes that the engine cranking action is initiated once
the
Crank Sense Speed
engine speed exceeds this value. Upon recognition, the governor executes the
Cranking Steps and then initiates the low speed governing phase.
Ramp Up Time Time taken by the engine to ramp the speed from initial low to target speed
Table 47: Engine Start Strategy
If Actuator Application is configured As Start/Stop Device, then following tab will popup.
Parameter Interpretation
Allows to select speed governing type. Available options:
Fixed Speed (0 % Droop): Fixed speed application.
Set Speed Selection
Speed Bias Input (0-5 V): Paralleling support application
Load Based Droop: Configurable droop application
Droop The percentage drop in the speed of engine from no load speed.
Target Speed Decides the target governing speed.
Proportional Gain (Kp) Decides the response of the controller in terms of the responsiveness of the
Integral Gain (Ki) controller to an error, the degree of speed oscillations and the degree to which
Derivative Gain (Kd) the controller overshoots or undershoots the target governing speed.
Friction Setoff To ensure wear and tear free operation of linkage and Actuator.
Gain Schedule Trigger Percentage RPM that triggers the engine overshoot/undershoot condition.
Loading Factor
To scale the PID control loop parameters.
Unloading Factor
Table 48: Generator EGov Configuration
Parameter Interpretation
Target Speed Decides the target governing speed.
Proportional Gain (Kp)
Decides the response of the controller in terms of the responsiveness of the
Integral Gain (Ki) controller to an error, the degree of speed oscillations and the degree to which the
controller overshoots or undershoots the target governing speed.
Derivative Gain (Kd)
Friction Setoff To ensure wear and tear free operation of linkage and Actuator.
Gain Schedule Trigger Percentage RPM that triggers the engine overshoot/undershoot condition.
Loading Factor
To scale the PID control loop parameters.
Unloading Factor
Table 49: Engine EGov Configuration
Electronic Governor parameters are not intended to be changed in the field without
consulting experts.
Expansion module parameters will be enabled if the Expansion Module is enabled (Refer section 22.1).
Following is an example showing configuration of Analog Input EX-S1 as a Pressure sensor (resistive).
Parameter Interpretation
Decides how the input will be interpreted. Available options:
Not used: The input will not be used.
Digital Input XF: The selected sensor input will be used as digital input. The
parameters identical to digital inputs will be displayed and the input can
configured in the same way as that of digital input being configured (Refer
Use Input As
section 22.2 and 22.2.1).
Pressure Sensor: The input will be used as analog input for pressure sensor
(resistive).
Temperature Sensor: The input will be used as analog input for temperature
sensor (resistive).
Allows to select the action taken by the controller if undesirable condition is
detected. Available options:
None: No action will be taken.
Warning: A warning will be displayed without affecting the operation of
Action
genset.
Electric Trip: The genset will be first unloaded by deactivating the contactor
before genset being stopped.
Shutdown: Genset will be shutdown.
The text string entered here will distinguish the corresponding sensor from the
Name
sensors on other terminal.
Allows to select alarm generation condition. Available options:
Less Than Threshold: Alarm will be generated if measured sensor value is less
Threshold Type than selected threshold.
Greater Than Threshold: Alarm will be generated if measured sensor value is
greater than selected threshold.
Allows to select the threshold on the measured sensor value above/below
Threshold
which selected action for undesirable condition will be triggered.
Allows to select alarm generation condition, when the selected sensor circuit
open condition is detected. Available options:
None: No action will be taken.
Warning: A warning will be displayed without affecting the operation of
Circuit Open Fault
genset.
Electric Trip: The genset will be first unloaded by deactivating the contactor
before genset being stopped.
Shutdown: Genset will be shutdown.
A table that defines relation between the sensor value and corresponding
Sensor Calibration Table
physical quantity.
Analog Input EX-S1, Analog Input EX-S2, Analog Input EX-S3, Analog Input EX-S4 and Analog Input EX-S5 can be
configured as Digital Inputs. Refer section 22.2 and 22.2.1 for configuration details.
Extended Digital Outputs can be configured same as that of controller Digital Outputs (Refer section 22.4 and
22.4.1).
24 Menu Bar
Toolbar is located at the top of the screen.
• Connect KG-645 controller to PC. Put the controller in Programming mode (Refer section 8).
• Now, enter the Engine Serial No (optional).
• Browse and select configuration file. On selecting this file, profile name will be read from file and
displayed on screen of the flashing utility.
• Now, select Write To Device. This tab will be active only when connection between KG -645 controller and
PC is active. Once the configuration is written to device, confirmation window will be shown.
Disclaimer: Due to continuous development, the details provided in this document are subject to change
without any prior notice.