Abbas y 2001

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

SPE 71478

Field Testing Coriolis Mass Flowmeter in Central Ghawar, Saudi Arabia


Imran Abbasy, SPE, Saudi Arabian Oil Company

Copyright 2001, Society of Petroleum Engineers Inc.

This paper was prepared for presentation at the 2001 SPE Annual Technical Conference and Introduction
Exhibition held in New Orleans, Louisiana, 30 September–3 October 2001.
The test separators in Uthmaniyah Gas Oil Separation Plants
This paper was selected for presentation by an SPE Program Committee following review of
information contained in an abstract submitted by the author(s). Contents of the paper, as
(GOSPs) were originally equipped with a turbine flowmeter
presented, have not been reviewed by the Society of Petroleum Engineers and are subject to for oil/water emulsion flowrate and a capacitance type meter
correction by the author(s). The material, as presented, does not necessarily reflect any
position of the Society of Petroleum Engineers, its officers, or members. Papers presented at to measure water cut. In a low water cut environment, these
SPE meetings are subject to publication review by Editorial Committees of the Society of
Petroleum Engineers. Electronic reproduction, distribution, or storage of any part of this paper
measurements were reliable and results were representative of
for commercial purposes without the written consent of the Society of Petroleum Engineers is the well behavior. With the maturing of the field, most wells
prohibited. Permission to reproduce in print is restricted to an abstract of not more than 300
words; illustrations may not be copied. The abstract must contain conspicuous now flow at high water cuts and consequently inaccuracies
acknowledgment of where and by whom the paper was presented. Write Librarian, SPE, P.O. were experienced in the water cut meter measurements. These
Box 833836, Richardson, TX 75083-3836, U.S.A., fax 01-972-952-9435.
inaccuracies were not entirely unexpected, as theses devices
are only suitable for oil-continuous phases. A field test
Abstract conducted by Saudi Aramco concluded that the capacitance
Field test results of a Coriolis mass flowmeter are presented water cut meters were unable to accurately measure water cuts
for a crude oil gathering facility located in a mature part of the above 40%, and as such an alternative mode of measurement
Ghawar field in Saudi Arabia. Due to the maturity of the field, was required to overcome this shortcoming1 .
conventional well test measurements under low flow rate and
high water cut conditions suffered from inaccuracies and gave Saudi Aramco started field-testing various multi phase
erroneous and sometimes incorrect readings; consequently meters in the early 1990s. The objective of this initiative was
there was a need to find a replacement mode of measurement. to select an appropriate technology to measure phase fractions
This paper highlights advantages mass flowmeter technology under various operating conditions and to take advantage of
has to offer under such difficult conditions. The Coriolis new technology that was becoming available. Furthermore,
technology has been around for several years but its reliability and maintenance support was also evaluated for
performance has not been adequately documented in oilfield each type of meter tested. The meters were tested under
applications and only recently has become economically different operating conditions and performance was carefully
viable and user-friendly as a result of the manufacturer’s evaluated2 . A Coriolis mass flowmeter was field-tested on an
efforts to expand their application base. onshore location in Saudi Arabia and the results were found to
be within 10% of the test separator measurement and thus
In the past, 3-phase testing was necessary due to inability of deemed acceptable. There were no operational problems
conventional sensors to accurately measure flow at low and reported during this testing.
high water cut ranges. The instrumentation was expensive to
maintain and large quantity of chemicals were required to The presence of small fraction of gas in the liquid stream
achieve proper separation. Moreover, error was introduced due generally has little effect on the mass flow reading3 . In
to an additional water rate measurement that was necessary to situations where there is a larger gas fraction in the liquid
quantify the total water production. stream, the accompanying density change is interpreted as a
decrease in water cut. Furthermore, mass flow readings are
This field test covered a very wide range of flow rates and also flawed due to the absorption of vibration energy by the
water cuts and gave an insight into the improvements this gas. It is clear therefore, that Coriolis mass flowmeters are
technology has to offer. The test results established the better suited for applications downstream of the separator or
accuracy and repeatability of this measurement. This where the liquid is flowing above the bubble point. For the test
technology has therefore been adopted as the primary separator application, the actual retrofit of the vessel was
measurement for all well testing in Central Ghawar where the relatively straightforward to implement and thus considered an
water cut ranges are extreme. The field test also concluded added advantage.
that 3-phase testing was no longer necessary, which resulted in
significant saving in maintenance and chemical costs.
2 IMRAN ABBASY SPE 71478

The turbine flowmeter, being a mechanical device, requires Qt is the flowrate measured by the Coriolis meter and Qw and
a minimum flow to overcome friction. Consequently, there is a Qo are the calculated water and oil rates, respectively. These
minimum flow threshold below which the flowmeter does not rates are instantaneous, which are accumulated and averaged
make any measurement. The turbine flowmeter installed in the by the NOC to provide total barrels and average production
plant has a limited accuracy outside the 3 to 30 thousand rate in barrels/day.
barrels per day (MBD) range and the readings tend to be
unreliable and non-repeatable whenever the flow rates fall Field Test Methodology
outside this band. As the fields mature, more and more wells Excessive pressure drop across the sensor can cause gas
are producing at low flow rates and deterioration in flowmeter breakout, thereby introducing 2-phase flow condition in the
performance becomes very evident. flow tubes. This can result in an improper operation of the
sensor. High fluid velocity through the flow tubes can also
Theory of Operation cause erosion. Therefore, care should be taken when sizing the
Coriolis mass flowmeter technology has evolved over the sensor to ensure that pressure drop and fluid velocity are
years from a relatively niche application to widespread within the recommended limit. For this application, ELITE®
commercial use. Chevron took the initiative and worked with CMF-400 sensor was selected, which can handle >60 MBD.
a Coriolis -meter manufacturer to develop a Net Oil Computer This is a 4” diameter, Stainless Steel 316L device and is the
(NOC) system that provides accurate data from 0 to 100% largest size available in this range. Micro Motion (a division
water cut. This work4 is now the basis of most of the of Emerson Process Management) manufactures this Coriolis
commercial Coriolis meters available in the market today. mass flowmeter. The sensor is shown in Figure 1.

Water cut measurement has been the source of large errors Micro Motion sensor measures the flow rate accurately over
in testing producing wells. Conventional water cut meters are a 100:1 turndown ratio and density in the range of 0 to 5
either operating on the capacitance principle or the differential gm/cc. Consequently, the sensor measures water cut in the
head pressure measurements. Capacitance meters provide range of 0-100%. Pressure drop through the device is minimal
reasonable accuracy in oil continuous emulsion range in low and is generally less than 5 psi. The Micro Motion is equipped
water cut environments. However, large discrepancies are with a NOC that produces real-time measurements of water
introduced in these measurements at higher water cut, or cut, net oil volume flow and net water volume flow. The oil
where the oil/water emulsion has a water-continuous phase. and water densities at 60°F are manually entered into the NOC
Differential pressure transducers on the other hand perform or measured on-line, if desired. The sensor measures the actual
poorly due to the fact that friction correction between the two fluid temperature, density and mass flow rate, and then the
measuring points is difficult to quantify. NOC extrapolates the standard densities to the operating
temperature. The water cut is calculated at the operating
A Coriolis meter consists of a flow tube that vibrates due to temperature (using Equation 1), and then referenced back to
an electro-magnetic drive coil mechanism. Fluid flow through 60°F.
this tube introduces a twisting motion and the magnitude of
this twisting motion is proportional to the mass flow-rate. Oil density is well known for a particular area, however
Similarly, the vibrating frequency of this tube is related to the water density can vary significantly depending on where the
density of the fluid flowing through it. Instantaneous water cut well is located in relation to the flood front. For this test, 8
(Yw ) is then calculated by the measured emulsion density (ρm) wells were sampled randomly in the area and it was
using the following equation: determined that the water density was in the range of 1.0435
and 1.0628 gm/cc. Seawater is 1.0484 gm/cc, which
Yw = (ρ m - ρ o ) / (ρ o - ρ w ) ………………… (1) corresponds to 36,000 mg/L Chlorides. The maximum
variation in water cut due to maximum expected error in water
ρ o and ρ w are the densities of crude and produced water density was calculated to be about 1%. It was therefore
respectively. As is apparent, these parameters have to be decided to use a fixed density of 1.0547 gm/cc for all testing.
known with certainty and input in the NOC. The Coriolis mass It was however recognized that this approach would be too
flowmeter measures the operating temperature of the fluid simplistic in an environment that was not as mature as ours,
stream, which is used to correct the above densities to some and where injection and formation water mixing had not
temperature base, usually 60°F. Oil and water phase flowrates occurred to this extent. For oil density, an average value of
are then calculated as follows: 0.8371 gm/cc was used and found to be accurate for all the
wells that were tested.
Qw = Yw . Qt …………………………. (2)
The Coriolis flowmeter was installed upstream of the
Qo = Qt – Qw …………………………. (3) Halliburton turbine meter and the capacitance water cut
(BS&W) meter of the test separator. A schematic of test
separator instrumentation is given in Figure 2.
SPE 71478 FIELD TESTING CORIOLIS MASS FLOWMETER IN CENTRAL GHAWAR, SAUDI ARABIA 3

This interim retrofit was used to check the Micro Motion Tests were considered to be good when the test separator
readings against the conventional test separator measurements. and the Micro Motion measurements met one of the above two
Since this instrumentation was on the oil outlet of the test conditions. This incidentally is also the standard that is used
separator, it was necessary to test the wells in 2-phase mode to for validating routine well tests within Aramco. The results for
get a representative comparison. In cases where the test the wells tested are plotted in Figure 4 and 5 along with a
separator was incapable of giving a representative rate, 3- 10% error band.
phase testing was also done and compared against Micro
Motion measurements in 2-phase mode. The performance of the Micro Motion against conventional
test separator measurements for all tests was as follows:
Correction for Shrinkage
The conventional oil measurements from the test separator are Oil Rate: 85% (69 tests were valid)
used for projecting the oil deliverability from the field, Water Rate; 75% (61 tests were valid)
consequently it is critical that the volumetric rates measured
are corrected to a condition which are commensurate with As can be seen from Figures 4 and 5, the error in oil and
what is being delivered downstream of the crude stabilization water rates were essentially due to errors in water cut
plant. measurements. This was not entirely unexpected as sited
earlier on in this paper. Reasons underlying these
In the past, a set of shrinkage factors were used to correct discrepancies were investigated and the findings are given
the test separator oil rates to the stock tank barrels downstream below:
of the crude stabilization plant. These factors compensate for
temperature as well as pressure. The Micro Motion readings Water Cut. It was observed that water cut reading did not
are already corrected to 60°F, therefore a new set of shrinkage match the conventional water cut meter at very low and high
values had to be determined to account for pressure shrinkage water cuts, hence the water rates were falling outside the
alone. acceptable range (Figure 5). The conventional water cut
measurement works on the capacitance principle and one
A commercial process simulator was used to develop a set would expect that there would be inaccuracies at the low and
of shrinkage factors to take into account the various test the high end due to the inherent limitation of this gauge.
separator operating pressures and temperatures. The
simulation data was curve fit using a 3-dimensional curve- In high water cut situations, water-continuous phase flowing
fitting program, to generate a 3-D shrinkage curve, shown in through the BS&W meter was electrically shorting out the
Figure 3. The simulation used a calibrated model for the capacitance probe, thereby giving a water cut reading that was
plant. The test separator oil inlet was flashed at a pressure significantly higher than actual. This pattern was very
ranging from 100 psig to 160 psig and a temperature ranging consistent at high water cuts. Micro Motion read a relatively
from 70°F to 180°F. Then the test separator oil was flashed to lower water cut, whereas the BS&W meter constantly gave
50 psig to simulate the second stage separation conditions and artificially high water cut readings. As a result, water rate was
flashed again to a Reid Vapor Pressure (RVP) of 10 psia to over-estimated and oil rate underestimated by the conventional
simulate the stock oil conditions at the crude stabilization well test system. This phenomenon was apparent at water cuts
plant. These factors are a function of the test separator in excess of 75%.
temperature and pressure.
At water cuts below 5%, oil-continuous phase dominates the
Test Results flow through the BS&W meter. The insulating property of oil
The field test was carried out over the period February to May forces the capacitance probe to underestimate water and hence
2000. A total of 81 tests were done in 2-phase mode through show predominantly oil. Micro Motion on the other hand
the test separator. Some wells were also tested in 3-phase consistently saw small quantities of water. Salt analysis of the
mode so that all possible operating scenarios were compared. samples confirmed the presence of water in these supposedly
Total number of wells tested was 41. The wells were chosen dry oil producers. Although water cut from Micro Motion is
with the objective of subjecting the Micro Motion to the entire an average measured over a certain period of time, the values
spectrum of flow rates and water cuts that we encounter in the were generally closer to the sampled water cuts in comparison
plant. The liquid from the test separator oil outlet was to the BS&W meter measured water cuts. The BS&W meter is
measured by the Micro Motion and compared against the therefore limited in accuracy to the intermediate range.
conventional test trap measurements. The validity criteria
chosen was, Flow Rate. During the test it was observed that at low flow
rates (<2 MBD), Micro Motion generally read higher than the
Difference in Rate < 500 bbls/day or < 10% Halliburton turbine flowmeter (Figure 4). To fully understand
this phenomenon, refer to the test separator schematic (Figure
2). The objective of the Level Control Valve (LCV) on the 4”
line is to hold level in the vessel. Consequently, this LCV
4 IMRAN ABBASY SPE 71478

tends to be either barely cracked open or fully closed for low water volumes between tests. Out of the 22 tests that were
flow rates. At higher rates however, this LCV remains wide repeated in 18 wells, only one test did not repeat within 10%
open most of the time. During the installation of the Micro and a vast of majority repeated within 5%.
Motion it was observed that the 4” LCV 4003-2, and possibly
the 2” LCV 4003-1, were leaking. This was discovered as the Material selection is one of the critical points to be
turbine read zero flow with these LCVs closed, whereas the considered while selecting a Coriolis mass flowmeter for
Micro Motion read a small rate. Once the upstream block crude oil applications, as produced oil often contains high
valve was closed, both these meters read zero flow. levels of Chloride ions and Hydrogen Sulphide. Generalized
corrosion tables are not sufficient for selecting the material of
As discussed earlier, a turbine flowmeter requires a Coriolis sensors, as these tables do not take into account effect
minimum flow to overcome friction and to start measuring. of cyclic loading to which Coriolis sensors are subjected.
This threshold flowrate is not always achieved due to surging Corrosion in combination with cyclic loading causes corrosion
and in wells that have low productivity. In an attempt to fatigue that can lead to cracking of sensor flow tubes.
ensure that this minimum flow is maintained through the Therefore, for such applications it is generally recommended
turbine meter at all times, an over-lock system was designed to use Hastalloy-C sensor, which is a Nickel-based Stainless
on the test separator LCVs that would close the outlet valves Steel alloy with vastly superior corrosion resistance and higher
of the vessel during low flow rate situations. Once a flow that strength.
is sufficient to start the turbine meter is established in the trap,
the valves would open. Therefore, due to leaking LCVs and Conclusions
friction, the turbine flow rate inherently lagged behind the The results of the field test established the accuracy and
Coriolis mass flowmeter rate on a cumulative basis. repeatability of the Coriolis mass flowmeter over the entire
range of flow. The measurement does not suffer from the
During 3-phase testing, some of the water is separated from inherent non-linearity problems of the conventional
the wet crude by injecting demulsifier, and then each stream is capacitance water cut meters. The device is robust, reliable
measured separately using turbine flowmeters to give a total and as there are no moving parts, maintenance requirements
water rate. This summation from two separate devices results are minimal.
in a higher measurement error. As per the manufacturer, the
turbine flowmeter has a turndown ratio of 1:10 and a range of 3-phase testing is no longer necessary in a high water cut
30 MBD. Therefore, the device is inaccurate at rates below 3 environment and therefore all related instrumentation is
MBD. redundant. All piping and instrument loops associated with the
turbine flowmeter and the capacitance water cut meter on the
During 2-phase testing, the turbine meter calculates the flow oil outlet can be removed. Moreover, since testing is to be
rate and the water cut meter measures the water cut in the done in 2-phase only, all water outlet piping and associated
fluid. The rates are then calculated as in equations 2 and 3. It instrumentation can also be decommissioned. Dismantling of
is clear that any error in water cut would have a direct effect this redundant hardware would result in substantial saving in
on the calculated oil and water rates. terms of maintenance costs.

All the above problems were inherent to the instrumentation Future Plans
and equipment at the GOSP and therefore had no bearing on It has been decided to gradually phase out all 3-phase testing
the performance of the Micro Motion. Consequently, tests at in plants where water cuts are high. Several plants in Central
low flow rate (<2 MBD), low water cut (<5%) and high water Ghawar are now targeted for the installation of Coriolis mass
cut (>75%) applications were not taken as a benchmark and flowmeters, which would translate to lower maintenance and
excluded from the comparison. The performance of the Micro demulsifier costs; and above all, provide more accurate and
Motion was then as follows: repeatable data. A plan is also underway to retrofit these test
separators for 2-phase testing and eliminate unnecessary
Oil Rate: 94% (76 tests were valid) hardware.
Water Rate: 85% (69 tests were valid)
An initiative is also underway to validate the simulated
It should be kept in mind that some of the tests that shrinkage factors against laboratory-derived parameters. Once
remained invalid were on wells, which have a history of this study is complete, these factors will be applied for oil
giving erratic results. Some of these wells were high water cut, allocations and projections for all plants.
low rate and prone to surging. Testing on these wells over the
past six months had not been very consistent and there were At this time CMF-400 is only available in Stainless Steel.
large variation in rates. Consequently, their invalidity had to CMF-300 is available in Hastalloy-C metallurgy, however it is
do with well behavior rather than any instrumentation per se. restricted to about 24 MBD flow rate. Based on the review of
The issue of Micro Motion repeatability was studied in wells in the area, CMF-300 should be adequate for this
detail. The repeatability criteria chosen was 10% of oil and application and thus this metallurgy issue will be resolved.
SPE 71478 FIELD TESTING CORIOLIS MASS FLOWMETER IN CENTRAL GHAWAR, SAUDI ARABIA 5

Acknowledgments
The author would like to thank F.A. Hajji, D.P. Delavan and HPTT
D-401 0-100% watercut
S.G. Barlow of Saudi Aramco for their input and invaluable meter AT
4001
comments while writing this paper. Thanks are also due to Water
Outlet
Oil LCV-4003-1
Outlet
Asghar Satvilker of Fisher Rosemount for providing product
information. This is used
only during 3- To LPPT
Strainer
phase testing LCV-4003-2
References FM-4003
Turbine
MicroMotion
1. Stephens, J.F., “Report on Flowmeter and Water Cut Tests in
Hawtah,” Saudi Aramco, Internal Correspondence, November 30,
1992.
2. Al-Taweel, A.B., and Barlow, S.G., “Field Testing of Multiphase To WOSEP
Meters,” SPE 56583, presented at the 1999 SPE Annual Technical Strainer
LCV-4001
FM-4002
Conference and Exhibition, Houston, Texas, October 3-6, 1999. Turbine

3. Taylor, R.D.H., and Nuttall, R.C.H., “On-Line Well Monitoring


and its Application in South Oman Oil Field,” SPE 25619,
presented at the SPE Middle East Oil Technical Conference and
Figure 2 - Instrument Schematic – Test Separator.
Exhibition, Bahrain, April 3-6, 1993.
4. Aslesen, K.S., Bocek, R., Canfield, D.R., and Liu, K.T., “Method
and Apparatus for Testing the Outflow from Hydrocarbon Wells
on Site,” U.S. Patent 4,689,989, September 1, 1987. Micro Motion Shrinkage Factors
Rank 4 Eqn 310
r^2=0.99996061 DF Adj r^2=0.99991685 FitStdErr=0.00010091333 Fstat=28209.729
z=a+bx+cy+dx^2+ey^2+fxy+gx^3+hy^3+ixy^2+jx^2y
a=0.97859106 b=0.00041258311 c=-0.000621469 d=-4.4534132e-07 e=1.9128087e-06
f=1.3221692e-06 g=-3.6910966e-09 h=-2.133067e-09 i=-6.0240899e-09 j=3.1248812e-09

0.995
0.99
0.995 0.985

Shrinkage Factor
0.99 0.98
0.985 0.975
Shrinkage Factor

0.98 0.97
0.975 0.965
0.97 0.96
0.965 0.955
0.96 0.95
0.955 170
160
150
0.95 140
130
150 120
140 110
130 100
90 Separator Temp., deg.
120 80
Separator Pressure, PSIG 110 70 F
100

z = a + bx + cy + dx^2 + ey^2 + fxy + gx^3 + hy^3 + ixy^2 + jx^2y


[Where z = Shrinkage Factor, x = Temperature (°F) and y = Pressure
(psig)]

Figure 3 - Shrinkage Factors from the Process Simulator.

Figure 1 - Micro Motion CMF-400 Elite® Meter.


6 IMRAN ABBASY SPE 71478

20000
18000
MIRCO MOTION, bbls/day

16000
14000
12000
10000
8000
6000
4000
2000
0
0 5000 10000 15000 20000
Test Separator, bbls/day

2-Phase 3-Phase

Figure 4 - Total Fluid, Oil + Water - Micro Motion vs.


Turbine Flowmeter.

100%
90%
80%
MICRO MOTION

70%
60%
50%
40%
30%
20%
10%
0%
0% 20% 40% 60% 80% 100%
Test Separator

2-Phase 3-Phase

Figure 5 - Water Cut - Micro Motion vs. BS&W Meter.

You might also like