STRUCTURAL DESIGN CALCULATION

Project .:
MAIN RECEIVING SUB-STATION (MRSS)

Client .:

LOC. NO.: PROJECT NO.: DOCUMENT NO.: REV. NO.:

- - - -
STRUCTURAL DESIGN CALCULATION

Project .:
MAIN RECEIVING SUB-STATION (MRSS)

Client .:

A Issued for Approval S.H.A S.H.A - -

REV Description Prep'd Chk'd App'd Date

TITLE

STRUCTURAL DESIGN CALCULATION

LOC. NO.: PROJECT NO.: DOCUMENT NO.: REV. NO.:

- - - -
PROJ NAME. SUB-STATION (MRSS)

CLIENT. -

PROJ NO. -

JOB NO. -

DOC NO. -
JOB TITLE A. Design Criteria
LOC. -

A. DESIGN CRITERIA

1 APPLICABLE BUILDING CODES

a Building Codes - MNBC-2016


b Steel Design - AISC 360-05
c Reinforced Concrete Design - ACI 318-05

2 DESIGN LOADS

a Roof Live Load - 0.96 kN/m2


2
b Construction Live Load - 0.96 kN/m
c Wall Load - 0.73 kN/m

3 MATERIAL SPECIFICATIONS

a Concrete (Cylindrical)
Compressive Strength, f'c = 24 Mpa
b Reinforcing Steel
Yield Strength, Fy = 420 Mpa
c Structural Steel
Yield Strength, Fy= 235 Mpa
Fracture Strength, Fu= 400 Mpa

4 Wind Load
a Basic Wind Speed mph
b Exposure Catergory C
c Important Factor 1
d Topographical Factor, Kzt 1
e Gust Factor 0.85
f Directionality Factor, Kd 0.85

pg 1
PROJ NAME. SUB-STATION (MRSS)

CLIENT. -

PROJ NO. -

JOB NO. -

DOC NO. -
JOB TITLE A. Design Criteria
LOC. -

5 EARTH QUAKE

a Region Yangon
b Occupancy Catergory 1.0
c Spectral Response Acceleration, Ss 0.77
d Sepctral Response Acceleration, S1 0.31
e Site Class D
f Seismic Design Catergory D
g Site Coefficient, Fa 1.192
h Site Coefficient, Fv 1.74
i Design Spectral Acce. Parameter, SDS 0.612
j Design Spectral Acce. Parameter, SD1 0.36

BUILDING TRANSVERSE DIRECTION


Intermediate Concrete Moment Frame
a Building Framing System
b Response Modificaiton Coefficient, R 5
c System Overstrength Factor, Ω0 3
d Deflection Amplification Factor, Cd 4.5

BUILDING LONGITUDINAL DIRECTION


Intermediate Concrete Moment Frame
a Building Framing System
b Response Modificaiton Coefficient, R 5
c System Overstrength Factor, Ω0 3
d Deflection Amplification Factor, Cd 4.5

pg 2
PROJ NAME. SUB-STATION (MRSS)

CLIENT. -

PROJ NO. -

JOB NO. -

DOC NO. -
JOB TITLE A. Design Criteria
LOC. -

6 LOAD COMBINATION

Foundation Design (RC) (MNBC-2016)

Dead Load Live Load WX WY EQX EQY

1.) 1 - - - - -
2.) 1 1 - - - -
3.) 1 0.75 - - - -
4.) 1 1 0.75 - - -
5.) 1 1 -0.75 - - -
6.) 1 1 - 0.75 - -
7.) 1 1 - -0.75 - -
8.) 1 1 - - 0.7 -
9.) 1 1 - - -0.7 -
10.) 1 1 - - - 0.7
11.) 1 1 - - - -0.7
12.) 1 0.75 0.75 - - -
13.) 1 0.75 -0.75 - - -
14.) 1 0.75 - 0.75 - -
15.) 1 0.75 - -0.75 - -
16.) 1 0.75 - - 0.525 -
17.) 1 0.75 - - -0.525 -
18.) 1 0.75 - - - 0.525
19.) 1 0.75 - - - -0.525
20.) 0.6 - 1 - - -
21.) 0.6 - -1 - - -
22.) 0.6 - - 1 - -
23.) 0.6 - - -1 - -
24.) 0.6 - - - 0.7 -
25.) 0.6 - - - -0.7 -
26.) 0.6 - - - - 0.7
27.) 0.6 - - - - -0.7

pg 3
PROJ NAME. SUB-STATION (MRSS)

CLIENT. -

PROJ NO. -

JOB NO. -

DOC NO. -
JOB TITLE A. Design Criteria
LOC. -

For Super Structure Design (RC) (MNBC -2016)

Dead Load Live Load WX WY EQX EQY

1.) 1.4 - - - - -
2.) 1.2 1.6 - - - -
3.) 1.2 1.6 0.8 - - -
4.) 1.2 1.6 -0.8 - - -
5.) 1.2 1.6 - 0.8 - -
6.) 1.2 1.6 - -0.8 - -
7.) 1.2 1 1.6 - - -
8.) 1.2 1 -1.6 - - -
9.) 1.2 1 - 1.6 - -
10.) 1.2 1 - -1.6 - -
11.) 1.2 1 - - 1-
12.) 1.2 1 - - -1 -
13.) 1.2 1 - - - 1
14.) 1.2 1 - - - -1
15.) 0.9 - 1.6 - - -
16.) 0.9 - -1.6 - - -
17.) 0.9 - - 1.6 - -
18.) 0.9 - - -1.6 - -
19.) 0.9 - - - 1-
20.) 0.9 - - - -1 -
21.) 0.9 - - - - 1
22.) 0.9 - - - - -1

pg 4
PROJ NAME. SUB-STATION (MRSS)

CLIENT. -

PROJ NO. -

JOB NO. -

DOC NO. -
JOB TITLE A. Design Criteria
LOC. -

7 Design Parameters

Material Usage

1.) Piles, Pile Caps, Beam And Column 30 Mpa ( Grade 30)

2.) Rebar, Grade 60 420 Mpa

8 Concrete Design

A. Concrete Cover
Cover To Alll Reinforcement To Be As Follows.

- Concrete Cast In Water 100 mm


- Concrete Cast Against And Permanently Expo-
sed To Earth 80 mm

- Concrete Exposed To Earth Or Weather


Bar Dia > 29 mm 60 mm
19 mm <= Bar Dia <= 25 mm 50 mm
Bar Dia <=16 mm 40 mm

- Concrete Not Exposed To Earth Or Weather


Slabs, Walls And Joists:
Bar Dia >35 mm 40 mm
Bar Dia <= 35 mm 40 mm

- Beams, Columns
Concrete Exposed To Salt, Salt Water And Sea Water
Walls And Slab With 16 mmm Diameter And Smaller 50 mm
All Members And Other Than Noted Above 80 mm

pg 5