Breaker Rating (In) Correction Factors: Voltage Drop Calculation (Mcc23 Final Circuits)
Breaker Rating (In) Correction Factors: Voltage Drop Calculation (Mcc23 Final Circuits)
CUMULATIVE VOLTAGE
TABULATED CURRENT
CORRECTION
SELECTED CABLE
FACTORS
MINIMUM CABLE
LOAD CURRENT
SIMULTANEOUS
NO. OF CORES
DEMAND kVA
REF/CKT NO
VD FACTOR
OVERLOAD
DROP IN %
AMPACITY
SIZE(mm2)
CAPACITY
VOLTAGE
LENGTH
CORRECTION @
TEMPERATURE
SR. NO
(VD1)
It ≥ Iz
IN %
GROUPING
(Iz)
FROM TO REMARKS
(It)
Ib
FACTOR
In ≥ Ib
50°C
(Cg)
(Ca)
AF
AT
1 L1/1, L2/1, L3/1 MCC23 CHILLED WATER PU (02-225) 400 3.3 4.76 100 16 0.9 0.72 NO 18.1 38 1 4 4 18 8.7 0.19 3.04
2 L1/2, L2/2, L3/2 MCC23 PMP-01 (02-225) 400 18.75 27.06 100 50 0.9 0.72 NO 59.1 67 1 4 10 12 3.5 0.28 3.13
3 L1/3, L2/3, L3/3 MCC23 PMP-02 (02-225) 400 18.75 27.06 100 50 0.9 0.72 NO 59.1 67 1 4 10 10 3.5 0.24 3.09
4 L1/4, L2/4, L3/4 MCC23 PMP-03 (02-225) 400 18.75 27.06 100 50 0.9 0.72 NO 59.1 67 1 4 10 9 3.5 0.21 3.06
5 L1/5, L2/5, L3/5 MCC23 PMP-04 (02-225) 400 18.75 27.06 100 50 0.9 0.72 NO 59.1 67 1 4 10 9 3.5 0.21 3.06
1. FEEDER VOLTAGE DROP IN % (VD1) - Voltage drop between equipments in the "FROM" and "TO" columns
2. MAX. VOLTAGE DROP IN FINAL CIRCUITS % (VD2) - Highest Voltage drop among the branch circuits of Panels in the "TO" column including the final circuits connected to it
3. Voltage drop Equation: Current (Ib) x Length of the cable in Mtrs (L) x VD Factor(V/A/kM) x 100%
400 x 1000
4. Minimum Cable Ampacity (Iz): As per BS7671 appendix 4.5, equation 2, 3 &4