Overview of MTS Fault Ride-Through TECHOP

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 31

AN OVERVIEW

OF
TECHOP_ODP_09_(D)
(A METHOD FOR PROVING THE FAULT RIDE-THROUGH CAPABILITY
OF DP VESSELS WITH HV POWER PLANT)
OCTOBER 2014
Acknowledgements
• The MTS DP Committee thanks ABS, DNV and the
following companies for their contribution to the
preparation of this Techop:
– ABB
– GE
– Siemens
– AKA

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
CASE FOR ACTION
• There is a need to improve efficiency and reduce
emissions from DP power plants – Operating power
plants with closed busties is a means of achieving this.
• Industries experience of loss of position incidents on
DP vessels operating with closed busties suggests a
lack of sufficient fault ride through capability – Loss of
all thrusters or blackout.
• 18 examples of such incidents are given in the Techop.
• Increasingly difficult to get stakeholder concurrence for
operation with closed busties.

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
PURPOSE OF TECHOP
• Build confidence in common power systems by
testing fault ride-through capability using an
established method.
• Contribute to proof of equivalent station keeping
integrity for DP class 3 vessels IMO MSC 645
Section 3.2.4.
• Communicate experience of doing it successfully.
• Enhance the knowledge of stakeholders.
• NOTE: If there is no intention to carry out DP
operations with closed busties then you don’t need
to prove fault ride through capability.
A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
CONTENT OF TECHOP
• Information on one method of proving fault ride-
through that has been carried out safely and
effectively.
• Practical details on how to carry out the testing.
• Details of the power system attributes to be proven.
• Guidance on computer simulation and preparatory
work.
• To provide focus on risk assessment, typical roles
and responsibilities for stakeholders.

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
FAULT RIDE-THROUGH TESTING IS NOT NEW
G
GENERATOR
TERMINAL
VOLTAGE FALLS

• Fault Ride-Through VOLT DROP VOLT RISE

Testing on LV DP
DSVs in the 1980s.
BUS VOLTAGE
G MAINTAINED
FAULT CURRENT

• Built to be tested. VOLT DROP VOLT RISE

• Tested by G

application of
bolted short circuit VOLT DROP VOLT RISE

to 660V feeder.
A

VOLT DROP VOLT RISE

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
FAULT RIDE THROUGH CAPABILITY –
A LOOK BACK
• Requirements for fault ride-though capability have
always existed based on single failure criteria.
• What has changed is that more focus is now placed
on proving this capability by testing.
• Traditional methods inadequate to meet stakeholder
expectations:
– History of too great a reliance on limited analysis only e.g.
short circuit calculations.
– FMEA testing did not create realistic conditions for fault
ride through proof.

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
SEVEN PILLARS
These pillars
require more
focus when
cross-connections
Incident Free DP Operations are introduced.

Fault ride through


Fault resistance
Fault tolerance
Differentiation
Independence
Segregation

Autonomy

Predictability

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
PRE-REQUISITES FOR CARRYING OUT FAULT RIDE -
THROUGH TESTING

• Expertise - Already available from several


well known sources.
• Qualification and approval – Early
engagement with class.
• Roles and responsibilities – Agree in
advance.
• Action in the event of unsuccessful tests –
Agree in advance.

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
INDUSTRY READINESS FOR TESTING

• Recent experiences of successful testing.


• More than 10 tests carried out - plus
experience of real short circuits on DP
vessels.
• Initial apprehension overcome:
– Crew safety.
– Test personnel safety.
– Risk assessment.
– Equipment damage – leaving hidden failures (weakness) –
actually helps reveal them.

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
EFFECT ON CIRCUIT BREAKER LIFE

50000
TEST FEEDER 30000
20000
Build to test

PERMISSIBLE OPERATING CYCLES


10000

BUSTIES 5000

2000
1000
500

100
100
50

20
10
1 2 5 10 kA 20 50
31.5
BREAKING CURRENT (r.m.s. value)

You need to check what your circuit breakers are rated for.

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
EFFECT ON BUSBARS

• Forces on bus bars are proportional to the


square of the current.
• As peak test current in the example in the
Techop is around 1/3rd of rating.
• Forces are around 1/10th of rating.

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
EFFECT ON GENERATORS

• Generators rated for a defined number of


short circuits – for example 3.
• Generator sees ‘almost’ a full short – there
is some impedance – more could be added
but considered unnecessary on HV systems
by manufacturers – no reports of damage.

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
PRACTICAL CONSIDERATIONS FOR
CARRYING OUT TESTING

1. Advance modelling.
2. Building confidence for the fault ride-
through test – commissioning.
3. Fault ride-through test.
4. Earth fault test.

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
TEST CONDITIONS
• Vessel at sea trials location.
• DP system in full auto DP.
• Two generators online (on different busses).
supplying DP & Hotel.
• All transformers connected.
• All busties closed.
• Instrumentation and logging facilities
operating.
• Carry out test.
A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
FAULT RIDE-THROUGH TEST

DG DG
THIS CABLE MUST BE RATED 4 THIS CIRCUIT BREAKER IS 6
FOR FULL S/C CAPACITY CLOSED REMOTELY TO
APPLY THE TEST FAULT
CLOSED CLOSED CLOSED CLOSED

CLOSED CLOSED

EARTHING
X3 X3 X3
TRANSFORMER

LV LV LV

RUNNING RUNNING RUNNING RUNNING RUNNING RUNNING

DRILLING DRILLING DRILLING

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
EXPECTED RESULT
• Test fault applied.
• Busties open to isolate switchboard with
fault.
• All thrusters stay online and selected to DP.
• All DP essential systems continue to
operate without malfunction.
• Feeder removes test fault.
• Both generators remain on line.
• All buses healthy.
A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
TEST DATA AQUISITION
Signal sources that can be instrumented
(Build to Test) or used to collect data include:
• Generator VTs and protection & measuring CTs.
• Bus VTs and protection & measuring CTs.
• Feeder protection and measuring CTs.
• Serial links from protection relays.
• Serial links from governors and AVRs.
• Serial links from thruster drives.
Vessel management systems, history stations, data
loggers can be used to record any changes in plant
status.
A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
POWER SYSTEM ATTRIBUTES TO BE VERIFIED

• This section of the Techop deals with


various functions and features to be verified
as part of the analysis and testing process:
– Fault cleared by busties.
– Voltage dip ride-through.
– No protection operation on plant recovery current.
– No protection operation on plant recovery over
voltage.
– Model mal-synchronisation and inadvertent gen CB
closure.
– Decrement curve and model validated.
A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
FAULT CURRENT RECORDINGS

Peak test current 30% of rated

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
MAIN BUS VOLTAGE RECOVERY & OVERSHOOT

Overshoot

Recovery

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
PLANT RECOVERY

Voltage dip

Plant recovery current


Fault Current

removed
Fault applied

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
COMPUTER SIMULATION

• Time Domain Modelling – e.g.


MatlabTM SimulinkTM or equivalent.
• Real Time Digital Simulation or similar.
– Protection relays.
– Enhanced generator protection.
– Drive controllers.
• Use test data to validate model
predictions.
A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
EARTH FAULT TEST

DG DG
4 THIS CIRCUIT BREAKER IS 6
CLOSED REMOTELY TO
APPLY THE FAULT
CLOSED CLOSED CLOSED CLOSED

CLOSED CLOSED

EARTHING
X3 X3 X3
TRANSFORMER

LV LV LV

RUNNING RUNNING RUNNING RUNNING RUNNING RUNNING

DRILLING DRILLING DRILLING

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
EFFECT ON LINE TO EARTH VOLTAGE

This phase earthed

Increase in line to earth voltage

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
EARTH FAULT CURRENT

Fault isolated by busties

Fault isolated by test feeder

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
TEST REPORT
INTRODUCTION
• Vessel, DP system and power systems description.
• Redundancy design intent and worst case failure design intent.
• Power plant configurations and fault types to be modelled and tested.
APPLICABLE RULES, STANDARDS AND CLASS NOTATION.
TEST METHODOLOGY
• Description of test method with supporting sketches.
DISCUSSION OF SIMULATION METHODOLOGY
• Simulation package, TDS, RTDS, HIL etc. Discussion of any
assumptions made in modelling of configurations which were
not tested. Means by which the worst case conditions were
identified.

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
TEST REPORT - CONT
RESULTS
• Comparison of measured and modelled waveforms.
• Comparison with the results of static studies such as short circuit
calculations.
• Results of RTDS or HIL demonstrating that actual protection and
control systems respond correctly.
• Presentation of worst case conditions and confirmation that the
severity of the failure effect does not exceed the DP system’s worst
case failure design intent.

CONCLUSIONS
• Compliance with the applicable rules & requirements.

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
INSPECTION AFTER TEST
• Removal of test equipment.
• A general inspection of the generators used for
testing could include visual inspection of:
– End winding.
– Auxiliary components, AVRs, CTs etc.
– Cable terminations.

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
CHALLENGES
• Build to Test
– Thruster drives may need braking resistors.
• Special cases
– HV power plant with limitations which make it more difficult
to test.
– Older power plants – Uncertainty in relation equipment spec.
– LV power plant.
• Complementary methods for periodic testing
where required.

A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT
CONCLUSIONS
• There is a case for action.
• It is possible to carry out fault ride
through testing with acceptably low risk
when properly executed.
• A combination of design requirements,
computer simulation and testing,
produces common power systems with
comparable integrity to independent
power systems.
A METHOD FOR PROVING THE FAULT RIDE-THROUGH OF DP VESSELS WITH HV POWER PLANT

You might also like