Conception of Plant Automation Solution
1 = emulsifier
of Plant Automation Solution
expanding of technology scheme to P&tl
Emulsionsbildung
1 Emulsifer P2
2 Motor M2
3 Contactor kt
water supply
4 Intake valve V4
5 Water tank
6 Feed valve V2
7 Water level sensor L1
8 Floating switch L2
‘mixing
Feed pump P1
10 Motor Mt
11 Frequency convertor FU
12 Flow fuelF2
13 Flow water FtConception of Plant Automation Solution
description of function areas > water supply
> inlet valve (V2) open and close for adding the water
> inlet valve fill up the water tank, it’s activated by solenoid switch
» solenoid switch activate > valve open
2 solenoid switch deactivate > valve close
> ready conditions:
» water level low
o emergency stop is deactivated
> shut down conditions:
2 water level high
> essential regulation variable and sensors
» solenoid switch (24 V DC)
o status display solenoid switch (24 V DC)Conception of Plant Automation Solution
description of function areas > water supgely
>water tank, stovage the water , the water level should be
between minimum and maximum value
> control function:
o filling of tank by achieving of low level
> disturbance massage:
o by low low level
> essential regulation variables and sensors:
o water level sensor 7 (L1, 4 ..20 mA > O till 100 %)
o floating switch & level to low (L2, potential free contact)
> essential parameter:
o maximum value water level
o minimum value water level
Conception of Plant Automation Solution
description of function areas > water supply
> feed valve (V2) open and close for draining the water
> feed water valve responses the water for mixing
» Solenoid switch activated > valve open
o Solenoid switch deactivated > valve close
> ready condition:
o low level in water tank
o emergency stop deactivated
» shut down conditions
o water level low to low
> essential regulation variables and sensors
0 Solenoid switch (24 V DC)
o Status display solenoid switch (24 V DC)