FCU reference Room Reference Room Name VAV reference Area Total Sensible Air flow Total Sensible Airflow Specific Ref. On coil temp - Off coil - DB/WB Fresh Air Fresh Air Power Input Equipment status
Combined Combined Combined Load flow DB/WB flow Combined (approx.)
m2 kW kW L/s kW kW L/s W/m2 L/s Celsius/Celisus Celsius/Celisus L/s L/s KW
GROUND FLOOR
FCU-GF-01/CU-GF-01 Reception/Entrance Hall/Stair 31.8 9.1 4.3 360 9.1 8.7 721 219.8 23.8 / 17.2 13.9 / 13.3 20 40 5.20 New
Office / BOH 7.5 2.9 241 15
MEP Store 2.1 1.5 120 5
FCU-GF-02/CU-GF-02 Waiting Lounge 1 & 2 26.2 4.4 4.0 339 4.4 4.0 339 167.9 23.9 / 17.5 14.2 / 13.6 30 30 2.40 New
FCU-GF-03/CU-GF-03 Nail's Lounge / Pedi 35.7 10.9 9.8 814 10.9 9.8 814 305.3 23.5 / 17.1 13.5 / 12.9 60 60 6.40 New
FCU-GF-04/CU-GF-04 Dining - Staff 6.6 6.1 3.1 260 6.1 4.6 378 448.5 23.5 / 17.8 13.5 / 13.0 15 25 3.70 New
Pantry 7.0 1.4 118 10
FCU-GF-05/CU-GF-05 Threading / Waxing 7.8 3.1 1.9 157 3.1 3.8 311 125.0 23.9 / 17.3 14.2 / 13.6 10 30 2.40 New
Disinfect Station / Sto 2.0 0.3 21 5
Secondary Hallway 9.6 0.5 44 5
Staff & Delivery 3.9 0.3 22 5
Laundry Back up 1.5 0.8 67 5
FIRST FLOOR
FCU-FF-01/CU-FF-01 Prive Studio 18.6 11.3 6.5 538 11.3 10.8 885 286.8 23.6 / 17.0 13.7 / 13.1 30 50 6.50 New
Changing Room 1.1 90 5
Storage 2.1 1.3 105 5
VIP Hallway 2.5 0.3 23 5
Landing Hallway 16.2 1.6 129 5
FCU-FF-02-CU-FF-02 Washing Area 26.8 10.6 7.9 655 10.6 10.0 827 296.1 23.5 / 16.9 13.6 / 12.9 30 40 6.40 New
Colour Box & Disinfect 9.0 2.1 172 10
FCU-FF-03/CU-FF-03 Working Area 55.4 15.7 13.8 1146 15.7 14.6 1216 270.2 23.5 / 16.9 13.5 / 12.9 60 65 7.80 New
Change 2.7 0.8 70 5
TOTAL 275.0 71.2 66.2 5491 71.2 66.3 5491 0.00 340 340 40.80
S. No. Unit Reference Unit Location Total Load Sensible Load Airflow Refrigerant FCU Served Airflow Electrical Input Suggested
KW KW L/s L/s L/s kW Volt/Phase/Hz Model
FCU-GF-01 40
FCU-GF-02 30
FCU-GF-03 60
1 PAHU-RF-01 Roof 13.4 9.7 340 - FCU-GF-04 25 8 400/3/50
FCU-GF-05 30
FCU-FF-01 50
FCU-FF-02 40
FCU-FF-03 65
S. No. Unit Reference Equipment Location Served Airflow Total Airflow Electrical Input (approx.) Fan Type
Location w/FOS
L/s L/s Watt Volt/Phase/Hz
GROUND FLOOR
FIRST FLOOR
S. No. Unit Reference Unit Location Location Served Type Capacity Electrical Input
Litre kW Volt/Phase/Hz
GROUND FLOOR
FIRST FLOOR
3 EWH-FF-01 Water Closet Prive Lounge & Water Closet In-ceiling/Wall-mounted 50 1.5 240/1/50
4 EWH-FF-02 Water Closet Washing Area In-ceiling/Wall-mounted 100 2 240/1/50
5 EWH-FF-03 Water Closet Colour Box, Water Closet & Powder In-ceiling/Wall-mounted 100 2
Area 240/1/50
PUMP SCHEDULE
S. No. Unit Reference Location Pump Type Max. Flow Pressure Rating Electrical Input
Bar Watt Volt/Phase/Hz
GROUND FLOOR
1 CDP-GF-01 In-ceiling / Reception Condensate Drain Pump 35 L/h @ 0 head 100 240/1/50
2 CDP-GF-02 In-ceiling / Reception Condensate Drain Pump 35 L/h @ 0 head 100 240/1/50
3 TP-GF-01 Pump Room (Under Stairway landing) Transfer Pump 20 gpm 2 0.75 400/3/50
4 TP-GF-02 Pump Room (Under Stairway landing) Transfer Pump 20 gpm 2 0.75 400/3/50
ROOF
1 BP-RF-01 Roof Booster Pump 40 gpm 4 0.75 400/3/50
2 BP-RF-02 Roof Booster Pump 40 gpm 4 0.75 400/3/50