Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Superconducting Fault Current Limiters Dr.

Joachim Bock, Nexans Superconductors, Germany

Short-circuit
protection to a fault:
Superconducting fault
current limiters
Nexans has commissioned the world’s first superconducting fault current
limiter to protect a power plant’s internal power supply at the Boxberg lignite
plant in Germany. Joachim Bock, CEO of Nexans Superconductors, explains
how this technology can help to increase personnel and plant safety while
Vattenfall Europe Generation AG’s Boxberg power station in Germany is
simultaneously reducing investment costs.

A
n increasingly decentralized supply of power, higher power SCFL’s active Module
flows and the present backlog of investment in equipment are all The active part of the SCFL consists of 48 superconducting elements per
developments that will require stronger adaptations to the power phase connected in series and immersed in liquid nitrogen in a cryogenic
network in the coming years. In this context, high short-circuit currents play vessel. The element assemblies are connected to the outside of the vessel
an essential role. through high-voltage bushings and current leads designed to cope with the
For example, in power networks short circuits can arise because of temperature gradient between the liquid nitrogen and the exterior of the
lightning strikes or failures of system components and power lines, resulting vessel. The liquid nitrogen is cooled by an external cryocooler.
in high fault currents. These cause extremely high dynamic and thermal A circuit breaker in series with the limiter is tripped when the fault current
loads that all system components of the power network must resist. has been reduced. The SCFL is thoroughly instrumented to continually
Due to their modular construction, superconducting fault current limiters monitor its operation and the series circuit-breaker will be tripped if
(SCFLs) can be used for various nominal voltages and currents, and can abnormal conditions (e.g. cryocooler failure) occur.
be adapted to particular limiting characteristics in case of short circuits. Communication with the DNO telecontrol systems covers operational
Electrical equipment that controls high fault currents can increase the items and ancillary information such as failure of auxiliary electricity
security of the network and allow power equipment to be designed more supplies.
cost effectively.
The SCFL is such a device. In contrast to a high-voltage fuse it does not Maintenance-free operation
disconnect the line in case of a short circuit but limits the very high currents After a short circuit, the limiter must be powered off for a short period
to defined values. In addition, it allows electrical interconnections of exist- so that it can automatically return to the operational state by means of
ing systems, which would not be possible without limiters. cooling. After a few seconds or minutes, depending on the design, the
During operation, the superconductors of the limiter are cooled to limiter can again accept the nominal power and is ready for the next short
a temperature of around -200 °C, which is easily and cost effectively circuit event.
accomplished by means of liquid nitrogen. At these temperatures, the The compactly designed current limiter provides close to ideal operating
materials used have virtually no electrical resistance – even at nominal conditions. In normal operation, it is virtually ‘transparent’ to the network;
power loads. in case of a fault, it limits the short circuit current automatically and reliably
However, if the so-called ‘critical current’, i.e. above the nominal current, – independent of its level.
is exceeded, the material suddenly loses its superconducting properties By using a SCFL as a protection device, networks can be coupled
and behaves like a ‘normal’ resistor. This relatively high resistance limits without causing the short circuit currents to be added. A short circuit current
the current to a predefined value. These material properties only make is limited to a defined value by the current limiter, which is within the realms
superconductors ideal self-actuating current limiting elements. of milliseconds.

24 www.peimagazine.com June 2010 - PEi


Superconducting Fault Current Limiters

piloting the new SCFL based high temperature superconductor technology developed by Nexans Superconductor

potential uses for SFCLs continuous security and reliability of the equipment is guaranteed.
Typical uses of SCFLs are: The SCFL is perceived to be a low-risk fail-safe device, utilizing a
nonlinear ‘high temperature’ superconducting ceramic rather than electronic,
• Busbar coupling while retaining the switching equipment electromechanical, mechanical or pyrotechnic components. When the
• Transformer in-line protection superconducting material is operated at below its critical temperature it
• Protection of local networks in industrial areas or chemical parks loses all electrical resistance, thereby allowing normal load current to flow
• Protection of the house load in power plants with negligible losses.
• Coupling of networks for the reduction of harmonics Either the increased current density caused by the passage of fault current
or the loss of the liquid nitrogen cooling medium cause the temperature of
Additional advantages of SCFLs include: the superconducting material to rise with the result that the material reverts
to a normal resistive state.
•D  ue to the passive limiting characteristics of the superconductor, the This added resistance has the effect of reducing the fault current to a
current is reliably limited within the first half cycle in the presence of a lower, more acceptable level. This process is referred to as ‘clamping’
short circuit. because it effectively sets a limit above which the fault current will not rise.
• The SCFL is inherently safe and is free from wear and maintenance; on- The SCFL operates in a few milliseconds, after which its resistance remains
site activation is not required. Thus, no additional operating costs arise high until the fault current is cleared by a circuit breaker.
from a short circuit. The SCFL’s operation is sufficiently fast to ensure that the first peak of
• Considerable cost savings can be attained within the initial installation the fault current is limited; this is vitally important when considering the
or revision of switching equipment because the equipment can be scaled closing of a circuit breaker onto a section of faulty network. The degree
down to lower short circuit power. to which the subsequent current is limited can be set at the design stage
• The peak limited current and the symmetrically limited current can be to suit a specific application. It will, in many cases, be convenient to
defined independently of each other. choose this level such that existing protection arrangements do not need
• In case of a short circuit, the power flow is not interrupted completely, so to be adjusted.
that existing protection designs can be retained.
• During a short circuit, system components are subject to less mechanical strategic deplayment onto networks
and thermal stresses. This can significantly increase their lifetime. Trials will result in the development of commercially available devices, that
are capable of clamping fault levels to within network design limits.This can
In addition to the design, production and installation of current limiters, bring a number of benefits. SCFLs could be strategically deployed onto the
Nexans can also provide for their maintenance and service. Thus, the network in areas either with existing high fault level issues, or experiencing

PEi - June 2010 www.peimagazine.com 25


Superconducting Fault Current Limiters

a high degree of distributed generation connection activity (e.g. urban


combined heat and power generation systems). In this application, SCFL
could provide a method of deferring the replacement of switchboards or
reconfiguration of networks, whilst ensuring fault levels are maintained
within safe limits.
Where fault levels are generally high, there may be operational benefits
associated with minimizing the often complicated switching required
to ensure that equipment operates within its fault rating during network
reconfiguration and outages. This could reduce the risk of incurring customer
interruptions and customer minutes lost arising from either network switching
or from operating parts of the network temporarily on a single circuit. An
improvement in staff safety may also be delivered.
If network fault current magnitudes are restricted equipment will be
subjected to reduced electrodynamic and thermal stresses – these are both
proportional to the square of the current, so a modest reduction in fault level
results in a considerable reduction in these stresses – potentially reducing
the probability of follow-on faults and prolonging the asset life.
SCFLs may, subject to resolution of protection issues, allow radial circuits
to be interconnected, with associated improvements to customer supply
continuity and power quality (i.e. flicker and harmonics). This could facilitate
a radical change in the way networks are designed and operated.
In addition to the above, there are specific benefits associated with the
type of design being implemented here, which uses the superconducting
Boxberg power plant is fueled by lignite and has a capacity of 1900 MW
to normal transition.

26 www.peimagazine.com http://pei.hotims.com RS 14 June 2010 - PEi


Superconducting Fault Current Limiters

In its normal state, the SCFL does not add significant reactance to the Choice of HTS material
network and therefore does not affect the upper threshold of impedance ‘High-temperature’ superconductors (HTS) were first discovered in 1986
envelope that DNOs need to stay within to ensure that they do not exceed when Müller and Bednorz at IBM in Switzerland found a lanthanum-
voltage levels in the event of sudden loss of load etc. It will also not in- barium-copper oxide ceramic exhibiting superconductivity at 30 K. Since
crease system losses. then, the numerous discoveries of materials displaying superconductivity at
A significant issue for DNOs today is the increase in X/R ratio which temperatures above 77 K have increased the potential for exploitation of
increases the DC component and therefore the asymmetrical current at superconductivity in a variety of applications.
break time. This also (to a lesser effect) impacts the peak making current Prior to these discoveries it was necessary to use helium, which liquefies
under fault conditions. Although a series reactor will reduce the AC at 4 K, to cool the metallic superconductors sufficiently. Helium is very
component of short circuit current it may make the X/R ratio rise, and expensive and cooling to below 4 K is also costly in terms of equipment
although it reduces the overall asymmetrical current, the DC component and the energy consumed. The discovery of HTS promised to reduce the
can be made greater. Circuit breakers are not tested for this increased DC costs of cooling and to deliver new applications including high-capacity
component and associated longer arcing times. power cables, more compact transformers, motors and fault current limiters.
Due the superconducting/normal transition, the SCFL adds resistance However, it has taken longer than expected for manufacturers to develop
to the fault path. This reduces the AC and DC components of current and ways to produce HTS materials suitable for use in high-power applications.
the level of asymmetry dramatically. This provides much easier making and Ceramics are brittle by nature and susceptible to shattering when stressed
breaking duties for a circuit-breaker and additionally, greatly reduces the which is undesirable in practical applications such as cables.
peak voltage generated (transient recovery voltage) at the point of current Bismuth strontium calcium copper oxide (BSCCO) and similar materials
interruption. have a layered structure and the superconductivity occurs in the layers
The level of fault contribution from connected inductive load is now containing mainly copper and oxygen atoms. It is very difficult to
calculated according to IEC909 and DNOs are finding sites where the peak manufacture large single crystals of these materials so superconducting
making currents of circuit breakers are being exceeded. The fast clamping of components made from bulk material, as well as tapes and wires where
the SCFL reduces these peaks to within circuit breaker ratings. This eliminates the HTS material is deposited on or in a metallic strip, incorporate the HTS
the need to reconfigure networks before closing operations. in a polycrystalline form.

PEi - June 2010 http://pei.hotims.com RS 15 www.peimagazine.com 27


Superconducting Fault Current Limiters

The orientation of the individual crystals with respect to each other has Deployment of first SFCL
to be controlled so that the superconducting planes are substantially par- The site for the first pilot was selected in 2006. It is in a semi-urban location
allel and much work has been done on production methods to achieve in Lancashire and was chosen for two reasons. Firstly, there is plenty of
this. SCFL prototypes have been designed using Bi-2212 and YBCO in a space for the installation and secondly, the site provides an example of
variety of guises. where an SFCL might be installed in response to real need.
A Bi-2212 sheet, bonded to a metal shunt and cut into a meander to pro- The two 33/11 kV transformers feeding the substation were recently
vide a low inductance current path provided the basis for ABB’s singe-phase upgraded, with the result that the fault level increased to above the making
demonstrator reported in 2002. At around the same time, thin-film YBCO on and breaking capacities of the existing circuit breakers. It was therefore
a sapphire substrate was used by Siemens for a high-voltage prototype. A necessary to build a new substation and install a new 11 kV switchboard
Bi-2212 tube, bonded to a tubular shunt and cut into a bifilar helical mean- of primary distribution circuit breakers comprising ten feeders, two incomers
der, manufactured by Nexans Superconductors, was used for the first major and one bus-section.
live network trial, known as ‘CURL 10’, hosted by RWE at Siegen in Ger- Thus, while the fault level problem was addressed in a conventional
many in 2004. Consideration of the costs, availability and suitability of the manner, the situation has allowed the design of the SFCL to be determined
various candidate materials for application in fault current limiting led to bulk according to realistic criteria, as though it were being used to provide a
Bi-2212 in tubular form emerging as the most attractive material to use in solution to the fault level issue. The rating of the old switchgear was taken
a commercial SFCL. as the basis on which the operating characteristics of the SFCL would be
Based on the experience gained in providing the superconducting determined.
elements for the CURL 10 demonstrator, Nexans was clearly in a
good position to supply the superconducting components for the UK
“SCFLs could provide a method of deferring the
trial.The company has developed a Bi-2212 component for use in
the first UK pilot. The component is made from a tube of melt-cast
reconfiguration of networks, while ensuring fault
Bi-2212 soldered to the interior of a copper-nickel-manganese tube, which levels are maintained within safe limits”
provides a metallic shunt to prevent the formation of hot spots in the HTS.
This arrangement is then cut into a helix giving an effective length of The old switchgear was rated at 11 kV with a short circuit capability of
3 metres for each component. The components are supported from the 150 MVA. This equates to a breaking capacity of 7.87 kA and a making
interior by a tube of fibre-reinforced plastic. Pairs of tubes are joined end- capacity of 19.7 kA.The fault contribution of each of the two transformers
to-end and 24 of these connected in series provide the current limiting is calculated to be 11 kA peak, 4.2 kA rms. It was decided that the SFCL
function for each of the three phases. should limit the fault current seen by any circuit breaker to 95 per cent of
the old breaker rating, i.e. 7.48 kA break and 18.72 kA.
The SFCL, which is deployed in a bus-section configuration, effectively in
parallel with the existing bus section circuit breaker (which of course will be
left open during the trial) must limit the fault contribution from the healthy to
the faulted busbar when a fault occurs on an outgoing circuit.
This contribution, together with the contribution from the transformer di-
rectly feeding the faulted bar, must be no more than 95 per cent of the
rating of the old switchgear. The limiting, or clamping performance of the
SFCL is thus defined by the network characteristics and the rating of the
available plant.

FIRST POWER PLANT INSTALLATION


In a pilot project for Vattenfall Europe Generation AG, the SFCL will provide
short circuit protection for the internal medium voltage power supply that
feeds coal mills and crushers in the Boxberg brown coal power plant in
Saxony, Germany. Vattenfall’s SFCL, based on Nexans´ HTS technology
and designed for a rated current of 800 A, is undergoing live testing
by daily routine operation in a feeder bar of the 12 kV power supply for
rebound hammer mills (used for crushing coal).
For the SFCL used in Boxberg, Nexans Superconductors designed and
built the device according to the specifications from Vattenfall and the Bran-
denburg Technical University in Cottbus (Germany), which is providing sci-
entific support for this project. The device can limit a 63 kA prospective
short circuit current to less than 30 kA immediately and to about 7 kA after
The SCFL will provide short circuit protection for Boxberg’s internal medium voltage supply for its coal mills and crushers 10 milliseconds.

28 www.peimagazine.com June 2010 - PEi

You might also like