发电机保护 A 屏调试报告

Generator protection panel A test report

发电机保护 A 屏调试报告
GEN. PROTECTION PANEL A TEST REPORT
1.铭牌 NAMEPLATE:

装置型号 出厂编号
PCS-985GE GE1700117PG001
Device model Ex-factory No.
版本号 厂家
1.05 NR
Delivery date Manufacturer
程序校验码
03141A8E
CRC

2.装置外观检查 DEVICE ASPACT CHECK:

项目序号 检 查 结 果 Check results


保护装置的硬件配置、标注及接线等均符合图纸要求。
1 The hardware configuration, marking and wiring of the protection device are in line with the
requirements of the drawings
背板接线良好,抗干扰元件焊接等项均良好。
2
Backplane wiring is good, anti-interference components, welding and other items are good
直流电源输出电压正确。
3
The output voltage of DC power supply is correct
保护装置固定良好,不松动、端正无损坏变形现象。
4
The protection device is well fixed, not loose, correct, no damage and deformation
保护装置的端子连接可靠。
5
The terminal connection of the protection device is reliable
切换开关、按钮、键盘等操作灵活,手感良好。
6
Switch, button, keyboard and other flexible operation, feel good
7 各部件清洁良好。All parts clean well
装置配件齐全,符合供货清单,部件紧固牢靠接地良好。
8 The fittings are complete and conform to the supply list. The parts are firmly fastened and
the grounding is good

3 . 绝 缘 电 阻 介 质 强 度 检 测 Dielectric strength test of insulation


resistance
回路绝缘电阻检测 Loop insulation resistance test
序号 测试项目 绝缘电阻(MΩ)
1 交流电压回路对地 >100MΩ
AC voltage circuit ground
2 交流电流回路对地 >100MΩ
AC current loop to ground
3 直流回路对地 >100MΩ
DC circuit to ground
1
发电机保护 A 屏调试报告
Generator protection panel A test report

4 开关量输入回路对地 >100MΩ
Switching input circuit to ground
5 远动回路对地 >100MΩ
Remote control circuit to ground
6 信号回路对地 >100MΩ
Signal circuit to ground
整个回路的绝缘电阻检测 Insulation resistance test of the whole circuit
整个回路的绝缘电阻 测量值 measured value
Insulation resistance of the whole >100MΩ
circuit
介质强度检测 Dielectric strength test
绝缘电阻 Insulation resistance 整个回路介质强度
Dielectric strength of the whole circuit
试验前 Pre-test 试验后 Pre-test
合格 Qualified 合格 Qualified 合格 Qualified
通电检查 Electrify examination
检 验 项 目 Inspection items 检验 结 果 est result
保护装置通电检查 Power on check of 合格 Qualified
protective device
检 验 键 盘 Check keyboard 合格 Qualified

4.开入节点检查 CHECK THE EVENT INPUT


表 1 保护压板 FORM 1 PROTECTION CLAMP

序号 NO. 开入量名称 THE EVENT INPUT 压板编号 CLAMP NO. 检查结 RESULT

1 投发电机差动保护 EIL_ Diff_ Gen 1LP1 OK

2 投失步保护 EIL_ OOS_ Gen 1LP2 OK

3 投定子接地保护 EIL_ StaEF 1LP3 OK

4 投转子接地保护 EIL_EF_RotWdg 1LP4 OK

5 投定子过负荷保护 EIL_OvLd_Sta 1LP5 OK

6 投负序过负荷保护 EIL_ NegOC _Gen 1LP6 OK

7 投失磁保护 EIL_LossExc _ Gen 1LP7 OK

8 投发电机功率保护 EIL_PwrProt_Gen 1LP8 OK

9 投电压保护 EIL_VoltProt_Gen 1LP9 OK

2
发电机保护 A 屏调试报告
Generator protection panel A test report

10 投变压器投频率保护 EIL_FreqProt_Gen 1LP10 OK

11 投变压器投发电机复压&阻抗 EIL_ PPF _ Gen 1LP11 OK

12 投 GCB 失灵保护 EIL _BFP _GCB 1LP12 OK

13 投过励磁保护 EIL_ OvExc _Gen 1LP13 OK

14 备用 EIL_ SPARE 1LP14 OK

15 投励磁变速断,过流保护 EIL_ OC _Exc 1LP15 OK

16 备用 EIL_ SPARE 1LP16 OK

17 备用 EIL_ SPARE 1LP17 OK

18 投检修态 EIL _Maintenance 1LP18 OK

19 跳发电机断路器-1 LK_TrpGCB-1 1TLP1 OK

20 跳发电机断路器-2 LK_TrpGCB-2 1TLP2 OK

21 跳灭磁开关-1 LK_TrpFSS-1 1TLP3 OK

22 跳灭磁开关-2 LK_TrpFSS-2 1TLP4 OK

23 关主汽门-1 LK_Off_Valve-1 1TLP5 OK

24 关主汽门-2 LK_Off_Valve-2 1TLP6 OK

25 关主汽门-3 LK_Off_Valve-3 1TLP7 OK

26 备用 LK_Spare 1TLP8 OK

27 备用 LK_Spare 1TLP9 OK

28 备用 LK_Spare 1TLP10 OK

29 备用 LK_Spare 1TLP11 OK

表 2 外部强电开入量 FORM 2 HIGEH POWER INPUT


序号 NO. 开入量名称 THE EVENT INPUT 端子编号 CLAMP NO. 检查结果 RESULT

3
发电机保护 A 屏调试报告
Generator protection panel A test report

1 GCB 跳位 1 GCB opened 1 1QD11 OK

2 主汽门位置接点 1 BI _Valve_Turbine1 1QD12 OK

3 备用 BI_Spare 1QD13 OK

4 启动 GCB 失灵 BI_ InitBFP _GCB 1QD14 OK

5 备用 BI_Spare 1QD15 OK

6 汽机 GCB 紧急停机 ST GEN EMERG STP 1QD18 OK

7 励磁跳闸信号 EXCITATION TRIP SIGNAL 1QD19 OK

8 汽机已跳闸 ST TRIPPED 1QD20 OK

9 励磁转子接地跳闸 EXC rotor earth fault trip 1QD21 OK

5.采样值检查 SAMPLING VALUE CHECK


5.1 电流回路采样 CURRENT SAMPLE
5.1.1 发电机机端电流 GENERATOR OUTGOING FEEDER CURRENT
通入电流 相序
Ia(A) Ib(A) Ic(A)
INFLUENT CURRENT Phase sequence
1 0.99 1.00 1.01 Positive phase sequence
3 3.00 3.00 2.99 Positive phase sequence
5 5.01 4.99 4.99 Positive phase sequence
5.1.2 发电机中性点电流 GENERATOR NEUTRAL POINT CURRENT
通入电流 相序
Ia(A) Ib(A) Ic(A)
INFLUENT CURRENT Phase sequence
1 1.00 1.01 1.01 Positive phase sequence
3 3.01 3.01 2.99 Positive phase sequence
5 5.01 5.01 4.99 Positive phase sequence
5.1.3 励磁变高压侧电流 ET HV CURRENT
通入电流 相序
Ia(A) Ib(A) Ic(A)
INFLUENT CURRENT Phase sequence
1 1.01 0.99 1.01 Positive phase sequence
3 3.00 3.01 3.00 Positive phase sequence
5 5.00 5.00 4.99 Positive phase sequence
5.2 电压回路采样 VOLTAGE SAMPLE
5.2.1 机端 TV1 GENERATOR OUTGOING FEEDER TV1 VOLTAGE
通入电压 相序
Ua(V) Ub(V) Uc(V)
INFLUENT VOLTAGE Phase sequence
20V 19.99 20.01 19.98 Positive phase sequence
4
发电机保护 A 屏调试报告
Generator protection panel A test report

40V 40.01 39.99 40.01 Positive phase sequence


63.5V 63.52 63.49 63.48 Positive phase sequence
5.2.2 机端零序 GENERATOR OUTGOING FEEDER ZERO SEQUENCE VOLTAGE
通入电压
U0(V)
INFLUENT VOLTAGE
10 10.00
40 40.03
50HZ
60 60.04
110 110.06
10 10.01
150HZ 30 29.99
110 109.98
5.2.3 中性点零序 GENERATOR NEUTRAL POINT ZERO-SEQUENCE VOLTAGE
通入电压
U0(V)
INFLUENT VOLTAGE
10 10.01
40 40.01
50HZ
60 60.01
110 110.21
10 10.03
150HZ 30 30.01
110 110.36
5.2.4 转子电压 ROTOR VOLTAGE
通入电压
U(V)
INFLUENT VOLTAGE
50 V 49.3
100 V 99.7
120V 120.0
150V 150.2

6.发电机保护功能试验 GENERATOR PROTECTION FUNCTION


6.1 发电机差动保护试验 GENERATOR DIFFERENTIAL PROTIECTION
6.1.1 试验整定值:Set Value for Test
整定值 SET VALUE

比率差动启动定值
0.2Ie
Percentage differential starting current
差流报警定值 differential alarm current 0.15Ie
起始斜率 Initiating slope 0.1
最大斜率 Maximal slope 0.5
速断定值 Instantaneous multiples 4Ie
6.1.2 差流报警试验 DIFFERENTIAL ALARM CURRENT
机端电流 中性点电流

5
发电机保护 A 屏调试报告
Generator protection panel A test report

Outgoing Feeder Current Neutral Point Current


A 0.15Ie 0.15Ie
B 0.15Ie 0.15Ie
C 0.15Ie 0.15Ie
6.1.3 比率差动试验 PERCENTAGE DIFFERENTIAL PROTECTION
6.1.3.1 比率差动启动定值 Percentage differential starting current
机端电流 中性点电流
Outgoing Feeder Current Neutral Point Current
A 0.2Ie 0.2Ie
B 0.2Ie 0.2Ie
C 0.2Ie 0.2Ie
6.1.3.2 比率制动特性 The ratio of braking characteristics
差动电流
机端电流(A) 中性点电流(A) 制动电流(Ie)
(Ie)DIFFERENTIAL
Outgoing Feeder Current Neutral Point Current RESTRAINT CURREN
CURREN
1.87 1 0.25 0.45
4.23 3 0.36 1.05
6.78 5 0.52 1.72
12.43 9 1.00 3.14
差动动作时间:29.2ms
OPEREATING TIME: 29.2ms
6.1.4 差动速断试验 GENERATOR INSTANTANEOUS DIFFERENTIAL TEST
相别 机端电流(A) 动作值(Ie) 动作情况
PHASE SEQUENCE OUTGOING FEEDER CURRENT OF GEN. TEST VALUE OPERATING RESULT
A 13.69
动作
B 13.68 4Ie
OPERATING
C 13.70

相别 中性点电流(A) 动作值(Ie) 动作情况


PHASE SEQUENCE NEUTRAL POINT CURRENT OF GEN. TEST VALUE OPERATING RESULT
A 13.7
动作
B 13.69 4Ie
OPERATING
C 13.7
速断动作时间:31.1ms
INSTANTANEOUS OPERAERTING TIME: 31.1ms
6.1.5 TA 断线闭锁试验 BLOCKING TO DIFFERENTIAL PROTECTION TA CIRCUIT FAILURE
发电机两侧均加上额定电流,断开任意一相电流,差动保护未动作,同时报 TA 断线闭
锁告警。TA 断线闭锁功能正常;
ADDING RATED CURRENT TO GENERATOR OUTGOING FEEDER AND GENERATOR NEUTRAL
POINT,THEN WILFULLY OPENED ONE PHASE CURRENT ,THE DIFFERENTIAL PROTECTION WILL
NOT OPERATING,ALARM OR BLOCKING TO DIFFERENTIAL PROTECTION TA CIRCUIT FAILURE AT
THE SAME TIME.

6
发电机保护 A 屏调试报告
Generator protection panel A test report

6.1.6 结论 CONCLUSION
发电机差动保护功能正确。
THE FUNCTION OF GENERATOR DIFFERENTIAL PROTECTION IS RIGHT.
6.2 发电机阻抗保护试验 IMPEDANCE PROTECTION OF GENERATOR
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE

OFFSET 0.32Ω
FORWARD 3.21Ω
Delay time 1.8S
(2)保护试验内容 TEST CONTENT
相别 机端电压(V) 机端电流(A) 延时
PHASESEQUENCE OUTGOING VOLTAGE OUTGOING CURRENT TIME
A 15∠89 5∠0
B 15∠-31 5∠-120 1.8230S
C 15∠-151 5∠120

(3)结论 CONCLUSION
发电机阻抗保护功能正确。
THE FUNCTION OF IMPEDANCE PROTECTION OF GENERATOR IS RIGHT
6.3 发 电 机 复 合 电 压 过 流 保 护 试 验 COMPOSITE-VOLTAGE OVERCURRENT PROTECTION OF
GENERATOR
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE

负序电压定值 Negative-sequence voltage 6.6V


低电压定值 Under voltage 66V
过流定值 Operating current for over current protection 4.47A
过流延时 Operating time for over current protection 1.8S
(2)保护试验内容 TEST CONTENT
相别 机端电流(A) 动作值(A) 延时 备注
PHASESEQUENCE OUTGOING FEEDER OPEREATING VOLUE TIME REMARK
A 4.47 4.47
B 4.47 4.47 1.81S 过流 Over-current protection
C 4.47 4.47

(3)负序电压定值 6.6V . ,低电压定值 . 66.1 V


NEGATIVE-SEQUENCE VOLTAGE SETTING VALUE: 6.6V .,
LV SETTING VALUE: .66.1V
(4)结论 CONCLUSION
发电机复合电压过流保护功能正确。
THE FUNCTION OF NEGATIVE SEQUENCE OVERCURRENT PROTECTION OF GENERATOR IS RIGHT
6.4 发电机定子接地保护试验 EARTH FAULT PROTECTION OF STATOR OF GENERATOR
6.4.1 95%定子接地保护试验 95% EARTH FAULT PROTECTION OF STATOR OF GENERATOR
(1)试验整定值:SET VALUE FOR TEST
7
发电机保护 A 屏调试报告
Generator protection panel A test report

整定值 SET VALUE

基波零序电压定值 Operating voltage for sensitive zone 10V


零序电压高定值 Higher value of zero-sequence operating voltage 25V
零序电压保护延时 Operating time delay for principal wave zero-sequence voltage protection 1S
高值保护延时 Operating time delay for principal wave zero-sequence voltage protection 0.5
(2)保护试验内容 TSET CONTENT
试验项目 电压(V) 动作值 动作时间
TEST ITEM VOLTAGE OPERATING VALUE TIME
发电机中性点零序电压
10
Generator neutral point zero-sequence voltage
10 1S
发电机机端零序电压
0
Generator outgoing feeder zero-sequence voltage
电压
动作值 动作时间
试验项目 TEST ITEM (V)VOLTAG
OPERATING VALUE TIME
E
发电机机端零序电压
0
Generator outgoing feeder zero-sequence voltage
25.07 0.518S
发电机中性点零序电压
25.07
Generator neutral point zero-sequence voltage
6.4.2 100%定子接地保护试验 100% EARTH FAULT PROTECTION OF STATOR OF GENERATOR
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE

并网前三次谐波比率定值 Operating 3rd –harmonic ratio before synchronizing 1.5


并网后三次谐波比率定值 Operating 3rd –harmonic ratio after synchronizing 1.5
三次谐波差动比率定值 3rd –harmonic differential restraint coefficient 0.3
三次谐波保护延时 Operating time delay for 3rd –harmonic stator ground protection 5S
(2)保护试验内容 TSET CONTENT
机端零序电压(三次谐波)U1: 12V
Generator outgoing feeder zero-sequence voltage (150Hz):
中性点零序电压(三次谐波)U2: 10V
Generator neutral point zero-sequence voltage (150Hz):
机端 A 相电压(基波):63.5V
Generator outgoing feeder A phase (50Hz):
并网前:U1 增加至, 15.1V 保护动作;
Before synchronizing: when U1 add to, 15.1V the protection will operating
并网后:U1 增加至, 15.1V 保护动作;
After synchronizing: when U1 add to 15.1V, the protection will operating
动作时间:5.003S
Operating time: 5.003S
6.4.3 三次谐波电压差动定子接地保护 Percentage third harmonic voltage earth fault protection
备注
试验项目 TEST ITEM 试验数值 TEST VALUE
REMARK
机端电压(V) 63.5V

8
发电机保护 A 屏调试报告
Generator protection panel A test report

outgoing feeder voltage of Gen


机端三次谐波零序电压(V)
10V
Outgoing feeder zero-sequence voltage of Gen.
中性点三次谐波零序电压(V)
10V
neutral point zero-sequence voltage of Gen.
突变机端三次谐波零序电压 3 V ,报警出现;突变 2.5V,未报警;
Breaking generator outgoing feeder zero-sequence voltage 3V,the protection will operating ; Breaking
generator outgoing feeder zero-sequence voltage 2.5V,the protection will not operating
6.4.4 结论 CONCLUSION
发电机定子接地保护功能正确。
The function of generator stator earth fault protection is right.
6.5 发电机转子接地保护试验 EARTH FAULT PROTECTION OF ROTOR
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE

一点接地灵敏段电阻定值 Higher operating resistance for one-point ground protection 10kΩ


一点接地电阻定值 Lower operating resistance for one-point ground protection 4kΩ
一点接地延时报警定值 Operating time delay for one-point ground protection 5s
一点接地延时跳闸定值 Operating time delay for one-point ground protection 5s
两点接地延时定值 Operating time delay for two-point ground protection 1s
(2)保护试验内容 TSET CONTENT
试验项目 TEST ITEM 动作阻值 Operating resistance 转子电压 Rotor voltage 时间 Delay time
转子一点接地报警 10.04KΩ 40V 5S
转子一点接地跳闸 3.90KΩ 40V 5.42S
转子两点接地跳闸 40V 2.56S

(3)结论 CONCLUSION
发电机转子接地保护功能正确。
The function of generator rotor earth fault is right
6.6 发电机定子过负荷保护试验 GENERATOR STATOR OVERLOAD PROTECTION

(1)试验整定值:SET VALUE FOR TEST


(2)定时限过负荷保护试验内容 Definite time-limit overload protection
试验项目 TEST ITEM 动作值 时间 备注
整定值 SETOPERATING
VALUE VALUE TIME REMARKS
发电机机端电流(A)Generator outgoing feeder current
定时限报警定值 3.78S 6.2S 报警 ALARM
3.78A
Operating current for Definite time-limit overload protection alarming zone
定时限报警延时 6S
Operating time for Definite time-limit overload protection alarming zone
反时限起动电流 Upper-limit starting current for the inverse time-limit 3.97A
反时限上限延时 Upper-limit starting current for the inverse time-limit 0.3S
定子绕组热容量 Stator thermal capacity 37.5
散热效应系数 Heat emission effect coefficient 1.03

(3)反时限过负荷保护试验内容 Inverse time-limit Overload Protection


序号 NO. 输入电流 INPUT CURRENT 动作时间 TIME 计算时间 COUNT TIME
1 5A 34.93S 35.24S
9
发电机保护 A 屏调试报告
Generator protection panel A test report

2 8A 8.566S 8.5S
(4)结论 CONCLUSION
发电机定子过负荷保护功能正确
The function of generator stator overload is right
6.7 发电机定子负序过负荷保护试验 Generator Negative-sequence Overload Protection
(1) 试验整定值:SET VALUE FOR TEST
整定值 SET VALUE

定时限报警电流定值 Operating current for Definite time-limit alarming zone 0.30A


定时限报警延时 Operating time for Definite time-limit alarming zone 6S
反时限起动负序电流
0.41A
Lower limit negative-sequence current for Inverse time-limit negative-sequence overload protection
长期允许负序电流 Allowable steady-state negative-sequence current 0.27A
反时限上限延时
0.3S
Upper limit time delay for Inverse time-limit negative-sequence overload protection
负序转子发热常数 Calorific value 8
(2) 定时限负序过负荷保护试验内容
Definite time-limit negative-sequence overload protection
动作值 时间 备注
试验项目 TEST ITEM
OPERATING VALUE TIME REMARKS
报警
负序过负荷报警 negative-sequence overload protection alarm 0.3A 6S
ALARM
(3) 反时限负序过负荷保护试验内容 Inverse time-limit negative-sequence overload protection
序号 NO. 输入电流 INPUT CURRENT 动作时间 TIME 计算时间 COUNT TIME
1 2A 24.03S 23.96S
2 3A 10.526S 10.54S
(4) 结论 CONCLUSION
发电机定子负序过负荷保护功能正确
The function of generator negative-sequence overload protection is right.
6.8 发电机失磁保护试验 Loss-of-Excitation PROTECTION
(1) 试验整定值:SET VALUE FOR TEST
整定值 SET VALUE

阻抗定值 1 Impedance setting 1 -2.23Ω


阻抗定值 2 Impedance setting 2 -30.31Ω
无功反向定值 Reactive reverse power 10%
转子低电压定值 Operating value of the rotor under-voltage 79V
转子空载电压定值 No-load excitation voltage 99V
转子低电压判据系数定值 Coefficient of the rotor under-voltage element 1.52
低电压定值 Under-voltage setting 93.5V
延时 Operating time 1S
(2) 发电机失磁保护试验内容 Loss-of-Excitation PROTECTION TSET
无功反向判据 REACTIVE POWER CRITERION
动作值
试验项目 TEST ITEM 试验数值 TEST VALUE
OPERATING VALUE
10
发电机保护 A 屏调试报告
Generator protection panel A test report

机端电压(V)
13.290∠-90 13.290∠150 13.290∠30
outgoing feeder voltage of Gen.
机端电流(A) 10.01%
1.31∠0 1.31∠-120 1.31∠120
outgoing feeder current of Gen.
Q -10.02%
转子电压判据 ROTOR VOLTAGE CRITERION
动作值
试验项目 TEST ITEM 试验数值 TEST VALUE
OPERATING VALUE
机端电压(V)
63.5V∠-90 63.5V∠-150 63.5V∠30
outgoing feeder voltage of Gen.
机端电流(A) 78V
3A∠0 3A∠-120 3A∠120
outgoing feeder current of Gen.
转子电压(V)Rotor Voltage 79V
阻抗判据 Impedance CRITERION
动作值
试验项目 TEST ITEM 试验数值 TEST VALUE
OPERATING VALUE
机端电压(V)
15V∠0 15V∠-120 15V∠120
outgoing feeder voltage of Gen.
15Ω
机端电流(A)
1A∠90 1A∠-150 1A∠-30
outgoing feeder current of Gen.

(3)失磁 I 段延时: 1.026S


Operating time for zone I: 1.026S
(3)结论 CONCLUSION
发电机失磁保护功能正确
The function of loss-of-excitation protection is right
6.9 发电机失步保护试验 Loss-of-Step Protection
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE

阻抗定值 ZA Shelter characteristic ZA 2.65Ω


阻抗定值 ZB Shelter characteristic ZB -4.33Ω
阻抗定值 ZC Reactance characteristic ZC 2.10Ω
灵敏角 Alarming interior angle 85º
透镜内角 Lens interior angle 120
区外滑极数整定 Oscillation center outside the GEN.-Gscillation 4
区内滑极数整定 Oscillation center inside the GEN.-GT. block 1
跳闸允许电流 Allowable tripping current 6.3A
(2)保护试验内容 TSET CONTENT

区外震荡 OUTSIDE OSCILLATION

试验项目 TEST ITEM 试验数值 TEST VALUE 动作情况 OPERATING


机端电压(V) 12.590V 12.590V 12.590V 震荡 4 次报警
outgoing feeder voltage of Gen. ALARM WHEN OSCILLATION TEN

11
发电机保护 A 屏调试报告
Generator protection panel A test report

机端电流(A)
5A 5A 5A TIMES
outgoing feeder current of Gen.

区内震荡 INSIDE OSCILLATION

试验项目 TEST ITEM 试验数值 TEST VALUE 动作情况 OPERATING


机端电压(V)
20.560V 20.560V 20.560V 震荡 1 次跳闸
outgoing feeder voltage of Gen.
TRIP WHEN OSCILLATION TWO
机端电流(A)
5A 5A 5A TIMES
outgoing feeder current of Gen.
跳闸允许电流闭锁 Trip current blocking
试验项目 TEST ITEM 试验数值 TEST VALUE 动作情况 OPERATING
机端电压(V)
24.6V 24.6V 24.6V 震荡 1 次跳闸
outgoing feeder voltage of Gen.
TRIP WHEN OSCILLATION TWO
机端电流(A)
6A 6A 6A TIMES
outgoing feeder current of Gen.
机端电压(V)
24.6V 24.6V 24.6V
outgoing feeder voltage of Gen.
保护不动
机端电流(A)
6.31A 6.31A 6.31A
outgoing feeder current of Gen.
(3)结论 CONCLUSION
发电机失步保护功能正确
The function of loss-of-step protection is right
6.10 发电机过电压保护试验 OVERVOLTAGE PROTECTION
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE

过电压定值 Operating voltage for Over-voltage zone I 143V


过电压延时 Operating time for Over-voltage zone I 0.5S
(2)保护试验内容 TSET CONTENT
动作值
相别 机端电压(V) 延时 备注
(V)OPERATING
PHASESEQUENCE Outgoing feeder voltage of Gen. TIME REMARKS
VALUE
A 82.56
过电压
B 82.56 142.99 0.5264S
OVER VOLTAGE
C 82.56
(3)结论 CONCLUSION
发电机过电压保护功能正确
The function of over-voltage protection is right
6.11 发电机过励磁保护试验 OVEREXCITING PRTECTION
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE

定时限定值 V/f for Definite time 1.25


定时限 I 段延时 Time for Definite time Zone I 2S

12
发电机保护 A 屏调试报告
Generator protection panel A test report

报警段定值 V/f for Definite time Zone alarming 1.07


报警段延时 Time for Definite time Zone alarming 10S
反时限上限定值 V/f for Inverse time-delay Upper limit 1.25
反时限上限延时 Time for Inverse time-delay Upper limit 4S
反时限Ⅰ定值 V/f for Inverse time-delay zone I 1.19
反时限Ⅰ延时 Time for Inverse time-delay zone I 6S
反时限Ⅱ定值 V/f for Inverse time-delay zone II 1.15
反时限Ⅱ延时 Time for Inverse time-delay zone II 8S
反时限Ⅲ定值 V/f for Inverse time-delay zone III 1.12
反时限Ⅲ延时 Time for Inverse time-delay zone III 12S
反时限Ⅳ定值 V/f for Inverse time-delay zone IV 1.10
反时限Ⅳ延时 Time for Inverse time-delay zone IV 16S
反时限Ⅴ定值 V/f for Inverse time-delay zone V 1.09
反时限Ⅴ延时 Time for Inverse time-delay zone V 24S
反时限Ⅵ定值 V/f for Inverse time-delay zone VI 1.08
反时限Ⅵ延时 Time for Inverse time-delay zone VI 36S
反时限下限定值 V/f for Inverse time-delay lower limit 1.07
反时限下限延时 Time for Inverse time-delay upper limit 48
(2)定时限过励磁保护试验内容 Definite time-limit OVEREXCITATION PROTECTION
相别
机端电压(V) 动作值 延时 备注
PHASESEQUENC
outgoing feeder voltage of Gen. Operating Value TIME REMARKS
E
A 79.390
过励磁
B 79.390 125% 2.0514S
OVEREXCITATION
C 79.390

动作值
相别 机端电压(V) 延时
(V)OPERATING 备注 REMARKS
PHASESEQUENCE outgoing feeder voltage of Gen. TIME
VALUE
A 68.00 过励磁信号段
B 68.00 107% 10.138S OVEREXCITATION
C 68.00 ALARM

(3)反时限过励磁保护试验内容 Inverse time-limit Over-excitation Protection


序号 NO. 输入电压(V)INPUT VOLTAGE 频率 FREQUENCY 动作时间(S)TIME
1 79.4 50Hz 4.0169
2 75.6 50Hz 6.0090
3 73.08 50Hz 7.9920
4 71.14 50Hz 12.0394
5 69.89 50Hz 16.0477
6 69.22 50Hz 24.0210
7 68.59 50Hz 36.0100
8 68.00 50Hz 47.8378
(4)结论 CONCLUSION
发电机过励磁保护功能正确
13
发电机保护 A 屏调试报告
Generator protection panel A test report

The function of over-excitation protection is right


6.12 发电机逆功率保护试验 Generator Reverse Power Protection
(1)试验整定值:SET VALUE FOR TEST
逆功率定值
1%
Operating power for Reverse power protection
逆功率信号延时 Operating time of Alarming zone for Reverse power protection 15s
逆功率跳闸延时 Operating time of tripping zone for Reverse power protection 60s
程序逆功率定值 Operating power for Program reverse power protection 1%
程序逆功率延时 Operating time for Program reverse power protection 1s
(2)发电机逆功率保护试验内容 Generator Reverse Power Protection
动作值
报警时 动作时间
试验项目 TEST ITEM 试验数值 TEST VALUE OPERATIN
间 TIME TIME
G VALUE
机端电压(V)
15V∠0 15V∠-120 15V∠120
outgoing feeder voltage of Gen.
1.01% 15S 59.9917S
机端电流(A)
0.3A∠243 0.3A∠123 0.3A∠3
outgoing feeder current of Gen.
(3)发电机程序逆功率保护试验内容 Generator Sequence-tripping Reverse Power Protection
发电机主汽门开关位置节点闭合;
The steam value of turbine has to be closed and circuit breaker of GCB has to be opened
试验项目 试验数值 TEST VALUE 时间
TEST ITEM A B C TIME
机端电压(V)
15V∠0 15V∠-120 15V∠120
outgoing feeder voltage of Gen.
1.0539S
机端电流(A)
0.3A∠243 0.3A∠123 0.3A∠3
outgoing feeder current of Gen.
(4)结论 CONCLUSION
发电机逆功率保护功能正确
The function of generator reverse power protection is right
6.13 发电机频率异常保护试验 Generator abnormal frequency protection
(1)保护试验内容 TSET CONTENT
频率定值 频率动作值
试验项目 TEST ITEM FREQUENCY FREQUENCY 动作时间 TIME
VALUE OPERATING VALUE
低频 I 段
Operating frequency for Under-frequency protection 48Hz 47.980Hz alarm
Zone I
低频 II 段
Operating frequency for Under-frequency protection 47.5Hz 47.49Hz 30.1567S
Zone II
低频 III 段
Operating frequency for Under-frequency protection 47Hz 46.97Hz 0.507S
Zone III
过频 I 段
51Hz 51.02Hz alarm
Operating frequency for HF protection Zone I
14
发电机保护 A 屏调试报告
Generator protection panel A test report

过频 II 段
51.5Hz 51.52Hz 21.05S
Operating frequency for HF protection Zone II
过频 III 段
52Hz 52.02Hz 0.506S
Operating frequency for HF protection Zone III
(2)结论 CONCLUSION
发电机频率保护功能正确
The function of generator abnormal frequency protection is right
6.14 发电机低电压保护 GENERATOR UNDERVOLTAGE PROTECTION
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE

低电压定值 Operating voltage for Over-voltage zone I 77V


低电压延时 Operating time for Over-voltage zone I 2S
(2)保护试验内容 TSET CONTENT
动作值
相别 机端电压(V) 延时 备注
(V)OPERATING
PHASESEQUENCE Outgoing feeder voltage of Gen. TIME REMARKS
VALUE
A 44.45
低电压
B 44.45 76.98 2.02S
OVER VOLTAGE
C 44.45

(3)结论 CONCLUSION
发电机低电压保护功能正确
The function of undervoltage protection is right
6.15 低功率保护 Low forward power protection
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE

动作值 Pickup value 3%Pn


动作延时 Delay time 0.5S
(2)保护试验内容 TSET CONTENT
动作值
动作时间
试验项目 TEST ITEM 试验数值 TEST VALUE OPERATING
TIME
VALUE
机端电压(V)
63.5V∠0 63.5V∠-120 63.5V∠120
outgoing feeder voltage of Gen.
2.99% 0.5510S
机端电流(A)
0.2A∠-68 0.2A∠-188 0.2A∠52
outgoing feeder current of Gen.
(3)结论 CONCLUSION
发电机低功率保护功能正确
The function of low forward power protection is right
6.16 断路器失灵保护 GENERATOR BF PROTECTION
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE

15
发电机保护 A 屏调试报告
Generator protection panel A test report

失灵动作电流 Operating current for BF 4.12A


负序电流动作值 Operating negative current for BF 0.52A
动作延时 Delay time 0.25S
(2)保护试验内容 TSET CONTENT
动作时间
试验项目 TEST ITEM 动作值 OPERATING VALUE
TIME
电流(A)
4.10A
CURRENT
0.2747S
负序电流(A)
0.523A
Negative current
(3)结论 CONCLUSION
失灵保护功能正确。
The function of BF protection is right
6.17 励磁变过流保护 ET OVERCURRENT PROTECTION
(1)试验整定值:SET VALUE FOR TEST
过流 I 段定值 Operating current for over-current protection zone I 31.63A
过流 I 段延时 Operating time for over-current protection zone I 0
过流 II 段定值 Operating current for over-current protection zone II 6.87A
过流 II 段延时 Operating time for over-current protection zone II 1S
(2)保护试验内容 TSET CONTENT
试验项目 动作值 时间
试验数值 TEST VALUE
TEST ITEM OPERATING VALUE TIME
励磁变三相电流
31.61 31.61 31.61 31.61 0.0397S
ET current(A)

试验项目 动作值 时间
试验数值 TEST VALUE
TEST ITEM OPERATING VALUE TIME
励磁变三相电流
6.87 6.87 6.87 6.87 1.0219S
ET current(A)
(3)结论 CONCLUSION
励磁变过流保护功能正确。
The function of ET over current protection is right
6.18 整组传动

投入保护软压板以及出口压板 , 合上开关,加入相应的电流、电压 , 模拟各种故障 , 开关动


作正确。

Put into the protection of soft platen and outlet plate, close the switch, add the corresponding
current, voltage, simulate all kinds of faults, switch action correctly

7.试验结论 CONCLUSION

7.1 二次接线正确,回路符合设计要求。

The two wiring is correct, the circuit meets the design requirements

16
发电机保护 A 屏调试报告
Generator protection panel A test report

7.2 绝缘符合要求,逻辑传动正确。
The insulation meets the requirements and the logic drive is correct
7.3 装置面板灯光指示信号正确。
The panel light indication signal is correct
7.4 保护开入量正确,保护出口方式正确,保护信号远传正确。
The protection input quantity is correct, the protection outlet way is correct, the protection signal
remote transmission is correct
7.5 打印机工作正常。
The printer is working properly.
7.6 交流回路通电完好。
AC circuit power intact.
7.7 输入、输出开关量、模拟量正确 , 测试值误差符合技术条件要求。
The input and output analog switch, correct, test error meets the technical requirements.
7.8 保护压板正确投退保护、出口跳闸压板传动正确。
The protection plate is correctly put back and protected, and the outlet trip plate is driven correctly
7.9 保护装置可在 80%额定直流电压(176V)工作状态下可靠动作。
The protection device can operate reliably at the rated DC voltage (176V) of 80%;
经过发变组保护各项试验后,试验合格,保护装置工作稳定,动作准确、可靠,具备投
入生产运行的条件。
After the protection test of generator transformer unit, the test is qualified, the protection
device works stably, the action is accurate and reliable, and it has the condition of putting into
production operation