发电机保护 A 屏调试报告 Generator protection panel A test report
发电机保护 A 屏调试报告 Generator protection panel A test report
发电机保护 A 屏调试报告 Generator protection panel A test report
发电机保护 A 屏调试报告
GEN. PROTECTION PANEL A TEST REPORT
1.铭牌 NAMEPLATE:
装置型号 出厂编号
PCS-985GE GE1700117PG001
Device model Ex-factory No.
版本号 厂家
1.05 NR
Delivery date Manufacturer
程序校验码
03141A8E
CRC
4 开关量输入回路对地 >100MΩ
Switching input circuit to ground
5 远动回路对地 >100MΩ
Remote control circuit to ground
6 信号回路对地 >100MΩ
Signal circuit to ground
整个回路的绝缘电阻检测 Insulation resistance test of the whole circuit
整个回路的绝缘电阻 测量值 measured value
Insulation resistance of the whole >100MΩ
circuit
介质强度检测 Dielectric strength test
绝缘电阻 Insulation resistance 整个回路介质强度
Dielectric strength of the whole circuit
试验前 Pre-test 试验后 Pre-test
合格 Qualified 合格 Qualified 合格 Qualified
通电检查 Electrify examination
检 验 项 目 Inspection items 检验 结 果 est result
保护装置通电检查 Power on check of 合格 Qualified
protective device
检 验 键 盘 Check keyboard 合格 Qualified
序号 NO. 开入量名称 THE EVENT INPUT 压板编号 CLAMP NO. 检查结 RESULT
2
发电机保护 A 屏调试报告
Generator protection panel A test report
26 备用 LK_Spare 1TLP8 OK
27 备用 LK_Spare 1TLP9 OK
28 备用 LK_Spare 1TLP10 OK
29 备用 LK_Spare 1TLP11 OK
3
发电机保护 A 屏调试报告
Generator protection panel A test report
3 备用 BI_Spare 1QD13 OK
5 备用 BI_Spare 1QD15 OK
比率差动启动定值
0.2Ie
Percentage differential starting current
差流报警定值 differential alarm current 0.15Ie
起始斜率 Initiating slope 0.1
最大斜率 Maximal slope 0.5
速断定值 Instantaneous multiples 4Ie
6.1.2 差流报警试验 DIFFERENTIAL ALARM CURRENT
机端电流 中性点电流
5
发电机保护 A 屏调试报告
Generator protection panel A test report
6
发电机保护 A 屏调试报告
Generator protection panel A test report
6.1.6 结论 CONCLUSION
发电机差动保护功能正确。
THE FUNCTION OF GENERATOR DIFFERENTIAL PROTECTION IS RIGHT.
6.2 发电机阻抗保护试验 IMPEDANCE PROTECTION OF GENERATOR
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE
OFFSET 0.32Ω
FORWARD 3.21Ω
Delay time 1.8S
(2)保护试验内容 TEST CONTENT
相别 机端电压(V) 机端电流(A) 延时
PHASESEQUENCE OUTGOING VOLTAGE OUTGOING CURRENT TIME
A 15∠89 5∠0
B 15∠-31 5∠-120 1.8230S
C 15∠-151 5∠120
(3)结论 CONCLUSION
发电机阻抗保护功能正确。
THE FUNCTION OF IMPEDANCE PROTECTION OF GENERATOR IS RIGHT
6.3 发 电 机 复 合 电 压 过 流 保 护 试 验 COMPOSITE-VOLTAGE OVERCURRENT PROTECTION OF
GENERATOR
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE
8
发电机保护 A 屏调试报告
Generator protection panel A test report
(3)结论 CONCLUSION
发电机转子接地保护功能正确。
The function of generator rotor earth fault is right
6.6 发电机定子过负荷保护试验 GENERATOR STATOR OVERLOAD PROTECTION
2 8A 8.566S 8.5S
(4)结论 CONCLUSION
发电机定子过负荷保护功能正确
The function of generator stator overload is right
6.7 发电机定子负序过负荷保护试验 Generator Negative-sequence Overload Protection
(1) 试验整定值:SET VALUE FOR TEST
整定值 SET VALUE
机端电压(V)
13.290∠-90 13.290∠150 13.290∠30
outgoing feeder voltage of Gen.
机端电流(A) 10.01%
1.31∠0 1.31∠-120 1.31∠120
outgoing feeder current of Gen.
Q -10.02%
转子电压判据 ROTOR VOLTAGE CRITERION
动作值
试验项目 TEST ITEM 试验数值 TEST VALUE
OPERATING VALUE
机端电压(V)
63.5V∠-90 63.5V∠-150 63.5V∠30
outgoing feeder voltage of Gen.
机端电流(A) 78V
3A∠0 3A∠-120 3A∠120
outgoing feeder current of Gen.
转子电压(V)Rotor Voltage 79V
阻抗判据 Impedance CRITERION
动作值
试验项目 TEST ITEM 试验数值 TEST VALUE
OPERATING VALUE
机端电压(V)
15V∠0 15V∠-120 15V∠120
outgoing feeder voltage of Gen.
15Ω
机端电流(A)
1A∠90 1A∠-150 1A∠-30
outgoing feeder current of Gen.
11
发电机保护 A 屏调试报告
Generator protection panel A test report
机端电流(A)
5A 5A 5A TIMES
outgoing feeder current of Gen.
12
发电机保护 A 屏调试报告
Generator protection panel A test report
动作值
相别 机端电压(V) 延时
(V)OPERATING 备注 REMARKS
PHASESEQUENCE outgoing feeder voltage of Gen. TIME
VALUE
A 68.00 过励磁信号段
B 68.00 107% 10.138S OVEREXCITATION
C 68.00 ALARM
过频 II 段
51.5Hz 51.52Hz 21.05S
Operating frequency for HF protection Zone II
过频 III 段
52Hz 52.02Hz 0.506S
Operating frequency for HF protection Zone III
(2)结论 CONCLUSION
发电机频率保护功能正确
The function of generator abnormal frequency protection is right
6.14 发电机低电压保护 GENERATOR UNDERVOLTAGE PROTECTION
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE
(3)结论 CONCLUSION
发电机低电压保护功能正确
The function of undervoltage protection is right
6.15 低功率保护 Low forward power protection
(1)试验整定值:SET VALUE FOR TEST
整定值 SET VALUE
15
发电机保护 A 屏调试报告
Generator protection panel A test report
试验项目 动作值 时间
试验数值 TEST VALUE
TEST ITEM OPERATING VALUE TIME
励磁变三相电流
6.87 6.87 6.87 6.87 1.0219S
ET current(A)
(3)结论 CONCLUSION
励磁变过流保护功能正确。
The function of ET over current protection is right
6.18 整组传动
Put into the protection of soft platen and outlet plate, close the switch, add the corresponding
current, voltage, simulate all kinds of faults, switch action correctly
7.试验结论 CONCLUSION
7.1 二次接线正确,回路符合设计要求。
The two wiring is correct, the circuit meets the design requirements
16
发电机保护 A 屏调试报告
Generator protection panel A test report
7.2 绝缘符合要求,逻辑传动正确。
The insulation meets the requirements and the logic drive is correct
7.3 装置面板灯光指示信号正确。
The panel light indication signal is correct
7.4 保护开入量正确,保护出口方式正确,保护信号远传正确。
The protection input quantity is correct, the protection outlet way is correct, the protection signal
remote transmission is correct
7.5 打印机工作正常。
The printer is working properly.
7.6 交流回路通电完好。
AC circuit power intact.
7.7 输入、输出开关量、模拟量正确 , 测试值误差符合技术条件要求。
The input and output analog switch, correct, test error meets the technical requirements.
7.8 保护压板正确投退保护、出口跳闸压板传动正确。
The protection plate is correctly put back and protected, and the outlet trip plate is driven correctly
7.9 保护装置可在 80%额定直流电压(176V)工作状态下可靠动作。
The protection device can operate reliably at the rated DC voltage (176V) of 80%;
经过发变组保护各项试验后,试验合格,保护装置工作稳定,动作准确、可靠,具备投
入生产运行的条件。
After the protection test of generator transformer unit, the test is qualified, the protection
device works stably, the action is accurate and reliable, and it has the condition of putting into
production operation