Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Fenwal® In-Cabinet™

Effective: September 2004

SMALL ENCLOSURE CYLINDER AND


VALVE ASSEMBLIES

93-3000

FEATURES
• UL Listed System;
Tested to UL 2166 Standards
• Tested Per NFPA 2001
• Designed Specifically to Protect
Electrical Cabinets and Industrial Equipment
• No Software Required for Design
• Discharges in Less then 10 Seconds,
Attacking the Fire Quickly
• Quick and Easy to Install—Uses Standard Brass
or Stainless Steel Compression Fittings and
Copper or Stainless Steel Tubing
• Multiple Fill Options; Conveniently Offered
with Eight Different Fills
• Optional Kit Packages with Panel Detection
and Alarm Equipment
• Working Pressure of 360 PSIG @ 70°F
(24.8 bar @ 21°C)
OPERATION
DESCRIPTION For system actuation, the cylinder and valve assemblies
Fenwal Protection Systems, In-Cabinet™/Small Enclosure have been designed to use a wall mounted control
fire suppression system is Listed by the Underwriters Labo- head (CXV™ Control System, P/N 93-487100-001), which
ratory, Inc. (UL) and designed for total flooding in accor- has been designed specifically for these In-Cabinet/Small
dance with NFPA 2001, Standard on Clean Agent Enclosure applications. The CXV Controller pneumatically
Extinguishing Systems. These systems have been tested ties to the cylinder valve assembly and allows the system to
to: UL 2166 and other standards established jointly by Un- be actuated electrically, manually or locally. For more detail
derwriters Laboratory and Fenwal Protection Systems. on how to use and install the CXV Controller, please con-
The Fenwal In-Cabinet/Small Enclosure Clean Agent Sys- sult the Design, Installation, Operation and Maintenance
tem has been designed and engineered specifically for pro- Manual, P/N 93-FM200M-040.
tecting small, high value equipment. Electrical cabinets, OPERATING RANGE LIMITATIONS
Industrial Equipment, CNC machines and small volume en-
closures are just a few of the applications that can be pro- The operating temperature range for all components used
tected with this product offering. The cylinder and valve in the Fenwal In-Cabinet/Small Enclosure system is
assemblies are available in eight (8) different fills to easily 32°F to 130°F (0°C to 54°C).
accommodate the equipment envelope. The suppression Table 1. Cylinder Bracket Assemblies
system uses a unique nozzle style called an ADA (Agent
Distribution Assembly) to distribute the agent within the haz- Part Number Cylinder Volume
ard being protected—ADA (P/N 93-220036-001). The ADA
does not require any calculations or custom drilling. Once 06-220037-001 145 cu. in.
the designer determines the appropriate amount of FM-200®
06-220037-002 500 cu. in.
and the number of ADAs, a chart is used to determine the
length and size of tubing. Tubing is easily fitted using gen-
06-220037-003 1050 cu. in.
eral purpose compression fittings to quickly install the dis-
tribution network.

1
LIFT

2320 Control Panel FIRE


ALARM
(with Optional Front Cover)
FENWAL Fire Alarm
Pull Station
Output Devices
F
I
R
E

Notification Appliances
CXV Controller
(P/N 93-487100-001)
Smoke/Heat
Detection
Cable Manual
Pull Station
Set

Distribution
Manual/Pneumatic Tubing
Control Head
(P/N 06-236419-001)
Agent Distribution
Assembly (ADA)
(P/N 93-220036-001)

Actuation Hose
(P/N 06-236444-001)
or
High-Pressure Tubing Cabinet/Equipment

FM-200
Agent Cylinder

Figure 1. In-Cabinet/Small Enclosure Suppression System

2
FM-200 B
Cylinder

Figure 2. Cylinder and Valve Assembly


Table 2. Operating Range Limitations

Dimensions
Empty
Cylinder and Cylinder Fill
Weight*
Valve Assembly Volume (lb.)
(Nominal, lb.) A B C
(Valve Height) (Total Height) (Cylinder Dia.)

93-410103-00X thru 13.38 in. 17.05 in. 4.29 in.


145 cu. in. 3 or 5 4.10
93-410105-00X (339.9 mm) (433.1 mm) (108.9 mm)

93-410107-00X thru 16.65 in. 20.32 in. 7.16 in.


500 cu. in. 7 or 10 14.00
93-410110-00X (422.9 mm) (516.1 mm) (181.8 mm)

93-410112-00X thru 12, 15, 17 31.73 in. 35.40 in. 7.16 in.
1050 cu. in. 24.97
93-410123-00X or 20 (805.9 mm) (899.1 mm) (181.8 mm)

*Note: Empty weight does not include the agent weight; it includes the cylinder valve, siphon tube, shipping cap
and safety cap.

3
C
D

Figure 2-5. Quick-Release Cylinder Bracket,


P/N 06-220037-00X
Table 2-8. Dimensions, Cylinder Bracket

Dimensions
Cylinder
Part Number
Size
A B C D

2.00" 3.31" 14.56" 8.40"


06-220037-001 145 in.3
(50.8 mm) (84.1 mm) (369.8 mm) (213.4 mm)

2.00" 4.73" 17.88" 10.00"


06-220037-002 500 in.3
(50.8 mm) (120.1 mm) (454.2 mm) (254.0 mm)

2.00" 4.73" 32.95" 12.00"


06-220037-003 1050 in.3
(50.8 mm) (120.1 mm) (836.9 mm) (304.8 mm)

4
INSTALLATION MAINTENANCE
The In-Cabinet/Small Enclosure System is based on the According to NFPA standards, the following inspection and/
requirements of NFPA 2001, Standard on Clean Agent Ex- or maintenance procedure must be scheduled as listed
tinguishing Systems. Refer to the Design, Installation, Op- below, and performed upon the occurrence of any event
eration and Maintenance Manual, P/N 93-FM200M-040, for that might affect the reliability of the system.
more detailed instructions.
SEMI-ANNUAL
CYLINDER AND VALVE ASSEMBLY Qualified Fenwal personnel should conduct the following
The Cylinder and Valve Assembly comes pre-assembled check/tests:
with a specified fill of FM-200. It be easily mounted in a Required functional tests of system devices and equipment.
horizontal or vertical position with the quick release cylinder Refer to the Design, Installation, Operation and Maintenance
bracket (See Table 1 for Part Number). The bracket has Manual, P/N 93-FM200M-040.
been designed such that the cylinder will seat only one way
into the bracket. This ensures that the cylinder will be in the RECONDITIONING
correct orientation for the agent to be released effectively After a system has been discharged, it is recommended
through the siphon tube. that the local authorized Fenwal Distributor be contacted to
Note: Horizontal mounted cylinders cannot be mounted recondition the system. Refer to the Design, Installation,
to a vertical wall; they must be horizontally mounted Operation and Maintenance Manual, P/N 93-FM200M-040,
on a horizontal plane. for appropriate reconditioning information and hardware.

ACTUATION SPECIFICATIONS
The CXV Controller is to be mounted vertically next to • Cylinder Working Pressure: 360 PSIG (24.8 bar)
the Cylinder and Valve Assembly. The CXV Controller • Clean Agent: FM-200
ships ready to install, and includes three EMT connec- • DOT Cylinder SPEC: DOT 4B-360
tors, a system solenoid actuator, two microswitches and
• Valve Material: Brass
two cartridges. The actuation hose is then connected from
the CXV Controller to the Manual/Pneumatic Control Head • Cylinder Material: Welded Steel
(P/N 06-236419-001) located on the Cylinder and Valve Table 3. Tubing Specifications:
Assembly. The Manual/Pneumatic Control Head also al- Type K Copper or Stainless Steel
lows for simultaneous discharge of up to
20 cylinders. However, each cylinder must have its own Tube Size O.D. I.D. Wall Size
independent distribution network. For more information,
3/8 in. 1/2 in. 0.402 in. 0.049 in.
refer to the Design, Installation, Operation and Mainte-
nance Manual, P/N 93-FM200M-040. 1/2 in. 5/8 in. 0.527 in. 0.049 in.

5/8 in. 3/4 in. 0.652 in. 0.049 in

Note: Only Type K Copper tubing may be used for instal-


lations; stainless steel may be any type. Intermix-
ing metal types for fittings/tubing is not
recommended.
Fitting Specifications
• Self-aligning, general purpose brass compression fit-
tings (Elbows, Tees and Unions)
• Any general purpose Stainless Steel compression fit-
tings are acceptable.

5
ORDERING INFORMATION Table 5. Detection, Alarm and Control Kit Contents
Fenwal Protection Systems offers both Cylinder and Valve Part Number* Quantity Description
Assemblies Kits, and Suppression Kits with or without de-
tection and alarm. Table 4 lists the contents in a Suppres- 30-232000-103 1
Fenwal 2320 Basic Panel, ***
240 Vac**
sion Kit, Table 5 lists the contents of the Detection, Alarm
and Control Kit and Table 6 lists the part numbers to order Fenwal 2320 Front Panel, ***
30-232001-001 1
either a Suppression or Suppression, Detection, Alarm and 240 Vac**
Control Kit. 70-510000-001 2 Two Ion Detectors
Table 4. Suppression Kit Contents
71-550000-001 2 Two Photoelectric Detectors
Part Number Qty. Description
75-000016-002 1 Multi-Tone Horn/Strobe
93-4101XX-00X 1 Cylinder and Valve Assembly
70-501000-102 4 Four, 4 in. Bases
93-190000-001 A/R Agent, FM-200
06-129520-000 10 End-of-Line Resistors
06-220037-00X 1 Quick-Release Cylinder Bracket
(X is equal to: Notes:
1=150 in.3 Cylinder * All products fall under Product Code 93, regardless of their prefix.
2=500 in.3 Cylinder, ** If a 110 Vac 2320 panel is required, the equipment listed above
3=1050 in.3 Cylinder) will be sold separately.
*** Batteries are sold separately. The Fenwal 2320 Panel requires
93-220036-001 1 Agent Distribution Assembly (ADA) two, 1.2AH, 12 Vdc lead acid batteries (P/N 06-115915-020)

93-487100-001 1 CXV Controller Kit, which includes:


Table 6. Available Kits
1 • Manual/Pneumatic Control Head
(P/N 06-236419-001)
Vertical or Horizontal Mount* Fill Weight/
1 • System Nitrogen Cartridge Cylinder and
Agent Weight
(P/N 87-120042-001) Valve Assembly*
(lb.)
Vertical Horizontal
1 • System Test Cartridge
(P/N 87-120044-001) 93-400X03- -001 -002 3

1 • Electric Actuator 93-400X05- -001 -002 5


(Factory Installed,
P/N 83-100034-001) 93-400X07- -001 -002 7
2 • Microswitches, Stacked,
93-400X10- -001 -002 10
High-Mounted
(Bottom Microswich is 93-400X12- -001 -002 12
Factory Installed,
P/N 87-120039-001) 93-400X15- -001 -002 15
1 • 24" Actuation Hose
(P/N 06-236444-001) 93-400X17- -001 -002 17

- • Fitting Adapters for Actuation Hose 93-400X20- -001 -002 20


(P/N 06-118410-001)
*Note: Use 1 for a Suppression Kit, or 2 for a Suppression,
1 • G1/8" Plug Detection, Alarm and Control Kit. The -001 indicates a vertical mount
(P/N 06-118408-001) cylinder, -002 indicates a horizontal mount. For example, to order a
12 lb. Horizontal Mount Cylinder with Suppression, Detection, Alarm
1 • G1/8 x 1/4 MJIC Fitting and Control Kit, the P/N would be: 93-400212-002.
(P/N 06-118409-001)

Fenwal is a registered trademark of Kidde-Fenwal, Inc.


In-Cabinet and CXV are trademarks of Kidde-Fenwal, Inc.
FM-200 is a registered trademark of Great Lakes Chemical Corporation.

TM
R
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes no
responsibility for the product's suitability for a particular application. The product must be
properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or question,
Protection Systems contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
KIDDE-FENWAL, INC.
400 MAIN STREET, ASHLAND, MA 01721 93-3000 09/04 ©2004 Kidde-Fenwal, Inc. Printed in U.S.A.
TEL: (508)881-2000 FAX: (508) 881-8920
www.fenwalfire.com

You might also like