Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

t [s] Protection Documentation: WTG-08

WTG # 08 1000

N654

L296

WTG-08 LV

100
GSU-8 to Conv-8

N192

GSU Trafo # 8

GSU-08A - Input Data & Range


N190
I>> = 2.0 xIs (1.0 - 20.0 xIs)
T>> = 0.6 S (0.04 - 3.0 S)
GSU-08A
IE> = 0.2 xIs (0.1 - 2.5 xIs)
RMU (8-1) to GSU-8
TIE> = 0.6 S (0.06 - 300.0 S) 10

WTG-08 RMU
GSU-08B - Input Data & Range
GSU-08C - Input Data & Range
I> = 2.0 xIs (0.5 - 2.5 xIs)
T> = 2.0 a (0.05 - 10.0 a) I> = 0.9 xIs (0.5 - 2.5 xIs)
IE> = 0.2 xIs (0.1 - 2.5 xIs) T> = 3.0 a (0.05 - 10.0 a)
TIE> = 0.6 a (0.05 - 10.0 a) GSU-08B GSU-08C IE> = 0.1 xIs (0.1 - 2.5 xIs)
TIE> = 0.8 a (0.05 - 10.0 a)
RMU (7-3) to RMU (8-2) RMU (8-3) to RMu (19-2)

GSU-07C - Input Data & Range GSU-19B - Input Data & Range
I> = 1.8 xIs (0.5 - 2.5 xIs) GSU-07C GSU-19B I> = 1.0 xIs (0.5 - 2.5 xIs)
T> = 2.0 a (0.05 - 10.0 a) T> = 3.0 a (0.05 - 10.0 a)
IE> = 0.2 xIs (0.1 - 2.5 xIs) IE> = 0.1 xIs (0.1 - 2.5 xIs) 1
TIE> = 0.5 a (0.05 - 10.0 a) TIE> = 0.8 a (0.05 - 10.0 a)

WTG-07 RMU WTG-19 RMU

0.1

0.01 I [A] (22 kV)


100 1000 10000 100000

GSU-07C - Tripping Curve (Phase) GSU-08B - Tripping Curve (Phase) GSU-08C - Tripping Curve (Phase)
GSU-19B - Tripping Curve (Phase) GSU-08A - Tripping Curve (Phase)