The following daily check as recommended by manufacturer for preventive maintenance

of diesel generator :
 Fuel level……………………………………………Check
 Radiator Water Level………………………………Check
 Lubricating oil level ………………………………..Check
 Air inlet filter.…………………………………………Check
 Engine coolant level……………………………….. Check
 Fan, cooling………………………………………….Check
 Crankcase Breather tube………………………….. Check
 Drive belts…………………………………………… Check
 Engine mounts……………………………………… Check
 Engine air cleaner service indicator……………… Check
 Battery cable and connection……………………….Check
 Generator room clean properly.

Diesel Generator Maintenance – Preventive


– work at every 150 hrs
 Lubricating oil & lubricating oil filter change.
 Air filter clean.
 Clean cooling tank
 Fuel filters change.
 Change radiator water and mixed coolant.
 Fuel filters water separator change.
 Air filters restriction check & correct.
 Battery water check or refill.

Diesel Generator Maintenance – Preventive


– work at every 300 hrs
 Lubricating oil & lubricating oil filter change.
 Air filter change.
 Fuel filters change
 Change radiator water and mixed coolant.
 Fuel filters water separator change.
 Air filters restriction check & correct.
 Battery water check or refill.

Diesel Generator Maintenance – Preventive


– work at every 450 hrs
 Lubricating oil & lubricating filter change.
 Air filter clean.
 Fuel filters change.
 Change radiator water and mixed coolant.
 Fuel filters water separator change.
 Air filters restriction check & correct.
 Battery water check or refill.
 Water filters change.

Diesel Generator Maintenance – Preventive


– work at every 600 hrs
 Lubricating oil & lubricating oil filter change.
 Air filter………………………………………Change/ if needed
 Fuel filters change
 Change radiator water and mixed coolant.
 Fuel filters water separator change.
 Air filters restriction check & correct.
 Battery water check or refill.
 Overhead set ………………………………..Adjust
 Engine wiring harness………………………Check/replace if need.
 Engine cranking breather……….…………..Clean
 Ignition system……………………………….Check /Replace
 Supplement coolant additive as needed…..Check/add

Diesel Generator Maintenance – Preventive


– work at every 750 hrs
 Lubricating oil & lubricating oil filter change.
 Air filter clean.
 Fuel filters change.
 Change radiator water and mixed coolant.
 Fuel filters water separator change.
 Air filters restriction check & correct.
 Battery water check or refill.
 Ignition fuel system……………………… Check/Replace if needed
 Supplemental coolant additive…………..Check / Test
 Stator leads connection…………………..Check/Connect if needed

Diesel Generator Maintenance – Preventive


– work at every 900 hrs
 Lubricating oil & lubricating oil filter change.
 Air filter change.
 Fuel filters change
 Change radiator water and mixed coolant.
 Fuel filters water separator change.
 Air filters restriction check & correct.
 Battery water check or refill.
 Fuel injector and fuel system..………Change/replaced if needed
 HP fuel pump…………………………. Check/replaced if needed
 Fuel pressure maintaining valve……. Check/replaced if needed
 Engine Mounts……………………..…..Check/replaced if needed
 Engine Protective Devices……………Replace/Check
 Starting motor ………………….………Inspect/correction if needed
 Water pump (HT & LT)………………….Inspect/correction if needed
 Main alternator…………………………Check