GENERAL INFORMATION

Project identification: LIVING ROOM


(Given name of area and/or building and room number)

Average maintained illuminance for design: 200 lux or Foot-candles Lamp data:
Type and color: Daylight
Luminaire data: Number per luminaire: 1
Manufacturer: FUMACO Total lumens per luminaire: 3000
Catalog number: FUMACO LED DL 72 5700K

SELECTION OF COEFFICIENT OF UTILIZATION

Step 1: Fill in sketch at right

80 0

Step 2: Determine Cavity Ratios 9.94 m


50
Room Index = 1.9315 2.6 m
Room Cavity Ratio, RCR = 2.5886 50
Ceiling Cavity Ratio, CCR = 0
Floor Cavity Ratio, FCR = 0.3983
10.15 m
50 30 0.4 m

Step 3: Obtain Effective Ceiling Cavity Reflectance (ρCC) ρCC = 0.80

Step 4: Obtain Effective Floor Cavity Reflectance (ρFC) ρFC = 0.29

Step 5: Obtain Coefficient of Utilization (CU) from Manufacturer’s Data CU = 0.4999

SECTION OFLIGHT LOSS FACTORS

Nonrecoverable Recoverable

Luminaire ambient temperature ______ Room surface dirt depreciation (RSDD) 0.8543

Voltage to luminaire ______ Lamp lumen depreciation (LLD) 1

Ballast factor ______ Lamp burnouts factor (LBO) 1

Luminaire surface depreciation ______ Luminaire dirt depreciation (LDD) 0.79

Lamp maintance factor LaMF 1

Total light loss factor, LLF (product of individual factor above) = 0.6749

CALCULATIONS

(Average Maintained Illuminance)


(𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑛𝑐𝑒)𝑥(𝐴𝑟𝑒𝑎) 200∗100.891
Number of Luminaries = (𝐿𝑢𝑚𝑒𝑛𝑠 = =19.94≈20
𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 3000∗0.4999∗0.6749

(𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝐿𝑢𝑚𝑖𝑛𝑎𝑟𝑖𝑒𝑠)𝑥(𝐿𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 19.94∗3000∗0.4999∗0.6749


Illuminance = = = 200lux
(𝐴𝑟𝑒𝑎) 100.891

Calculated by: John Michael E. Padrigo Date: May 2, 2019


CALCULATIONS:
L = 9.94m; W = 10.15m

𝐴𝑅𝐸𝐴 = 𝐿 ∗ 𝑊 = 9.94 ∗ 10.15 = 100.891 𝑚2


Em = 200 lux
hCC = 0m; hRC = 2.6m; hFC = 0.4m
pc = 80%; pw = 50%; pf = 30%
COEFFICIENT OF UTILIZATION
𝐿+𝑊 9.94 + 10.15
𝑅𝐶𝑅 = 5 ∗ ℎ𝑅𝐶 ∗ = 5 ∗ 2.6 ∗ = 2.5886
𝐿∗𝑊 9.94 ∗ 10.15

ℎ𝐶𝐶 0
𝐶𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 2.5886 ∗ = 0
ℎ𝑅𝐶 2.6

ℎ𝐹𝐶 0.4
𝐹𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 2.5886 ∗ = 0.3983
ℎ𝑅𝐶 2.6

%pc 80 %pf 30
%pw 50 𝑝𝑓𝑐 − 29 29 − 29
%pw 50 = ; 𝑝𝑓𝑐 = 29%
0.3983 − 0.2 0.2 − 0.4
CCR FCR 0.3983
0 80 0.2 29
0.3983 pfc
pcc = 80% 0.4 29

%pcc 30 29 10 𝑌 − 0.53 0.53 − 0.50


= ; 𝑌 = 0.5285
%pw 50 29 − 30 30 − 10
RCR
2 0.53 Y 0.50 𝑍 − 0.48 0.48 − 0.46
= ; 𝑍 = 0.4790
2.5886 CU 29 − 30 30 − 10
3 0.48 Z 0.46
𝐶𝑈 − 𝑌 𝑌−𝑍
= ; 𝐶𝑈 = 0.4999
2.5886 − 2 2−3
𝐿∗𝑊 9.94∗10.15
𝑅𝐼 = ℎ = = 1.9315
𝑅𝐶 ∗(𝐿+𝑊) 2.6∗(9.94+10.15)

Type Direct/ Type Direct/ Type Direct/


Indirect Indirect Indirect
RI = 1.5 RI = 1.93 RI >= 2.5
Maintenance 3 years Maintenance 3 years Maintenance 3 years
Interval Interval Interval
Environmental Environmental Environmental
Clean 0.85 Clean RSDD Clean 0.86

𝑅𝑆𝐷𝐷 − 0.85 0.85 − 0.86


= ; 𝑅𝑆𝐷𝐷 = 0.8543
1.93 − 1.5 1.5 − 2.5

8ℎ𝑟𝑠 30𝑑𝑎𝑦𝑠 10𝑚𝑜𝑛𝑡ℎ𝑠


𝐻𝑜𝑢𝑟𝑠 𝑜𝑓 𝑂𝑝𝑒𝑟𝑎𝑡𝑖𝑜𝑛 = ∗ ∗ ∗ 3𝑦𝑒𝑎𝑟𝑠 = 7200 ℎ𝑜𝑢𝑟𝑠
𝑑𝑎𝑦 𝑚𝑜𝑛𝑡ℎ 𝑦𝑒𝑎𝑟

LLMF = LLD = 1; LBO = 1; LaMF = 1

Type Diffuser
𝐿𝐷𝐷 = 0.79
Maintenance Interval 3 years
Environmental
Clean 0.79

𝐿𝐿𝐹 = 𝑅𝑆𝐷𝐷 ∗ 𝐿𝐿𝐷 ∗ 𝐿𝐵𝑂 ∗ 𝐿𝐷𝐷 ∗ 𝐿𝑎𝑀𝐹


𝐿𝐿𝐹 = 0.8543 ∗ 1 ∗ 1 ∗ 0.79 ∗ 1 = 0.6749

1 𝐴 1 100.891
𝑆𝐻𝑅 = √ = √ = 0.8652
ℎ𝑅𝐶 𝑛 2.6 20

𝑀𝑎𝑥 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = 𝑀𝑆 = ℎ𝑅𝐶 ∗ 𝑆𝐻𝑅 = 2.6 ∗ 0.8652 = 2.2496


𝑤𝑖𝑑𝑡ℎ 10.15
𝑟𝑜𝑤𝑠 = = = 4.51 ≈ 5
𝑀𝑆 2.2496
𝑛 20
𝑐𝑜𝑙𝑢𝑚𝑛 = = =4
𝑟𝑜𝑤𝑠 5
𝑤𝑖𝑑𝑡ℎ 10.15
𝐴𝑥𝑖𝑎𝑙 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 2.2496
𝑟𝑜𝑤𝑠 5
𝑙𝑒𝑛𝑔ℎ𝑡 9.94
𝑇𝑟𝑎𝑛𝑠𝑣𝑒𝑟𝑠𝑒 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 2.2496
𝑐𝑜𝑙𝑢𝑚𝑛𝑠 4

𝑙𝑢𝑚𝑒𝑛𝑠
𝑛∗( ) ∗ 𝐶𝑈 ∗ 𝐿𝐿𝐹 20 ∗ 3000 ∗ 0.4999 ∗ 0.6749
𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑐𝑒 𝑙𝑒𝑣𝑒𝑙 = 𝑙𝑢𝑚𝑒𝑛𝑎𝑖𝑟𝑒 = = 200 𝑙𝑢𝑥
𝐴𝑟𝑒𝑎 100.891
GENERAL INFORMATION

Project identification: DINING ROOM


(Given name of area and/or building and room number)

Average maintained illuminance for design: 200 lux or Foot-candles Lamp data:
Type and color: Daylight
Luminaire data: Number per luminaire: 1
Manufacturer: PHILIPS Total lumens per luminaire: 660
Catalog number: Luxspace Micro 11W, 4000K

SELECTION OF COEFFICIENT OF UTILIZATION

Step 1: Fill in sketch at right

80 0

Step 2: Determine Cavity Ratios 10.72 m


50
Room Index = 1.7999 2.6 m
Room Cavity Ratio, RCR = 2.7779 50
Ceiling Cavity Ratio, CCR = 0
Floor Cavity Ratio, FCR = 0.4274
8.30 m
50 30 0.4 m

Step 3: Obtain Effective Ceiling Cavity Reflectance (ρCC) ρCC = 0.80

Step 4: Obtain Effective Floor Cavity Reflectance (ρFC) ρFC = 0.287

Step 5: Obtain Coefficient of Utilization (CU) from Manufacturer’s Data CU = 0.4899

SECTION OFLIGHT LOSS FACTORS

Nonrecoverable Recoverable

Luminaire ambient temperature ______ Room surface dirt depreciation (RSDD) 0.9460

Voltage to luminaire ______ Lamp lumen depreciation (LLD) 1

Ballast factor ______ Lamp burnouts factor (LBO) 1

Luminaire surface depreciation ______ Luminaire dirt depreciation (LDD) 0.79

Lamp maintance factor LaMF 1

Total light loss factor, LLF (product of individual factor above) = 0.6749

CALCULATIONS

(Average Maintained Illuminance)


(𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑛𝑐𝑒)𝑥(𝐴𝑟𝑒𝑎) 200∗89.03
Number of Luminaries = (𝐿𝑢𝑚𝑒𝑛𝑠 = =73.7≈74
𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 660∗0.4899∗0.7473

(𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝐿𝑢𝑚𝑖𝑛𝑎𝑟𝑖𝑒𝑠)𝑥(𝐿𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 73.7∗660∗0.4899∗0.7473


Illuminance = = = 200lux
(𝐴𝑟𝑒𝑎) 89.03

Calculated by: John Michael E. Padrigo Date: May 2, 2019


CALCULATIONS:
L = 10.7227m; W = 8.3038m

𝐴𝑅𝐸𝐴 = 𝐿 ∗ 𝑊 = 10.72 ∗ 8.30 = 89.0392 𝑚2


Em = 200 lux
hCC = 0m; hRC = 2.6m; hFC = 0.4m
pc = 80%; pw = 50%; pf = 30%
COEFFICIENT OF UTILIZATION
𝐿+𝑊 10.72 + 8.30
𝑅𝐶𝑅 = 5 ∗ ℎ𝑅𝐶 ∗ = 5 ∗ 2.6 ∗ = 2.7779
𝐿∗𝑊 10.72 ∗ 8.30

ℎ𝐶𝐶 0
𝐶𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 2.7779 ∗ = 0
ℎ𝑅𝐶 2.6

ℎ𝐹𝐶 0.4
𝐹𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 2.7779 ∗ = 0.4274
ℎ𝑅𝐶 2.6

%pc 80 %pf 30
%pw 50 𝑝𝑓𝑐 − 29 29 − 28
%pw 50 = ; 𝑝𝑓𝑐 = 28.7%
0.4274 − 0.4 0.4 − 0.6
CCR FCR 0.4274
0 80 0.4 29
0.4274 pfc
pcc = 80% 0.6 28

%pcc 30 28.7 10 𝑌 − 0.53 0.53 − 0.50


= ; 𝑌 = 0.5285
%pw 50 28.7 − 30 30 − 10
RCR 2.7779
2 0.53 Y 0.50 𝑍 − 0.48 0.48 − 0.46
= ; 𝑍 = 0.4790
2.7779 CU 28.7 − 30 30 − 10
3 0.48 Z 0.46
𝐶𝑈 − 𝑌 𝑌−𝑍
= ; 𝐶𝑈 = 0.4899
2.7779 − 2 2−3
𝐿∗𝑊 10.72∗8.30
𝑅𝐼 = ℎ = = 1.7999
𝑅𝐶 ∗(𝐿+𝑊) 2.6∗(10.72+8.30)

Type Direct Type Direct Type Direct


RI = 1.5 RI = 1.7999 RI >= 2.5
Maintenance 3 years Maintenance 3 years Maintenance 3 years
Interval Interval Interval
Environmental Environmental Environmental
Clean 0.94 Clean RSDD Clean 0.96

𝑅𝑆𝐷𝐷 − 0.94 0.94 − 0.96


= ; 𝑅𝑆𝐷𝐷 = 0.9460
1.7999 − 1.5 1.5 − 2.5

8ℎ𝑟𝑠 30𝑑𝑎𝑦𝑠 10𝑚𝑜𝑛𝑡ℎ𝑠


𝐻𝑜𝑢𝑟𝑠 𝑜𝑓 𝑂𝑝𝑒𝑟𝑎𝑡𝑖𝑜𝑛 = ∗ ∗ ∗ 3𝑦𝑒𝑎𝑟𝑠 = 7200ℎ𝑜𝑢𝑟𝑠
𝑑𝑎𝑦 𝑚𝑜𝑛𝑡ℎ 𝑦𝑒𝑎𝑟

LLMF = LLD = 1; LBO = 1; LaMF = 1

Type Diffuser
𝐿𝐷𝐷 = 0.79
Maintenance Interval 3 years
Environmental
Clean 0.79

𝐿𝐿𝐹 = 𝑅𝑆𝐷𝐷 ∗ 𝐿𝐿𝐷 ∗ 𝐿𝐵𝑂 ∗ 𝐿𝐷𝐷 ∗ 𝐿𝑎𝑀𝐹


𝐿𝐿𝐹 = 0.9460 ∗ 1 ∗ 1 ∗ 0.79 ∗ 1 = 0.7473

1 𝐴 1 89.0392
𝑆𝐻𝑅 = √ = √ = 0.4228
ℎ𝑅𝐶 𝑛 2.6 74

𝑀𝑎𝑥 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = 𝑀𝑆 = ℎ𝑅𝐶 ∗ 𝑆𝐻𝑅 = 2.6 ∗ 0.4228 = 1.0992


𝑤𝑖𝑑𝑡ℎ 8.30
𝑟𝑜𝑤𝑠 = = = 7.55 ≈ 8
𝑀𝑆 1.0992
𝑛 74
𝑐𝑜𝑙𝑢𝑚𝑛 = = = 9.8 ≈ 10
𝑟𝑜𝑤𝑠 7.55
𝑤𝑖𝑑𝑡ℎ 8.30
𝐴𝑥𝑖𝑎𝑙 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 1.0992
𝑟𝑜𝑤𝑠 7.55
𝑙𝑒𝑛𝑔ℎ𝑡 10.72
𝑇𝑟𝑎𝑛𝑠𝑣𝑒𝑟𝑠𝑒 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 1.0992
𝑐𝑜𝑙𝑢𝑚𝑛𝑠 9.8
𝑙𝑢𝑚𝑒𝑛𝑠
𝑛∗( ) ∗ 𝐶𝑈 ∗ 𝐿𝐿𝐹 74 ∗ 660 ∗ 0.4899 ∗ 0.7473
𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑐𝑒 𝑙𝑒𝑣𝑒𝑙 = 𝑙𝑢𝑚𝑒𝑛𝑎𝑖𝑟𝑒 = = 200 𝑙𝑢𝑥
𝐴𝑟𝑒𝑎 89.0392
GENERAL INFORMATION

Project identification: MASTER’S BEDROOM


(Given name of area and/or building and room number)

Average maintained illuminance for design: 300 lux or Foot-candles Lamp data:
Type and color: LED Downlight
Luminaire data: Number per luminaire: 1
Manufacturer: PHILIPS Total lumens per luminaire: 2000
Catalog number: Smart LED Downlight 42W, 4000K

SELECTION OF COEFFICIENT OF UTILIZATION

Step 1: Fill in sketch at right

80 0

Step 2: Determine Cavity Ratios 7.9180 m


30
Room Index = 1.6957 2.6 m
Room Cavity Ratio, RCR = 2.9486 30
Ceiling Cavity Ratio, CCR = 0
Floor Cavity Ratio, FCR = 0.4536
9.9483 m
30 10 0.4 m

Step 3: Obtain Effective Ceiling Cavity Reflectance (ρCC) ρCC = 0.80

Step 4: Obtain Effective Floor Cavity Reflectance (ρFC) ρFC = 0.10

Step 5: Obtain Coefficient of Utilization (CU) from Manufacturer’s Data CU = 0.43

SECTION OFLIGHT LOSS FACTORS

Nonrecoverable Recoverable

Luminaire ambient temperature ______ Room surface dirt depreciation (RSDD) 0.9439

Voltage to luminaire ______ Lamp lumen depreciation (LLD) 0.89

Ballast factor ______ Lamp burnouts factor (LBO) 0.975

Luminaire surface depreciation ______ Luminaire dirt depreciation (LDD) 0.79

Lamp maintance factor LaMF 0.875

Total light loss factor, LLF (product of individual factor above) = 0.5662

CALCULATIONS

(Average Maintained Illuminance)


(𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑛𝑐𝑒)𝑥(𝐴𝑟𝑒𝑎) 300∗78.7706
Number of Luminaries = (𝐿𝑢𝑚𝑒𝑛𝑠 = =48.53≈49
𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 2000∗0.43∗0.5662

(𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝐿𝑢𝑚𝑖𝑛𝑎𝑟𝑖𝑒𝑠)𝑥(𝐿𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 49∗2000∗0.43∗0.5662


Illuminance = = = 300 𝑙𝑢𝑥
(𝐴𝑟𝑒𝑎) 78.7706

Calculated by: John Michael E. Padrigo Date: May 2, 2019


CALCULATIONS:
L = 7.9180 m; W = 9.9483 m

𝐴𝑅𝐸𝐴 = 𝐿 ∗ 𝑊 = 7.9180 ∗ 9.9483 = 78.7706 𝑚2


Em = 300 lux
hCC = 0m; hRC = 2.6m; hFC = 0.4m
pc = 80%; pw = 30%; pf = 10%
COEFFICIENT OF UTILIZATION
𝐿+𝑊 7.9180 + 9.9483
𝑅𝐶𝑅 = 5 ∗ ℎ𝑅𝐶 ∗ = 5 ∗ 2.6 ∗ = 2.9486
𝐿∗𝑊 7.9180 ∗ 9.9483

ℎ𝐶𝐶 0
𝐶𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 2.9486 ∗ = 0
ℎ𝑅𝐶 2.6

ℎ𝐹𝐶 0.4
𝐹𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 2.9486 ∗ = 0.4536
ℎ𝑅𝐶 2.6

%pc 80 %pf 10
%pw 30 𝑝𝑓𝑐 − 10 10 − 10
%pw 50 = ; 𝑝𝑓𝑐 = 10%
0.4536 − 0.4 0.4 − 0.6
CCR FCR 0.4536
0 80 0.4 10
0.4536 pfc
pcc = 80% 0.6 10

%pcc 30 10 10 𝑌 − 0.51 0.51 − 0.48


= ; 𝑌 = 0.43
%pw 30 10 − 30 30 − 10
RCR 2.9486
2 0.51 Y 0.48 𝑍 − 0.45 0.45 − 0.43
= ; 𝑍 = 0.43
2.9486 CU 10 − 30 30 − 10
3 0.45 Z 0.43
𝐶𝑈 − 𝑌 𝑌−𝑍
= ; 𝐶𝑈 = 0.43
2.9486 − 2 2−3
𝐿∗𝑊 7.9180∗9.9483
𝑅𝐼 = ℎ = = 1.6957
𝑅𝐶 ∗(𝐿+𝑊) 2.6∗(7.9180+9.9483)

Type Direct Type Direct Type Direct


RI = 1.5 RI = 1.6957 RI >= 2.5
Maintenance 3 years Maintenance 3 years Maintenance 3 years
Interval Interval Interval
Environmental Environmental Environmental
Clean 0.94 Clean RSDD Clean 0.96

𝑅𝑆𝐷𝐷 − 0.94 0.94 − 0.96


= ; 𝑅𝑆𝐷𝐷 = 0.9439
1.6957 − 1.5 1.5 − 2.5

8ℎ𝑟𝑠 30𝑑𝑎𝑦𝑠 10𝑚𝑜𝑛𝑡ℎ𝑠


𝐻𝑜𝑢𝑟𝑠 𝑜𝑓 𝑂𝑝𝑒𝑟𝑎𝑡𝑖𝑜𝑛 = ∗ ∗ ∗ 3𝑦𝑒𝑎𝑟𝑠 = 7200ℎ𝑜𝑢𝑟𝑠
𝑑𝑎𝑦 𝑚𝑜𝑛𝑡ℎ 𝑦𝑒𝑎𝑟

LLMF = LLD =0.89; LBO = 0.975; LaMF = 0.875

Type Diffuser
𝐿𝐷𝐷 = 0.79
Maintenance Interval 3 years
Environmental
Clean 0.79

𝐿𝐿𝐹 = 𝑅𝑆𝐷𝐷 ∗ 𝐿𝐿𝐷 ∗ 𝐿𝐵𝑂 ∗ 𝐿𝐷𝐷 ∗ 𝐿𝑎𝑀𝐹


𝐿𝐿𝐹 = 0.9439 ∗ 0.89 ∗ 0.975 ∗ 0.79 ∗ 0.875 = 0.5662

1 𝐴 1 89.0392
𝑆𝐻𝑅 = √ = √ = 0.49
ℎ𝑅𝐶 𝑛 2.6 49

𝑀𝑎𝑥 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = 𝑀𝑆 = ℎ𝑅𝐶 ∗ 𝑆𝐻𝑅 = 2.6 ∗ 0.49 = 1.2740


𝑤𝑖𝑑𝑡ℎ 9.9483
𝑟𝑜𝑤𝑠 = = = 7.81 ≈ 8
𝑀𝑆 1.2740
𝑛 48.53
𝑐𝑜𝑙𝑢𝑚𝑛 = = = 6.22 ≈ 6
𝑟𝑜𝑤𝑠 7.81
𝑤𝑖𝑑𝑡ℎ 9.9483
𝐴𝑥𝑖𝑎𝑙 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 1.2740
𝑟𝑜𝑤𝑠 7.81
𝑙𝑒𝑛𝑔ℎ𝑡 7.9180
𝑇𝑟𝑎𝑛𝑠𝑣𝑒𝑟𝑠𝑒 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 1.2740
𝑐𝑜𝑙𝑢𝑚𝑛𝑠 6.22
𝑙𝑢𝑚𝑒𝑛𝑠
𝑛∗( ) ∗ 𝐶𝑈 ∗ 𝐿𝐿𝐹 49 ∗ 2000 ∗ 0.43 ∗ 0.5662
𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑐𝑒 𝑙𝑒𝑣𝑒𝑙 = 𝑙𝑢𝑚𝑒𝑛𝑎𝑖𝑟𝑒 = = 300 𝑙𝑢𝑥
𝐴𝑟𝑒𝑎 78.7706
GENERAL INFORMATION

Project identification: TERRACE


(Given name of area and/or building and room number)

Average maintained illuminance for design: 200 lux or Foot-candles Lamp data:
Type and color: Daylight
Luminaire data: Number per luminaire: 1
Manufacturer: FUMACO Total lumens per luminaire: 3000
Catalog number: FUMACO LED DL 72 5700K

SELECTION OF COEFFICIENT OF UTILIZATION

Step 1: Fill in sketch at right

80 0

Step 2: Determine Cavity Ratios 5.8370 m


50
Room Index = 1.4149 2.6 m
Room Cavity Ratio, RCR = 3.5339 50
Ceiling Cavity Ratio, CCR = 0
Floor Cavity Ratio, FCR = 0.5437
9.9483 m
50 30 0.4 m

Step 3: Obtain Effective Ceiling Cavity Reflectance (ρCC) ρCC = 0.80

Step 4: Obtain Effective Floor Cavity Reflectance (ρFC) ρFC = 0.29

Step 5: Obtain Coefficient of Utilization (CU) from Manufacturer’s Data CU = 0.4999

SECTION OFLIGHT LOSS FACTORS

Nonrecoverable Recoverable

Luminaire ambient temperature ______ Room surface dirt depreciation (RSDD) 0.8543

Voltage to luminaire ______ Lamp lumen depreciation (LLD) 1

Ballast factor ______ Lamp burnouts factor (LBO) 1

Luminaire surface depreciation ______ Luminaire dirt depreciation (LDD) 0.79

Lamp maintance factor LaMF 1

Total light loss factor, LLF (product of individual factor above) = 0.6749

CALCULATIONS

(Average Maintained Illuminance)


(𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑛𝑐𝑒)𝑥(𝐴𝑟𝑒𝑎) 200∗58.0682
Number of Luminaries = (𝐿𝑢𝑚𝑒𝑛𝑠 = =12.75≈13
𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 3000∗0.4999∗0.6749

(𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝐿𝑢𝑚𝑖𝑛𝑎𝑟𝑖𝑒𝑠)𝑥(𝐿𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 13∗3000∗0.4999∗0.6749


Illuminance = = = 200lux
(𝐴𝑟𝑒𝑎) 58.0682

Calculated by: John Michael E. Padrigo Date: May 2, 2019


CALCULATIONS:
L = 5.8370 m; W = 9.9483 m

𝐴𝑅𝐸𝐴 = 𝐿 ∗ 𝑊 = 5.8370 ∗ 9.9483 = 58.0682 𝑚2


Em = 200 lux
hCC = 0m; hRC = 2.6m; hFC = 0.4m
pc = 80%; pw = 50%; pf = 30%
COEFFICIENT OF UTILIZATION
𝐿+𝑊 5.8370 + 9.9483
𝑅𝐶𝑅 = 5 ∗ ℎ𝑅𝐶 ∗ = 5 ∗ 2.6 ∗ = 3.5339
𝐿∗𝑊 5.8370 ∗ 9.9483

ℎ𝐶𝐶 0
𝐶𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 3.5339 ∗ = 0
ℎ𝑅𝐶 2.6

ℎ𝐹𝐶 0.4
𝐹𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 3.5339 ∗ = 0.5437
ℎ𝑅𝐶 2.6

%pc 80 %pf 30
%pw 50 𝑝𝑓𝑐 − 29 29 − 28
%pw 50 = ; 𝑝𝑓𝑐 = 25.3%
0.5437 − 0.2 0.4 − 0.6
CCR FCR 0.3983
0 80 0.4 29
0.3983 pfc
pcc = 80% 0.6 28

%pcc 30 25.3 10 𝑌 − 0.48 0.48 − 0.46


= ; 𝑌 = 0.4753
%pw 50 25.3 − 30 30 − 10
RCR
3 0.48 Y 0.46 𝑍 − 0.44 0.44 − 0.41
= ; 𝑍 = 0.4330
3.5339 CU 25.3 − 30 30 − 10
4 0.44 Z 0.41
𝐶𝑈 − 𝑌 𝑌−𝑍
= ; 𝐶𝑈 = 0.4527
3.5339 − 2 3−4
𝐿∗𝑊 5.8370∗9.9483
𝑅𝐼 = ℎ = = 1.4149
𝑅𝐶 ∗(𝐿+𝑊) 2.6∗(5.8370+9.9483 )

Type Direct/ Type Direct/ Type Direct/


Indirect Indirect Indirect
RI = 1.5 RI = 1.41 RI >= 2.5
Maintenance 3 years Maintenance 3 years Maintenance 3 years
Interval Interval Interval
Environmental Environmental Environmental
Clean 0.85 Clean RSDD Clean 0.86

𝑅𝑆𝐷𝐷 − 0.85 0.85 − 0.86


= ; 𝑅𝑆𝐷𝐷 = 0.8491
1.4149 − 1.5 1.5 − 2.5

8ℎ𝑟𝑠 30𝑑𝑎𝑦𝑠 10𝑚𝑜𝑛𝑡ℎ𝑠


𝐻𝑜𝑢𝑟𝑠 𝑜𝑓 𝑂𝑝𝑒𝑟𝑎𝑡𝑖𝑜𝑛 = ∗ ∗ ∗ 3𝑦𝑒𝑎𝑟𝑠 = 7200 ℎ𝑜𝑢𝑟𝑠
𝑑𝑎𝑦 𝑚𝑜𝑛𝑡ℎ 𝑦𝑒𝑎𝑟

LLMF = LLD = 1; LBO = 1; LaMF = 1

Type Diffuser
𝐿𝐷𝐷 = 0.79
Maintenance Interval 3 years
Environmental
Clean 0.79

𝐿𝐿𝐹 = 𝑅𝑆𝐷𝐷 ∗ 𝐿𝐿𝐷 ∗ 𝐿𝐵𝑂 ∗ 𝐿𝐷𝐷 ∗ 𝐿𝑎𝑀𝐹


𝐿𝐿𝐹 = 0.8491 ∗ 1 ∗ 1 ∗ 0.79 ∗ 1 = 0.6708

1 𝐴 1 100.891
𝑆𝐻𝑅 = √ = √ = 0.8209
ℎ𝑅𝐶 𝑛 2.6 13

𝑀𝑎𝑥 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = 𝑀𝑆 = ℎ𝑅𝐶 ∗ 𝑆𝐻𝑅 = 2.6 ∗ 0.8209 = 2.1342


𝑤𝑖𝑑𝑡ℎ 9.9483
𝑟𝑜𝑤𝑠 = = = 4.66 ≈ 5
𝑀𝑆 2.1342
𝑛 13
𝑐𝑜𝑙𝑢𝑚𝑛 = = ≈4
𝑟𝑜𝑤𝑠 5
𝑤𝑖𝑑𝑡ℎ 9.9483
𝐴𝑥𝑖𝑎𝑙 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 2.1342
𝑟𝑜𝑤𝑠 5
𝑙𝑒𝑛𝑔ℎ𝑡 5.8370
𝑇𝑟𝑎𝑛𝑠𝑣𝑒𝑟𝑠𝑒 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 2.1342
𝑐𝑜𝑙𝑢𝑚𝑛𝑠 4

𝑙𝑢𝑚𝑒𝑛𝑠
𝑛∗( ) ∗ 𝐶𝑈 ∗ 𝐿𝐿𝐹 13 ∗ 3000 ∗ 0.4999 ∗ 0.6749
𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑐𝑒 𝑙𝑒𝑣𝑒𝑙 = 𝑙𝑢𝑚𝑒𝑛𝑎𝑖𝑟𝑒 = = 200 𝑙𝑢𝑥
𝐴𝑟𝑒𝑎 58.0682
GENERAL INFORMATION

Project identification: LAUNDRY AREA


(Given name of area and/or building and room number)

Average maintained illuminance for design: 300 lux or Foot-candles Lamp data:
Type and color: Daylight
Luminaire data: Number per luminaire: 1
Manufacturer: PHILIPS Total lumens per luminaire: 1034
Catalog number: Fugato LED, 4000K, 104ᵒ

SELECTION OF COEFFICIENT OF UTILIZATION

Step 1: Fill in sketch at right

80 0

Step 2: Determine Cavity Ratios 5.5832 m


50
Room Index = 0.8859 2.6 m
Room Cavity Ratio, RCR = 5.6438 50
Ceiling Cavity Ratio, CCR = 0
Floor Cavity Ratio, FCR = 0.8683
3.9211 m
50 30 0.4 m

Step 3: Obtain Effective Ceiling Cavity Reflectance (ρCC) ρCC = 0.80

Step 4: Obtain Effective Floor Cavity Reflectance (ρFC) ρFC = 0.10

Step 5: Obtain Coefficient of Utilization (CU) from Manufacturer’s Data CU = 0.43

SECTION OFLIGHT LOSS FACTORS

Nonrecoverable Recoverable

Luminaire ambient temperature ______ Room surface dirt depreciation (RSDD) 0.855

Voltage to luminaire ______ Lamp lumen depreciation (LLD) 0.93

Ballast factor ______ Lamp burnouts factor (LBO) 0.91

Luminaire surface depreciation ______ Luminaire dirt depreciation (LDD) 0.93

Lamp maintance factor LaMF 0.79

Total light loss factor, LLF (product of individual factor above) = 0.5079

CALCULATIONS

(Average Maintained Illuminance)


(𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑛𝑐𝑒)𝑥(𝐴𝑟𝑒𝑎) 300∗21.8923
Number of Luminaries = (𝐿𝑢𝑚𝑒𝑛𝑠 = =33.80≈34
𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 1034∗0.37∗0.5079

(𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝐿𝑢𝑚𝑖𝑛𝑎𝑟𝑖𝑒𝑠)𝑥(𝐿𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 34∗1034∗0.37∗0.5079


Illuminance = = = 300 𝑙𝑢𝑥
(𝐴𝑟𝑒𝑎) 21.8923

Calculated by: John Michael E. Padrigo Date: May 2, 2019


CALCULATIONS:
L = 5.5832 m; W = 3.9211 m

𝐴𝑅𝐸𝐴 = 𝐿 ∗ 𝑊 = 5.5832 ∗ 3.9211 = 21.8923𝑚2


Em = 300 lux
hCC = 0m; hRC = 2.6m; hFC = 0.4m
pc = 80%; pw = 50%; pf = 30%
COEFFICIENT OF UTILIZATION
𝐿+𝑊 5.5832 + 3.9211
𝑅𝐶𝑅 = 5 ∗ ℎ𝑅𝐶 ∗ = 5 ∗ 2.6 ∗ = 5.6438
𝐿∗𝑊 5.5832 ∗ 3.9211

ℎ𝐶𝐶 0
𝐶𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 5.6438 ∗ = 0
ℎ𝑅𝐶 2.6

ℎ𝐹𝐶 0.4
𝐹𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 5.6438 ∗ = 0.8683
ℎ𝑅𝐶 2.6

%pc 80 %pf 30
%pw 50 𝑝𝑓𝑐 − 28 28 − 27
%pw 50 = ; 𝑝𝑓𝑐 = 27.7%
0.8683 − 0.8 0.8 − 1.0
CCR FCR 0.8683
0 80 0.8 28
0.8683 pfc
pcc = 80% 1.0 27

%pcc 30 27.7 10 𝑌 − 0.39 0.39 − 0.37


= ; 𝑌 = 0.39
%pw 50 27.7 − 30 30 − 10
RCR 5.6438
5 0.39 Y 0.37 𝑍 − 0.36 0.36 − 0.34
= ; 𝑍 = 0.36
5.6438 CU 27.7 − 30 30 − 10
6 0.36 Z 0.34
𝐶𝑈 − 𝑌 𝑌−𝑍
= ; 𝐶𝑈 = 0.37
5.6438 − 5 5−6
𝐿∗𝑊 5.5832∗3.9211
𝑅𝐼 = ℎ = = 0.8859
𝑅𝐶 ∗(𝐿+𝑊) 2.6∗(5.5832+3.9211)

Type Direct Type Direct Type Direct


RI <=0.8 RI = 0.8859 RI >= 1.5
Maintenance 3 years Maintenance 3 years Maintenance 3 years
Interval Interval Interval
Environmental Environmental Environmental
Clean 0.84 Clean RSDD Clean 0.95

𝑅𝑆𝐷𝐷 − 0.84 0.84 − 0.95


= ; 𝑅𝑆𝐷𝐷 = 0.8535
0.8859 − 0.8 0.8 − 1.5

8ℎ𝑟𝑠 30𝑑𝑎𝑦𝑠 10𝑚𝑜𝑛𝑡ℎ𝑠


𝐻𝑜𝑢𝑟𝑠 𝑜𝑓 𝑂𝑝𝑒𝑟𝑎𝑡𝑖𝑜𝑛 = ∗ ∗ ∗ 3𝑦𝑒𝑎𝑟𝑠 = 7200ℎ𝑜𝑢𝑟𝑠
𝑑𝑎𝑦 𝑚𝑜𝑛𝑡ℎ 𝑦𝑒𝑎𝑟

LLMF = LLD = 0.93; LBO = 0.91; LaMF = 0.89

Type Diffuser
𝐿𝐷𝐷 = 0.79
Maintenance Interval 3 years
Environmental
Clean 0.79

𝐿𝐿𝐹 = 𝑅𝑆𝐷𝐷 ∗ 𝐿𝐿𝐷 ∗ 𝐿𝐵𝑂 ∗ 𝐿𝐷𝐷 ∗ 𝐿𝑎𝑀𝐹


𝐿𝐿𝐹 = 0.8535 ∗ 0.93 ∗ 0.91 ∗ 0.79 ∗ 0.89 = 0.5079

1 𝐴 1 21.8923
𝑆𝐻𝑅 = √ = √ = 0.3095
ℎ𝑅𝐶 𝑛 2.6 33.80

𝑀𝑎𝑥 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = 𝑀𝑆 = ℎ𝑅𝐶 ∗ 𝑆𝐻𝑅 = 2.6 ∗ 0.3095 = 0.8048


𝑤𝑖𝑑𝑡ℎ 3.9211
𝑟𝑜𝑤𝑠 = = = 4.87 ≈ 5
𝑀𝑆 0.8048
𝑛 33.80
𝑐𝑜𝑙𝑢𝑚𝑛 = = = 6.94 ≈ 7
𝑟𝑜𝑤𝑠 4.87
𝑤𝑖𝑑𝑡ℎ 3.9211
𝐴𝑥𝑖𝑎𝑙 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 0.8048
𝑟𝑜𝑤𝑠 4.87
𝑙𝑒𝑛𝑔ℎ𝑡 5.5832
𝑇𝑟𝑎𝑛𝑠𝑣𝑒𝑟𝑠𝑒 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 0.8048
𝑐𝑜𝑙𝑢𝑚𝑛𝑠 6.94
𝑙𝑢𝑚𝑒𝑛𝑠
𝑛∗( ) ∗ 𝐶𝑈 ∗ 𝐿𝐿𝐹 34 ∗ 1034 ∗ 0.37 ∗ 0.5079
𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑐𝑒 𝑙𝑒𝑣𝑒𝑙 = 𝑙𝑢𝑚𝑒𝑛𝑎𝑖𝑟𝑒 = = 300 𝑙𝑢𝑥
𝐴𝑟𝑒𝑎 21.8923
GENERAL INFORMATION

Project identification: BEDROOM 1 & 2


(Given name of area and/or building and room number)

Average maintained illuminance for design: 300 lux or Foot-candles Lamp data:
Type and color: LED Downlight
Luminaire data: Number per luminaire: 1
Manufacturer: PHILIPS Total lumens per luminaire: 2000
Catalog number: Smart LED Downlight 42W, 4000K

SELECTION OF COEFFICIENT OF UTILIZATION

Step 1: Fill in sketch at right

80 0

Step 2: Determine Cavity Ratios 5.5832 m


30
Room Index = 0.935 2.6 m
Room Cavity Ratio, RCR = 5.4142 30
Ceiling Cavity Ratio, CCR = 0
Floor Cavity Ratio, FCR = 0.8330
4.2128 m
30 10 0.4 m

Step 3: Obtain Effective Ceiling Cavity Reflectance (ρCC) ρCC = 0.80

Step 4: Obtain Effective Floor Cavity Reflectance (ρFC) ρFC = 0.10

Step 5: Obtain Coefficient of Utilization (CU) from Manufacturer’s Data CU = 0.3276

SECTION OFLIGHT LOSS FACTORS

Nonrecoverable Recoverable

Luminaire ambient temperature ______ Room surface dirt depreciation (RSDD) 0.9285

Voltage to luminaire ______ Lamp lumen depreciation (LLD) 0.89

Ballast factor ______ Lamp burnouts factor (LBO) 0.975

Luminaire surface depreciation ______ Luminaire dirt depreciation (LDD) 0.79

Lamp maintance factor LaMF 0.875

Total light loss factor, LLF (product of individual factor above) = 0.5569

CALCULATIONS

(Average Maintained Illuminance)


(𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑛𝑐𝑒)𝑥(𝐴𝑟𝑒𝑎) 300∗23.5209
Number of Luminaries = (𝐿𝑢𝑚𝑒𝑛𝑠 = =19.34≈19
𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 19∗1034∗0.3276∗0.5569

(𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝐿𝑢𝑚𝑖𝑛𝑎𝑟𝑖𝑒𝑠)𝑥(𝐿𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 19∗1034∗0.3276∗0.5569


Illuminance = = = 300 𝑙𝑢𝑥
(𝐴𝑟𝑒𝑎) 23.5209

Calculated by: John Michael E. Padrigo Date: May 2, 2019


CALCULATIONS:
L = 5.5832 m; W = 4.2128 m

𝐴𝑅𝐸𝐴 = 𝐿 ∗ 𝑊 = 5.5832 ∗ 4.2128 = 23.5209 𝑚2


Em = 300 lux
hCC = 0m; hRC = 2.6m; hFC = 0.4m
pc = 80%; pw = 30%; pf = 10%
COEFFICIENT OF UTILIZATION
𝐿+𝑊 7.9180 + 9.9483
𝑅𝐶𝑅 = 5 ∗ ℎ𝑅𝐶 ∗ = 5 ∗ 2.6 ∗ = 5.4142
𝐿∗𝑊 7.9180 ∗ 9.9483

ℎ𝐶𝐶 0
𝐶𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 5.4142 ∗ = 0
ℎ𝑅𝐶 2.6

ℎ𝐹𝐶 0.4
𝐹𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 5.4142 ∗ = 0.8330
ℎ𝑅𝐶 2.6

%pc 80 %pf 10
%pw 30 𝑝𝑓𝑐 − 10 10 − 10
%pw 50 = ; 𝑝𝑓𝑐 = 10%
0.8330 − 0.8 0.8 − 1.0
CCR FCR 0.8330
0 80 0.8 10
0.4536 pfc
pcc = 80% 1.0 10

%pcc 30 10 10 𝑌 − 0.36 0.36 − 0.34


= ; 𝑌 = 0.34
%pw 30 10 − 30 30 − 10
RCR 5.4142
5 0.36 Y 0.34 𝑍 − 0.32 0.32 − 0.31
= ; 𝑍 = 0.31
2.9486 CU 10 − 30 30 − 10
6 0.32 Z 0.31
𝐶𝑈 − 𝑌 𝑌−𝑍
= ; 𝐶𝑈 = 0.3276
5.4142 − 5 5−6
𝐿∗𝑊 5.5832∗4.2128
𝑅𝐼 = ℎ = = 0.9235
𝑅𝐶 ∗(𝐿+𝑊) 2.6∗(5.5832+4.2128)

Type Direct Type Direct Type Direct


RI = 1.5 RI = 0.9235 RI >= 2.5
Maintenance 3 years Maintenance 3 years Maintenance 3 years
Interval Interval Interval
Environmental Environmental Environmental
Clean 0.94 Clean RSDD Clean 0.96

𝑅𝑆𝐷𝐷 − 0.94 0.94 − 0.96


= ; 𝑅𝑆𝐷𝐷 = 0.9285
0.9235 − 1.5 1.5 − 2.5

8ℎ𝑟𝑠 30𝑑𝑎𝑦𝑠 10𝑚𝑜𝑛𝑡ℎ𝑠


𝐻𝑜𝑢𝑟𝑠 𝑜𝑓 𝑂𝑝𝑒𝑟𝑎𝑡𝑖𝑜𝑛 = ∗ ∗ ∗ 3𝑦𝑒𝑎𝑟𝑠 = 7200ℎ𝑜𝑢𝑟𝑠
𝑑𝑎𝑦 𝑚𝑜𝑛𝑡ℎ 𝑦𝑒𝑎𝑟

LLMF = LLD = 0.89; LBO = 0.975; LaMF = 0.875

Type Diffuser
𝐿𝐷𝐷 = 0.79
Maintenance Interval 3 years
Environmental
Clean 0.79

𝐿𝐿𝐹 = 𝑅𝑆𝐷𝐷 ∗ 𝐿𝐿𝐷 ∗ 𝐿𝐵𝑂 ∗ 𝐿𝐷𝐷 ∗ 𝐿𝑎𝑀𝐹


𝐿𝐿𝐹 = 0.9285 ∗ 0.89 ∗ 0.975 ∗ 0.79 ∗ 0.875 = 0.5569

1 𝐴 1 23.5209
𝑆𝐻𝑅 = √ = √ = 0.4242
ℎ𝑅𝐶 𝑛 2.6 19

𝑀𝑎𝑥 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = 𝑀𝑆 = ℎ𝑅𝐶 ∗ 𝑆𝐻𝑅 = 2.6 ∗ 0.4242 = 1.1029


𝑤𝑖𝑑𝑡ℎ 4.2128
𝑟𝑜𝑤𝑠 = = = 3.82 ≈ 4
𝑀𝑆 1.1029
𝑛 19.34
𝑐𝑜𝑙𝑢𝑚𝑛 = = = 5.06 ≈ 5
𝑟𝑜𝑤𝑠 3.82
𝑤𝑖𝑑𝑡ℎ 4.2128
𝐴𝑥𝑖𝑎𝑙 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 1.1029
𝑟𝑜𝑤𝑠 3.82
𝑙𝑒𝑛𝑔ℎ𝑡 5.5832
𝑇𝑟𝑎𝑛𝑠𝑣𝑒𝑟𝑠𝑒 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 1.1029
𝑐𝑜𝑙𝑢𝑚𝑛𝑠 5.06
𝑙𝑢𝑚𝑒𝑛𝑠
𝑛∗( ) ∗ 𝐶𝑈 ∗ 𝐿𝐿𝐹 19 ∗ 1034 ∗ 0.3276 ∗ 0.5569
𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑐𝑒 𝑙𝑒𝑣𝑒𝑙 = 𝑙𝑢𝑚𝑒𝑛𝑎𝑖𝑟𝑒 = = 300 𝑙𝑢𝑥
𝐴𝑟𝑒𝑎 23.5209
GENERAL INFORMATION

Project identification: CR 1 & 2


(Given name of area and/or building and room number)

Average maintained illuminance for design: 200 lux or Foot-candles Lamp data:
Type and color: Daylight
Luminaire data: Number per luminaire: 1
Manufacturer: FUMACO Total lumens per luminaire: 3000
Catalog number: FUMACO LED DL 72 5700K

SELECTION OF COEFFICIENT OF UTILIZATION

Step 1: Fill in sketch at right

80 0

Step 2: Determine Cavity Ratios 5.5832 m


50
Room Index = 0.8184 2.6 m
Room Cavity Ratio, RCR = 6.1091 50
Ceiling Cavity Ratio, CCR = 0
Floor Cavity Ratio, FCR = 0.9399
3.4385 m
50 30 0.4 m

Step 3: Obtain Effective Ceiling Cavity Reflectance (ρCC) ρCC = 0.80

Step 4: Obtain Effective Floor Cavity Reflectance (ρFC) ρFC = 0.273

Step 5: Obtain Coefficient of Utilization (CU) from Manufacturer’s Data CU = 0.3531

SECTION OFLIGHT LOSS FACTORS

Nonrecoverable Recoverable

Luminaire ambient temperature ______ Room surface dirt depreciation (RSDD) 0.8429

Voltage to luminaire ______ Lamp lumen depreciation (LLD) 1

Ballast factor ______ Lamp burnouts factor (LBO) 1

Luminaire surface depreciation ______ Luminaire dirt depreciation (LDD) 0.79

Lamp maintance factor LaMF 1

Total light loss factor, LLF (product of individual factor above) = 0.6659

CALCULATIONS

(Average Maintained Illuminance)


(𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑛𝑐𝑒)𝑥(𝐴𝑟𝑒𝑎) 200∗19.1978
Number of Luminaries = (𝐿𝑢𝑚𝑒𝑛𝑠 = =5.44≈5
𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 3000∗0.3531∗0.6659

(𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝐿𝑢𝑚𝑖𝑛𝑎𝑟𝑖𝑒𝑠)𝑥(𝐿𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 5∗3000∗0.3531∗0.6659


Illuminance = = = 200lux
(𝐴𝑟𝑒𝑎) 19.1978

Calculated by: John Michael E. Padrigo Date: May 2, 2019


CALCULATIONS:
L = 5.5832m; W = 3.4385m

𝐴𝑅𝐸𝐴 = 𝐿 ∗ 𝑊 = 5.5832 ∗ 3.4385 = 19.1978 𝑚2


Em = 200 lux
hCC = 0m; hRC = 2.6m; hFC = 0.4m
pc = 80%; pw = 50%; pf = 30%
COEFFICIENT OF UTILIZATION
𝐿+𝑊 5.5832 + 3.4385
𝑅𝐶𝑅 = 5 ∗ ℎ𝑅𝐶 ∗ = 5 ∗ 2.6 ∗ = 6.1091
𝐿∗𝑊 5.5832 ∗ 3.4385

ℎ𝐶𝐶 0
𝐶𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 6.1091 ∗ = 0
ℎ𝑅𝐶 2.6

ℎ𝐹𝐶 0.4
𝐹𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 6.1091 ∗ = 0.9399
ℎ𝑅𝐶 2.6

%pc 80 %pf 30
%pw 50 𝑝𝑓𝑐 − 28 28 − 27
%pw 50 = ; 𝑝𝑓𝑐 = 27.3%
0.9399 − 0.8 0.8 − 1.0
CCR FCR 0.9399
0 80 0.8 29
0.9399 pfc
pcc = 80% 1.0 29

%pcc 30 27.3 10 𝑌 − 0.36 0.36 − 0.34


= ; 𝑌 = 0.3573
%pw 50 27.3 − 30 30 − 10
RCR
6 0.36 Y 0.34 𝑍 − 0.32 0.32 − 0.31
= ; 𝑍 = 0.3187
2.5886 CU 27.3 − 30 30 − 10
7 0.32 Z 0.31
𝐶𝑈 − 𝑌 𝑌−𝑍
= ; 𝐶𝑈 = 0.3531
6.1091 − 6 6−7
𝐿∗𝑊 5.5832∗3.4385
𝑅𝐼 = ℎ = = 0.8184
𝑅𝐶 ∗(𝐿+𝑊) 2.6∗(5.5832+3.4385)

Type Direct Type Direct Type Direct


RI <= 0.8 RI = 1.93 RI = 1.5
Maintenance 3 years Maintenance 3 years Maintenance 3 years
Interval Interval Interval
Environmental Environmental Environmental
Clean 0.84 Clean RSDD Clean 0.95

𝑅𝑆𝐷𝐷 − 0.84 0.84 − 0.95


= ; 𝑅𝑆𝐷𝐷 = 0.8429
0.8184 − 0.8 0.8 − 1.5

8ℎ𝑟𝑠 30𝑑𝑎𝑦𝑠 10𝑚𝑜𝑛𝑡ℎ𝑠


𝐻𝑜𝑢𝑟𝑠 𝑜𝑓 𝑂𝑝𝑒𝑟𝑎𝑡𝑖𝑜𝑛 = ∗ ∗ ∗ 3𝑦𝑒𝑎𝑟𝑠 = 7200 ℎ𝑜𝑢𝑟𝑠
𝑑𝑎𝑦 𝑚𝑜𝑛𝑡ℎ 𝑦𝑒𝑎𝑟

LLMF = LLD = 1; LBO = 1; LaMF = 1

Type Diffuser
𝐿𝐷𝐷 = 0.79
Maintenance Interval 3 years
Environmental
Clean 0.79

𝐿𝐿𝐹 = 𝑅𝑆𝐷𝐷 ∗ 𝐿𝐿𝐷 ∗ 𝐿𝐵𝑂 ∗ 𝐿𝐷𝐷 ∗ 𝐿𝑎𝑀𝐹


𝐿𝐿𝐹 = 0.8429 ∗ 1 ∗ 1 ∗ 0.79 ∗ 1 = 0.6749

1 𝐴 1 19.1978
𝑆𝐻𝑅 = √ = √ = 0.7223
ℎ𝑅𝐶 𝑛 2.6 5.44

𝑀𝑎𝑥 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = 𝑀𝑆 = ℎ𝑅𝐶 ∗ 𝑆𝐻𝑅 = 2.6 ∗ 0.7223 = 1.8780


𝑤𝑖𝑑𝑡ℎ 3.4385
𝑟𝑜𝑤𝑠 = = = 1.83 ≈ 2
𝑀𝑆 1.8780
𝑛 5.44
𝑐𝑜𝑙𝑢𝑚𝑛 = = = 2.97 ≈ 3
𝑟𝑜𝑤𝑠 1.83
𝑤𝑖𝑑𝑡ℎ 3.4385
𝐴𝑥𝑖𝑎𝑙 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 1.8780
𝑟𝑜𝑤𝑠 1.83
𝑙𝑒𝑛𝑔ℎ𝑡 5.5832
𝑇𝑟𝑎𝑛𝑠𝑣𝑒𝑟𝑠𝑒 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 1.8780
𝑐𝑜𝑙𝑢𝑚𝑛𝑠 2.97

𝑙𝑢𝑚𝑒𝑛𝑠
𝑛∗( ) ∗ 𝐶𝑈 ∗ 𝐿𝐿𝐹 5 ∗ 3000 ∗ 0.3531 ∗ 0.6659
𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑐𝑒 𝑙𝑒𝑣𝑒𝑙 = 𝑙𝑢𝑚𝑒𝑛𝑎𝑖𝑟𝑒 = = 200 𝑙𝑢𝑥
𝐴𝑟𝑒𝑎 19.1978
GENERAL INFORMATION

Project identification: KITCHEN


(Given name of area and/or building and room number)

Average maintained illuminance for design: 500 lux or Foot-candles Lamp data:
Type and color: Daylight
Luminaire data: Number per luminaire: 1
Manufacturer: FUMACO Total lumens per luminaire: 3000
Catalog number: FUMACO LED DL 72 5700K

SELECTION OF COEFFICIENT OF UTILIZATION

Step 1: Fill in sketch at right

80 0

Step 2: Determine Cavity Ratios 9.1362 m


50
Room Index = 0.9676 2.6 m
Room Cavity Ratio, RCR = 5.1675 50
Ceiling Cavity Ratio, CCR = 0
Floor Cavity Ratio, FCR = 0.7950
3.4717 m
50 30 0.4 m

Step 3: Obtain Effective Ceiling Cavity Reflectance (ρCC) ρCC = 0.80

Step 4: Obtain Effective Floor Cavity Reflectance (ρFC) ρFC = 0.2403

Step 5: Obtain Coefficient of Utilization (CU) from Manufacturer’s Data CU = 0.379

SECTION OFLIGHT LOSS FACTORS

Nonrecoverable Recoverable

Luminaire ambient temperature ______ Room surface dirt depreciation (RSDD) 0.8663

Voltage to luminaire ______ Lamp lumen depreciation (LLD) 0.85

Ballast factor ______ Lamp burnouts factor (LBO) 0.94

Luminaire surface depreciation ______ Luminaire dirt depreciation (LDD) 0.79

Lamp maintance factor LaMF 0.90

Total light loss factor, LLF (product of individual factor above) = 0.4921

CALCULATIONS

(Average Maintained Illuminance)


(𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑛𝑐𝑒)𝑥(𝐴𝑟𝑒𝑎) 200∗31.7181
Number of Luminaries = (𝐿𝑢𝑚𝑒𝑛𝑠 = =28.33≈28
𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 3000∗0.379∗0.4921

(𝑁𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝐿𝑢𝑚𝑖𝑛𝑎𝑟𝑖𝑒𝑠)𝑥(𝐿𝑢𝑚𝑒𝑛𝑠 𝑝𝑒𝑟 𝐿𝑢𝑚𝑖𝑛𝑎𝑖𝑟𝑒)𝑥(𝐶𝑈)𝑥(𝐿𝐿𝐹) 28∗3000∗0.379∗0.4921


Illuminance = = = 500lux
(𝐴𝑟𝑒𝑎) 31.7181

Calculated by: John Michael E. Padrigo Date: May 2, 2019


CALCULATIONS:
L = 9.1362m; W = 3.4717m

𝐴𝑅𝐸𝐴 = 𝐿 ∗ 𝑊 = 9.1362 ∗ 3.4717 = 31.7181 𝑚2


Em = 200 lux
hCC = 0m; hRC = 2.6m; hFC = 0.4m
pc = 80%; pw = 50%; pf = 30%
COEFFICIENT OF UTILIZATION
𝐿+𝑊 9.1362 + 3.4717
𝑅𝐶𝑅 = 5 ∗ ℎ𝑅𝐶 ∗ = 5 ∗ 2.6 ∗ = 5.1675
𝐿∗𝑊 9.1362 ∗ 3.4717

ℎ𝐶𝐶 0
𝐶𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 5.1675 ∗ = 0
ℎ𝑅𝐶 2.6

ℎ𝐹𝐶 0.4
𝐹𝐶𝑅 = 𝑅𝐶𝑅 ∗ = 5.1675 ∗ = 0.7950
ℎ𝑅𝐶 2.6

%pc 80 %pf 30
%pw 50 𝑝𝑓𝑐 − 28 28 − 27
%pw 50 = ; 𝑝𝑓𝑐
0.7950 − 0.8 0.8 − 1.0
CCR FCR 0.7950 = 24.03%
0 80 0.8 29
0.7950 pfc
1.0 29
pcc = 80%

%pcc 30 24.03 10 𝑌 − 0.39 0.39 − 0.37


= ; 𝑌 = 0.3840
%pw 50 24.03 − 30 30 − 10
RCR
5 0.39 Y 0.37 𝑍 − 0.36 0.36 − 0.34
= ; 𝑍 = 0.3540
5.1675 CU 24.03 − 30 30 − 10
6 0.36 Z 0.34
𝐶𝑈 − 𝑌 𝑌−𝑍
= ; 𝐶𝑈 = 0.3790
5.1675 − 5 5−6
𝐿∗𝑊 9.1362∗3.4717
𝑅𝐼 = ℎ = = 0.9676
𝑅𝐶 ∗(𝐿+𝑊) 2.6∗(9.1362+3.4717)

Type Direct Type Direct Type Direct


RI <= 0.8 RI = 0.9676 RI = 1.5
Maintenance 3 years Maintenance 3 years Maintenance 3 years
Interval Interval Interval
Environmental Environmental Environmental
Clean 0.84 Clean RSDD Clean 0.95

𝑅𝑆𝐷𝐷 − 0.84 0.84 − 0.95


= ; 𝑅𝑆𝐷𝐷 = 0.8663
0.9676 − 0.8 0.8 − 1.5

8ℎ𝑟𝑠 30𝑑𝑎𝑦𝑠 10𝑚𝑜𝑛𝑡ℎ𝑠


𝐻𝑜𝑢𝑟𝑠 𝑜𝑓 𝑂𝑝𝑒𝑟𝑎𝑡𝑖𝑜𝑛 = ∗ ∗ ∗ 3𝑦𝑒𝑎𝑟𝑠 = 7200 ℎ𝑜𝑢𝑟𝑠
𝑑𝑎𝑦 𝑚𝑜𝑛𝑡ℎ 𝑦𝑒𝑎𝑟

LLMF = LLD = 0.85; LBO = 0.94; LaMF = 0.90

Type Diffuser
𝐿𝐷𝐷 = 0.79
Maintenance Interval 3 years
Environmental
Clean 0.79

𝐿𝐿𝐹 = 𝑅𝑆𝐷𝐷 ∗ 𝐿𝐿𝐷 ∗ 𝐿𝐵𝑂 ∗ 𝐿𝐷𝐷 ∗ 𝐿𝑎𝑀𝐹


𝐿𝐿𝐹 = 0.8663 ∗ 0.85 ∗ 0.94 ∗ 0.79 ∗ 0.90 = 0.4921

1 𝐴 1 19.1978
𝑆𝐻𝑅 = √ = √ = 0.4069
ℎ𝑅𝐶 𝑛 2.6 28.33

𝑀𝑎𝑥 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = 𝑀𝑆 = ℎ𝑅𝐶 ∗ 𝑆𝐻𝑅 = 2.6 ∗ 0.4069 = 1.0581


𝑤𝑖𝑑𝑡ℎ 3.4717
𝑟𝑜𝑤𝑠 = = = 3.28 ≈ 3
𝑀𝑆 1.0581
𝑛 28.33
𝑐𝑜𝑙𝑢𝑚𝑛 = = = 8.63 ≈ 9
𝑟𝑜𝑤𝑠 3.28
𝑤𝑖𝑑𝑡ℎ 3.4717
𝐴𝑥𝑖𝑎𝑙 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 1.0581
𝑟𝑜𝑤𝑠 3.28
𝑙𝑒𝑛𝑔ℎ𝑡 9.1362
𝑇𝑟𝑎𝑛𝑠𝑣𝑒𝑟𝑠𝑒 𝑠𝑝𝑎𝑐𝑖𝑛𝑔 = = = 1.0581
𝑐𝑜𝑙𝑢𝑚𝑛𝑠 8.63

𝑙𝑢𝑚𝑒𝑛𝑠
𝑛∗( ) ∗ 𝐶𝑈 ∗ 𝐿𝐿𝐹 28 ∗ 3000 ∗ 0.379 ∗ 0.4921
𝐼𝑙𝑙𝑢𝑚𝑖𝑛𝑎𝑐𝑒 𝑙𝑒𝑣𝑒𝑙 = 𝑙𝑢𝑚𝑒𝑛𝑎𝑖𝑟𝑒 = = 500 𝑙𝑢𝑥
𝐴𝑟𝑒𝑎 31.7181