ATTACHMENT 1..

PABRIK

REVISION 0 1 2 3 JOB. NO. P/12013


INDOOR LIGHTING CALCULATION
DATE 04/08/17 DOC. NO -
Ref. Dwg. No. DESIGNED LST SHEET 1 OF 1
DBAC302692 CHECKED BDA
APPROVED BDA
ROOM / LOCATION : COAL STORAGE (+.0.00)
AVERAGE MAINTAINED ILLUMINATION DESIGN PER SPECIFICATION : 200 Lux

1. Room Data :
Ceiling cavity
Length (L) 32 M hCC
Width (W) 24 M
High (H) 14 M Room cavity
Work Plan (HI) 0,75 M Room hRC
Room area (A) 768,00 M²
Work Plane
2. Fixture and Lamp data :
Floor cavity hFC
Manufacturer -
Catalog No. -
Lamp type & color INDUSTRIAL LAMP
Number / Fixture LED 100 W
Total Lumen 12000 LUMENS 5. Base reflectances factor in room

3. Cavity data : Wall Reflectances (r W) see table-1 0,5


h CC 0,00 M Ceiling Reflectances (r C) see table-1 0,5
h RC 13,25 M Floor Reflectances (r F) 0,3
h FC 0,75 M
TABLE - 1 Reflectances in room :
No. Color Reflection factor
4. Selection Light Lost Factor :
Very clean 0,80 1 White 0.80
Clean 0,75 2 Light tint's of blue green, cream blue 0.70
Medium 0,70 buff of gray
Dirty 0,60 3 Medium buff, or gray 0.50
Very dirty 0,55 4 Dark gray, medium blue 0.30
5 Dark blue, brown, dark green and 0.10
many wood finishes, such as :
6. Determine Coeficients of Utilization : dark oak abd mahogany

Ceiling Cavity Ratio = 5 x hC C ( L + W ) 5 x 0,0 ( 32 + 24 )= 0,00


(CCR) L x W 32 x 24

Room Cavity Ratio = 5 x h RC ( L + W ) 5 x 13,3 ( 32 + 24 ) = 4,83


(RCR) L x W 32 x 24

Floor Cavity Ratio = 5 x h FC ( L + W ) 5 x 0,8 ( 32 + 24 ) = 0,27


(FCR) L x W 32 x 24

7. Efective Cavity Reflectance


Ceiling Cavity Reflectance : rC = 0,50 (r CC) : 0,48 use 0,50 (*) according to IESNA Handbook
( r CC ) rW = 0,50
CCR = 0,00

Floor Cavity Reflectance : rF = 0,30


( r FC ) rW = 0,50 (r FC) : 0,25 (*) according to IESNA Handbook
FCR = 0,27

8. Selection Coeficient of Utilization (CU)

Coefficient of Untilization : r CC = 0,50


(CU) rW = 0,50 (CU) : 0,52 (*) according to IESNA Handbook
RCR = 4,83

Multiplier Corection Factor r CC = 0,50


r W = 0,50 (MCU) : 1,024 (*) according to IESNA Handbook
RCR = 4,83

Final Coefficient of Utilization (CU) : (CU) x (MCU) = 0,52 x 1,024 = 0,53

9. Number of Fixtures :

E x A 200 x 768 34,34 EA


N= = =
LM x CU x LLF 12000 x 0,53 x 0,7

10. Average Illumination Calculation :

N x LM x CU x LLF 35 x 12000 x 0,53 x 0,7 204 lux


E= = =
A 768

NOTES : MINIMUM 35 FIXTURE USING INDUSTRIAL LAMP LED 100 W