Bracing Pipe
Bracing Pipe
Sheet 3 of 3
P.O. Box 14330, Doha - Qatar. Prepared by AM
Tel.: 488 6531 Fax: 488 6507 Checked by JN
email : ammico@qatar.net.qa Date 15/09/2008
QNB TOWER PROJECT
DESIGN OF ANCHORS
Sand
- 4.0 QND
10.5m
- 7.1 QND 5.0m
10.0m
- 10.2 QND 5.0m Grouted part of anchors
8.5m
5.0m
- 13.3 QND
Limestone Rock
Excavation Level - 15.0 QND
- 19.5 QND
Note:
DESIGN OF ANCHORS
Sand
- 4.0 QND
10.5m
- 7.1 QND 5.0m
10.0m
- 10.2 QND 5.0m Grouted part of anchors
8.5m
5.0m
- 13.3 QND
7.0m
5.0m Limestone Rock
Excavation Level - 15.0 QND
- 19.5 QND
Note:
DESIGN OF ANCHORS
Surcharge = 25 Kpa
+ 2.5 QND EGL
Sand
- 4.0 QND
11.5m 6.0m
9.0m 7.5m
Limestone Rock
- 19.5 QND
Note:
DESIGN OF ANCHORS
Sand
- 4.0 QND
10.5m
- 7.1 QND 5.0m
10.0m
- 10.2 QND 5.0m Grouted part of anchors
8.5m
5.0m
- 13.3 QND
7.5m
5.0m Limestone Rock
Excavation Level - 15.0 QND
- 19.5 QND
Note:
g) Max. distance b/w property line & Extreme inner face of Diaphragm wall = b)+c)+d)
at wall top = 800+50+10.3
= 860.3 mm
h) Max. distance b/w property line & Extreme inner face of Diaphragm wall = b)+c)+e)+f)
at excavation level = 800+50+16.5+130
= 996.5 mm
say = 1000 mm
Ammico Contracting Co. W.L.L. Job No. Sheet 1 of 1
P.O. Box 14330, Doha - Qatar. Prepared by AM
Tel.: 488 6531 Fax: 488 6507 Checked by JN
email : ammico@qatar.net.qa Date 16-07-08
QNB TOWER PROJECT
g) Max. distance b/w property line & Extreme inner face of Diaphragm wall = b)+c)+d)
at wall top = 800+50+10.3
= 921 mm
h) Max. distance b/w property line & Extreme inner face of Diaphragm wall = b)+c)+e)+f)
at excavation level = 800+50+50+100
= 1000 mm
say = 1000 mm
Ammico Contracting Co. W.L.L. Job No. Sheet 1 of 1
P.O. Box 14330, Doha - Qatar. Prepared by MA
Tel.: 488 6531 Fax: 488 6507 Checked by MAA
email : ammico@qatar.net.qa Date 24-Oct-10
4B+G+M+7 Office Building
Columns & walls load ( take 40% of slab load),Dcw = 0.4*7.50 = 3.00 kPa
Total dead load for one storey, (DL=Dsw+Dcw) = 7.50+3.75 = 10.50 kPa
Columns & walls load ( take 40% of slab load),Dcw = 0.4*7.50 = 3.00 kPa
Total dead load for one storey, (DL=Dsw+Dcw) = 7.50+3.75 = 10.50 kPa
As the building is situated approximately 8 to 10m away from the shoring line so use total building
surcharge at a distance of 8m from shoring line and use surcharge of basement and raft immediate from
shoring line
BARZAN PILES
Entrance tent
Short column piles : The difference between the old design and new design is 116.23 kg steel.
Original contract rate : 3,999 QR / no
Revised rate : 4,450 QR / no Supply and fabrication of additional steel
Long column piles : The difference between the old design and new design is 115.56 kg steel.
Original contract rate : 3,756 QR / no
Revised rate : 4,205 QR / no Supply and fabrication of additional steel
Tent B / C / D / E / F
All pile (short & long column) are same as the piles on Children playground (old design), therefore
that rate available on the original contract shall be followed
Original contract rate : 1,955 QR / no
Revised rate : 1,994 QR / no Supply and fabrication of additional steel
Tent A
Short column piles : The difference between the piles on Tent B (new design) is only 0.5 kg steel,
all reamining pile details are same (diameter, length, etc)
Original contract rate : 1,968 QR / no
Revised rate : 2,000 QR / no Supply and fabrication of additional steel
Children Playground
Side column piles : Since pile length is increased (1m), the steel and concrete volume is increased.
Besides this new design of this pile is very similar to the old design of Entrance Tent long columns
Original contract rate : 2,803 QR / no
Revised rate : 3,427 QR / no Supply and fabrication of additional steel
Supply of additional concrete
Workmanship for extra drilling
Boundary column piles : The pile diameter is revised and the difference between the old design and
new design is 74.40 kg steel & 0.91m3 concrete. Meanwhile, this pile is same as the side column
piles.
Original contract rate : 1,944 QR / no
Revised rate : 3,427 QR / no Supply and fabrication of additional steel
Supply of additional concrete
Workmanship for bigger diameter drilling
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Ammico Contracting Co. W.L.L. Job No. Sheet 1 of 1
P.O. Box 14330, Doha - Qatar. Prepared by AM
Tel.: 488 6531 Fax: 488 6507 Checked by JN
email : ammico@qatar.net.qa Date 12/8/2008
QNB TOWER PROJECT
Columns & walls load ( take 50% of slab load),Dcw = 0.4*7.5 = 3.0 kPa
Total dead load for one storey, (DL=Dsw+Dcw) = 7.5+3.0 = 10.5 kPa
Total
Total Steel in
Concrete Steel in single
Sr. No. Description Shoring Type Wall Length (m) No. of Piles Wall Top Wall toe Wall Height Reinforcement hard piles
Volume hard pile (kg)
(kg)
(m3)
1 Road side 800@600 c/c 63.56 53 53 106 -1 -23 22 10 d 40 d 16 175 1172.191 2985.884 158,251.8
2 IBQ Side (3B Side) 750@650 c/c 58.415 46 45 91 -12 -21 9 7 d 28 d 12 225 361.823 420.776 18,934.90
3 Residential Bldg (2B) 750@600 c/c 63.56 54 53 107 -8 -22 14 7 d 32 d 12 200 661.796 880.440 46,663.33
HSBC Side (1B) with
4 800@600 58.415 49 49 98 -4 -23 19 6 d 32 d 12 125 935.943 1124.972 55,123.63
three anchors
3131.754 278,973.68
FFICE BUILDING - CONTRACTOR's DESIGN
Remarks
LUSAIL SANDS TWIN TOWER PROJECT - EHAAF
Pile Reinforcement Evaluation
1 Road side 800 1 22 22 40 10 1 2 2 260 260 2565.336 16 175 125.7 250 20 0.8 266.39 420.55 2985.88
2IBQ Side (3B Side)750 1 9 9 28 7 0 1.4 1.4 72.8 72.8 351.9641 12 225 40.0 74 6 0.6 77.49 68.81 420.78
2Residential Bldg (2B)750 1 14 14 32 7 1 1.6 1.6 120.4 120.4 760.2866 12 200 70.0 129 10 0.6 135.31 120.15 880.44
HSBC 4
Side (1B) with three 800
anchors 1 19 19 32 6 1 1.6 1.6 133.2 133.2 841.1144 12 125 152.0 305 25 0.6 319.66 283.86 1124.97
135.72
46.75
62.89
59.21
For member in axial compression, can be classified as: Class 3 - Semi Compact Ref: 2
Considering strut element as "pinned" at both ends, effective length shall be equal to length of strut.
One side of the strut is supported at the waller beam installed at the d-wall face and other end is at
pile foundation with pilecap installed for the strut.
Fc Mx My Ref: 2
+ + ≤ 1
Aeffpy Mcx Mcy
Fc mxMx Fc
Pcx
+
Mcx
(1 + 0.5 ) ≤ 1
Pcx Ref: 2
Fc myMy Fc
Pcy
+
Mcy
(1 + 0.5 ) ≤ 1
Pcx Ref: 2
0.582 + 0 = 0.582 ≤ 1
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 1
Prepared by: M
MEDICO
Checked by: G
Date 11-Nov-18
For member in axial compression, can be classified as: Class 4 - Slender Ref: 2
Considering strut element as "pinned" at both ends, effective length shall be equal to length of strut.
One side of the strut is supported at the waller beam installed at the d-wall face and other end is at
pile foundation with pilecap installed for the strut.
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 2
Prepared by: M
MEDICO
Checked by: G
Date 11-Nov-18
Fc Mx My Ref: 2
+ + ≤ 1
Aeffpy Mcx Mcy
Fc mxMx Fc
Pcx
+
Mcx
(1 + 0.5 ) ≤ 1
Pcx Ref: 2
Fc myMy Fc
Pcy
+
Mcy
(1 + 0.5 ) ≤ 1
Pcx Ref: 2
0.073 + 0 = 0.073 ≤ 1
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Bearing Plate
of 2
N
D
11-Nov-18
Reference
Ref: 1
Ref: 1
Ref: 1
367.56
Ref: 2
Ref: 2 0.7779308
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
atar@ammico.biz
of 2
N
D
11-Nov-18
Reference
Ref: 2
Ref: 2
Ref: 2
atar@ammico.biz
Sheet 1 of 2
Prepared by: M N
QIMC TOWER (4B+G+M+P+38F) @ WEST BAY
Checked by: G D
Date 9-Sep-16
For member in axial compression, can be classified as: Class 4 - Slender Ref: 2
Considering strut element as "pinned" at both ends, effective length shall be equal to length of strut.
One side of the strut is supported at the waller beam installed at the d-wall face and other end is at
pile foundation with pilecap installed for the strut.
Fc Mx My Ref: 2
+ + ≤ 1
Aeffpy Mcx Mcy
Fc mxMx Fc
Pcx
+
Mcx
(1 + 0.5 ) ≤ 1
Pcx Ref: 2
Fc myMy Fc
Pcy
+
Mcy
(1 + 0.5 ) ≤ 1
Pcx Ref: 2
0.917 + 0 = 0.917 ≤ 1
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 1
Prepared by: M
QIMC TOWER (4B+G+M+P+38F) @ WEST BAY
Checked by: G
Date 9-Sep-16
For member in axial compression, can be classified as: Class 4 - Slender Ref: 2
Considering strut element as "pinned" at both ends, effective length shall be equal to length of strut.
One side of the strut is supported at the waller beam installed at the d-wall face and other end is at
pile foundation with pilecap installed for the strut.
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 2
Prepared by: M
QIMC TOWER (4B+G+M+P+38F) @ WEST BAY
Checked by: G
Date 9-Sep-16
Fc Mx My Ref: 2
+ + ≤ 1
Aeffpy Mcx Mcy
Fc mxMx Fc
Pcx
+
Mcx
(1 + 0.5 ) ≤ 1
Pcx Ref: 2
Fc myMy Fc
Pcy
+
Mcy
(1 + 0.5 ) ≤ 1
Pcx Ref: 2
0.779 + 0 = 0.779 ≤ 1
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 4
Prepared by: M
QIMC TOWER (4B+G+M+P+38F) @ WEST BAY
Checked by: A
Date 12-May-15
Walling Beam
Ref 1 - Project Specification Reference
Ref 2 - BS 5950-1:2000
Ref 3 - PLAXIS Model
A) Steel Beam
= 0.89
Flanges Web
Plastic = 9Ɛ = 8.035 Plastic = 80Ɛ = 71.42
Compact = 10Ɛ = 8.928 Compact = 100Ɛ = 89.28
Sem-compact = 15 Ɛ = 13.39 Sem-compact = 120Ɛ = 107
Width to thickness ratio = b/T < Ref. 2
= 5.5 < 8.04 " Flange is Plastic"
Hence, the section can be classified into Class 1: Plastic as per BS: 5950 -1 2000
Check for Shear Reference
Shear Area, Av = Dt Ref. 2
= 428x20
= 8560.00 mm2
Shear Capacity, Pv = 0.6pyAv Ref. 2
= 1772 kN
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 6
Prepared by: M
QIMC TOWER (4B+G+M+P+38F) @ WEST BAY
Checked by: A
Date 12-May-15
Reference
Design of Connection of Bracket with Pile
Ref 1 - Project Specification
Ref 2 - BS 5950-1:2000
Ref 3 - PLAXIS Model
Concept: Walling beam is supported by a bearing plate which is resting on a pair of frame made of angle
sections. Frame is connected to shoring pile through connecting plate and bolts.
0.55m
Bearing Plate
A) Steel Beam
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 7
Prepared by: M
QIMC TOWER (4B+G+M+P+38F) @ WEST BAY
Checked by: A
Date 12-May-15
= 58 > 0 kN
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
of 2
N
D
9-Sep-16
Reference
Ref: 1
Ref: 1
Ref: 1
Ref: 2
Ref: 2 0.7733
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
atar@ammico.biz
of 2
N
D
9-Sep-16
Reference
Ref: 2
Ref: 2
Ref: 2
atar@ammico.biz
of 7
N
A
12-May-15
Reference
Ref 1
Ref. 2
Ref. 2
Ref. 2
Ref. 2
Ref. 2
atar@ammico.biz
of 7
N
A
12-May-15
Reference
Ref. 2
Ref. 2
Ref. 2
Ref. 2
atar@ammico.biz
of 7
N
A
12-May-15
Reference
Ref 1
atar@ammico.biz
of 7
N
A
12-May-15
Reference
Ref. 2
Ref. 2
atar@ammico.biz
Sheet 1
Prepared by: M
QIMC TOWER (4B+G+M+P+38F) @ WEST BAY
Checked by: G
Date 9-Sep-16
For member in axial compression, can be classified as: Class 3 - Semi Compact Ref: 2
Considering strut element as "pinned" at both ends, effective length shall be equal to length of strut.
One side of the strut is supported at the waller beam installed at the d-wall face and other end is at
pile foundation with pilecap installed for the strut.
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 2
Prepared by: M
QIMC TOWER (4B+G+M+P+38F) @ WEST BAY
Checked by: G
Date 9-Sep-16
Fc Mx My Ref: 2
+ + ≤ 1
Aeffpy Mcx Mcy
Fc mxMx Fc
Pcx
+
Mcx
(1 + 0.5 ) ≤ 1
Pcx Ref: 2
Fc myMy Fc
Pcy
+
Mcy
(1 + 0.5 ) ≤ 1
Pcx Ref: 2
0.517 + 0 = 0.517 ≤ 1
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 4
Prepared by: M
QIMC TOWER (4B+G+M+P+38F) @ WEST BAY
Checked by: A
Date 12-May-15
Walling Beam
Ref 1 - Project Specification Reference
Ref 2 - BS 5950-1:2000
Ref 3 - PLAXIS Model
A) Steel Beam
= 0.89
Flanges Web
Plastic = 9Ɛ = 8.035 Plastic = 80Ɛ = 71.42
Compact = 10Ɛ = 8.928 Compact = 100Ɛ = 89.28
Sem-compact = 15 Ɛ = 13.39 Sem-compact = 120Ɛ = 107
Width to thickness ratio = b/T < Ref. 2
= 5.5 < 8.04 " Flange is Plastic"
Hence, the section can be classified into Class 1: Plastic as per BS: 5950 -1 2000
Check for Shear Reference
Shear Area, Av = Dt Ref. 2
= 428x20
= 8560.00 mm2
Shear Capacity, Pv = 0.6pyAv Ref. 2
= 1772 kN
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 6
Prepared by: M
QIMC TOWER (4B+G+M+P+38F) @ WEST BAY
Checked by: A
Date 12-May-15
Reference
Design of Connection of Bracket with Pile
Ref 1 - Project Specification
Ref 2 - BS 5950-1:2000
Ref 3 - PLAXIS Model
Concept: Walling beam is supported by a bearing plate which is resting on a pair of frame made of angle
sections. Frame is connected to shoring pile through connecting plate and bolts.
0.55m
Bearing Plate
A) Steel Beam
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
Sheet 7
Prepared by: M
QIMC TOWER (4B+G+M+P+38F) @ WEST BAY
Checked by: A
Date 12-May-15
= 58 > 0 kN
P.O. Box 14330, Doha - Qatar Tel: +974 4488 6531 Fax: +974 4488 6507 email : qatar@ammico.biz
of 2
N
D
9-Sep-16
Reference
Ref: 1
Ref: 1
Ref: 1
Ref: 2
Ref: 2 0.7718
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
Ref: 2
atar@ammico.biz
of 2
N
D
9-Sep-16
Reference
Ref: 2
Ref: 2
Ref: 2
atar@ammico.biz
of 7
N
A
12-May-15
Reference
Ref 1
Ref. 2
Ref. 2
Ref. 2
Ref. 2
Ref. 2
atar@ammico.biz
of 7
N
A
12-May-15
Reference
Ref. 2
Ref. 2
Ref. 2
Ref. 2
atar@ammico.biz
of 7
N
A
12-May-15
Reference
Ref 1
atar@ammico.biz
of 7
N
A
12-May-15
Reference
Ref. 2
Ref. 2