Vol.02,Issue.13,
October-2013,
Pages:1436-1440
www.semargroups.org,
www.ijsetr.com
Abstract: In power system protection, relays play a very as dependability, security and immunity to variation in
important role in monitoring the system parameters and parameters of individual components. They are more
separating the faulty sections of the system from the flexible because of the programmable capability. This
healthy system. Transmission lines are most frequently paper concentrates on computation of relay settings and the
prone to faults and so their protection is of great development of programmable scheme logic (PSL) for
importance. With the advances in the technology, AREVA make P444 type of numerical distance relay. The
transmission line protection is being achieved by using PSL will be developed using MiCOM PSL editor and will
numerical distance relays. This paper concentrates on the be validated by testing it on universal numerical relay
protection of transmission lines using numerical distance testing kit (OMICRON make).
relays. Calculation of zonal settings and development of
programmable scheme logic (PSL) for a numerical A. Zonal protection of transmission lines
distance relay are being discussed.
To facilitate speedy removal of disturbance from a
Key Words: Numerical Relay, Zonal Reach, PSL, P444, power system, the system is divided in to protective zones
PSL Editor. and relays monitor the system quantities appearing in these
I. INTRODUCTION zones. Numerical relays generally provide 4 or 5 zones of
protection depending on the manufacturer. All zones are
Electrical energy is available to the user at the correct identical in terms of settings. However, zone 1 has extra
voltage and frequency, and exactly in the amount that is adaptive mechanisms built-in to enhance the transient
needed. This remarkable performance is achieved through reach accuracy even when the voltage signals are supplied
careful planning, design, installation and operation of a from poor quality voltage sources such as capacitive
very complex network of generators, transformers, and voltage transformers (CVTs). Ground zones 2 through 5, in
transmission and distribution lines. To the user of turn, have an extra zero-sequence directional supervision
electricity, the power system may appear to be in steady implemented for their time-delayed operation after the
state; imperturbable, constant and infinite in capacity. Yet, memory expires. Consequently, zone 1 is recommended as
the power system is subject to constant disturbances an under-reaching element, and zones 2 through 5 are
created by random load changes, by faults created by recommended as overreaching elements and for time-
natural causes and sometimes as a result of equipment or delayed tripping. Since the distance relays are fed from the
operation failure. In spite of these constant perturbations, secondary of line CTs and bus PTs/line CVTs, the line
the power system maintains its quasi-steady state because parameters are to be converted into secondary values to set
of two basic factors: the large size of power system in the relay as per requirements.
relation to the size of individual loads and generators, and
correct and quick remedial action taken by the protective Zsecy = Zpri/IR; (1)
relaying equipment. Protective relaying is governed by Where, impedance ratio
correct diagnosis of trouble, quickness of response and (IR) = P.T ratio/C.T ratio (2)
minimum disturbance to power system. The response must Note:
be automatic and response times of the orders of a few i) Where a three zone relay only is available, the zone 3
milliseconds are often required. Numerical relaying will be set to cover the adjacent longest line.
provides a good solution for meeting the needs of ii) The zonal timings will be carefully selected to
protection of the power systems. It provides features such properly grade with the relays on adjoining sections.
Where, Zpl impedance of the protected line Where, RG is ground reach and RP is the phase reach of
the respective zone with the inclusion of arc resistance
Zsal impedance of the shortest adjacent line
Zlal impedance of longest adjacent line values.t1 to t4 are the tripping times in each zone.
Zt impedance of transformer in ohms
III. P444 RELAY DESCRIPTION
To account for the effect of fault resistance on zonal P444 is an advanced numerical distance relay
settings the arc resistances calculated using Van manufactured by AREVA. In addition to the distance
Warrington’s empirical formula are added to the zonal protection it also provides some additional protection
reaches. The values of arc resistances added for different functions. The relay front panel consists of LED indicators,
voltage levels are as follows some for fixed purpose and some programmable and user
interface LED screen. In addition it has function keys
which are also programmable for different functions. The
communication with the relay can be achieved using
RS232 communication port. The relay settings can be
II.CASE STUDY made using the front panel keys or by communicating with
Based on the above zonal setting logic, settings for the the relay using RS232 port. MiCOM Studio S1 is the
following system are being calculated. The protected line is software that interfaces the relay with a computer. The
of 42 kms, has three adjacent lines and the relay is located at relay back panel has terminals for all current and voltage
pulivendula station. The settings for both primary side and signals, digital logic input signals and all output contacts.
secondary side are calculated. Here P.T ratio=220kv/110v Once communication with the relay is established the relay
and C.T ratio=800A/1A. logic can be developed using PSL editor in MiCOM Studio
S1.
CB Y-PH OPEN
DDB #066
CB Aux B (52-B)
DDB #1028
Tzp
DDB #265
&
CB B-PH OPEN CB Aux C (52-B)
DDB #067 DDB #1030
Z3
DDB #258
CARR RECEIVED
DDB #072
DIST. Chan Recv
DDB #1049 &
T3
Output contact: DDB #263
Any Start
DDB #317
&
Any Trip T4
DDB #321 DDB #264
General trip
SOTF/TOR Trip
0
Any Trip GENERAL TRIP DDB #332
&
DDB #321 Straight DDB #006
0
SOTF INITIATION
Trip LED DDB #064
DDB #1024
LED 5 Red
L2-L3 6.3 9.6 317 60
DDB #648
Z2
DDB #257
Latching
LED 5 Grn
L3-L1 6 8.2 320 51.7
DDB #649
L1-L2-L3 3.1 9.5 312 59
LED 6 Red
DDB #650
Latching
LED 6 Grn
Zp
DDB #651 Zone3:
DDB #260
Fault R X Trip time Location of
(m sec) fault(kms)
LED 7 Red
Latching
DDB #652
L1-G 3.7 13.5 615 84.94
LED 7 Grn
DDB #653
L2-G 9.6 14.2 609 89.75
Z3
DDB #258 L3-G 1 14.2 614 89.5
LED 8 Red
L1-L2 5 14.6 615 91.5
DDB #654
Latching
LED 8 Grn
L2-L3 11 14 611 87
DDB #655
L3-L1 1.12 15.16 609 94.5
Z4
DDB #259 L1-L2-L3 2.6 12.7 611 79.6
FnKey LED 1 Red
DDB #656
Latching
FnKey LED 1 Grn
DDB #657 Zone4:
SOTF/TOR Trip
DDB #332 Fault R X Trip time Location of
(msec) fault(kms)
L1-G 5.5 18.8 908 118
FnKey LED 2 Red
DDB #658 L2-G 1 18.8 906 117.7
Latching
Power Swing
FnKey LED 2 Grn
DDB #659 L3-G 7 18.4 913 115.7
DDB #269
L1-L2 1.3 18.5 918 115.6
IV. TESTING OF THE LOGIC L2-L3 1.12 17 910 107.7
L3-L1 5.7 16.3 913 101.7
Once the logic is developed, it is to be sent to the relay L1-L2-L3 10 18.4 909 115.2
and has to be tested before it is finally employed. The
testing of the logic will be done using OMICRON make
universal relay testing kit. The testing kit will have V. CONCLUSION
dedicated interface software to create various conditions of
test cases. The relay is connected to the testing kit and the This paper has discussed the protection of the
inputs for various conditions are fed from the interface transmission lines using numerical distance relays. Zonal
software. The settings of the above test case are fed to reaches of the numerical relay are discussed and reaches of
relay and testing is carried out with various test cases. The the relay are calculated for a test case with the inclusion of
effect of fault resistance. PSL is developed for a AREVA
results of the test are as follows:
International Journal of Scientific Engineering and Technology Research
Volume.02, IssueNo.13, October-2013, Pages:1436-1440
Computations of Relay Settings and Development of Programmable Scheme Logic for a Numerical Distance Relay
VI.REFERENCES