Analysis of Seismic Performance For High-Voltage Switchgear Equipment of GIS
Analysis of Seismic Performance For High-Voltage Switchgear Equipment of GIS
Abstract- According to the mechanical failure of Gas earthquakes, the damage ratio of the electric system is
Insulated Switchgear ( GIS) in the earthquake will cause a incredibly high. For instance, the magnitude 7.8
great loss to the power system. This paper, by using the earthquake happened in Tangshan in 1976 caused
three-dimension design software to build a geometric substantial damages of the high voltage switchgear, the
model of 420 kV GIS, by using the finite element analysis damage of isolating breaker rate reached 30%, circuit
method to make the mode analysis, and then acquired switch reached 58% and the arrester reached 66%
structural frequencies and mode features of the GIS, and among it [3-4]. Therefore, studying the distribution and
by using spectral analysis to get the stress distribution and structural deformation of GIS in earthquake stress is
structure deformation in the case of IX degree earthquake very necessary. According to IEC 62271-2:2003
based on it. Through the simulation result of this model, "High-voltage switchgear and controlgear - Part 2:
the structure of the maximum stress occurs at the bracket Seismic qualification for rated voltage of 72.5 kV and
where connected bus, and the maximum stress is 17.5Mpa above", this article uses the response spectrum analysis
that far less than the yield limit that is 235MPa. The method to simulate the stress distribution and structural
maximum deformation occurs in the middle of the bus, deformation of the 420 kV GIS in the earthquake level
and the maximum deformation is only 0.86 mm/m that for AF5, zero period acceleration is 5m/s2 , seismic
comply with the requirements of the bus deformation is intensity of IX degree with the finite element analysis
less than 3 mm/m. The results can provide a reference for software.
the seismic reliability analysis of the high-voltage
switchgear equipment. II. ESTABLISHMENT OF COMPUTATIONAL MODEL
Key- GIS, seismic performance, finite element, structural
Figure 1 shows the calculation of 420 kV GIS
deformation, modal analysis, spectral analysis.
structure diagram. In GIS, the diameter of the circuit
breaker 1 is 860 mm and its length is 4700 mm; the
1. INTRODUCTION
diameter of the bus 2 is 356 mm and its length is 42500
Gas Insulated Switchgear (GIS) is a kind of mm; the height of the bracket 3 is 4730 mm and the
composite apparatus which puts primary elements in bottom four cross-section of 100 x 100 mm; the height
addition to the transformer in the substation such as of the casing 4 is 4470 mm, the upper end of inner and
high-voltage circuit breakers, load-breaking switches, outer diameter are respectively 235 mm, 275 mm and
disconnectors, earthing switches, current transformers, the lower end of inner and outer diameter are
voltage transformers, lighting arresters and other respectively 445 mm, 485 mm. As can be seen from the
electrical appliances and enclosed in a metal enclosure above parameters, the equipment in the GIS, such as
filled with SF6 gas that has excellent arc-extinguishing casing and others has higher center of gravity, bus,
and insulating properties. Due to a series of advantages, bracket and others has slender body, the seismic
for example, it covers a small area and takes up less performance is greatly reduced.
space because it is not only closed but also combined, it Meshing include select unit data and set the meshing
is not affected by the influence of the external parameters [5-6]. Calculation model of unit type
environment condition, it does not produce noise and depends not only on the geometry of the component,
radio interference, it is running safe, reliable and low also depends on the type and direction of load. 420 kV
maintenance workload, GIS equipment in recent years GIS structure is irregular entities, so using
has been a wide range of applications [1]. three-dimensional solid tetrahedral elements describe its
It is quite common that power generation and supply structure to better reflect the true situation. In front of
are interrupted because of the high-pressure equipment the finite element analysis was carried out on the
is broken or damaged. This caused significant damage geometric model, five kinds of materials are defined,
to the national economy and electricity companies, also they are hot rolled steel Q235, aluminum alloy, silicon
brought serious difficulties to the work of earthquake rubber, cast aluminum alloy and T2 copper. Their
relief [2]. According to the data analysis of the modulus of elasticity, Poisson's ratio and density as
shown in Table 1. Considering the accuracy and the
Fund project: Project supported by National Natural Science
Foundation of China (51177104) and National Natural Science
Foundation of Liaoning province (2011220011)
May 16,2013
calculation under the premise, established the finite Where,[M] ,[K] are the mass and stiffness matrix of
element model. Figure 2 shows the local finite element the system, Let the solution of the equation having the
model. form of a simple harmonic motion, then
elasticity(Pa) ratio ( kg/m' ) characteristic values OJr 2 is the frequency of the system.
Bracket 2.0x1Oll 0.26 7.83x103
Take each characteristic value into (4), this can be
obtained by corresponding feature vector {<l>}r' it
Tank 7.0x1OlO OJ3 2.75x103 satisfies
Casing IJ5xlOlO OJ 1.53xl03
(5)
Flange 6.16x1OlO OJ 2.7x103
This vector is the feature vector and it is called modal,
Terminal Blocks 1.08x I011 OJ2 8.9x103 since it is the deformed shape of the system modal
vibration, also called mode shape [7].
Modal analysis can determine the structural vibration
characteristics of the design, that is, the dynamic
[M]{X}+[K]{x}={ O } (1) TABLE 2 THE FIRST 10 ORDER FREQUENCY VALUE OF 420 KV GIS
2
F,(m) = S: x(t)e-iWldt
Mode number Frequency 1Hz Mode number Frequency 1Hz
5 2.4195 55 14.584
Fz(m) = ( z(t)e-imtdt
15 4.5651 65 18.146
25 6.8961 75 22.751
The last type on the Fourier transform can be
35 10.266 85 23.403 obtained:
45 12.139 95 26.057
�(m) = H(m).�(m) (7)
. m02+ i2!;m0 m
In the equatIOn, H(m)= , call it
(mo2 - m2)+ i2!;mom
the frequency response function. And because
So
Fz = H(m).FJm) (8)
Make and
Wherein <!: and OJo are natural frequency and damping According to the inverse Fourier transform principle,
ratio of 420 kV GIS respectively; j.i(t), y(t), yet)
are the reaction of the acceleration, velocity,
displacement respectively; x(t) is ground acceleration, (9)
x(t) and x(t) are the velocity and displacement of the
ground respectively. With z(t) , i(t) , z(t)
respectively responses of absolute acceleration, velocity
and displacement of 420 kV GIS [9] , and In the above equation, T is the input seismic
acceleration duration, OJM is the cut-off frequency of
Fourier transform.
i(t)=y(t)+x(t)
According to lEe 6227 I -2:2003 "High-voltage
i(t)==y(t)+x(t) switchgear and control gear Part 2: Seismic
z(t)=y(t)+x(t) qualification/or rated voltage 0/ 72.5 kV and above". In
the 420 kV GIS spectrum analysis, the damping ratio is
Equation (6) can be turned into: 2 percent, seismic performance levels is AF5, zero
period acceleration is 5m/s2 , seismic intensity of IX
degree, the response corresponding spectrum is shown
in Figure 4.
Make
C. Result and Analysis
On the basis of the modal analysis of 420 kV GIS,
take six points sequentially from the curve of the
3
spectrum shown in Figure 4 as the spectral values of the the maximum stress is 17.SMPa, far less than the yield
·
limit that is 23SMPa.
·
,
/ \ IV CONCLUSION
·
\
\. Taking the 420kV GIS high voltage switch
·
,
equipment as the research object, using
,
three-dimensional design software to establish the
Frequenc:yfth:)
mathematical model, using the finite element analysis
software to modal analysis. Based on the first 10 order
Fig. 4. The spectrum of earthquake level for AF5
modal, analyzed the seismic performance of GIS in the
spectral analysis, as shown in Table 2, using earthquake resistant level for AFS. Through the analysis
single-point response spectrum analysis to be extended of the results, get the following conclusion:
modal, using square and then prescribing to merge I. 420 kV GIS bus is the strongest vibration in
modal, to complete seismic spectrum analysis of 420 kV high voltage switch equipment, so the maximum
GIS, get the results of the analysis. Bus is most intense deformation occurs and it is 36.Smm. The deformation
in the seismic response analysis of spectrum. As shown is 0.86mm/m, and comply with the requirements of
in Figure S, it has the largest deformation with 36.S mm, deformation that less than 3 mm/m; maximum stress
and its total length of 42.Sm, so the amount of occurs in the bracket A and the value is 17.SMPa, far
deformation of is 0.86 mm/m. As shown in Figure 6, less than the yield limit that is 23SMPa of the material
the structural stress is mainly distributed in the casing of Q23S ordinary carbon steel.
the bracket, the bracket A has the maximum with 2. For the seismic performance of GIS and other
17.SMPa. high-voltage switchgear, it is suggested that the analysis
should base on the vibration table experiments and
TABLE 3 THE SPECTRUM OF EARTHQUAKE LEVEL FOR AF5 analyzed according to the analog of computers in order
to fully understand its weak points and improve its
Frequency (Hz) Acceleration (m/s')
seismic performance finally.
0.5 0.43
ACKNOLEDGMENT
1.0 0.85
Supported by the department of Science and
2.4 1.4
Technology of Liaoning Program (201122001 I);
9.0 1.4 supported by NSFC (S I 177 I 04).
with the requirements of deformation that less than 3 [8] X. 1. Wang, "Earthquake response spectrum analysis of
large-span rail-cum-cable-stayed bridge," Wuhan University
mm/m. In order to further reduce bus deformation, make of Technology,Wuhan,Hubei,China,2006.
it more safe and reliable, the measures that add brackets [9] X. Lin, K. J. Shi, J. Y. XU, "Analysis and calculation of
shall be taken in the middle of the bus. Bottom of the seismic performance for UHV equipment of HGIS," Journal
of Shenyang University of Technology, vol. 35, pp. 121-125,
bracket in GIS fixed to the ground and the bus
2013.
connected with it has the strong vibration, so the joint of
bus and stent will generate obvious stress concentration, E-mail ofauthors:289428192@qq.com