Professional Documents
Culture Documents
11 - Chapter 5
11 - Chapter 5
11 - Chapter 5
CHAPTER 5
5.1 INTRODUCTION
Transmission line challenges are many, but the ways and means to solve it
are specific. Load shedding can be considered as one potential solution for handling
the line issues. Planned load shedding or scheduled load shedding is not of research
interest. Unplanned load shedding due to eventuality is of research interest. In this
chapter, un-planned case of load shedding and their nuances are analyzed for effective
load shedding process. If not clearly done, then it may trigger a cascaded failure in the
power system as a whole. Once cascaded failure has occurred lot of technical,
economical, political crisis occurs for which solutions are not instant. So it is better to
prevent rather than to cure it.
A.A. Mohd Zin et al. (2004)69 in their research work have highlighted
under-frequency load shedding and they have proven the results with a practical case
example. In their work, a real case example in Malaysia has been studied. UFLS has
been discussed by them. Yong Zheng and Chowdhury (2004)115 in their research
work have highlighted an expansion of transmission systems in deregulated scenario.
Their methodology is based on optimizing generation re-dispatch in case of
transmission line congestion. Economics behind transmission line expansion is also
discussed in their work.
Bottom line from the literature survey: From the above literature survey it is clear
that there are many workable methods proposed for load shedding. Many methods are
based on test cases and some methods are based on real time examples. Genetic
algorithm based approach is explored by many researchers. In this chapter, a novel
method for load shedding is proposed. This method is unique in its way. A path
analysis method is created for effective load shedding. Even though path model is
discussed by researchers it is not applied in Electrical Engineering. This research
98
gap is well studied and path analysis model for effective load shedding is formed.
This is the unique feature to be underscored.
There are various types and forms of load shedding, some are discussed
below.
Start
No
Frequency < fmin /
Voltage < Vmin
Yes
Shed load
Frequency = 50 Hz No
Voltage within range
Yes
End
Figure 5.1 Flow chart explaining the under frequency / under voltage load
shedding.
Load Shedding
Techniques
Under Frequency Under Voltage Artificial Neural Fuzzy Adaptive Neuro Particle
Genetic
Load Shedding Load Shedding Networks Logic Fuzzy Inference Swarm
Algorithm
Techniques Techniques (ANN) Control System (ANFIS) Optimization
Restore Mean
Tertiary
Take over Control
2H ∂f
∆P = × (5.1)
f ∂t
§ dv ·
¨ dq ¸
S = © ¹ pdiff
§ dv ·
¨ ¦ dq ¸
(5.2)
© ¹
Start
Measure Frequency
No
Frequency < fmin
Yes
No
Frequency = 50 Hz
Yes
End
Many intelligent approaches are available and also many more new
approaches are in pipeline in this area of load shedding in power systems. This shows
the potential threat of load shedding (if not done properly, cascaded failure may
occur). Also, load shedding is having potential opportunity for research.
2. Complex power system Cannot deal efficiently Can deal efficiently with
with modern and modern and complex power
complex power systems systems
(Source: [48], [57], [67], [83] and [105])
107
1. Artificial neural ANN can ensure an The ANN can provide satisfactory
networks (ANN) optimum amount of load results for known cases only and may
shedding fail to predict accurate results for
unknown or varying cases
2. Fuzzy logic control FLC can be used for load The membership parameters of FLC
(FLC) shedding application on a require prior system knowledge.
power system of any size Otherwise, it may fail to provide
optimum load shedding.
3. Adaptive Neuro- FLC parameters are It can only work with Sugeno-type
fuzzy inference optimized by using ANN, systems
systems (ANFIS) which may lead to
accurate load shedding
In this section, a practical substation data are taken for the case. The data
from a Thiruvalam sub station is taken. These data are tabulated and computational –
fuzzy based load shedding is carried on it. The below is the methodology adopted for
load shedding.
7. Each value in the above table will be the numerator in the formula.
9. Find out the value of load to be shed using the classical formula
mentioned in equation 5.2.
From the inputs received from the substation, the above table 5.4 is
obtained. Here, a prominent point to be observed is that in the above table the load to
be shed is calculated from classical formulae for load shedding.
Start
No
Check if frequency < 49.5 Hz ‘or’ Load shedding not
if voltage < 0.97 pu required
Yes
Stop
5.4.1 Thiruvalam
hiruvalam Substation One Line Diagram
The main bottom line in this research, case is that the application of fuzzy
as an intelligent system for load shedding problems. Here,
Here the problem taken for the
study is already explained in the above Table 5.4 and the results obtained through
conventional methodology is also presented in the same table. The main idea in this
case is that, whether fuzzy helps in arriving an optimality
op and an improved decision
process in addressing the non-linearity.
non
Pdiff (L3)
Output
Figure 5.7 Condition 1: If the voltage is high, Reactive Power is high and Real
Power is high then output is high.
Figure 5.8 Condition 2: If the voltage is high, Reactive power is high and Real
power is medium then output is medium. .
Figure 5.9 Condition 3: If the voltage is medium, Reactive Power is Low, Real
Power is Low then Output is Low.
Figure 5.10 Condition 4: If the voltage is Low, Reactive Power is low and Real
Power is medium then Output is medium.
So far the data of 110 KV and 230 KV bus systems are scaled using fuzzy
expert system. From the data obtained from the substation, this clearly indicates that
there is a significant benefit over the conventional methods. Also, taking three critical
parameters say voltage, reactive power, shaft power or real power and applying these
data in fuzzy expert system gives the output of the value of load to be shed, which is
much less than the system without fuzzy. This is applied to both 110KV and 230 KV
systems and the results reinforce the same idea. Here Matlab fuzzy tool box is applied
for data scaling and to minimize the load shedding. With the above procedure an
effective value of the amount of load to be shed is arrived. The results are tabulated
below.
The above results are shown graphically below where the yellow line
indicates the system without fuzzy and green line indicates the system with fuzzy.
Two separate graphical displays are shown each for 110 KV bus and 230 KV.
Conventional
Method
Fuzzy expert
system
Conventional
Method
Fuzzy expert
system
The same fuzzy logic based load shedding is applied over the IEEE-26
BUS system. In this case the test system selected is a classical test system.
Figure 5.14 IEEE -26 BUS system (Source : Hadi Saadat, 201039)
The following are the tables that represent the load data, dv/dt, dq/dt,df/dt
data for the above test case.
121
Table 5.10 Change in voltage, reactive power and frequency for IEEE 26 bus
system
Table 5.11 Pdiff and the load to be shed for IEEE -26 Bus System
Pdiff and the load to be shed are also found by the conventional rule set as
already discussed in the equation (5.2).
The following is the methodology adopted in this case; fuzzy rules are
formed based on the methodology.
• Apply the values in fuzzy MATLAB software and create the rules
from the table.
• It must be noted that the rules which are created must satisfy
• The final results obtained from the above fuzzy process are better
than the conventional methods.
125
0.968-1.05 Range
0-0.5 Range
Frequency (L3)
48.7-50 Range
0-0.37 Range
0-0.68 Range
The membership function for the load data is shown below. The
procedures to create membership function for the load data is same as followed above.
1.015-1.05 - Range
1.015-1.021-1.02 - Low (MF1)
1.027-1.033-1.039 - Medium (MF2)
1.039-1.045-1.05 - High (MF3)
0.33-2.24 - Range
0.33-0.65-0.97 - Low (MF1)
0.97-1.29-1.61 - Medium (MF2)
1.61-1.93-2.24 - High (MF3)
127
Frequency (L3)
48.5-49.7 - Range
48.5-48.7-48.9 - Low (MF1)
48.9-49.1-49.3 - Medium (MF2)
49.3-49.5-49.7 - High (MF3)
0.06-0.31 - Range
0.06-0.1-0.14 - Low (MF1)
0.14-0.18-0.22 - Medium (MF2)
0.22-0.26-0.31 - High (MF3)
0.04-0.89 - Range
0.04-0.18-0.32 - Low (MF1)
0.32-0.46-0.6 - Medium (MF2)
0.6-0.74-0.89 `- High (MF3)
The generator data, transformer data and dv/ dt values for an IEEE 26 bus
system is provided below.
From the above two cases, it is clear that fuzzy has proven its efficacy in
load shedding. Based on the above, a new model for load shedding is formed – Path
model for effective load shedding. This model not only validates the above two cases
but also proposes a new idea for load shedding problems. This can be taken as a
novelty in this research for the reason that, even though path model is applied in other
areas like life sciences, etc. It is not applied earlier in electrical engineering side and
for load shedding problems. In this way it is a novelty. It is explained as follows.
Power system networks are operating very close to their limits. In order to
prevent cascaded failures and eventually blackouts, load shedding is used as a tool.
There are many methodologies which discusses the effective ways for load shedding.
In this work, a new perspective is presented – path analysis. Path analysis is a
technique under structured equation modelling which explains about dependent
variable and independent variables. Here the output results are modelled and
presented in path analysis, through which the significant variable which is crucial in
determining the output can be identified. The correlations between crucial parameters
which are having an influence in output are also analyzed here.
The data from Thiruvalam substation were taken and the results were
already discussed in section 5.4 and the results are enumerated in the Tables 5.7 and
5.8.
These results are applied over path analysis and the following model was
obtained. The basic theoretical model is given below. Where H1, H2, H3, H4, H5
represents regression coefficients. Also, from the below model it is clear that the
output (load to be shed) is dependent on voltage values, reactive power and also Pdiff.
Where Pdiff is the difference in shaft power. Here, Pdiff is used as the moderating
variable. Through this section, it is been analyzed how a path analysis can be
effectively used to deeply understand how much critical is voltage, reactive power
and Pdiff in deciding the values of load to be shed. From this model, it is observed
that the input variables such as voltage, reactive power do not have a significant
impact on the output (load to be shed). When the Pdiff is used as a moderator variable
the impact on output is significant. The value of H5 > 0.5 it means its impact is more
compared to other variables. In our case, the value is 0.82. Here e1 and e2 are
assigned correction factors in order to address the non-linear behavior of power
systems, because from classical equations it is clear that Pdiff is dependent on df/dt,
which is highly non- linear. By assigning these correction factors e1 and e2 the
accuracy of results are improved.
From the model fit summary the CMIN/DF is 0.615 with the P value of
0.433 > 0.05 which indicates this model is free from the bad fit index. Similarly, the
table Root Mean Square Error Approximation (RMSEA) shows the value 0.000
indicates the model is free from the bad fit index. As far as good fitness of the index is
concerned, the value belongs to 0.980 which indicates the model has the goodness of
fit index.
135
From the estimate we can definitely conclude that reactive power has a
significant impact on Pdiff since the value is less than 0.05. In this case it is 0.03
0.05 (at the 5 % level of significance). It can be concluded that voltage has an impact
on Pdiff. Similarly, the impact on output with respect to Pdiff is also significant since
the P value is *** (from final estimate table). *** indicates the results are highly
authentic.
In the second case, the load shedding technique using fuzzy logic is
applied over classical IEEE 26 bus system and the crucial results are given below.
In the above classical test system, based on the fuzzy control rules load
shedding procedure is done and the results are summarized as follows.
136
These results are applied over path analysis and the following model was obtained.
-0.49
0.33
From the model fit summary, the CMIN/DF is 0.736 with the P value of
0.391 which is more than 0.05 (0.391>0.05) indicates this model is free from the bad
fit index. Similarly the table RMSEA (Root mean square error approximation) show
the value is 0.000 indicates the model is free from the bad fit index. Table RMR, GFI
indicates good fitness of the index. As far as good fitness of the index is concerned
the value belongs to 0.986 indicates the model has the goodness of fit index. From the
overall table estimate we can definitely conclude that voltage has significant impact
on Pdiff [since P value is less than 0.05, which indicates 5% level of coefficient].
From this it is concluded that voltage has an impact on Pdiff. Similarly, the impact on
output with respect to Pdiff is also significant since the P value is 0.006 which is less
than 0.05 (5% level of significance).
In the third case, the rate of change of voltage (dv/dt) and the rate of
change of reactive power (dq/dt) and its significance in the output (load to be shed) is
140
Table 5.38 Rate of change of voltage, Rate of change of reactive power and
Rate of change of frequency.
This is applied over path analysis and the model fit is as presented below.
141
dv
dq
From the model fit summary the CMIN/DF is 0.258 with the P value of
0.612 which is more than 0.05 (0.612>0.05) indicates this model is free from the bad
fit index. Similarly the table RMSEA (Root mean square error approximation) show
the value is 0.000 indicates the model is free from the bad fit index. Table RMR, GFI
indicates good fitness of the index. As far as good fitness of the index is concerned
the value belongs to 0.995 indicates the model has the goodness of fit index. From the
overall table estimate we can definitely conclude that change of voltage has
significant impact on output [since P value is less than 0.05, which indicates 5% level
of coefficient]. In this case, it is 0.03 0.05 . Also, it can be concluded that Pdiff has
a very strong impact on output – load to be shed. Since the value is *** It proves the
authenticity of the results.
5.7 SUMMARY