Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 7

ASHRAE Method L= 50 width 20.

7
air flow
Wp= A(0.0887+0.07815v)/Y(pw-pa)
total
area =A= Pool 1035 1100 m2

v = velocity of air over water 0.2 m/s

c1 = 0.0887
c2 = 0.07815
Y = latent heat required to change water to vapour
at surface water temperature kJ/kg 2436.92 kJ/kg

air temp 26 air sat 3.3631 50 RH pa = 1.68155 kPa


water temp 27 pw = 3.5673 kPa

Wp = evaporation of water kg/s 0.088806 kg/sec


216.4 kW
compare
No off
people load 380 50 19000 W
0.007797 kg/sec

total = 0.096603 kg/sec

simplified formula
Wp = 4.0E-5 x A (Pw-Pa)xFa 0.082973 kg / sec l/s = 25608.95

Fa = 1 latent load kW 207.4325 kW


(usage factor)
allow extra evapoatin in the return air plenum
Room conditions 26 deg C, 50% RH
Estimate of surface area

l/s = Wp /(1.2*(Wi- Ws))*1000 Length = 100 m


Width = 0.3 m
Wi = 0.0108 area = 30 m2
Ws 0.0081
wetted dro 35 say

l/s = 29816

Latent load (kW) 241.5081


sensible capacity 411458.2 w
411.5 kW
Latent load = 235.4143 kW less RSH 98.2
98.2
215.1

200000 w 5.589876

air flow (RSH) = 12531 l/s


ASHRAE Method L= 50 width 20.7
air flow
Wp= A(0.0887+0.07815v)/Y(pw-pa)
total
area =A= Pool 1035 1100 m2

v = velocity of air over water 0.15 m/s

c1 = 0.0887
c2 = 0.07815
Y = latent heat required to change water to vapour
at surface water temperature kJ/kg 2436.92 kJ/kg

air temp 26 air sat 3.3631 55 RH pa = 1.849705 kPa


water temp 27 pw = 3.5673 kPa

Wp = evaporation of water kg/s 0.077858 kg/sec


189.7 kW
compare
No off
people load 380 50 19000 W
0.007797 kg/sec

total = 0.085655 kg/sec

simplified formula
Wp = 4.0E-5 x A (Pw-Pa)xFa 0.075574 kg / sec l/s = 17494.02

Fa = 1 latent load kW 188.9355 kW


(usage factor)
allow extra evapoatin in the return air plenum
Room conditions 26 deg C, 55% RH
Estimate of surface area

l/s = Wp /(1.2*(Wi- Ws))*1000 Length = 100 m


Width = 0.3 m
Wi = 0.0117 area = 30 m2
Ws 0.0081
wetted dro 35 say

l/s = 19827

Latent load (kW) 214.1368

Latent load = 208.7337 kW


ASHRAE Method L= 50 width 20.7
air flow
Wp= A(0.0887+0.07815v)/Y(pw-pa)
total
area =A= Pool 1035 1100 m2

v = velocity of air over water 0.2 m/s

c1 = 0.0887
c2 = 0.07815
Y = latent heat required to change water to vapour
at surface water temperature kJ/kg 2436.92 kJ/kg

air temp 27 air sat 3.3631 60 RH pa = 2.01786 kPa


water temp 27 pw = 3.5673 kPa

Wp = evaporation of water kg/s 0.072968 kg/sec


177.8 kW
compare
No off
people load 380 50 19000 W
0.007797 kg/sec

total = 0.080765 kg/sec

simplified formula
Wp = 4.0E-5 x A (Pw-Pa)xFa 0.068175 kg / sec l/s = 11836

Fa = 1 latent load kW 170.4384 kW


(usage factor)
allow extra evapoatin in the return air plenum
Room conditions 27 deg C, 60% RH
Estimate of surface area

l/s = Wp /(1.2*(Wi- Ws))*1000 Length = 100 m


Width = 0.3 m
Wi = 0.0129 area = 30 m2
Ws 0.0081
wetted dro 35 say

l/s = 14022

Latent load (kW) 201.9131

Latent load = 196.8184 kW


Coil off Conditions

BF = (Tldb - Tadp) / (Tedb -Tadp)

BF used in calcs 0.1

Tldb = 12.7

Tadp 9

Tedb 46

BF = 0.1

Moisture

BF = (Wla-Wadp)/(Wea-Wadp)

Wla = 0.0081

Wadp = 0.0071

Wea = 0.0162

BF = 0.10989

You might also like