Current Affairs Pocket PDF - July 2015 by AffairsCloud

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Inside The pressure drop is comprised of the

friction losses of the components within the


Insights piping circuit, including the coil, valving,
pipe and fittings. Without getting in too
much detail, this typically amounts to 30
percent to 50 percent of the total system
pressure drop at design conditions. To a

Is Bigger Better for certain extent, the temperature control


system may correct for errors in estimated

Control Valves?
pressure losses by intelligently modulating
the control valve; however, if the pressure
drops are grossly overestimated, the result

Right-sizing combines art, will be an oversized valve.


If a valve is oversized, a small incre-
ment of valve movement varies the flow

science, experience greatly; hence, the valve is always modu-


lating or hunting trying to satisfy a set-
Steve Tredinnick, PE, Infrastructure Project Engineer/Manager, Affiliated Engineers Inc. point that is constantly being over- and
undershot. It’s just like trying to drink from
a fire hose: It is just too much flow to han-
dle, and it’s very hard to control properly.

Editor’s Note: : “Inside Insights” is a col- ● Rangeability (minimum to maximum Uncontrolled and unstable
umn designed to address ongoing issues flow or turn-down)
of interest to building owners, managers ● Valve-sizing coefficient (C )
flow will often lead to
v
and operating engineers who use district ● Shut-off pressure occupant discomfort and
energy services. ● Actuator selection

● Valve body-type configuration


system inefficiency...

I
, for one, will never complain about a (two-way or three-way)
TV that is too large, a stomach that is ● Valve type (ball, globe, butterfly, etc.) The constant modulation will lead to sys-
too flat, a bank account that is too ● Control type – two position or throttling tem control instability. Uncontrolled and
great, a car that is too fast, or having too ● Flow characteristics (linear, equal unstable flow will often lead to occupant
much vacation time! Yeah, baby! I am not percentage, etc.) discomfort and system inefficiency (low
all that different from any other American There are other valve selection param- Delta T). In addition, at low loads, the
– we want it all, and we want it big! But eters such as allowable noise/cavitation, valve barely lifts off its seat. That creates a
having the biggest and ‘baddest’ is not materials of construction, temperature and high-velocity fluid stream that produces
always the best alternative. Just like having pressure ratings, connection types, allow- noise from the turbulence and wears a
too much of a good thing is not always able leakage, normally open/closed, etc., thin channel or groove into the valve seat,
good, having something too big may not but these do not really affect the perform- reducing its life. The groove becomes a
be appropriate in all situations. ance of the valve. Correct flow and pres- ‘leak’ in the system even when the valve is
In the fourth quarter 2006 edition of sure-drop calculations are the two key closed, which results in a wire-drawn valve.
this column, I addressed the size of decou- selection parameters for pressure-depend- Such traditional methods of selecting
plers in primary/secondary chilled-water ent valves. a valve use the valve-sizing coefficient (Cv).
pumping systems and how some installa- A Cv is a unit-less parameter that is calcu-
tion/design deficiencies benefit from ‘super- Evaluating Flow and lated from the flow and differential pressure
sizing.’ Can this philosophy be applied to Pressure Drop duty of the valve. (See equation below.) Cv
other devices in a hydronic system such as The flow rate through the valve and is used in manufacturers’ valve charts to
control valves? Is bigger better all the time? coil are usually sized for the peak-load more accurately select a valve.
To explore the answers to these ques- condition on the hottest or coldest day –
tions, let’s start by defining the main param- an event that occurs less than 1 percent of For water at 60 degrees F,
eters required to correctly determine the the total heating/cooling hours in a year Cv = GPM x √1/∆P
size of a hydronic control valve: (based on ASHRAE climatic data) – so a little
● Flow rate (i.e., load) oversizing occurs here, since one does not Not only does control valve oversizing
● Pressure drop (coil, branch piping, want to undersize the coil. However, grossly affect system performance, but actuator
valve authority component) overestimating the loads will oversize the sizing does as well. The actuator should be
● Pipe size control valve. sized to close against system pressure greater

Reprinted from First Quarter 2007 District Energy magazine with permission of IDEA. First Quarter 2007 53
than the distribution system pump head. If the pressure differential across the valve cost. A successful control-valve selection
the actuator cannot close the valve against changes. Although not a panacea for all procedure that follows acceptable engi-
the system pressure, then the valve will be applications, the PICV’s use has improved neering practice and manufacturer’s recom-
lifted of its seat and create a ‘leak’ in the the Delta T performance of many water mendations will help ensure that occupant
system. System leaks resulting from over- systems and does not require any balancing. comfort and efficient operation are achieved.
sized valves and undersized actuators are Traditionally, throttling valves are one Right-sizing wins every time!
probably the largest contributor to low Delta size smaller than the pipe size serving the
T. Further, excessive modulation can lead to branch piping, and a line-sized valve may be
premature actuator failure and valve-seal oversized depending on its duty. However,
failure, creating maintenance issues. just because a valve is line-sized does not Steve Tredinnick, PE, , is
mean that it is oversized. Line-sized valves a project engineer/manager
A Look at Other Valve Types are acceptable in some applications, such for Affiliated Engineers in
Madison, Wis., with more
The above discussion pertains specifi- as two-position valves (e.g., actuated isola-
than 20 years’ experience
cally to pressure-dependent valves – proba- tion valves) where lower system pressure
related to building HVAC
bly the most prevalent valve type used. The drop is required. Line-sized valves are usually
systems. The past 10 years
selection process may sound complicated, not acceptable in throttling applications. of his work have been
but it is a mixture of art, science and expe- focused on district energy systems. Tredinnick
rience. Other valve types may be easier to Right-Sizing Is Best is a graduate of Pennsylvania State University
select and specify. Pressure-independent Since it regulates the system’s flow and with a degree in architectural engineering. He
control valves (PICVs) are being used increas- provides comfort to building occupants, the is a member of IDEA and ASHRAE and is cur-
ingly in the HVAC industry. control valve is probably the single-most rently chair of ASHRAE TC 6.2 District Energy.
PICVs are selected using a much simpler important element in a hydronic system. A Tredinnick may be reached at stredinnick@
method based on the maximum flow rate valve must be ‘right-sized’ for its specific aeieng.com.
expected in the coil and not on differential application: A valve that is too small will not
pressure or valve-sizing coefficient. A PICV have sufficient capacity, and a valve that is Column and previous columns available at
does not allow a change in flow rate when too large will cause instability issues and add www.districtenergy.org/de_magazine.htm

54 District Energy Reprinted from First Quarter 2007 District Energy magazine with permission of IDEA.

You might also like