CAST RESIN TRANSFORMER TEST REPORT

1.Customer :Ritz Carlton PJT


2.Sel. No. : 20038904 ( PJT No. : 431330035 )
3.Specification
Rated capacity : 3Phase 2500kVA Rated frequency : 50Hz
Rated Voltage/ Current : HV : 11000V / 131.2 A, LV : 433V / 3333.4 A
Tap voltage : F11550 - F11275 - R11000 - 10725 - 10450V
Kind of rating : Continuous Type of cooling : AN
Insulation Class : F/F Temperature rise : 100/100K
BIL : 75/- kV Standard : IEC60076-11
Vector group : Dyn11 Total weight : 6600 Kg
4. Test Results
1) Construction Dimension and Workmanship ------------------------------ Passed
2) Vector diagram : Dyn11 -------------------------------------- Passed
3) Voltage ratio tests Tolerance: ± 0.5 %
Rated U Phase V Phase W Phase
Voltages Remarks
ratio Measured error(%) Measured error(%) Measured error(%)
11550 46.201 46.230 0.06 46.126 -0.16 46.223 0.05 Good
11275 45.101 45.127 0.06 45.028 -0.16 45.127 0.06 Good
11000 44.001 44.025 0.05 43.926 -0.17 44.019 0.04 Good
10725 42.901 42.921 0.05 42.823 -0.18 42.921 0.05 Good
10450 41.801 41.822 0.05 41.725 -0.18 41.822 0.05 Good
4) Winding Resistance (at : 28 ℃ )
HV side LV side
U - V 0.212700 ohm u - v 0.000216 ohm
V - W 0.212500 ohm v - w 0.000217 ohm
W - U 0.211100 ohm w - u 0.000222 ohm
Average 0.212100 ohm Average 0.000218 ohm
5) Characteristics (P.F=1.0, Based on AN) at 75 ℃
Specifi- Measured
Items Units Tolerance Results
cation AN AF
No load current % 0.8 less than +30% 0.21 Good
No load loss W 3200 less than +15% 3119 Good
load loss W 13700 less than +15% 12349 Good
%IZ % 6.5 ±10% 6.31 Good
Voltages regulation % 1.0 less than 1.0 0.69 Good
Efficiency % 99.33 more than 99.33 99.39 Good
6) Separate source voltage withstand test
HV : AC 60Hz 28kV/1min. -------------------------------------- Passed
LV : AC 60Hz 3kV/1min. -------------------------------------- Passed
7) Induced over voltage withstand test
400Hz, 2.0E, 18sec. -------------------------------------- Passed
8) Partial discharge measurement -------------------------------------- Passed
(U : 5pC ,V : 5pC ,W : 5pC )-Including the Back ground noise
9) Measurement of sound level -------------------------------------- Passed
Background noise : 45 dB Measured noise : 66.6 dB Pressure level : 66.63dB
TEST RESULT : PASS
Test date : 2013.08.29
Tested by : Gi-Pyo, Hong Approved by : Eui - Bong Shim
Test engineer, Transformer Q.S. Manager, Transformer & Power Equipment
LS Industrial Systems Co.,Ltd