INSPECTION & TEST PLAN (ITP) ~ FAT PROCEDURE

Customer: GE ENERGY POWER CONVERSION Reference: 4000088051


Project: CARDIFF Internal Ref: O ITP 12 04 012

Specifying Document Limit Values


Approved Drawing
No. Test Item & Applicable Record Form Certificate
DTS No.
Standards Min. Average Max.

ROUTINE TESTS
1 Visual Inspection PR-FA-06 O MC 12 04 012 - - - DE-FA-01
-5mm +5mm
2 Dimensions Check PR-FA-06 C MC 12 04 012 DE-FA-01
-1 mm +1mm
PR-FA-06
3 Ohmic Value Measurement (At ambient Temperature) O MC 12 04 012 2 x 4.1Ω 2 x 4.1Ω 2 x 4.51Ω DE-FA-01
IEC 62 271 - 1
Insulation Resistance Measurement @ 1kV PR-FA-06
4 O MC 12 04 012 >6MΩ DE-FA-01
- for Power Circuit(1kΩ / V) IEC 61 439 - 1
Applied Dielectric Test: 20kV@50Hz / 60sec PR-FA-06
5 O MC 12 04 012 <50mA DE-FA-01
- for Power Circuit IEC 60 071 - 1
Insulation Resistance Measurement @ 1kV PR-FA-06
6 O MC 12 04 012 >6MΩ DE-FA-01
- for Power Circuit(1kΩ / V) IEC 61 439 - 1
Insulation Resistance Measurement @ 500V PR-FA-06
7 O MC 12 04 012 >230kΩ DE-FA-01
- for Control Circuit(1kΩ / V) IEC 61 439 - 1
Applied Dielectric Test: 2kV@50Hz / 60sec PR-FA-06
8 O MC 12 04 012 <50mA DE-FA-01
- for Control Circuit IEC 60 071 - 1
Insulation Resistance Measurement @ 500V PR-FA-06
9 O MC 12 04 012 >230kΩ DE-FA-01
- for Control Circuit (1kΩ / V) IEC 61 439 - 1
PT100 Probes Measurement at Ambient Temperature
10 - O MC 12 04 012 DE-FA-01
& Function Test
11 Function Test of Leakage Detector - O MC 12 04 012 DE-FA-01
12 Function test of Space Heater & Thermostat - O MC 12 04 012 DE-FA-01

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden
24/04/2012 1 O ITP 12 04 012 # 0 B. AUDOUARD C. MILLARD H. ELASSAD ROUTINE TESTS Page 1 / 1