CUSTOMER: M/s Unitek Power Solutions (I) Ltd. Data Considered

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

NICAD BATTERY SIZING CALCULATIONS

CUSTOMER : M/s Unitek Power Solutions (I) Ltd. Date: 24.08.15


Rev: 1
DATA CONSIDERED
UPS RATING 5 KVA Power Factor 0.80
Nominal Voltage 240 V Inverter efficiency 0.92
Max. Voltage 264 V Design Margin 1.10
Min. Voltage 216 V Ageing factor 1.25
ECV 1.10 V/cell TCF @ 5 Deg C 0.905
Back Up Time 60 Min

No. of Cells = 196.36 197 Cells

Max Load Current = KVA x 1000 x P. F 5 x 1000 x 0.8


No of cells x ECV x Inverter Eff 197 x 1.10 x 0.92

= 20.06 Amps

K Factor Value for a duration of 60 min. = 1.80


= 1.80 X 20.06
= 36.11 AH

Corrected AH = AH Required X Design margin X Ageing Factor = 36.11 x 1.10 x 1.25 / 0.905
TCF

= 54.87 AH

Nearest cell from our catalogue is VRNM 58 P

Battery Recommended is 197 cells of VRNM 58 P