Professional Documents
Culture Documents
Body 1 PDF
Body 1 PDF
INTRODUCTORY STATEMENT
1
2. OBJECTIVES OF THE ENGINEERING REPORT
This report will explain procedures in designing the fire sprinkler pipe sizing and
pump size based on National Fire Protection Association 13 design criteria.
Fire sprinkler system for an Educational Building is one of the type of
occupancy wherein many options for design are available yet recommending such
design and approach is still challenging and must be thoroughly checked in order to
maximize the cost and secure the efficiency of the system.
Sprinkler systems for all educational buildings can be designed under NFPA
13, Standard for the Installation of Sprinkler Systems.
The sprinkler systems are designed to deal mainly with solid-fuel fires, but can
serve also to hold a flammable-liquid fire in check and to extinguish some oil fires (e.g.
transformer oil fires) by deluge sprinklers, by purely using water. With suitable foam
concentrate added to the water, its fire-fighting capability on oil fires can be greatly
enhanced.
Each system is designed for its particular function, and its features may vary widely
according to the purpose. In general, a system will consist of the following items:
2
6. A detector, or detector system, capable of actuating the fire-fighting / protection
system. The detector can be the sprinkler itself or other detection device /
system.
7. Other features include flow detectors, pressure switches for starting pumps,
and control / signal monitoring alarm panels etc.
3
Fire Control. Limiting the size of a fire by distribution of water so as to decrease the
heat release rate and pre-wet adjacent combustibles, while controlling ceiling gas
temperatures to avoid structural damage.
Fire Suppression. Sharply reducing the heat release rate of a fire and preventing its
regrowth by means of direct and sufficient application of water through the fire plume
to the burning fuel surface.
Hydraulically Designed System. A calculated sprinkler system in which pipe sizes are
selected on a pressure loss basis to provide a prescribed water density, in gallons per
minute per square foot (mm/min), or a prescribed minimum discharge pressure or flow
per sprinkler, distributed with a reasonable degree of uniformity over a specified area.
Pipe Schedule System. A sprinkler system in which the pipe sizing is selected from a
schedule that is determined by the occupancy classification and in which a given
number of sprinklers are allowed to be supplied from specific sizes of pipe.
Small Rooms. A room of light hazard occupancy classification having unobstructed
construction and floor areas not exceeding 800 ft2 (74.3 m2) that are enclosed by
walls and a ceiling. Openings to the adjoining space are permitted if the minimum lintel
depth is 8 in. (203 mm) from the ceiling.
Sprinkler System. For fire protection purposes, an integrated system of underground
and overhead piping designed in accordance with fire protection engineering
standards. The installation includes one or more automatic water supplies. The portion
of the sprinkler system aboveground is a network of specially sized or hydraulically
designed piping installed in a building, structure, or area, generally overhead, and to
which sprinklers are attached in a systematic pattern. The valve controlling each
system riser is located in the system riser or its supply piping. Each sprinkler system
riser includes a device for actuating an alarm when the system is in operation. The
system is usually activated by heat from a fire and discharges water over the fire area.
System Working Pressure. The maximum anticipated static (non-flowing) or flowing
pressure applied to sprinkler system components exclusive of surge pressures.
4
• Circulating Closed-Loop Sprinkler System. A wet pipe sprinkler system having
non–fire protection connections to automatic sprinkler systems in a closed-
loop piping arrangement for the purpose of utilizing sprinkler piping to conduct
water for heating or cooling, where water is not removed or used from the
system but only circulated through the piping system.
• Combined Dry Pipe-Preaction Sprinkler System. A sprinkler system employing
automatic sprinklers attached to a piping system containing air under pressure
with a supplemental detection system installed in the same areas as the
sprinklers. Operation of the detection system actuates tripping devices that
open dry pipe valves simultaneously and without loss of air pressure in the
system. Operation of the detection system also opens listed air exhaust valves
at the end of the feed main, which usually precedes the opening of sprinklers.
The detection system also serves as an automatic fire alarm system.
• Gridded Sprinkler System. A sprinkler system in which parallel cross mains are
connected by multiple branch lines. An operating sprinkler will receive water
from both ends of its branch line while other branch lines help transfer water
between cross mains.
• Looped Sprinkler System. A sprinkler system in which multiple cross mains are
tied together so as to provide more than one path for water to flow to an
operating sprinkler and branch lines are not tied together.
5
so that water discharges immediately from sprinklers opened by heat from a
fire.
Branch Lines. The pipes in which the sprinklers are placed, either directly or through
risers.
Cross Mains. The pipes supplying the branch lines, either directly or through risers.
Feed Mains. The pipes supplying cross mains, either directly or through risers.
Flexible Listed Pipe Coupling. A listed coupling or fitting that allows axial displacement,
rotation, and at least 1 degree of angular movement of the pipe without inducing harm
on the pipe. For pipe diameters of 8 in. (203.2 mm) and larger, the angular movement
shall be permitted to be less than 1 degree but not less than 0.5 degree.
• Large Drop Sprinkler. A type of specific application control mode sprinkler that
is capable of producing characteristic large water droplets and that is listed for
its capability to provide fire control of specific high-challenge fire hazards.
6
• Nozzles. A device for use in applications requiring special water discharge
patterns, directional spray, or other unusual discharge characteristics.
• Old-Style/Conventional Sprinkler. A sprinkler that directs from 40 percent to 60
percent of the total water initially in a downward direction and that is designed
to be installed with the deflector either upright or pendent.
• Open Sprinkler. A sprinkler that does not have actuators or heat responsive
elements.
• Special Sprinkler. A sprinkler that has been tested and listed as prescribed in
8.4.9.
• Specific Application Control Mode Sprinkler (for Storage Use). A type of spray
sprinkler listed at a minimum operating pressure with a specific number of
operating sprinklers for a given protection scheme.
• Spray Sprinkler. A type of sprinkler listed for its capability to provide fire control
for a wide range of fire hazards.
7
• Flush Sprinkler. A sprinkler in which all or part of the body, including the shank
thread, is mounted above the lower plane of the ceiling.
• Pendent Sprinkler. A sprinkler designed to be installed in such a way that the
water stream is directed downward against the deflector.
• Recessed Sprinkler. A sprinkler in which all or part of the body, other than the
shank thread, is mounted within a recessed housing.
• Dry Sprinkler. A sprinkler secured in an extension nipple that has a seal at the
inlet end to prevent water from entering the nipple until the sprinkler operates.
• Churches
8
• Clubs
• Eaves and overhangs, if of combustible construction with no combustibles
beneath
• Educational
• Hospitals
• Institutional
• Libraries, except large stack rooms
• Museums
• Nursing or convalescent homes
• Offices, including data processing
• Residential
• Restaurant seating areas
• Theaters and auditoriums, excluding stages and prosceniums
• Unused attics
• Cereal mills
• Chemical plants — ordinary
• Confectionery products
• Distilleries
• Dry cleaners
9
• Feed mills
• Horse stables
• Leather goods manufacturing
• Libraries — large stack room areas
• Machine shops
• Metal working
• Mercantile
• Paper and pulp mills
• Paper process plants
• Piers and wharves
• Post offices
• Printing and publishing Repair garages
• Resin application area
• Stages
• Textile manufacturing
• Tire manufacturing
• Tobacco products manufacturing
• Wood machining
• Wood product assembly
10
• Flow coating
• Manufactured home or modular building assemblies (where finished enclosure
is present and has combustible interiors)
• Open oil quenching
• Plastics processing
• Solvent cleaning
• Varnish and paint dipping
5.6. SPRINKLERS
5.6.1. SPRINKLER DISCHARGE CHARACTERISTICS
11
5.6.2. TEMPERATURE CHARACTERISTICS
5. Hydraulic Calculation
12
5.9. BUILDING FIRE HAZARD CLASSIFICATION
• Light Hazard
• Ordinary Hazard
• Extra Hazard
This same section in NFPA 13 also indicates that the ordinary hazard
classification is divided into two sub-classifications an ordinary group 1 hazard and an
ordinary group 2 hazard. Similarly, the extra hazard classification is also divided into
two sub-classifications — an extra group1 hazard and an extra group 2 hazard.
The definitions of each of the hazard classifications are also included in section
2-1 in NFPA13, which defines hazard classification based upon a number of
occupancy characteristics.
• Storage height.
13
The NFPA 13 definition an ordinary group 1 hazard is as follows:
14
Faculty Office Ordinary Group 1
Lounge Light
The water supply for sprinklers only shall be determined either from the
density/area curves of Figure 11.2.3.1.5 in accordance with the method of 11.2.3.2 or
be based upon the room design method in accordance with 11.2.3.3, at the discretion
of the designer. NFPA 13 Standards.
15
5.10.3. SYSTEMS WITH MULTIPLE HAZARD CLASSIFICATIONS
For systems with multiple hazard classifications, the hose stream demand shall be in
accordance with one of the following:
(1) Add the hose demand for the highest hazard classification within the system,
or
(2) Add the hose demand for each individual hazard classification to the
calculations for the design area for that hazard, or
(3) For systems with multiple hazard classifications where the higher classification
only lies within single rooms less than or equal to 400 ft2 in area with no such rooms
adjacent, add the hose demand for the principal occupancy for the remainder of the
system.
5.10.4. RESTRICTIONS
Regardless of which of the two methods is used, the following restrictions shall apply:
(1) For areas of sprinkler operation less than 1500 ft 2 (139 m2) used for light and
ordinary hazard occupancies, the density for 1500 ft2 (139 m2) shall be used.
16
(2) For areas of sprinkler operation less than 2500 ft 2 (232 m2) for extra hazard
occupancies, the density for 2500 ft2 (232 m2) shall be used.
5.11.1. GENERAL
A calculated system for a building, or a calculated addition to a system in an
existing sprinklered building, shall supersede the rules in this standard governing pipe
schedules, except that all systems shall continue to be limited by area.
Pipe sizes shall be no less than 1 in. (25.4 mm) nominal for ferrous piping and
¾ in. (19 mm) nominal for copper tubing or non-metallic piping listed for fire sprinkler
service.
The size of pipe, number of sprinklers per branch line, and number of branch
lines per cross main shall otherwise be limited only by the available water supply.
However, sprinkler spacing and all other rules covered in this and other
applicable standards shall be observed.
where:
p = frictional resistance in psi per foot of pipe
Q = flow in gpm
C = friction loss coefficient
d = actual internal diameter of pipe in inches
where:
17
pm = frictional resistance in kPa per meter of pipe
Qm = flow in L/min
C = friction loss coefficient dm
mm
where:
Pn = Pt - Pv
where:
Pn = normal pressure
Pt = total pressure in psi (bar)
• Pressures at hydraulic junction points shall balance within 0.5 psi (0.03 bar).
• The highest pressure at the junction point, and the total flows as adjusted, shall
be carried into the calculations.
18
• Pressure balancing shall be permitted through the use of a K-factor developed
for branch lines or portions of systems using .
Specific friction loss values or equivalent pipe lengths for alarm valves, dry pipe
valves, deluge valves, strainers, and other devices shall be made available to the
authority having jurisdiction.
5.11.5. C-FACTORS
Table 14.4.3.1.1 shall be used with a Hazen-Williams C factor of 120 only. For
other values of C, the values in Table 14.4.3.1.1 shall be multiplied by the factors
indicated in Table 14.4.3.2 (NFPA 13).
19
5.11.6. ROOM DESIGN METHOD
Where the design is based on the room design method, the calculation shall be
based on the room and communicating space, if any, that is hydraulically the most
demanding.
The maximum allowable protection area of coverage for a sprinkler (As) shall
be in accordance with the value indicated in Table 8.6.2.2.1(a) through Table
8.6.2.2.1(d) NFPA 13, 2002.
20
21
5.11.8. MINIMUM OPERATING PRESSURE
Minimum operating pressure of any sprinkler shall be 7 psi (0.5 bar).
22
Schedule for Ordinary Hazard Occupancies
1. Design Area = 18 266 square feet is less than 52 000 square feet; therefore, one
sprinkler system is enough.
24
Floor lay-out of Sprinkler removing Lines.
25
3. Initial Pipe Sizing (Using Pipe Schedule)
For areas of sprinkler operation less than 1500 ft 2 (139 m2) used for light and
ordinary hazard occupancies, the density for 1500 ft2 (139 m2) shall be used.
No. of sprinkler = 1500 ft2 / 130 ft2 = 11.5, so use 12 minimum.
Most remote area (enclosed in red lines).
26
5. Noding or Number of Sections (enclosed in violet circles).
27
*Using Elite Fire Version 6.02.23 Software.
28
Node 1-3
Beginning – 1
End – 3
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 6.05 + 1 = 7.05 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = ET
(The rest is zero as default)
Node 2-3
Beginning – 2
End – 3
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 6.05 + 1 = 7.05 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = ET
(The rest is zero as default)
Node 3-6
Beginning – 3
End – 6
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 9.51 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = T
(The rest is zero as default)
Node 4-6
29
Beginning – 4
End – 6
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 6.05 + 1 = 7.05 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = ET
(The rest is zero as default)
Node 5-6
Beginning – 5
End – 6
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 6.05 + 1 = 7.05 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = ET
(The rest is zero as default)
Node 6-9
Beginning – 6
End – 9
Material – 4
Diameter = 40 mm = 1.5 in
Length (Layout) = 10.17 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = T
(The rest is zero as default)
30
Node 7-9
Beginning – 7
End – 9
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 7.05 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = ET
(The rest is zero as default)
Node 8-9
Beginning – 8
End – 9
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 6.05 + 1 = 7.05 ft
K-factor = 5.6
K-factor = 0.0
31
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = ET
(The rest is zero as default)
Node 9-12
Beginning – 9
End – 12
Material – 4
Diameter = 50 mm = 2 in
Length (Layout) = 9.51 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = T
(The rest is zero as default)
Node 10-12
Beginning – 10
End – 12
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 6.05 + 1 = 7.05 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = ET
(The rest is zero as default)
Node 11-12
Beginning – 11
End – 12
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 6.05 + 1 = 7.05 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = ET
(The rest is zero as default)
32
Node 12-15
Beginning – 12
End – 15
Material – 4
Diameter = 50 mm = 2 in
Length (Layout) = 10.76 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = T
(The rest is zero as default)
Node 13-15
Beginning – 13
End – 15
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 6.05 + 1 = 7.05 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 ft.
33
Standard Fitting = ET
(The rest is zero as default)
Node 14-15
Beginning – 14
End – 15
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 6.05 + 1 = 7.05 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = ET
(The rest is zero as default)
Node 15-18
Beginning – 15
End – 18
Material – 4
Diameter = 50 mm = 2 in
Length (Layout) = 9.84 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = T
(The rest is zero as default)
Node 16-18
Beginning – 16
End – 18
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 6.05 + 1 = 7.05 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = ET
(The rest is zero as default)
34
Node 17-18
Beginning – 17
End – 18
Material – 4
Diameter = 25 mm = 1 in
Length (Layout) = 6.05 + 1 = 7.05 ft
K-factor = 5.6
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = ET
(The rest is zero as default)
Node 18-19
Beginning – 18
End – 19
Material – 4
Diameter = 65 mm = 2.5 in
Length (Layout) = 10.76 ft
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 19.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = T
(The rest is zero as default)
35
Node 19-20
Beginning – 19
End – 20
Material – 4
Diameter = 65 mm = 2.5 in
Length (Layout) = 9.84 ft
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 19.7 ft.
Sprinkler Elevation = 19.7 ft.
Standard Fitting = T
(The rest is zero as default)
Node 20-21
Beginning – 20
End – 21
Material – 4
Diameter = 65 mm = 2.5 in
Length (Layout) = 19.77 ft
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 19.7 ft.
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Standard Fitting = 2ET
(The rest is zero as default)
Node 21-22
Beginning – 21
End – 22
Material – 4
Diameter = 65 mm = 2.5 in
Length (Layout) = 5.49 ft
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Standard Fitting = T
(The rest is zero as default)
Node 22-23
Beginning – 22
End – 23
Material – 4
36
Diameter = 65 mm = 2.5 in
Length (Layout) = 19.03 ft.
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Standard Fitting = T
(The rest is zero as default)
Node 23-24
Beginning – 23
End – 24
Material – 4
Diameter = 80 mm = 3 in
Length (Layout) = 21.43 ft
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Standard Fitting = T
(The rest is zero as default)
Node 24-25
Beginning – 24
End – 25
Material – 4
Diameter = 80 mm = 3 in
Length (Layout) = 7.44 ft
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Standard Fitting = T
(The rest is zero as default)
37
Node 25-26
Beginning – 25
End – 26
Material – 4
Diameter = 100 mm = 4 in
Length (Layout) = 8.97 ft
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Standard Fitting = T
(The rest is zero as default)
Node 26-27
Beginning – 26
End – 27
Material – 4
Diameter = 100 mm = 4 in
Length (Layout) = 17.61 ft
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Standard Fitting = T
(The rest is zero as default)
38
Node 27-28
Beginning – 27
End – 28
Material – 4
Diameter = 100 mm = 4 in
Length (Layout) = 22.97 ft
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Standard Fitting = T
(The rest is zero as default)
Node 28-29
Beginning – 28
End – 29
Material – 4
Diameter = 100 mm = 4 in
Length (Layout) = 13.78 ft
K-factor = 0.0
K-factor = 0.0
Sprinkler Elevation = 19.7 – 1 = 18.7 ft.
Sprinkler Elevation = 0 ft.
Standard Fitting = ET2GC
(The rest is zero as default)
39
5.12. WATER TANK SIZING
https://rcwapp.xyleminc.com/fp_select.asp
Electric Pump
40
Then,
Water flow rate = 6.23 GPM
Head = 184.6154 ft
Efficiency = 41.9%
Bhp = 0.649
Motor Hp = 0.649/0.419
Motor Hp = 1.55 hp
Use 2 hp.
5. SPECIFICATION
The Contractor shall supply and install fire-fighting pumps as shown and
detailed on the drawings.
The fire sprinkler pump/ duty/standby and the Jockey pump, shall be completely fully
automatic, factory assembled, skid mounted units includes the following features:
41
c. Galvanized Steel frame.
d. Galvanized suction and delivery manifolds with
flanged connections
e. Isolating valves and flexible connection on suction and delivery for each
pump
f. Check valves on delivery for each pump
g. Strainer on suction for each pump
h. Pressure gauges, pressure switches and pressure relief valves
i. One Pressure vessel diaphragm type of 200 liters capacity
j. Automatic control panel
k. Fire pump set (Duty / standby) to be electrical driven for hose reel and
fire hydrant.
Pump construction shall be in cast iron casing, bronze impeller, stainless steel
shaft complete with steel base frame / plate.
The motor shall be squirrel cage induction type and rated for continuous
operation at ambient temperature not less than 50 Deg. C, totally enclosed fan cooled
with insulation class F and IP 54-protection level and rated for 415 volt, 3 phase and
50 Hz.
The Engine shall be of 4-stroke mechanical injection air-cooled type with
automatic speed regulator and flywheel housing.
The Engine shall be provided with double battery kit (12 VDC) and charger,
complete with exhaust pipe (insulated) and arranged to discharge outside.
42
1 Cyclic Controller
1 Pressure switch and adjustable setting for each pump
1 Dry run prevention relay and floats switch in feed tank
1 Set of Volt free contacts for BMS interface
1 Multi attempt relay to allow at least 3 attempts for Engine Starting
1 Earth leakage sensor with hooter, mute push button and Indication lamp.
The “hand” button shall be spring-loaded and shall override all control circuits
exception the overload, so that the selected pump can be checked for performance
and operation.
The pump sets shall operate under the control of pressure switches
A. General:
1. Minimum sprinkler orifice size shall be 1/2 inch.
2. Sprinklers in non-public spaces such as mechanical/electrical
equipment, and storage rooms and sprinklers on exposed
piping shall have brass finish unless noted otherwise.
3. Sprinklers and escutcheons in finished areas to have polished
brass or white finish or finish as noted on plans.
43
4. Style, size, and temperature rating to be type specifically
approved for such use.
5. Thermosensitive glass bulbs to be of all one color for a given
temperature classification.
6. For each sprinkler style, all sprinklers to be of same type
(fusible link or glass bulb). B. Upright Sprinklers:
1. Thermosensitive glass-bulb or fusible solder/alloy standard
response.
2. Thermosensitive glass-bulb quick response.
3. Fusible solder/alloy quick response.
4. Installation style:
a. Exposed: No escutcheon
C. Pendent Sprinklers:
1. Thermosensitive glass-bulb or fusible solder/alloy standard
response.
2. Thermosensitive glass-bulb quick response.
3. Fusible solder/alloy quick response.
4. Installation style:
a. Exposed: No escutcheon.
44
G. Spare Sprinkler Cabinet: Wall mounted. Storage capacity of
not less than minimum designated by NFPA 13.
H. Sprinkler Wrench: To match style and brand of sprinklers used
Sprinklers shall be installed in accordance with NFPA 13.
These shall be local Fire officer’s approved, pendant glass
bulb sprinklers rated for 79 degree C. for sprinklers mounted
in non-air conditioned areas and 68 degree C. for sprinklers
mounted in air conditioned areas, and suitable for maximum
ambient temperature of 50 degree C. sprinklers shall have k
factor of 80 with 15 mm (1/2”) MSPT male inlets. Recessed
type of sprinklers shall be installed in the false ceilings in order
to make the surroundings decorative. There shall be a 2piece
design of the recessed enclosure and mounting plate allows
installation of the sprinklers prior to the installation of the false
ceiling. Both sprinklers and escutcheon plates shall have
chrome finish.
Toilet and pantry areas (AHU Plant room) shall be provided
with side wall type sprinklers and shall have chrome finish.
Samples are to be submitted to the consultant for
approval.
Side sprinkler head to be installed at plant room of swimming
pool.
PREPARATION
45
4. Install piping as follows, unless noted otherwise:
a. Parallel to walls.
b. Above suspended ceilings.
c. Behind walls.
5. Galvanized pipe and fittings:
a. Use where exposed to corrosive atmospheres in the
following locations:
Exterior piping
b. Field paint damaged galvanizing on pipe and fittings.
6. Label piping appropriately.
c) Pipe Supports:
Install hangers in compliance with Section 15140 and NFPA 13 (as
referenced by the authority having jurisdiction). All pipe hangers, bolts,
nuts, washers and other hardware to be hot dipped galvanized
construction for use at the cooling towers. All outdoor piping to be hot
dipped galvanized construction with all threads coated to prevent
corrosion from outdoor elements.
d) Pipe Sleeves and Seals:
Install sleeves and seals in compliance with Section 15140. e) Drains:
Provide drainage facilities as follows:
a. In accordance with NFPA standards, and as indicated.
b. Drain entire system by gravity.
c. Drain size not less than 3/4 inch.
d. Provide nipple and cap or brass plug for systems or
partial systems of 5 gallons or less.
e. Provide valve and plug for systems or partial systems of
more than 5 gallons.
f) Control Valves:
1. Bolt position on lugged butterfly valves to allow removal of
downstream piping.
g) Sprinklers:
1. Unless noted otherwise, provide sprinkler types as indicated on
drawings.
2. Install sprinklers in fittings after piping is in place.
3. Install exposed sprinklers with frame parallel to branch line.
4. Install sprinkler guards where sprinklers are within 2.2 meters of
floor, or when subject to injury.
5. Line sprinklers up with themselves.
46
6. Prior to Date of Substantial Completion, deliver spare heads and
wrench and place in spare head cabinet(s).
47
9. MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEM
Introduction
When properly installed and maintained, automatic fire sprinkler systems have
proven to be the most effective means for protecting life and property against fire. In
recognition of their excellent track record in controlling the spread of fire, both state
codes and national standards offer fire sprinklers as a costeffective alternative to
meeting many of their base code requirements.
A lot is riding, therefore, on a sprinkler system’s ability to operate and function
properly. So much so, in fact, that state law prohibits the occupancy of any portion of
a building until the required suppression system has been tested and approved.
Further, it requires that such systems be maintained in an operative condition at all
times and be repaired or replaced when defective.
In order to meet both certification requirements and licensure requirements,
automatic fire sprinkler systems are required to be inspected, tested and maintained
in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintenance
of Water-Based Fire Protection Systems.. While the provisions in this edition of the
standard applicable to fire sprinkler systems are very similar to those found in the
1998 edition, you’ll find that the 2002 edition contains more restrictive testing
requirements for dry sprinklers and sprinklers subjected to harsh environments.
Application
It must be noted that this document is intended to serve as a quickreference
guide only and is not intended to be all-inclusive. It covers most, but not all, of the
inspection, testing and maintenance requirements applicable to fire sprinkler systems.
Some facilities may have additional equipment not covered in this guide. It is
important, therefore, that the user have access to, and become familiar with all the
requirements found in, NFPA 25.
System types
The requirements contained in NFPA 25 are based on the type of sprinkler
system installed.
The two types most commonly found in healthcare occupancies are wet pipe
and dry pipe sprinkler systems. Some buildings contain both types of systems – a wet
pipe system in heated areas and a dry-pipe system in unheated areas. Simply put, a
wet pipe sprinkler system is a piping system containing water so arranged that water
discharges immediately from sprinklers activated by heat from a fire. A dry pipe
sprinkler system is a piping system containing air or nitrogen under pressure so
arranged that upon activation of a sprinkler, the water pressure opens a valve allowing
water to flow into the pipe and out the opened sprinkler.
48
Definitions
In order to follow the requirements of the standard, it’s important to have a good
understanding of what’s meant by “inspection”, “testing” and “maintenance”. Those
terms are defined in NFPA 25(98), Sec. 1-5 as follows [see also NFPA 25(02), Sec.
3.3]:
49
Applicable Standards
Specific Requirements
The inspection, testing and maintenance requirements that apply to your
building’s fire sprinkler system start from the date of initial installation and continue on
at specific intervals throughout the life of the system. What follows is a brief synopsis
of some of the major requirements you need to be aware of.
New installations
In order to meet both federal certification requirements and state licensure
requirements, automatic fire sprinkler systems are required to be installed in
accordance with NFPA 13, Standard for the Installation of Sprinkler Systems.
All newly installed fire sprinkler systems are required to meet specific
acceptance requirements, such as flushing of fire service mains and testing of both
underground and aboveground piping [see NFPA13(99]. These services must be
provided by licensed contractors.
Monthly
The following monthly inspections can be performed by facility staff:
50
Note: Where air pressure is not supervised at a constantly attended location,
these gauges need to be inspected on a weekly basis.
Quarterly
Note: Most newly installed fire sprinkler systems are now hydraulically
designed.
b. Inspect alarm devices to verify that they are free of physical damage.
c. Inspect fire department connections to verify that:
• They are visible and accessible
• Couplings or swivels are not damaged and rotate smoothly
• Plugs or caps are in place and not damaged
• Gaskets are in place and in good condition
• Identification signs are in place
• The check valve is not leaking
• The automatic drain valve is in place and operating properly
2. With proper training the following quarterly tests can be performed by facility
staff:
a. Test the water flow alarm on wet pipe sprinkler systems by opening the
inspector’s test connection. This simulates the opening of a sprinkler
head.
Note: Where freezing weather conditions or other circumstances prohibit the use of
the inspector’s test connection; the bypass connection is allowed to be used.
b. Test the water flow alarm on dry pipe sprinkler systems by using the
bypass connection.
Caution: Opening the inspector’s test connection can cause the system to trip
accidentally, allowing the pipes to fill with water and creating a potential for a serious
freeze problem.
Annually
In addition to the monthly and quarterly inspections and tests, NFPA 25 has
very detailed and specific inspection, testing and maintenance services that need to
be performed on an annual basis. Because of their complexity, and to comply with
51
Minnesota state law, these services must be performed by a licensed sprinkler
contractor and would include such things as:
1. A full flow trip test is required for dry pipe sprinkler systems every 3 years [see
NFPA 25(98), Sec. 9-4.4.2.2.1 or NFPA 25(02), Sec. 12.4.4.2.2.2].
2. Sprinkler system gauges typically have a life expectancy of 10 to 15 years. As
a result, these gauges must be replaced every 5 years or tested every 5 years
by comparison to a calibrated gauge. Gauges not accurate to within 3 percent
of the full scale must be recalibrated or replaced [see NFPA 25(98), Sec. 2-3.2
or NFPA 25(02), Sec. 5.3.2].
3. System check valves must be inspected internally every 5 years to verify that
all components operate properly, move freely and are in good condition [see
NFPA 25(98), Sec. 9-4.2.1 or NFPA 25(02), Sec. 12.4.2.1].
4. The 1998 edition of NFPA 25 has specific requirements dealing with testing of
sprinkler heads that have been in service for an extended period of time [see
NFPA 25(98), Sec. 2-3.1]. These requirements, which emphasize the
importance of knowing the history of your facility’s fire sprinkler system, would
include:
a. Sprinklers manufactured prior to 1920 must be replaced.
b. Representative samples of solder-type, extra-high temperature
sprinklers (i.e. 325°- 375° F) that are exposed to semi-continuous or
continuous maximum allowable ambient temperature conditions are
required to be tested at 5 year intervals. These would be sprinklers you
might find, for example, in your boiler room and would have red-colored
frame arms.
c. Sprinklers manufactured using fast response elements that have been
in service for 20 years are required to be tested. Retesting is required at
10-year intervals.
52
Note: The first residential sprinkler was listed for service in 1981 and the first quick
response sprinkler was listed for service in 1983.
1. Fire pumps, where present, are also subject to very specific inspection, testing
and maintenance requirements to help ensure that they will function properly
when needed. Some of the basics include:
a. Fire pumps must be inspected weekly to verify that the pump assembly
appears to be in operating condition and is free from physical damage
[see NFPA 25(98), Sec. 5-2 or NFPA 25(02), Sec.
8.2 for specific conditions that must be checked].
b. Fire pump assemblies must be tested weekly [see NFPA 25(98), Sec.
5-3.2 or NFPA 25(02), Sec. 8.3 for specific observations and
adjustments that need to be made while the pump is running].
c. An annual test of the fire pump assembly is required. This test must be
conducted under minimum, rated and peak flows of the pump [see
NFPA 25(98), Sec. 5-3.3 or NFPA 25(02), Sec. 8.3.3 for specific visual
observations, measurements and adjustments that need to be made
while the pump is running and flowing water under the specified output
condition].
53
2. NFPA 25 requires that a preventive maintenance program be established on
all components of the pump assembly in accordance with manufacturer’s
recommendations [see NFPA 25(98), Sec. 5-5 or NFPA
25(02), Sec. 8.5].
54
b. Discharge densities over the design area(s)
c. Required flow and residual pressure demand at the base of the riser
d. Occupancy classification or commodity classification and maximum
permitted storage height and configuration
e. Hose stream demand included in addition to the sprinkler demand
1. A tag or card showing the following must be attached to dry pipe system
valves [see NFPA 25(98), Sec. 9-4.4.2.5 or NFPA 25(02), Sec.
12.4.4.2.5]:
• Date dry pipe valve last tripped
• Name of person and organization conducting the test
2. Separate records of initial air and water pressure, tripping air pressure and
dry pipe valve operating condition must be maintained on the premises for
comparison with previous test results.
It’s important that at least two people in your facility know where your
records are kept to increase the likelihood that they can be readily provided
if requested during an inspection.
It is required that these records be maintained on the premises for at least
three years and must be copied for the fire code official on request.
55
10. ENGINEERING ECONOMICS – ANALYSIS
56
11.2. CONCLUSION
In the design of fire sprinkler system, only the most remote area is considered.
Getting the required water demand and pressure develop. Sizing fire pump is from the
sum of sprinkler water demand and hose demand. Fire pump package includes on-
duty fire pump which is electric driven, standby fire pump which is diesel engine driven
and a jockey pump to maintain the system pressure which is also electric driven. This
for educational building which is a two-level school building, the main parts of the
design that need further consideration on the calculation of the required pressure at
the most remote sprinkler.
11.3. RECOMMENDATION
Standard procedure based on NFPA 13, and other related standard shall be
consulted first before proceeding to the design.
57
12. REFERENCES
Gummerhaul, M.L. and Pennel G.T. Hotel and Motel Fire Sprinkler Systems
Article in www.pmengineer.com, Nov. 1, 2008.
NFPA 13 – Standard for the Installation of Fire Sprinkler Systems, 2002 Ed.
Pipe Fittings and Flanges. Pipe Fittings by Type. Retrieved Jan. 10, 2016
from http://www.thepipefittings.com/pipe-fittings-types.html
Sanguri, Mohit. (July 12, 2012). Marine Insight. Pipe and Bends – An
Essential Guide for Second Engineers: Part 2. Retrieved Jan. 10, 2016
from http://www.marineinsight.com/tech/pipeing/pipes-and-bendsan-
essential-guide-for-second-engineers-part-2/
58
APPENDICES
59
APPENDIX A – FIRE PUMPS MODEL BROCHURE
60
Pump Designs
Flowserve offers a wide range of
complementary pump types,
built to recognized global
standards and costumer
specification. These include:
• Single-stage process
• Between bearing single-
stage
• Between bearing
multistage
• Vertical
• Submersible motor
• Positive displacement
• Nuclear
• Specially
Available Configurations
• Sealed and seal less
• Axially and radially split
• Volute and diffuser
• Close coupled and spacer
coupled
• Single and double case
61
62
63
APPENDIX B – SPRINKLER MODEL BROCHURE
64
APPENDIX C – SPRINKLER SYSTEM PIPING LAYOUT
65
APPENDIX D – DESIGN CALCULATION
66