MCset 4
24 kV
Withdrawable SF6 circuit-breaker
Catalogue
2010
General 5
Presentation 13
Cubicle description 21
Switchgear 39
Installation 47
Appendices 51
AMTED306032EN.indd 3
Field of application 6
Continuity of service and complete safety 7
MCset, a comprehensive solution 8
Quality assurance - environment 11
A few references 12
AMTED306032EN.indd 5
requirements from 1 to 24 kV
MCset is an indoor, metal-clad switchgear unit intended for the MV section
of HV/MV substations and high power MV/MV substations.
Applications
87158
MT20052
Power plants
b Auxiliary substations
Industry
b Oil & gas
b Chemical industry
b Metallurgy
b Car industry
b Mining
b Cement plants
b…
Infrastructure
b Airports
b Ports
b Hospitals
b Water treatment
b…
6 AMTED306032EN.indd
Reliability
MT20058EN
b Type testing was carried out for each performance level in the MCset range.
b The design, manufacturing and testing of MCset was carried out
according to ISO 9001: 2000 quality standard.
b Three-dimensional computer modeling techniques were used to study
the electrical fields.
Simplicity
b A user interface which is easily understood by everybody.
PE56386
Safety
b Operations are all performed from the front, including access to
connections and busbars.
b Racking in and out is only possible with the door closed.
b The power-on indicator is situated on the front of the functional unit.
b The earthing switch has making capacity.
b One single ‘‘anti-reflex” handle is used for all MCset operations.
b Internal arc withstand developed for all functional units.
AMTED306032EN.indd 7
MCset provides the most efficient means to control and protect a wide
range of applications.
Due to the devices it comprises, MCset can be easily integrated into
a monitoring and control system.
PE57021
Easy evolution
Addition of communication, digital I/O’s, analog output, or temperature
acquisition are possible due to its modular design.
8 AMTED306032EN.indd
Hub
Front socket
Simple choice
A simple choice between WRM-1 and WRM-2 service levels allows you
EGX400 to easily order your Web Remote Monitoring MCset switchboard.
A customized level is also available.
Your Web Remote Monitoring MCset switchboard comes equipped with
Sepam
a Web server including Web pages dedicated to power equipment data.
Sepam
Easy commissioning
Web Remote Monitoring equipment is delivered ready to connect and
CM/PM
commission.
A Quick Start guide, packaged with your switchboard, provides three easy-
MCset switchboard to-follow steps.
Functionalities provided
WRM-1 WRM-2
PE57471
Instantaneous readings b b
Displays automatically updated meter values
Circuit summary b b
Displays the RMS current 3-phase average (A),
the real power (kW), the power factor,
the circuit breaker status (if applicable), etc.
Load current summary b b
Displays the current RMS value for each phase (A),
for all circuits
Demand current summary b b
Displays the average demand current value for each phase (A),
PE57472
Log displays b
Displays data as time curves, or tables
Export of data tables b
Allows data tables to be exported in a standard
Windows format
AMTED306032EN.indd 9
Modernizing Specifying
throughout the life of your installation
Specifying
We help you to define your solutions: selection guide,
technical assistance, advice…
Implementing
We oversee the completion and commissioning of your installation:
design, cost optimization, guaranteed performances and dependability,
commissioning tests, etc.
Operating Implementing
Operating
We help run your daily operations in real time: maintenance contract,
technical assistance, supply of replacement parts, corrective and
preventive maintenance, operation and maintenance training, etc.
Modernizing
We can bring the performance of your installation up to date:
installation audit, switchgear diagnosis, adaptation and modification,
end of life recycling, etc.
10 AMTED306032EN.indd
A major asset
In each of its units, Schneider Electric integrates a functional organization
whose main role is to check quality and monitor compliance with standards.
This procedure is:
b uniform throughout all departments
b recognized by many customers and approved organizations.
But above all, it is its strict application that has allowed us to obtain
the recognition of an independent organization:
The French Quality Assurance Association (AFAQ).
The quality system for the design and manufacture of MCset
is certified to be in conformity with the requirements of ISO 9001:
2000 quality assurance standard.
PE58000
Protected environment
PE56733
AMTED306032EN.indd 11
Industry
b Water
PE57981
Buildings
b Hotels
Hamilton Hotels Australia
Grand Indonesia Project Indonesia
New Islands Project Abu Dhabi
b Hospital
Slim River Hospital Malaysia
12 AMTED306032EN.indd
Description 14
Technical characteristics 16
Operating conditions 17
Protection of people 18
Specific applications 19
AMTED306032EN.indd 13
PE56741
Busbars
LV control
cabinet
Sepam
Wiithdrawable
part
Current
transformers
Cables
connection
Voltage
transformers
compartment
14 AMTED306032EN.indd
AMTED306032EN.indd 15
Technical data
PE56742
Rated voltage
(kV) 24
Rated insulation level
Power frequency withstand voltage (r ms kV) 50
50 Hz - 1 min
Lightning impulse withstand voltage (kV peak) 125
1.2/50 µs
Nominal current and maximum short time withstand current (1)
Functional unit with circuit breaker
Short time withstand current Ith. max (kA/3 s) 16
25
31,5
Rated current In max busbars (A) 2500 (2)
In CB (A) 630
1250
2500
Functional unit with fuse switch (DI cubicle)
Short time withstand current Ith. max (kA) 31.5 (3)
Rated current In max y (A) 200
Internal arc withstand
(kA/1 s) 25
(kA/0.15 s) 31.5
Protection degree
IP3X
IP4X
IPX1 (2)
IAC (internal arc classification): (1) For functional units equipped with circuit breakers,
the breaking capacity is equal to the short time withstand current.
The metal enclosed switchgear may In all cases, the device peak making capacity is equal to 2.5 times
have different types of accessibility the short time withstand current.
(2) For higher performances, consult us
on the various sides of its enclosure. (3) Limited by fuses.
For identify purpose of different sides of
the enclosure, the following code shall be
used (according to IEC 62271-200
standard).
A: restricted access to authorized personnel
only
F: access to the front side
L: access to the lateral side
R: access to the rear side.
16 AMTED306032EN.indd
Operating conditions
MT20072
Standards
The MCset 4 range meets the following international standards:
b IEC 62271-1: clauses common to high voltage switchgear
b IEC 62271-100: high voltage alternating current circuit breakers
b IEC 62271-102: alternating current disconnectors and earthing switches
b IEC 62271-103: switches for rated voltages above 1 and less than 52 kV
b IEC 62271-200: metal-enclosed switchgear for alternating current
at rated voltages of between 1 and 52 kV
b IEC 60282-2: high voltage fuses
b IEC 60255: measurement relay and protection unit (Sepam)
b IEC 60044-1: current transformers
b IEC 60044-2: voltage transformers.
AMTED306032EN.indd 17
All operations are carried out from the front face, including access to connections
and busbars.
The user is guided through icon-diagrams on each front panel making it easy
to understand the operating sequence and device status.
Interlocks and padlocks prevent operator errors.
Several additional levels of security also protect operators:
b racking in and out is only possible with the door closed.
b the very extensive set of mechanical and electrical interlocks do not allow operator
error. These can be added to by key locks or padlocks according to specific
operating procedures. Each selector can be fitted with one to three padlocks.
b all operations are carried out from the front face including access to connections
and busbars.
b the voltage present indicator is located on the front face of the functional unit,
in the immediate vicinity of the earthing switch control.
b disarming of circuit-breaker when racking out. This function enables the circuit
breaker control springs to be disarmed during the extraction operation.
b Locking of withdrawable part/cable compartment. This function disables the
possibility of racking the withdrawable part in if the front panel (cable compartment)
is not installed.
b Locking of the MV door open if the LV plug of the circuit breaker is not plug-in.
18 AMTED306032EN.indd
Seismic areas
PE56575
DEP Shell
MCset 4 switchboards are certified by Shell in compliance with DEP 33.67.51.31
Gen (November 2006) for MV equipments.
AMTED306032EN.indd 19
AMTED306032EN.indd 21
Device Circuit breaker Circuit breaker Circuit breaker Circuit breaker Circuit breaker Fuse-switch
MT20081
MT20082
Sepam
22 AMTED306032EN.indd
MT20084
MT20081
MT20078
AMTED306032EN.indd 23
AD4 RD4
DE55085
DE57782
DE57765
DE57766
1 1
7 7
H H
4 4
5 5
6
3 3
W W D D
AD4 RD4
DE57760
DE57761
MV components
1 busbars for cubicle interconnection
2 withdrawable part (SF1-2 circuit breaker, disconnector truck or earthing truck)
3 MV connections by cables accessible from the front face
Sepam Sepam 4 earthing switch
5 current sensors
6 voltage transformers (optionally equipped with withdrawable fuses)
LV control cabinet
7 low voltage auxiliaries and protection, monitoring and control unit
are in one control cabinet, separated from the medium voltage part.
Characteristics
AD4 RD4
Rated voltage kV 24 24
Rated insulation level kV r ms 50 Hz - 1 min 50 50
kV impulse 1.2/50 µs 125 125
Rated current A 630 b b
1250 b b
2500 b b
Breaking capacity kA 31.5 –
Short time withstand current kA r ms 3 s 16, 25, 31.5 16, 25, 31.5
Dimensions mm Width (W) 900 900
Height (H) 2325 2325
Depth (D) (1) 1750 1750
Approximative weight (2) kg 1100 930
(1) Overall + 175 mm for 4-sided internal arcing protected switchboards, or 2 sets of CT’s.
(2) Fully equipped cubicle.
24 AMTED306032EN.indd
DE57767
DE56765
1 1
I O tri
5 5
V/H W/ W clear alar rese
2
H 3
L L L
W W D D
CL4 and GL4
DE57762
MV components
1 busbars to connect the bussectioning functional unit with other switchboard
cubicles
2 withdrawable part (circuit breaker SF1-2, disconnector truck or earthing truck)
3 current sensors
4 voltage transformers (optionally equipped with withdrawable fuses)
Sepam
LV control cabinet
5 low voltage auxiliaries and protection, monitoring and control unit
are in one control cabinet, separated from the medium voltage part.
Characteristics
CL4 - GL4
Rated voltage kV 24
Rated insulation level kV r ms 50 Hz - 1 min 50
kV impulse 1.2/50 µs 125
Rated current A 630 b
1250 b
2500 b
Breaking capacity kA 31.5
Short time withstand current kA r ms 3 s 16, 25, 31.5
Dimensions mm Width (W) 900 (x 2)
Height (H) 2325
Depth (D) (1) (3) 1750
Approximative weight (2) kg 1600 (CL4 + GL4)
(1) Overall + 175 mm for 4-sided internal arcing protected switchboards.
(2) Fully equipped cubicle.
(3) Overall + 500 mm for upstream CTs.
AMTED306032EN.indd 25
TT4
DE57785
DE57769
1
4
W D
TT4
DE57763
MV components
1 busbars to connect the TT functional unit with other switchboard cubicles
2 earthing switch
3 voltage transformers (optionally equipped with withdrawable fuses)
LV control cabinet
4 low voltage auxiliaries and protection, monitoring and control unit
are in one control cabinet, separated from the medium voltage part.
Characteristics
TT4
Rated voltage kV 24
Rated insulation level kV r ms 50 Hz - 1 min 50
kV impulse 1.2/50 µs 125
Busbars current A 1250 b
2500 b
Short time withstand current kA r ms 3 s 16, 25, 31.5
Dimensions mm Width (W) 900
Height (H) 2325
Depth (D) (1) 1750
Weight kg 560
(1) Overall + 175 mm for 4-sided internal arcing protected switchboards.
26 AMTED306032EN.indd
DI4
DE57770
DE57771
4
1
2
H
3
W D
DI4
DE57764
MV components
1 busbars to connect the DI functional unit with other switchboard cubicles
2 switch - earthing switch
3 MV fuses
LV control cabinet
4 low voltage auxiliaries and protection, monitoring and control unit
are in one control cabinet, separated from the medium voltage part.
Characteristics
DI4
Rated voltage kV 24
Rated insulation level kV r ms 50 Hz - 1 min 50
kV impulse 1.2/50 µs 125
Rated current A 200 b
Breaking capacity (2) kA 31.5
Short time withstand current (2) kA r ms 31.5
Dimensions mm Width (W) 900
Height (H) 2325
Depth (D) (1) 1750
Weight kg 640
(1) Overall + 175 mm for 4-sided internal arcing protected switchboards.
(2) Limited by fuses.
DI cubicles including a fuse switch are used to supply power and protect low power
transformers.
E.g.: auxiliary service transformers in primary substations.
All operations are carried out from the front face, including access to connections
and busbars.
All functional interlocks meet recommendations in IEC 62271-200:
b the switch is only possible to close if the earthing switch is open and the connection
access panel is in place
b closing of the earthing switch is only possible if the switch is open
b opening of the access panel to medium voltage connections and fuses is only
possible of the earthing switches upstream and downstream of the fuses are closed
b the switch is locked in the open position when the access panel is taken off.
The voltage presence indicator is situated on the front face of the functional unit,
integrated in the switch’s control panel.
AMTED306032EN.indd 27
Protection system 30
Sepam series 20, series 40, series 80, Sepam 100 31
Instrument transformers 33
AMTED306032EN.indd 29
DE57772
with a comprehensive protection, monitoring
Protection relays
and control system comprising: metering equipment
b instrument transformers to measure the
necessary electrical values (phase current,
residual current, voltages, etc.)
b protection relays, providing functions Switchgear
(circuit breaker and contactor)
adapted to the part of the network to be
protected
b metering equipment, to inform operators
b low voltage relaying, i.e. to provide control
of the breaking device and
of the withdrawable part
b various auxiliaries: secondary circuit test
Instrument transformers
units, etc.
Like the MCset range, the Sepam range is a range of units defined to provide
an optimal solution for each application, and includes (eg):
b Sepam S, substation incomer and feeder
b Sepam B, bussectioning
b Sepam T, transformer feeder
b Sepam G, generator feeder
b Sepam C, capacitor feeder.
(*) Please check in the Sepam catalogue the sensor to use with
each Sepam version.
30 AMTED306032EN.indd
PE57125
PE57126
AMTED306032EN.indd 31
Sepam series 20
b 10 logic inputs Current S20 T20
DE57493
frequency
protection
Sepam series 40
b 10 logic inputs Current, S40 T40 G40
DE57495
frequency
protection for
two sets of
busbars
Capacitor C86
DE57499
bank
unbalance
32 AMTED306032EN.indd
Transformer ARJP2/N2J
b Double primary current, double secondary current for measurement or protection
b Frequency 50-60 Hz
I1n / I2n (A) 50-100 75-150 100-200 150-300 200-400 250-500 600 750
Ith (kA) 40 40 31.5-40 40 40 40 50 50
t (s) 1 1 1 1 1 1 1 1
Measuring* cl 0.5 5-10 VA 10-20 VA 7.5-15 VA 10-20 VA 20 VA 20 VA
ARJP2 protection* 5P10 2.5-5 VA 2.5-5 VA 2.5-5 VA 2.5-5 VA 5-10 VA 5-10 VA 7.5 VA 7.5 VA
Transformer ARJP3/N2J
b Single primary current, double secondary current for measurement or protection
b Frequency 50-60 Hz
I1n / I2n (A) 1000 / 5 1250 / 5
Ith (kA) 50 50
t (s) 1 1
Measuring* cl 0.5 30 VA 30 VA
protection* 5P20 10 VA 10 VA
ARJP3
AMTED306032EN.indd 33
34 AMTED306032EN.indd
Voltage transformers
E74401
AMTED306032EN.indd 35
Withdrawable
part
Extraction
table
36 AMTED306032EN.indd
DE57773
b the lever-type propulsion mechanism A circuit breaker is a safety device enabling
for racking in-out switching and protection of electrical distribution
b interlocks to fix the withdrawable parts networks. Installed in the MCset cubicle, it protects
onto the fixed part. all components situated downstream during
MCset circuit breakers SF1-2, switches a short-circuit.
use sulphur hexafluoride (SF6) for insulation
and breaking.
The live parts are housed in an insulating enclosure
in the sealed pressure system in compliance Earthing truck
DE57774
with IEC 62271-100. The earthing truck is a safety feature which allows
The devices used to equip the MCset range of the cubicle busbar to be earthed. It is installed
functional units have outstanding features: instead of the circuit breaker and has the same
b long service life interlock possibilities.
b maintenance-free live parts
b high electrical endurance
b very low overvoltages
b operating safety
b insensitivity to the environment Disconnector truck
DE57775
b breaking capacity and dielectric strength The disconnector truck enables the upper and lower
maintained at atmospheric pressure part of the cubicle to be short-circuited.
b low filling pressure. It is installed instead of the circuit breaker
and has the same interlock possibilities.
SF circuit breaker
PE56744
Presentation
SF range circuit breakers equip cubicles AD4 and CL4 for rated voltage values
of 24 kV.
They work on the basis of the “puffer” type principle in SF6, which is used as
a breaking and insulating medium.
Each of the 3 poles have an independent insulating enclosure which forms a filled
pressure system in compliance with IEC standard 62271-100.
Each pole forms a gas-tight unit filled with low pressure SF6 at low relative pressure of
0.05 to 0.35 MPa (0.5 to 3.5 bars) according to the performance level required.No
filling is required during the equipment’s life.
According to the performance levels, it is possible to optionally equip SF6 circuit
breakers with a pressure switch to act on an alarm in the case of a pressure drop.
SF6 range circuit breakers are actuated by a GMH type spring mechanism.
AMTED306032EN.indd 37
Withdrawable parts 40
Accessories - Withdrawable parts extraction 42
DI switch cubicle 44
AMTED306032EN.indd 39
The main contacts and arcing contacts are initially closed (Fig. 1).
Pre-compression (Fig. 2)
When the contacts begin to open, the piston slightly compresses the SF6 gas
in the pressure chamber.
Arcing period (Fig. 3)
The arc appears between the arcing contacts. The piston continues its downward
movement.
A small quantity of gas, directed by the insulating nozzle is injected across the arc.
For the breaking of low currents, the arc is cooled by forced convection.
However, for high currents, thermal expansion causes the hot gases to move
towards the cooler parts of the pole unit.
Fig. 1 Fig. 2 The distance between the two arcing contacts becomes sufficient for the current to be
broken when it reaches the zero point, due to the dielectric properties of the SF6.
Sweeping overstroke (Fig. 4)
The moving parts finish their movement and the injection of cold gas continues until
the contacts are completely open.
Fig. 3 Fig. 4
40 AMTED306032EN.indd
SF range circuit breakers are actuated by a GMH operating mechanism that ensures a
switching device closing and opening rate that is independent of the operator.
This operating mechanism, always motorised, enables remote operation and fast
reclosing cycles.
The GMH operating mechanism includes:
b a spring system that stores the energy needed to close and open the breaker
b a manual spring charging system
b an electrical motor spring charging device that automatically recharges
the mechanism as soon as the contacts close (recharging time < 15 s)
b two mechanical push buttons for opening and closing, accessible with
the cubicle door open (circuit breaker in test position)
b an electrical closing system comprising a closing release for remote control
and an anti-pumping relay
b an electrical opening system comprising one or more opening releases
of the following type:
v shunt
v undervoltage.
b an operation counter
b an optional “operating mechanism charged” indication contact
b an end of charging contact
b a black-white mechanical “open-closed” position indicator
b a multi-pin connector to isolate auxiliary circuits in the “racked out” position.
Contact characteristics Auxiliary contacts
The GMH operating mechanism is equipped with a block of 14 auxiliary contacts
Rated current 10 A
including:
Breaking capacity AC 220 V (cos ϕ ≥ 0.3) 10 A
b 1 changeover contact for the electrical operating mechanism
DC 110 or 220 V (L/R ≤ 0.01 s) 1.5 A b 1 changeover contact for indication
b 1 contact for the shunt release.
AMTED306032EN.indd 41
Extraction table
DE57468
Racking handle
DE57582
42 AMTED306032EN.indd
Extraction Racking-out
Removed Disconnected Test position Service
1 - Cradle Fool-proof
protection (1)
Anti-drop (2)
No opening shutters
Connected No unplugging
Closed No racking-in
(1) This protection mechanism ensures that the performance levels of the circuit breaker correspond with those of the cradle.
(2) Device that prevents the circuit breaker from dropping when extracted from the cradle.
The device can be either unlocked manually or when the extraction rig is put in position.
(3) Option.
(4) Interlocking device to be fitted to the cubicle door. If there is no interlocking, the circuit breaker device should be inhibited.
AMTED306032EN.indd 43
SM6 switch
E74222
The three rotating contacts are placed in an enclosure filled with gas to a relative
pressure of 0.04 MPa (0.4 bars).
The system offers maximum operating reliability:
Gas tightness
The SF6 filled enclosure is of the “sealed pressure system type”. Sealing tightness is
always checked in the factory.
Safety
b the switch may be in one of three positions: “closed”, “open” or “earthed”,
giving a natural interlocking system that prevents operator error. Moving contact
rotation is driven by a fast acting mechanism that is independent of the operator.
b the device combines the breaking and disconnecting functions.
b the SF6-enclosed earthing switch has a short-circuit making capacity
in compliance with standards.
Breaking principle
The outstanding qualities of SF6 gas are used to extinguish the electrical arc.
To increase cooling of the arc, a relative movement is created between the arc
and the gas. The arc strikes when the fixed and moving contacts separate.
The combination of the current and a magnetic field created by a permanent magnet
causes the arc to rotate around the fixed contact, extending and cooling it until
it is extinguished at current zero point. The distance between the fixed and moving
contacts is then sufficient to withstand the recovery voltage.
This system is both simple and dependable, and it provides improved electrical
endurance due to very low wear of contacts.
1 Enclosure
DE57486
2 6
2 Cover
3 Operating shaft
4 Fixed contact
5 Moving contact
6 Seal
1 3 4 5
DE55122
44 AMTED306032EN.indd
b auxiliary contacts:
v switch (2 O + 2 C)
v switch (2 O + 3 C) and earthing switch (1 O + 1 C)
v switch (1 C) and earthing switch (1 O + 1 C) if motor option.
b motor option
b opening release:
v shunt
v undervoltage (option).
b closing release: shunt trip.
b fuse blown release: any fuse blown trips the opening of the switch.
AMTED306032EN.indd 45
Fuse ratings for MCset protection units depend, among other things,
on the following criteria:
b service voltage
b transformer rating
b fuse technology (manufacturer).
Different types of fuses with medium loaded striker maybe installed:
v Solefuse fuses as per standard UTE NCF 64.210
v Fusarc CF fuses as per IEC recommendation 60.282.1 and DIN dimensions 43.625.
For fuse-switch combination unit, refer only to the selection table and reference list of
fuses. For all other type of fuses, consult us.
Example: for the protection of a 400 kVA transformer at 22 kV, select either Solefuse
fuses rated 16 A or Fusarc CF fuses rated 25 A.
Fuses dimensions
Solefuse (UTE standards)
ø 55 ø6 Ur Ir L Ø Weight
DE57466
450 23
35 35
Fusarc CF
ø 45 Ø ø6 Ur Ir L Ø Weight
DE57467
SIBA
ø 45 Ø ø6 Ur Ir L Ø Weight
DE57467
L 23
33 33
46 AMTED306032EN.indd
Implementation examples 48
Connections 49
AMTED306032EN.indd 47
Line up switchboard
(2 supplies cubicles and 1 bussection at 24 kV)
DE57777
500 900 900 900 900 900 900 900 900 900 900 900 500
3 feeders incomer bussection incomer 4 feeders
cubicle AD4 cubicle AD4 cubicles CL4/GL4 cubicle AD4 cubicle AD4
room
entrance
(1) (1)(5)
2500 2800
(3) (4)
150 1750 1700 - 2600
(1) Minimum dimensions to be complied with when installing
the MCset switchboard.
(2) The cable basement or cable trench depth can be reduced
if it is compatible with the bending radius of the cables used.
(3) Operating distance. B A
(4) Distance needed to extract a functional unit. (1) (2)
330 550 1200
(5) Provide an exhaust tunnel above the switchboard when the
room height is less than 4 metres (see page 12).
A anchor point
B adjustment point
48 AMTED306032EN.indd
3 key factors
b The need for correctly made connections
New cold connecting technologies offer easy installation and favour durability in time.
Their design means they can be used in polluted environments with harsh
atmospheres.
b The impact of relative humidity
The installing of a heating element is essential in climates with high relative
humidities and significant temperature differentials.
b Ventilation control
The dimensions of air vents must be appropriate for the dissipated energy
in the substation. They must only sweep across the transformer environment.
Cold connected terminals
Schneider Electric’s experience has led it to favour this technology wherever
possible for optimum durability.
The maximum acceptable cable cross-section for standard assemblies are:
b 630 mm2 for incomer or feeder cubicles with single-pole cables;
b 400 mm2 for incomer or feeder cubicles with three-pole cables;
b 95 mm2 for transformer protection cubicles with fuses.
Access to the compartment is only possible when the earthing switch is closed.
Tightening torques for cables will be attained using a dynamo wrench set to 50 mN.
AMTED306032EN.indd 49
b The cubicles and cables requiring the maximum depth should be taken into
consideration when determining the depth P of a switchboard cable duct (Fig. 1).
H b When using cables of length greater than 430 mm for MCset 4, install
an additional compartment as marked (A) under the cubicle (Fig. 2).
P
Fig. 1
DE57780
Fig. 2
DE57781
Fig. 3
50 AMTED306032EN.indd
Cubicle equipment 52
Current transformers (Selection guide) 53
Notes 54
AMTED306032EN.indd 51
b : basic equipment.
v : option.
(1) Basic equipment with earthing switch option.
(2) According to the room in which the MCset switchboard is installed, you can choose AFL or AFLR,
and possibly an exhaust tunnel for hot gases (≥ 4 m and ≤ 4 m).
(3) Basic equipment when the cubicle is equipped with an earthing switch.
(4) Connection 1 or 2 cables per phase.
(5) Possibility of 1 phase-phase VT.
(6) Only for 630 A cubicle.
(7) 1 NO + 1 NC available.
(8) For IPX2, consult us.
(9) Compartment protection.
52 AMTED306032EN.indd
50-100/1-5 v
2.5-5 VA - 5P20
75-150/1 or 5 v
2.5-5 VA - 5P20
100-200/1-1 or 5-5 v
2.5-5 VA - 5P20
150-300/1-1 or 5-5 v
2.5-5 VA - 5P20
10-20 VA - cl 0.5
200-400/1-1 or 5-5 v
5-10 VA - 5P20
7.5-15 VA - cl 0.5
250-500/1-1 or 5-5 v
5-10 VA - 5P20
10-20 VA - cl 0.5
600/1-1 or 5-5 v
7.5 VA - 5P20
20 VA - cl 0.5
750/1-1 or 5-5 v
7.5 VA - 5P20
20 VA - cl 0.5
1000/1-1 or 5-5 v v
10 VA - 5P20
30 VA - cl 0.5
1250/1-1 or 5-5 v v
10 VA - 5P20
30 VA - cl 0.5
1500/1-1 or 5-5 v v
15 VA - 5P20
30 VA - cl 0.5
2000/1-1 or 5-5 v v
15 VA - 5P20
30 VA - cl 0.5
2500/1-1 or 5-5 v v
15 VA - 5P20
30 VA - cl 0.5
v : option.
Other characteristics are available, including the possibility of having 3 secondary windings.
Please consult us detailing the type of protection or measuring required as well as
the impedance of the outside loads and the cabling.
AMTED306032EN.indd 53
54 AMTED306032EN.indd
Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation
35, rue Joseph Monier of the information given in this publication.
CS 30323
F - 92506 Rueil Malmaison Cedex This document has been printed
on ecological paper
RCS Nanterre 954 503 439
Capital social 896 313 776 € Publishing: Schneider Electric Industries SAS
www.schneider-electric.com Design: Graphème
Printing: Made in France
AMTED306032EN 07-2010