Calculation of Restrained Pipe Length at TR-02 (Ch-14+426) - 1.2m
Calculation of Restrained Pipe Length at TR-02 (Ch-14+426) - 1.2m
Rs = KnPpD′
L= Sf PA tan (θ/2) Sf = 1.5
Ff + 1/2 Rs P = 11bar=159.5 psi
D′ = 48/12 = 4 ft
A = π(D”)2 = 1809.56in2
4
θ = 11.25°
Kn = 0.60 (From Table 1)
For Ff = 0.7xFs (For Polyethylene encased pipe)
N = tan2(45+/2)=tan2(45+ 25)=2.46
2
Then:
Pp = (100x5.94x2.46)+ (2x225)√2.46 Where:
Pp = 2167.04 lbs/ft2
Rs = KnPpD'
Rs = 0.6x2167.04x4
Now From STEP 1 to determine required restrained length.
= 5200.89
(1.5x159.5x1809.56)tan(11.25/2)
L=
1144.42+ 1/2x5200.89
= 42640.59
3744.86
L = 11.4 ft.
= 3.5 m
Soil Parameters (Table-1):
3 4 5
GW & SW 35 0.76 0 0.0 110 0.60 0.85 1.00
GP & SP 31 0.80 0 0.0 110 0.60 0.85 1.00
GM & SM 30 0.76 0 0.0 110 0.60 0.85 1.00
GC & SC 25 0.65 225 0.4 100 0.60 0.85 1.00
CL 20 0.50 250 0.8 100 0.60 0.85 1.00
ML 29 0.75 0 0.0 100 0.60 0.85 1.00
CL, GP & SP 31 0.80 450 0.0 100 0.60 0.85 1.00
ML, GP & SP 31 0.80 300 0.0 100 0.60 0.85 1.00
CH, GP & SP 31 0.80 400 0.0 100 0.40 0.60 0.85
MH, GP & SP 31 0.80 250 0.0 100 0.40 0.60 0.85