Project Ref. No.

X-301
Project 66/11 kV Switcyard
Customer M/s SMCC Construction India Limited
Client M/s HONDA MOTORCYCLE & SCOOTER INDIA PVT. LTD.
Location VITHALAPUR, GUJRAT
Subject: Fault level calculation for 66kV substation HMSI, Vithalapur

INPUT DATA
1 66kV Power reciving from Getco - Mandal S/s through over hear transmission line (ACSR Panther)
2 Getco - Mandal S/s to HMSI S/s - 20 KM ( Aproxx)
3 2 nos. transformer each having 20 MVA capacity, 66/11 kV are in parallel at 66kV HMSI S/S
4 % impedence of 16/20 MVA, 66/11 kV transformer is 10.

CALCULATION
1 Fault level at 66 kV GETCO- Mandal S/s = 575 MVA (Refer GETCO Fault Level )
Fault Current = MVA Fault /(V x √3) = 5.03 kA

2 Panthar Conductor
Length = 20KM /Phase
Dia = 21 mm (Area - 261 Sq. MM)
Resistance of Panthar conductor R = 0.132 Ω/km
Reactance of Panthar conductor XL = 0.416 Ω/km
Capacitance of Panthar conductor C = 8.7 F/km

Impedence Z (per KM) = √R²+( XL- XC)² Where XC = 1/2 лfc


XC = 1/2*3.14*50*8.7
= 0.00037 Ω/km
Z = √(0.0174)²+( 0.416 – 0.00037)²
= 0.433 Ω/km
Thus Net impedance Znet 1 = 0.433 x 20
= 8.66 Ω

3 Fault MVA at HSMI S/s - 66kV Side = V2/z


= 662/8.68
= 503 MVA
Fault Current = MVA Fault /(V x √3) = 4.40 kA

4 20 MVA, 25/10 kV transformers -


impedence = 10

5 Fault level at 11 kV(HMSI S/S) = Total MVA Capacity x 100


Total impedence
= 40.00 x 100
((10/2)+8.66)
= 292.65 MVA

6 Fault Current at 11kV(HMSI) = MVA Fault /(V x √3)


= 15.36 kA

Document Name Fault level calculation


Prepared By Shree
Reviewed By Vishnu Shanker Document No. (SPIPL) X-301/C-010
Approved By S.S.Singh Date 19th March 2015 Rev. 0