Download as pdf or txt
Download as pdf or txt
You are on page 1of 224

Relion® 615 series

Transformer Protection and Control


RET615
Application Manual
Document ID: 1YHT530003D05
Issued: 2014-05-14
Revision: C
Product version: 4.1

© Copyright 2014 ABB. All rights reserved


Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.

The software or hardware described in this document is furnished under a license


and may be used, copied, or disclosed only in accordance with the terms of such
license.

Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.

Warranty
Please inquire about the terms of warranty from your nearest ABB representative.

ABB
Nanjing SAC Power Grid Automation Co., Ltd.
No. 11 Phoenix Road, Jiangning Development Zone
211100 Nanjing
China
Telephone: +86 25 51183000
Facsimile: +86 25 51183883
Customer hotline: 4008876268
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.

This product has been designed to be connected and communicate data and
information via a network interface which should be connected to a secure
network. It is the sole responsibility of the person or entity responsible for network
administration to ensure a secure connection to the network and to take the
necessary measures (such as, but not limited to, installation of firewalls, application
of authentication measures, encryption of data, installation of anti virus programs,
etc.) to protect the product and the network, its system and interface included,
against any kind of security breaches, unauthorized access, interference, intrusion,
leakage and/or theft of data or information. ABB is not liable for any such damages
and/or losses.

This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents

Table of contents

Section 1 Introduction.......................................................................5
This manual........................................................................................5
Intended audience..............................................................................5
Product documentation.......................................................................6
Product documentation set............................................................6
Document revision history.............................................................6
Related documentation..................................................................7
Symbols and conventions...................................................................7
Symbols.........................................................................................7
Document conventions..................................................................8
Functions, codes and symbols......................................................8

Section 2 RET615 overview...........................................................11


Overview ..........................................................................................11
Product version history................................................................11
PCM600 and IED connectivity package version..........................12
Operation functionality......................................................................12
Optional functions........................................................................12
Physical hardware............................................................................12
Local HMI.........................................................................................14
Display.........................................................................................15
LEDs............................................................................................16
Keypad........................................................................................16
Web HMI...........................................................................................17
Authorization.....................................................................................18
Audit trail......................................................................................19
Communication.................................................................................21
Ethernet redundancy...................................................................22

Section 3 RET615 standard configurations....................................25


Standard configurations....................................................................25
Addition of control functions for primary devices and the
use of binary inputs and outputs..................................................28
LED functionality..........................................................................28
Connection diagrams........................................................................30
Presentation of standard configurations...........................................38
Standard configuration A..................................................................39
Applications.................................................................................39
Functions.....................................................................................40
Default I/O connections..........................................................41

RET615 1
Application Manual
Table of contents

Default disturbance recorder settings.....................................43


Functional diagrams....................................................................43
Functional diagrams for protection.........................................44
Functional diagrams for disturbance recorder and
supervision functions..............................................................50
Functional diagrams for control and interlocking....................52
Standard configuration B..................................................................56
Applications.................................................................................56
Functions.....................................................................................57
Default I/O connections..........................................................58
Default disturbance recorder settings.....................................60
Functional diagrams....................................................................60
Functional diagrams for protection.........................................61
Functional diagrams for disturbance recorder and
supervision functions..............................................................67
Functional diagrams for control and interlocking....................69
Standard configuration C..................................................................73
Applications.................................................................................73
Functions.....................................................................................74
Default I/O connections..........................................................75
Default disturbance recorder settings.....................................77
Functional diagrams....................................................................77
Functional diagrams for protection.........................................78
Functional diagrams for disturbance recorder and
supervision functions..............................................................84
Functional diagrams for control and interlocking....................86
Standard configuration D..................................................................90
Applications.................................................................................90
Functions.....................................................................................91
Default I/O connections..........................................................92
Default disturbance recorder settings.....................................94
Functional diagrams....................................................................94
Functional diagrams for protection.........................................95
Functional diagrams for disturbance recorder and
supervision functions ...........................................................101
Functional diagrams for control and interlocking..................103
Standard configuration E................................................................107
Applications...............................................................................107
Functions...................................................................................108
Default I/O connections........................................................109
Default disturbance recorder settings...................................111
Functional diagrams..................................................................111
Functional diagrams for protection.......................................112

2 RET615
Application Manual
Table of contents

Functional diagram for disturbance recorder and


supervision functions............................................................118
Functional diagrams for control and interlocking..................120
Standard configuration F................................................................124
Applications...............................................................................124
Functions...................................................................................124
Default I/O connections........................................................126
Default disturbance recorder settings...................................127
Functional diagrams..................................................................128
Functional diagrams for protection.......................................128
Functional diagram for disturbance recorder and
supervision functions............................................................135
Functional diagrams for control and interlocking..................137
Standard configuration G................................................................141
Applications...............................................................................141
Functions...................................................................................141
Default I/O connections........................................................143
Default disturbance recorder settings...................................144
Functional diagrams..................................................................145
Functional diagrams for protection.......................................145
Functional diagram for disturbance recorder and trip
circuit supervision ................................................................152
Functional diagrams for control and interlocking..................154
Standard configuration H................................................................158
Applications...............................................................................158
Functions...................................................................................158
Default I/O connections........................................................160
Default disturbance recorder settings...................................161
Functional diagrams..................................................................162
Functional diagrams for protection.......................................162
Functional diagram for disturbance recorder and
supervision functions............................................................169
Functional diagrams for control and interlocking..................171
Standard configuration J.................................................................175
Applications...............................................................................175
Functions...................................................................................175
Default I/O connections........................................................176
Default disturbance recorder settings...................................177
Functional diagrams..................................................................178
Functional diagrams for protection.......................................178
Functional diagrams for disturbance recorder and
supervision...........................................................................183
Functional diagrams for control and interlocking..................184
Standard configuration K................................................................187

RET615 3
Application Manual
Table of contents

Applications...............................................................................187
Functions...................................................................................188
Default I/O connections........................................................189
Default disturbance recorder settings...................................191
Functional diagrams..................................................................191
Functional diagrams for protection.......................................192
Functional diagrams for disturbance recorder and
supervision...........................................................................199
Functional diagrams for control and interlocking..................201

Section 4 Requirements for measurement transformers..............205


Current transformers......................................................................205
Current transformer requirements for non-directional
overcurrent protection................................................................205
Current transformer accuracy class and accuracy limit
factor....................................................................................205
Non-directional overcurrent protection.................................206
Example for non-directional overcurrent protection..............207

Section 5 IED physical connections.............................................209


Inputs..............................................................................................209
Energizing inputs.......................................................................209
Phase currents.....................................................................209
Residual current...................................................................209
Phase voltages.....................................................................209
Residual voltage...................................................................210
RTD/mA inputs..........................................................................210
Auxiliary supply voltage input....................................................210
Binary inputs..............................................................................211
Optional light sensor inputs.......................................................212
Outputs...........................................................................................212
Outputs for tripping and controlling............................................212
Outputs for signalling.................................................................213
IRF.............................................................................................214

Section 6 Glossary.......................................................................215

4 RET615
Application Manual
1YHT530003D05 C Section 1
Introduction

Section 1 Introduction

1.1 This manual

The application manual contains application descriptions and setting guidelines


sorted per function. The manual can be used to find out when and for what purpose
a typical protection function can be used. The manual can also be used when
calculating settings.

1.2 Intended audience

This manual addresses the protection and control engineer responsible for
planning, pre-engineering and engineering.

The protection and control engineer must be experienced in electrical power


engineering and have knowledge of related technology, such as protection schemes
and principles.

RET615 5
Application Manual
Section 1 1YHT530003D05 C
Introduction

1.3 Product documentation

1.3.1 Product documentation set

deinstallation & disposal


Decommissioning,
Commissioning

Maintenance
Engineering
Planning &

Installation

Operation
Quick start guide purchase
Quick installation guide
Brochure
Product guide
Operation manual
Installation manual
Connection diagram
Engineering manual
Technical manual
Application manual c
Communication protocol manual c
IEC 61850 Engineering guide
Point list manual

GUID-12DC16B2-2DC1-48DF-8734-0C8B7116124C V1 EN

Figure 1: The intended use of documents during the product life cycle

Product series- and product-specific manuals can be downloaded


from the ABB Website http://www.abb.com/relion.

1.3.2 Document revision history


Document revision/date Product version History
A/2009-09-29 2.0 First release
B/2010-07-02 3.0 Content updated
C/2014-05-14 4.1 Content updated to correspond to the
product version

Download the latest documents from the ABB Website


http://www.abb.com/substationautomation.

6 RET615
Application Manual
1YHT530003D05 C Section 1
Introduction

1.3.3 Related documentation


Name of the document Document ID
Modbus Communication Protocol Manual 1MRS756468
IEC 60870-5-103 Communication Protocol Manual 1MRS756710
IEC 61850 Engineering Guide 1MRS756475
Engineering Manual 1MRS757121
Installation Manual 1MRS756375
Operation Manual 1MRS756708
Technical Manual 1YHT530004D05

1.4 Symbols and conventions

1.4.1 Symbols

The electrical warning icon indicates the presence of a hazard


which could result in electrical shock.

The warning icon indicates the presence of a hazard which could


result in personal injury.

The caution icon indicates important information or warning related


to the concept discussed in the text. It might indicate the presence
of a hazard which could result in corruption of software or damage
to equipment or property.

The information icon alerts the reader of important facts and


conditions.

The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.

Although warning hazards are related to personal injury, it is necessary to


understand that under certain operational conditions, operation of damaged
equipment may result in degraded process performance leading to personal injury
or death. Therefore, comply fully with all warning and caution notices.

RET615 7
Application Manual
Section 1 1YHT530003D05 C
Introduction

1.4.2 Document conventions


A particular convention may not be used in this manual.

• Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
• Push-button navigation in the LHMI menu structure is presented by using the
push-button icons.
To navigate between the options, use and .
• HMI menu paths are presented in bold.
Select Main menu/Settings.
• LHMI messages are shown in Courier font.
To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
• IED input/output messages and monitored data names are shown in Courier font.
When the function starts, the START output is set to TRUE.

1.4.3 Functions, codes and symbols


Table 1: RET615 functions, codes and symbols
Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
PHLPTOC1 3I> (1) 51P-1 (1)
protection, low stage, instance 1
Three-phase non-directional overcurrent
PHLPTOC2 3I> (2) 51P-1 (2)
protection, low stage, instance 2
Three-phase non-directional overcurrent
PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent
PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent
PHIPTOC1 3I>>> (1) 50P/51P (1)
protection, instantaneous stage, instance 1
Three-phase non-directional overcurrent
PHIPTOC2 3I>>> (2) 50P/51P (2)
protection, instantaneous stage, instance 2
Non-directional earth-fault protection, low
EFLPTOC1 Io> (1) 51N-1 (1)
stage, instance 1
Non-directional earth-fault protection, low
EFLPTOC2 Io> (2) 51N-1 (2)
stage, instance 2
Non-directional earth-fault protection, high
EFHPTOC1 Io>> (1) 51N-2 (1)
stage, instance 1
Non-directional earth-fault protection, high
EFHPTOC2 Io>> (2) 51N-2 (2)
stage, instance 2
Negative-sequence overcurrent protection,
NSPTOC1 I2> (1) 46 (1)
instance 1
Table continues on next page

8 RET615
Application Manual
1YHT530003D05 C Section 1
Introduction

Function IEC 61850 IEC 60617 IEC-ANSI


Negative-sequence overcurrent protection,
NSPTOC2 I2> (2) 46 (2)
instance 2
Negative-sequence overcurrent protection,
NSPTOC3 I2> (3) 46 (3)
instance 3
Negative-sequence overcurrent protection,
NSPTOC4 I2> (4) 46 (4)
instance 4
Residual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1)
Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2)
Three-phase undervoltage protection, instance
PHPTUV1 3U< (1) 27 (1)
1
Three-phase undervoltage protection, instance
PHPTUV2 3U< (2) 27 (2)
2
Three-phase overvoltage protection, instance 1 PHPTOV1 3U> (1) 59 (1)
Three-phase overvoltage protection, instance 2 PHPTOV2 3U> (2) 59 (2)
Positive-sequence undervoltage protection,
PSPTUV1 U1< (1) 47U+ (1)
instance 1
Positive-sequence undervoltage protection,
PSPTUV2 U1< (2) 47U+ (2)
instance 2
Negative-sequence overvoltage protection,
NSPTOV1 U2> (1) 47O- (1)
instance 1
Negative-sequence overvoltage protection,
NSPTOV2 U2> (2) 47O- (2)
instance 2
Three-phase thermal overload protection for
T2PTTR1 3Ith>T 49T
power transformers, two time constants
Stabilized and instantaneous differential
TR2PTDF1 3dI>T 87T
protection for 2W –transformers
Numerical stabilized low impedance restricted
LREFPNDF1 dIoLo> 87NL
earth-fault protection
High impedance based restricted earth-fault
HREFPDIF1 dIoHi> 87NH
protection
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)
Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)

Multi-purpose protection, instance 1 1) MAPGAPC1 MAP (1) MAP (1)

Multi-purpose protection, instance 2 1) MAPGAPC2 MAP (2) MAP (2)

Multi-purpose protection, instance 3 1) MAPGAPC3 MAP (3) MAP (3)

Multi-purpose protection, instance 4 1) MAPGAPC4 MAP (4) MAP (4)

Multi-purpose protection, instance 5 1) MAPGAPC5 MAP (5) MAP (5)

Multi-purpose protection, instance 6 1) MAPGAPC6 MAP (6) MAP (6)

Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
Table continues on next page

RET615 9
Application Manual
Section 1 1YHT530003D05 C
Introduction

Function IEC 61850 IEC 60617 IEC-ANSI


Disconnector control, instance 1 DCXSWI1 I <-> O DCC (1) I <-> O DCC (1)
Disconnector control, instance 2 DCXSWI2 I <-> O DCC (2) I <-> O DCC (2)
Earthing switch control ESXSWI1 I <-> O ESC I <-> O ESC
Disconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
Disconnector position indication, instance 3 DCSXSWI3 I <-> O DC (3) I <-> O DC (3)
Earthing switch indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
Earthing switch indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Tap changer position indication TPOSSLTC1 TPOSM 84M
Condition monitoring
Circuit-breaker condition monitoring SSCBR1 CBCM CBCM
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Fuse failure supervision SEQRFUF1 FUSEF 60
Runtime counter for machines and devices MDSOPT1 OPTS OPTM
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement, instance 1 CMMXU1 3I 3I
Three-phase current measurement, instance 2 CMMXU2 3I(B) 3I(B)
Sequence current measurement, instance 1 CSMSQI1 I1, I2, I0 I1, I2, I0
Sequence current measurement, instance 2 I1I(B), I2I(B), I1I(B), I2I(B),
CSMSQ2
I0I(B) I0I(B)
Residual current measurement, instance 1 RESCMMXU1 Io In
Residual current measurement, instance 2 RESCMMXU2 Io(B) In(B)
Three-phase voltage measurement VMMXU1 3U 3U
Residual voltage measurement RESVMMXU1 Uo Vn
Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0
Three-phase power and energy measurement PEMMXU1 P, E P, E
RTD/mA measurement XRGGIO130 X130 (RTD) X130 (RTD)

1) Multi-purpose protection is used for example for RTD/mA based protection.

10 RET615
Application Manual
1YHT530003D05 C Section 2
RET615 overview

Section 2 RET615 overview

2.1 Overview

RET615 is a dedicated transformer protection and control IED (intelligent


electronic device) for power transformers, unit and step-up transformers including
power generator-transformer blocks in utility and industry power distribution
systems. RET615 is a member of ABB’s Relion® product family and part of its 615
protection and control product series. The 615 series IEDs are characterized by
their compactness and withdrawable-unit design.

Re-engineered from the ground up, the 615 series has been designed to unleash the
full potential of the IEC 61850 standard for communication and interoperability
between substation automation devices. Once the standard configuration IED has
been given the application-specific settings, it can directly be put into service.

The 615 series IEDs support a range of communication protocols including IEC
61850 with GOOSE messaging, IEC 60870-5-103 and Modbus®.

2.1.1 Product version history


Product version Product history
2.0 Product released
3.0 • New configurations E, F, G and H
• Additions to configuration A, B, C, D, J and K
• Application configurability support
• Analog GOOSE support
• Large display with single line diagram
• Enhanced mechanical design
• Increased maximum amount of events and fault records
• Frequency measurement and protection
• RTD/mA measurement and protection
• Voltage measurement and protection
• Fuse failure supervision
• Three-phase power and energy measurements
• Multi-port Ethernet option

4.1 • Additions/changes for configurations A-H


• Dual fibre optic Ethernet communication option (COM0032)
• Generic control point (SPCGGIO) function blocks
• Additional logic blocks
• Button object for SLD
• Controllable disconnector and earth switch objects for SLD
• Additional multi-purpose protection instances
• Increased maximum amount of events and fault records
• High-availability seamless redundancy (HSR) protocol
• Parallel redundancy protocol (PRP-1)
• Parallel use of IEC 61850 and IEC 60870-5-103 protocols
• Two selectable indication colors for LEDs (red or green)
• Online binary signal monitoring with PCM600

RET615 11
Application Manual
Section 2 1YHT530003D05 C
RET615 overview

2.1.2 PCM600 and IED connectivity package version


• Protection and Control IED Manager PCM600 Ver. 2.6 or later
• RET615 Connectivity Package Ver. 4.1 or later
• Parameter Setting
• Firmware Update
• Disturbance Handling
• Signal Monitoring
• Lifecycle Traceability
• Signal Matrix
• Communication Management
• Configuration Wizard
• Label Printing
• IED User Management
• Application Configuration
• Graphical Display Editor
• Differential Characteristics Tool
• Event Viewer

Download connectivity packages from the ABB Website


http://www.abb.com/substationautomation.

2.2 Operation functionality

2.2.1 Optional functions


• Arc protection
• Modbus TCP/IP or RTU/ASCII
• IEC 60870-5-103
• RTD/mA measurements and multi-purpose protection (configurations A, B, C
and D only)

2.3 Physical hardware

The IED consists of two main parts: plug-in unit and case. The content depends on
the ordered functionality.

12 RET615
Application Manual
1YHT530003D05 C Section 2
RET615 overview

Table 2: Plug-in unit and case


Main unit Slot ID Content options
Plug-in - HMI Small (4 lines, 16 characters)
unit Large (8 lines, 16 characters)
X100 Auxiliary power/BO 48-250 V DC/100-240 V AC; or 24-60 V DC
module 2 normally-open PO contacts
1 change-over SO contact
1 normally-open SO contact
2 double-pole PO contacts with TCS
1 dedicated internal fault output contact
X110 BIO module 8 binary inputs
4 signal output contacts
X120 AI/BI module 6 phase current inputs (1/5A)
1 residual current input (1/5A)
Case X130 AI/BI module Only with configurations E, F, G, H and K:
3 phase voltage inputs (60-210 V)
1 residual voltage input (60-210 V)
4 binary inputs
Optional RTD/mA module Optional for configurations A, B, C, D and J:
2 generic mA inputs
6 RTD sensor inputs
Optional BIO module Optional for configurations A, B, C, D and J:
6 binary inputs
3 signal output contacts
X000 Optional communication See the technical manual for details about different
module types of communication modules.

Rated values of the current and voltage inputs are basic setting parameters of the
IED. The binary input thresholds are selectable within the range 18…176 V DC by
adjusting the binary input setting parameters.

The connection diagrams of different hardware modules are presented in this manual.

See the installation manual for more information about the case and
the plug-in unit.

Table 3: Number of physical connections in standard configurations


Conf. Analog channels Binary channels
CT VT RTD/mA BI BO
- 8 (14)1) 10 (13)1)
A 7 -
6/22) 8 10

- 8 (14)1) 10 (13)1)
B 7 -
6/22) 8 10

- 8 (14)1) 10 (13)1)
C 7 -
6/22) 8 10

Table continues on next page

RET615 13
Application Manual
Section 2 1YHT530003D05 C
RET615 overview

Conf. Analog channels Binary channels


CT VT RTD/mA BI BO
- 8 (14)1) 10 (13)1)
D 7 -
6/22) 8 10

E 7 5 - 12 10
F 7 5 - 12 10
G 7 5 - 12 10
H 7 5 - 12 10

- 8 (14)1) 10 (13)1)
J 7 -
6/22) 8 10

K 7 5 - 12 10

1) With optional BIO module


2) With optional RTD/mA module

2.4 Local HMI

The LHMI is used for setting, monitoring and controlling the IED. The LHMI
comprises the display, buttons, LED indicators and communication port.

14 RET615
Application Manual
1YHT530003D05 C Section 2
RET615 overview

REF615

Overcurrent
Dir. earth-fault
Voltage protection
Phase unbalance
Thermal overload
Breaker failure
Disturb. rec. Triggered
CB condition monitoring
Supervision
Arc detected
Autoreclose shot in progr.

A070704 V3 EN

Figure 2: Example of the LHMI

2.4.1 Display
The LHMI includes a graphical display that supports two character sizes. The
character size depends on the selected language. The amount of characters and
rows fitting the view depends on the character size.

Table 4: Small display

Character size1) Rows in the view Characters per row


Small, mono-spaced (6x12 pixels) 5 20
Large, variable width (13x14 pixels) 4 8 or more

1) Depending on the selected language

Table 5: Large display

Character size1) Rows in the view Characters per row


Small, mono-spaced (6x12 pixels) 10 20
Large, variable width (13x14 pixels) 8 8 or more

1) Depending on the selected language

RET615 15
Application Manual
Section 2 1YHT530003D05 C
RET615 overview

The display view is divided into four basic areas.


1 2

3 4
A070705 V3 EN

Figure 3: Display layout

1 Header
2 Icon
3 Content
4 Scroll bar (displayed when needed)

2.4.2 LEDs
The LHMI includes three protection indicators above the display: Ready, Start and
Trip.

There are also 11 matrix programmable LEDs on front of the LHMI. The LEDs
can be configured with PCM600 and the operation mode can be selected with the
LHMI, WHMI or PCM600.

2.4.3 Keypad
The LHMI keypad contains push-buttons which are used to navigate in different
views or menus. With the push-buttons you can give open or close commands to
objects in the primary circuit, for example, a circuit breaker, a contactor or a
disconnector. The push-buttons are also used to acknowledge alarms, reset
indications, provide help and switch between local and remote control mode.

16 RET615
Application Manual
1YHT530003D05 C Section 2
RET615 overview

A071176 V1 EN

Figure 4: LHMI keypad with object control, navigation and command push-
buttons and RJ-45 communication port

2.5 Web HMI

The WHMI allows accessing the IED via a Web browser. The supported Web
browser versions are Internet Explorer 7.0, 8.0 and 9.0.

WHMI is disabled by default.

WHMI offers several functions.

• Programmable LEDs and event lists


• System supervision
• Parameter settings
• Measurement display
• Disturbance records
• Phasor diagram
• Single-line diagram

The menu tree structure on the WHMI is almost identical to the one on the LHMI.

RET615 17
Application Manual
Section 2 1YHT530003D05 C
RET615 overview

A070754 V4 EN

Figure 5: Example view of the WHMI

The WHMI can be accessed locally and remotely.

• Locally by connecting the laptop to the IED via the front communication port.
• Remotely over LAN/WAN.

2.6 Authorization

The user categories have been predefined for the LHMI and the WHMI, each with
different rights and default passwords.

The default passwords can be changed with Administrator user rights.

User authorization is disabled by default for LHMI but WHMI


always uses authorization.

18 RET615
Application Manual
1YHT530003D05 C Section 2
RET615 overview

Table 6: Predefined user categories


Username User rights
VIEWER Read only access
OPERATOR • Selecting remote or local state with (only locally)
• Changing setting groups
• Controlling
• Clearing indications

ENGINEER • Changing settings


• Clearing event list
• Clearing disturbance records
• Changing system settings such as IP address, serial baud rate
or disturbance recorder settings
• Setting the IED to test mode
• Selecting language

ADMINISTRATOR • All listed above


• Changing password
• Factory default activation

For user authorization for PCM600, see PCM600 documentation.

2.6.1 Audit trail


The IED offers a large set of event-logging functions. Normal process-related
events can be viewed by the normal user with Event Viewer in PCM600. Critical
system and IED security-related events are logged to a separate nonvolatile audit
trail for the administrator.

Audit trail is a chronological record of system activities that allows the


reconstruction and examination of the sequence of events and changes in an event.
Past user and process events can be examined and analyzed in a consistent method
with the help of Event List and Event Viewer in PCM600. The IED stores 2048
system events to the nonvolatile audit trail. Additionally, 1024 process events are
stored in a nonvolatile event list. Both the audit trail and event list work according
to the FIFO principle.

User audit trail is defined according to the selected set of requirements from IEEE
1686. The logging is based on predefined usernames or user categories. The user
audit trail events are supported in IEC 61850-8-1, PCM600, LHMI and WHMI.

Table 7: Audit trail events


Audit trail event Description
Configuration change Configuration files changed
Firmware change
Setting group remote User changed setting group remotely
Table continues on next page

RET615 19
Application Manual
Section 2 1YHT530003D05 C
RET615 overview

Audit trail event Description


Setting group local User changed setting group locally
Control remote DPC object control remote
Control local DPC object control local
Test on Test mode on
Test off Test mode off
Setting commit Settings have been changed
Time change
View audit log Administrator accessed audit trail
Login
Logout
Firmware reset Reset issued by user or tool
Audit overflow Too many audit events in the time period

PCM600 Event Viewer can be used to view the audit trail events together with
normal events. Since only the administrator has the right to read audit trail,
authorization must be properly configured in PCM600. The audit trail cannot be
reset but PCM600 Event Viewer can filter data. Some of the audit trail events are
interesting also as normal process events.

To expose the audit trail events also as normal process events,


define the level parameter via Configuration/Authorization/
Authority logging.

Table 8: Comparison of authority logging levels


Audit trail event Authority logging level
Configurati Setting Setting Settings All
None on change group group, edit
control
Configuration change ● ● ● ● ●
Firmware change ● ● ● ● ●
Setting group remote ● ● ● ●
Setting group local ● ● ● ●
Control remote ● ● ●
Control local ● ● ●
Test on ● ● ●
Test off ● ● ●
Setting commit ● ●
Time change ●
View audit log ●
Login ●
Table continues on next page

20 RET615
Application Manual
1YHT530003D05 C Section 2
RET615 overview

Audit trail event Authority logging level


Logout ●
Firmware reset ●
Audit overflow ●

2.7 Communication

The IED supports a range of communication protocols including IEC 61850, IEC
60870-5-103 and Modbus®. Operational information and controls are available
through these protocols. However, some communication functionality, for
example, horizontal communication between the IEDs, is only enabled by the IEC
61850 communication protocol.

The IEC 61850 communication implementation supports all monitoring and


control functions. Additionally, parameter settings, disturbance recordings and
fault records can be accessed using the IEC 61850 protocol. Disturbance recordings
are available to any Ethernet-based application in the standard COMTRADE file
format. The IED can send and receive binary signals from other IEDs (so-called
horizontal communication) using the IEC61850-8-1 GOOSE profile, where the
highest performance class with a total transmission time of 3 ms is supported.
Furthermore, the IED supports sending and receiving of analog values using
GOOSE messaging. The IED meets the GOOSE performance requirements for
tripping applications in distribution substations, as defined by the IEC 61850
standard. The IED can simultaneously report events to five different clients on the
station bus.

The IED can support five simultaneous clients. If PCM600 reserves one client
connection, only four client connections are left, for example, for IEC 61850 and
Modbus.

All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The IED can be connected to Ethernet-
based communication systems via the RJ-45 connector (100Base-TX) or the fibre-
optic LC connector (100Base-FX).

For the correct operation of redundant loop topology, it is essential that the external
switches in the network support the RSTP protocol and that it is enabled in the
switches. Otherwise, connecting the loop topology can cause problems to the
network. The IED itself does not support link-down detection or RSTP. The ring
recovery process is based on the aging of the MAC addresses, and the link-up/link-
down events can cause temporary breaks in communication. For a better
performance of the self-healing loop, it is recommended that the external switch
furthest from the IED loop is assigned as the root switch (bridge priority = 0) and
the bridge priority increases towards the IED loop. The end links of the IED loop
can be attached to the same external switch or to two adjacent external switches. A
self-healing Ethernet ring requires a communication module with at least two
Ethernet interfaces for all IEDs.

RET615 21
Application Manual
Section 2 1YHT530003D05 C
RET615 overview

Client A Client B

Network A
Network B

Managed Ethernet switch Managed Ethernet switch


with RSTP support with RSTP support

GUID-283597AF-9F38-4FC7-B87A-73BFDA272D0F V3 EN

Figure 6: Self-healing Ethernet ring solution

The Ethernet ring solution supports the connection of up to 30


IEDs. If more than 30 IEDs are to be connected, it is recommended
that the network is split into several rings with no more than 30
IEDs per ring. Each IED has a 50-μs store-and-forward delay, and
to fullfill the performance requirements for fast horizontal
communication, the ring size is limited to 30 IEDs.

2.7.1 Ethernet redundancy


IEC 61850 specifies a network redundancy scheme that improves the system
availability for substation communication. It is based on two complementary
protocols defined in the IEC 62439-3 standard: parallel redundancy protocol PRP
and high-availability seamless redundancy HSR protocol. Both the protocols rely
on the duplication of all transmitted information via two Ethernet ports for one
logical network connection. Therefore, both are able to overcome the failure of a
link or switch with a zero-switchover time, thus fulfilling the stringent real-time
requirements for the substation automation horizontal communication and time
synchronization.

PRP specifies that each device is connected in parallel to two local area networks.
HSR applies the PRP principle to rings and to the rings of rings to achieve cost-
effective redundancy. Thus, each device incorporates a switch element that
forwards frames from port to port. The HSR/PRP option is available for REF615,
REM615, RET615 and REU615.

22 RET615
Application Manual
1YHT530003D05 C Section 2
RET615 overview

PRP
Each PRP node, called a doubly attached node with PRP (DANP), is attached to
two independent LANs operated in parallel. These parallel networks in PRP are
called LAN A and LAN B. The networks are completely separated to ensure failure
independence, and they can have different topologies. Both networks operate in
parallel, thus providing zero-time recovery and continuous checking of redundancy
to avoid communication failures. Non-PRP nodes, called singly attached nodes
(SANs), are either attached to one network only (and can therefore communicate
only with DANPs and SANs attached to the same network), or are attached through
a redundancy box, a device that behaves like a DANP.

COM600
SCADA

Ethernet switch Ethernet switch


IEC 61850 PRP

REF615 REF620 RET620 REM620 REF615


GUID-334D26B1-C3BD-47B6-BD9D-2301190A5E9D V1 EN

Figure 7: PRP solution

In case a laptop or a PC workstation is connected as a non-PRP node to one of the


PRP networks, LAN A or LAN B, it is recommended to use a redundancy box
device or an Ethernet switch with similar functionality between the PRP network
and SAN to remove additional PRP information from the Ethernet frames. In some
cases, default PC workstation adapters are not able to handle the maximum-length
Ethernet frames with the PRP trailer.

There are different alternative ways to connect a laptop or a workstation as SAN to


a PRP network.

• Via an external redundancy box (RedBox) or a switch capable of connecting to


PRP and normal networks
• By connecting the node directly to LAN A or LAN B as SAN
• By connecting the node to the IED interlink port

RET615 23
Application Manual
Section 2 1YHT530003D05 C
RET615 overview

HSR
HSR applies the PRP principle of parallel operation to a single ring, treating the
two directions as two virtual LANs. For each frame sent, a node, DANH, sends two
frames, one over each port. Both frames circulate in opposite directions over the
ring and each node forwards the frames it receives, from one port to the other.
When the originating node receives a frame sent to itself, it discards that to avoid
loops; therefore, no ring protocol is needed. Individually attached nodes, SANs,
such as laptops and printers, must be attached through a “redundancy box” that acts
as a ring element. For example, a 615 series IED with HSR support can be used as
a redundancy box.

GUID-207430A7-3AEC-42B2-BC4D-3083B3225990 V1 EN

Figure 8: HSR solution

24 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Section 3 RET615 standard configurations

3.1 Standard configurations

RET615 is available in eight alternative standard configurations. The standard


signal configuration can be altered by means of the graphical signal matrix or the
graphical application functionality of the Protection and Control IED Manager
PCM600. Further, the application configuration functionality of PCM600 supports
the creation of multi-layer logic functions utilizing various logical elements
including timers and flip-flops. By combining protection functions with logic
function blocks the IED configuration can be adapted to user specific application
requirements.

Table 9: Standard configurations


Description Std. conf.
Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection
A
for the high-voltage (HV) side
Three-phase transformer differential protection for two-winding transformers, numerical restricted earth-fault protection
B
for the low-voltage (LV) side
Three-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-
C
fault protection for the high-voltage (HV) side
Three-phase transformer differential protection for two-winding transformers, high-impedance based restricted earth-
D
fault protection for the low-voltage (LV) side
Three-phase transformer differential protection with voltage protection for two-winding transformers, numerical
E
restricted earth-fault protection for the high-voltage (HV) side
Three-phase transformer differential protection with voltage protection for two-winding transformers, numerical
F
restricted earth-fault protection for the low-voltage (LV) side
Three-phase transformer differential protection with voltage protection for two-winding transformers, high-impedance
G
based restricted earth-fault protection for the high-voltage (HV) side
Three-phase transformer differential protection with voltage protection for two-winding transformers, high-impedance
H
based restricted earth-fault protection for the low-voltage (LV) side
Three-phase transformer differential protection with voltage protection for two-winding transformers J
Transformer backup protection with voltage protection K

Table 10: Supported functions


Function A B C D E F G H J K
Protection
Three-phase non-directional overcurrent
x HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV)
protection, low stage, instance 1
Three-phase non-directional overcurrent
● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV)
protection, low stage, instance 2
Table continues on next page

RET615 25
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Function A B C D E F G H J K
Three-phase non-directional overcurrent
● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV)
protection, high stage, instance 1
Three-phase non-directional overcurrent
● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV)
protection, high stage, instance 2
Three-phase non-directional overcurrent
● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV)
protection, instantaneous stage, instance 1
Three-phase non-directional overcurrent
● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV)
protection, instantaneous stage, instance 2
Non-directional earth-fault protection, low ● ● ● ● ●
stage, instance 1 HV)1) HV)2) HV)1) HV)2) HV)2)

Non-directional earth-fault protection, low ●


stage, instance 2 ● LV)3) LV)4) ● LV)3) ● LV)4) ● LV)4)

Non-directional earth-fault protection, high ● ● ● ● ●


stage, instance 1 HV)1) HV)2) HV)1) HV)2) HV)2)

Non-directional earth-fault protection, high ●


stage, instance 2 ● LV)3) ● LV)4) ● LV)3) LV)4) ● LV)4)

Negative-sequence overcurrent protection,


● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV)
instance 1
Negative-sequence overcurrent protection,
● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV)
instance 2
Negative-sequence overcurrent protection,
● HV)
instance 3
Negative-sequence overcurrent protection,
● LV)
instance 4
Residual overvoltage protection, instance 1 ● ● ● ●
HV)5) ● HV)5) HV)5) HV)5) HV)5)

Residual overvoltage protection, instance 2 ● ● ● ●


HV)5) ● HV)5) HV)5) HV)5) HV)5)

Three-phase undervoltage protection, instance 1 ● HV) ● HV) ● HV) ● HV) ● HV)


Three-phase undervoltage protection, instance 2 ● HV) ● HV) ● HV) ● HV) ● HV)
Three-phase overvoltage protection, instance 1 ● HV) ● HV) ● HV) ● HV) ● HV)
Three-phase overvoltage protection, instance 2 ● HV) ● HV) ● HV) ● HV) ● HV)
Positive-sequence undervoltage protection,
● HV) ● HV) ● HV) ● HV) ● HV)
instance 1
Positive-sequence undervoltage protection,
● HV) ● HV) ● HV) ● HV) ● HV)
instance 2
Negative-sequence overvoltage protection,
● HV) ● HV) ● HV) ● HV) ● HV)
instance 1
Negative-sequence overvoltage protection,
● HV) ● HV) ● HV) ● HV) ● HV)
instance 2
Three-phase thermal overload protection for
● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV)
power transformers, two time constants
Stabilized and instantaneous differential
● ● ● ● ● ● ● ● ●
protection for 2W –transformers
Numerical stabilized low impedance restricted
● HV) ● LV)6) ● HV) ● LV)6) ● HV)
earth-fault protection
Table continues on next page

26 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Function A B C D E F G H J K
High impedance based restricted earth-fault ●
protection ● HV) LV)7) ● HV) ● LV)7) ● HV)

Circuit breaker failure protection ● ● ● ● ● ● ● ● ●


HV)2) HV)2) HV)2) HV)2) HV)2) ● HV)2) HV)2) HV)2) HV)2) HV)2)

Master trip, instance 1 ● ● ● ● ● ● ● ● ● ●


Master trip, instance 2 ● ● ● ● ● ● ● ● ● ●
Arc protection, instance 1 o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8)
Arc protection, instance 2 o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8)
Arc protection, instance 3 o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8) o LV)8)

Multi-purpose protection, instance 1 9) o 10) o 10) o 10) o 10) o 10)

Multi-purpose protection, instance 2 9) o 10) o 10) o 10) o 10) o 10)

Multi-purpose protection, instance 3 9) o 10) o 10) o 10) o 10) o 10)

Multi-purpose protection, instance 4 9) o 10) o 10) o 10) o 10) o 10)

Multi-purpose protection, instance 5 9) o 10) o 10) o 10) o 10) o 10)

Multi-purpose protection, instance 6 9) o 10) o 10) o 10) o 10) o 10)


Control
Circuit-breaker control ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV)
Disconnector control, instance 1 ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10)
Disconnector control, instance 2 ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10)
Earthing switch control ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10)
Disconnector position indication, instance 1 ● ● ● ● ● ● ● ● ● ●
Disconnector position indication, instance 2 ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10)
Disconnector position indication, instance 3 ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10)
Earthing switch indication, instance 1 ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10)
Earthing switch indication, instance 2 ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10) ● 10)
Tap changer position indication ● ● ● ● ● ● ● ● ● ●
Condition monitoring
Circuit-breaker condition monitoring ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV)
Trip circuit supervision, instance 1 ● ● ● ● ● ● ● ● ● ●
Trip circuit supervision, instance 2 ● ● ● ● ● ● ● ● ● ●
Fuse failure supervision ● ● ● ● ●
Runtime counter for machines and devices ● ● ● ● ● ● ● ● ● ●
Measurement
Disturbance recorder ● ● ● ● ● ● ● ● ● ●
Three-phase current measurement, instance 1 ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV)
Three-phase current measurement, instance 2 ● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV) ● LV)
Sequence current measurement, instance 1 ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV) ● HV)
Sequence current measurement, instance 2 ● LV) ● LV)
Residual current measurement, instance 1 ● HV) ● HV) ● HV) ● HV) ● HV) ● HV)
Table continues on next page

RET615 27
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Function A B C D E F G H J K
Residual current measurement, instance 2 ● LV) ● LV) ● LV) ● LV)
Three-phase voltage measurement ● HV) ● HV) ● HV) ● HV) ● HV)
Residual voltage measurement ● HV) ● HV) ● HV) ● HV) ● HV)
Sequence voltage measurement ● HV) ● HV) ● HV) ● HV) ● HV)
Three-phase power and energy measurement ● HV) ● HV) ● HV) ● HV) ● HV)
RTD/mA measurement o o o o o
● = included, ○ = optional at the time of order
HV = The function block is to be used on the high voltage side in the application
LV = The function block is to be used on the low voltage side in the application

1) Io selectable by parameter and default value is Io measured


2) Io calculated is always used
3) IoB selectable by parameter, IoB measured as default
4) IoB calculated is always used
5) Uo selectable by parameter, Uo measured as default
6) IoB measured and 3IB are always used
7) IoB measured is always used
8) IoB calculated and 3IB are always used
9) Multi-purpose protection is used, for example, RTD/mA based protection
10) Available in IED and SMT but not connected to anything in logic.

3.1.1 Addition of control functions for primary devices and the


use of binary inputs and outputs
If extra control functions intended for controllable primary devices are added to the
configuration, additional binary inputs and/or outputs are needed to complement
the standard configuration.

If the number of inputs and/or outputs in a standard configuration is not sufficient,


it is possible either to modify the chosen IED standard configuration in order to
release some binary inputs or binary outputs which have originally been configured
for other purposes, or to integrate an external input/output module, for example
RIO600, to the IED.

The external I/O module’s binary inputs and outputs of can be used for the less time-
critical binary signals of the application. The integration enables releasing some
initially reserved binary inputs and outputs of the IED’s standard configuration.

The suitability of the IED’s binary outputs which have been selected for primary
device control should be carefully verified, for example make and carry and
breaking capacity. If the requirements for the primary device control circuit are not
met, using external auxiliary relays should be considered.

3.1.2 LED functionality


The IED has dynamic programmable LEDs. The presentation of the LEDs in this
manual differs from the actual function blocks in the configurations.

28 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-4576631D-C686-454F-8CF0-DC654779B178 V1 EN

Figure 9: Drawing symbol used in the manual and the default connection of
the LED function blocks in the configurations

RET615 29
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.2 Connection diagrams

GUID-529F6F95-5742-4D6F-8C55-04F6C14BFD94 V2 EN

Figure 10: Connection diagram for the A and K configurations

30 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-80F82A38-4519-4C09-A25D-86131D51331B V2 EN

Figure 11: Connection diagram for the B configuration

RET615 31
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-32E5D770-0A2D-4FF3-9EAF-E7A82DB8A66C V2 EN

Figure 12: Connection diagram for the C and J configurations

32 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-FC955C0D-4BF9-40A8-B953-429DE884FFE1 V2 EN

Figure 13: Connection diagram for the D and J configurations

RET615 33
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-D26C5FA8-D7E4-4959-AA36-B77D1A53392C V1 EN

Figure 14: Connection diagram for the E configuration

34 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-787C00E6-BEC2-4612-8183-195E01D9F5EF V

Figure 15: Connection diagram for the F configuration

RET615 35
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-AE41CEEF-C6E8-4292-8F0A-A5B962EBBC9C V1 EN

Figure 16: Connection diagram for the G configuration

36 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-4F252355-C97B-4110-8AAF-EB9816A13113 V1 EN

Figure 17: Connection diagram for the H configuration

RET615 37
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-59EE9058-5928-4E74-A3C1-3F2C9B6D3EB1 V1 EN

Figure 18: Connection diagram for the E, F, G and H configurations


(transformer current differential protection with phase-to-earth
voltage protection and measurement)

3.3 Presentation of standard configurations

Functional diagrams
The functional diagrams describe the IED's functionality from the protection,
measuring, condition monitoring, disturbance recording, control and interlocking
perspective. Diagrams show the default functionality with simple symbol logics
forming principle diagrams. The external connections to primary devices are also
shown, stating the default connections to measuring transformers. The positive
measuring direction of directional protection functions is towards the outgoing feeder.

The functional diagrams are divided into sections with each section constituting
one functional entity. The external connections are also divided into sections. Only
the relevant connections for a particular functional entity are presented in each
section.

38 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Protection function blocks are part of the functional diagram. They are identified
based on their IEC 61850 name but the IEC based symbol and the ANSI function
number are also included. Some function blocks, such as PHHPTOC, are used
several times in the configuration. To separate the blocks from each other, the IEC
61850 name, IEC symbol and ANSI function number are appended with a running
number, that is an instance number, from one upwards. If the block has no suffix
after the IEC or ANSI symbol, the function block has been used, that is,
instantiated, only once. The IED’s internal functionality and the external
connections are separated with a dashed line presenting the IED’s physical casing.

Signal Matrix and Application Configuration


With Signal Matrix and Application Configuration in PCM600, it is possible to
modify the standard configuration according to the actual needs. The IED is
delivered from the factory with default connections described in the functional
diagrams for binary inputs, binary outputs, function-to-function connections and
alarm LEDs. The Signal Matrix is used for GOOSE signal input engineering and
for making cross-references between the physical I/O signals and the function
blocks. The Signal Matrix tool cannot be used for adding or removing function
blocks, for example, GOOSE receive function blocks. The Application
Configuration tool is used for these kind of operations. If a function block is
removed with Application Configuration, the function related data disappears from
the menus as well as from the 61850 data model, with the exception of some basic
function blocks, which are mandatory and thus cannot be removed from the IED
configuration by removing them from the Application Configuration.

3.4 Standard configuration A

3.4.1 Applications
The standard configuration includes three-phase transformer differential protection
for two-winding transformers, numerical restricted earth-fault protection for the high-
voltage (HV) side. The standard configuration is mainly intended for protection of
the power transformer between current transformers.

The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.

RET615 39
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.4.2 Functions
Table 11: Functions included in the standard configuration A
Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
PHLPTOC1 3I> (1) 51P-1 (1)
protection, low stage, instance 1
Three-phase non-directional overcurrent
PHLPTOC2 3I> (2) 51P-1 (2)
protection, low stage, instance 2
Three-phase non-directional overcurrent
PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent
PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent
PHIPTOC1 3I>>> (1) 50P/51P (1)
protection, instantaneous stage, instance 1
Three-phase non-directional overcurrent
PHIPTOC2 3I>>> (2) 50P/51P (2)
protection, instantaneous stage, instance 2
Non-directional earth-fault protection, low
EFLPTOC1 Io> (1) 51N-1 (1)
stage, instance 1
Non-directional earth-fault protection, high
EFHPTOC1 Io>> (1) 51N-2 (1)
stage, instance 1
Negative-sequence overcurrent protection,
NSPTOC1 I2> (1) 46 (1)
instance 1
Negative-sequence overcurrent protection,
NSPTOC2 I2> (2) 46 (2)
instance 2
Three-phase thermal overload protection for
T2PTTR1 3Ith>T 49T
power transformers, two time constants
Stabilized and instantaneous differential
TR2PTDF1 3dI>T 87T
protection for 2W –transformers
Numerical stabilized low impedance restricted
LREFPNDF1 dIoLo> 87NL
earth-fault protection
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)
Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)
Multi-purpose protection, instance 1 MAPGAPC1 MAP (1) MAP (1)
Multi-purpose protection, instance 2 MAPGAPC2 MAP (2) MAP (2)
Multi-purpose protection, instance 3 MAPGAPC3 MAP (3) MAP (3)
Multi-purpose protection, instance 4 MAPGAPC4 MAP (4) MAP (4)
Multi-purpose protection, instance 5 MAPGAPC5 MAP (5) MAP (5)
Multi-purpose protection, instance 6 MAPGAPC6 MAP (6) MAP (6)
Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
Table continues on next page

40 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Function IEC 61850 IEC 60617 IEC-ANSI


I <-> O DCC I <-> O DCC
Disconnector control, instance 1 DCXSWI1
(1) (1)
I <-> O DCC I <-> O DCC
Disconnector control, instance 2 DCXSWI2
(2) (2)
Earthing switch control ESXSWI1 I <-> O ESC I <-> O ESC
Disconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
Disconnector position indication, instance 3 DCSXSWI3 I <-> O DC (3) I <-> O DC (3)
Earthing switch indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
Earthing switch indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Tap changer position indication TPOSSLTC1 TPOSM 84M
Condition monitoring
Circuit-breaker condition monitoring SSCBR1 CBCM CBCM
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Runtime counter for machines and devices MDSOPT1 OPTS OPTM
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement, instance 1 CMMXU1 3I 3I
Three-phase current measurement, instance 2 CMMXU2 3I(B) 3I(B)
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement, instance 1 RESCMMXU1 Io In
RTD/mA measurement XRGGIO130 X130 (RTD) X130 (RTD)

3.4.2.1 Default I/O connections


Table 12: Default connections for binary inputs
Binary input Description Connector pins
X110-BI1 Blocking of O/C high stage (high voltage) and X110-1,2
instantaneous stage (low voltage)
X110-BI2 External protection trip X110-3,4
X110-BI3 Circuit breaker low gas pressure indication X110-5,6
X110-BI4 Circuit breaker spring charged indication X110-7,6
X110-BI5 High-voltage side disconnector closed X110-8,9
X110-BI6 High-voltage side disconnector open X110-10,9
X110-BI7 High-voltage side circuit breaker closed X110-11,12
X110-BI8 High-voltage side circuit breaker open X110-13,12
X130-BI1 BCD sign bit (tap changer position) X130-1,2
X130-BI2 BCD bit 1 LSB X130-2,3
X130-BI3 BCD bit 2 X130-4,5
Table continues on next page

RET615 41
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Binary input Description Connector pins


X130-BI4 BCD bit 3 X130-5,6
X130-BI5 BCD bit 4 X130-7,8
X130-BI6 BCD bit 5 MSB X130-8,9

Table 13: Default connections for RDT/mA inputs


Binary input Description Connector pins
X130-AI1 X130-1,2
X130-AI2 X130-3,4
X130-AI3 Ambient temperature X130-5,6,11c
X130-AI4 X130-7,8,11c
X130-AI5 X130-9,10,11c
X130-AI6 X130-13,14,12c
X130-AI7 X130-15,16,12c
X130-AI8 X130-17,18,12c

Table 14: Default connections for binary outputs


Binary output Description Connector pins
X100-PO1 Close high-voltage circuit breaker X100-6,7
X100-PO2 Breaker failure backup trip to upstream breaker X100-8,9
X100-SO1 General start indication X100-10,11,(12)
X100-SO2 General operate indication X100-13,14
X100-PO3 Open circuit breaker/trip coil 1 high voltage X100-15-19
X100-PO4 Open circuit breaker/trip coil 2 low voltage X100-20-24
X110-SO1 Overcurrent operate alarm X110-14,15,16
X110-SO2 Differential protection operate alarm X110-17,18,19
X110-SO3 Earth fault operate alarm X110-20,21,22
X110-SO4 Thermal overload and negative phase-sequence X110-23,24
protection operate alarm

Table 15: Default connections for LEDs


LED Description
1 Transformer differential protection biased stage operate
2 Transformer differential protection instantaneous stage operate
3 Non-directional overcurrent protection operate
4 Restricted earth-fault protection operate
5 Earth fault protection operated
6 Circuit failure protection backup trip operated
7 NPS or thermal overload protection operated
Table continues on next page

42 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

LED Description
8 Disturbance recorder triggered
9 TCS, fuse failure, measuring circuit fault or circuit breaker supervision
10 Arc protection operate
11 Protection trip from external device

3.4.2.2 Default disturbance recorder settings

Table 16: Default analog channel selection and text settings


Channel Selection and text
1 IL1
2 IL2
3 IL3
4 IL1B
5 IL2B
6 IL3B
7 Io
8 -
9 -
10 -
11 -
12 -

Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.

3.4.3 Functional diagrams


The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.

The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings.

The analog channels are assigned to different functions. The common signal
marked with 3I represents the three phase currents of the high-voltage side of the
transformer and 3IB represents the three phase currents of the low-voltage side of

RET615 43
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

the transformer. The signal marked with Io represents the neutral current measured
between the start point of the transformer and grounding on the high voltage side.

3.4.3.1 Functional diagrams for protection

The functional diagrams describe the IED’s protection functionality in detail and
picture the factory set default connections.

GUID-924EE5B6-2E53-4547-AFEC-2BF37660AA66 V2 EN

Figure 19: Stabilized and instantaneous differential protection for 2W–


transformers

The stabilized and instantaneous differential protection for 2W–transformers


(TR2PTDF1) provides protection of power transformer unit including, for
example, winding short-circuit and interturn faults. The IED compares the phase
currents on both sides of the object to be protected. If the differential current of the
phase currents in one of the phases exceed the setting of the stabilized operation
characteristic or the instantaneous protection stage of the function, the function
provides an operate signal.

For transformers having an on-line tap changer, the tap position information is
recommended to be used in differential protection, as the ratio difference of tap
changer movements can be corrected in TR2PTDF.

44 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

All operate signals are connected to the Master Trip 1 and 2 and also to the alarm
LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for
instantaneous high-stage of the differential protection.

GUID-1C4B6EFB-C39F-4D99-832A-F141FFBCBA9F V3 EN

Figure 20: Overcurrent and short-circuit protection

RET615 45
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Three stages for both high-voltage and low-voltage sides as a total of six
overcurrent stages are offered for overcurrent and short-circuit protection. The high-
voltage side high stage (PHHPTOC1) can be blocked by energizing the binary
input 1 (X110:1-2) or by starting the high stage of the low-voltage side
(PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by
activating the binary input (X110_BI1).

A selective backup overcurrent protection can be achieved by using blockings


between high-voltage side and low-voltage side overcurrent stages. This kind of
blocking scheme enables coordinated overlapping of overcurrent protection zones.

The operate of the overcurrent protection functions is connected to the output SO1
(X110:14-15-16). This output is used for giving a specific alarm of the overcurrent
protection operation.

GUID-16AE196B-0ED9-478B-91FB-70CF4A9C0B23 V2 EN

Figure 21: Non-directional earth-fault protection

Two stages are offered for non-directional earth-fault protection. The earth-fault
protection measures the neutral current of the high-voltage side.

All operate signals are connected to the Master Trip as well as to the alarm LEDs.
LED 5 is used for non-directional earth-fault protection operate indication.

GUID-A8AB50BA-0D0A-454D-860C-2C721B3793F3 V2 EN

Figure 22: Restricted low-impedance earth-fault protection

46 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

The configuration includes restricted low-impedance earth-fault protection function


for high-voltage side of two-winding power transformers (LREFPNDF1). The
numerical differential current stage operates exclusively on earth faults occurring
in the protected area, that is, in the area between the phase and neutral current
transformers. An earth fault in this area appears as a differential current between
the residual current of the phase currents and the neutral current of the conductor
between the star-point of the transformer and earth.

GUID-BEC39E21-713A-434C-88E5-702CA4622699 V2 EN

Figure 23: Negative-sequence overcurrent protection

NSPTOC is designed for negative-phase sequence protection whenever the


operating characteristic is appropriate. It is applied for the protection of
transformers against thermal stress and damage.

NSPTOC1 measures negative-sequence current from the high-voltage side and


NSPTOC2 from the low-voltage side.

GUID-B4800F23-400A-40DF-BAED-A99B116638A5 V3 EN

Figure 24: Three-phase thermal overload protection for power transformers

Three-phase thermal overload protection for power transformers (T2PTTR1)


provides indication on overload situations. The operate signal of the thermal
overload protection is connected to the Master Trip 2. LED 7 is used for the

RET615 47
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

thermal overload protection alarm indication, the same as for negative-sequence


overcurrent protection operate indication.

GUID-C9527B95-0F59-42C3-A0D1-B468DD54B465 V2 EN

Figure 25: Circuit-breaker failure protection

The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input
by a number of different protection stages in the IED. CCBRBRF1 offers different
operating modes associated with the circuit-breaker position and the measured
phase and residual currents.

CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for retripping both the high-voltage and low-voltage side circuit
breakers through Master Trip 1 and 2. The TRBU operate output signal is
connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU)
operate indication.

48 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-42911654-7FC8-4A91-8E52-89E062039C69 V2 EN

Figure 26: Arc protection

Arc protection (ARCSARC1...3) is included as an optional function.

The arc protection offers individual function blocks for three arc sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.

RET615 49
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.4.3.2 Functional diagrams for disturbance recorder and supervision


functions

GUID-96BB51D1-DB86-49BE-A5FE-25B304403C59 V2 EN

Figure 27: Disturbance recorder

All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, the ARC protection
signals and the four binary inputs from X110 are also connected.

50 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-F8B12B36-DF24-4907-8288-814A7C34D70E V2 EN

Figure 28: Trip circuit supervision

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.

By default it is expected that there is no external resistor in the


circuit breaker tripping coil circuit connected parallel with circuit
breaker normally open auxiliary contact.

RET615 51
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.4.3.3 Functional diagrams for control and interlocking

GUID-FCB8739C-C3C7-4994-BAC6-18BA323962F7 V2 EN

Figure 29: Master Trip

The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op are connected directly to the output PO3
(X100:15-19).

TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.

The external trip indication is connected also to the alarm LED 11.

52 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-0D5A94B8-8D06-4710-8B97-31D9C05FAAA4 V2 EN

Figure 30: Disconnector position indication

There are two types of disconnector and earthing switch blocks available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration logic. If controllable operation is preferred, the controllable
type of disconnector and earthing switch blocks can be used instead of the status
only type. The connection and configuration of the control blocks can be done
using PCM600.

The binary inputs 5 and 6 of the additional card X110 are used for busbar
disconnector (DCSXSWI1) or circuit-breaker truck position indication.

Table 17: Device positions indicated by binary inputs 5 and 6


Primary device position Input to be energized
Input 5 (X110:8-9) Input 6 (X110:10-9)
Busbar disconnector closed x
Busbar disconnector open x
Circuit breaker truck in service position x
Circuit breaker truck in test position x

The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
the disconnector position status and the statuses of the master trip logics and gas
pressure alarm and circuit-breaker spring charging. The OKPOS output from the
DCSXSWI block defines if the disconnector or the breaker truck is definitely either

RET615 53
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

open (in test position) or close (in service position). This, together with non-active
trip signal and non-active gas pressure alarm, activates the close-enable signal to
the circuit-breaker control function block. The open operation is always enabled.

The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.

If the ENA_CLOSE and BLK_CLOSE signals are completely


removed from the breaker control function block CBXCBR with
PCM600, the function assumes that the breaker close commands
are allowed continuously.

The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 9.

54 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-EF27034F-786A-460C-9350-6A2E02C4A3BC V3 EN

Figure 31: Common alarm/indication 1 and 2

The signal outputs from the IED are connected to give dedicated information on:

• Start of any protection function SO1 (X100:10-12)


• Operation (trip) of any protection function SO2 (X100:13-15)
• Operation (trip) of any stage of the overcurrent protection function SO1
(X110:14-15-16)
• Operation (trip) of differential protection function SO2 (X110:17-18-19)
• Operation (trip) of any stage of the earth-fault protection function SO3
(X110:20-21-22)
• Operation (trip) of thermal or current negative-sequence protection function
SO4 (X110:23-24)

TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining

RET615 55
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

ones not described in the functional diagram are available in PCM600 for
connection where applicable.

GUID-F78772E5-8513-4422-B928-5B6D7C97B828 V2 EN

Figure 32: Tap changer position indication

To increase the sensitivity of the stabilized differential function, the tap position
information from the tap changer is connected to the IED via the tap changer
position indication function TPOSSLTC1. TPOSSLTC1 is connected to the binary
inputs of the X130 BIO card or alternatively to the mA input of the RTD card.
TPOSSLTC1 uses binary-coded methods to generate the integer value of the tap
changer position.

3.5 Standard configuration B

3.5.1 Applications

The standard configuration includes three-phase transformer differential protection


for two-winding transformers and numerical restricted earth-fault protection for the
low-voltage (LV) side. The standard configuration is mainly intended for
protection of the power transformer between current transformers.

The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.

56 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

3.5.2 Functions

Table 18: Functions included in the standard configuration B


Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
PHLPTOC1 3I> (1) 51P-1 (1)
protection, low stage, instance 1
Three-phase non-directional overcurrent
PHLPTOC2 3I> (2) 51P-1 (2)
protection, low stage, instance 2
Three-phase non-directional overcurrent
PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent
PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent
PHIPTOC1 3I>>> (1) 50P/51P (1)
protection, instantaneous stage, instance 1
Three-phase non-directional overcurrent
PHIPTOC2 3I>>> (2) 50P/51P (2)
protection, instantaneous stage, instance 2
Non-directional earth-fault protection, low
EFLPTOC2 Io> (2) 51N-1 (2)
stage, instance 2
Non-directional earth-fault protection, high
EFHPTOC2 Io>> (2) 51N-2 (2)
stage, instance 2
Negative-sequence overcurrent protection,
NSPTOC1 I2> (1) 46 (1)
instance 1
Negative-sequence overcurrent protection,
NSPTOC2 I2> (2) 46 (2)
instance 2
Three-phase thermal overload protection for
T2PTTR1 3Ith>T 49T
power transformers, two time constants
Stabilized and instantaneous differential
TR2PTDF1 3dI>T 87T
protection for 2W –transformers
Numerical stabilized low impedance restricted
LREFPNDF1 dIoLo> 87NL
earth-fault protection
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)
Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)
Multi-purpose protection, instance 1 MAPGAPC1 MAP (1) MAP (1)
Multi-purpose protection, instance 2 MAPGAPC2 MAP (2) MAP (2)
Multi-purpose protection, instance 3 MAPGAPC3 MAP (3) MAP (3)
Multi-purpose protection, instance 4 MAPGAPC4 MAP (4) MAP (4)
Multi-purpose protection, instance 5 MAPGAPC5 MAP (5) MAP (5)
Multi-purpose protection, instance 6 MAPGAPC6 MAP (6) MAP (6)
Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
Table continues on next page

RET615 57
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Function IEC 61850 IEC 60617 IEC-ANSI


I <-> O DCC I <-> O DCC
Disconnector control, instance 1 DCXSWI1
(1) (1)
I <-> O DCC I <-> O DCC
Disconnector control, instance 2 DCXSWI2
(2) (2)
Earthing switch control ESXSWI1 I <-> O ESC I <-> O ESC
Disconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
Disconnector position indication, instance 3 DCSXSWI3 I <-> O DC (3) I <-> O DC (3)
Earthing switch indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
Earthing switch indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Tap changer position indication TPOSSLTC1 TPOSM 84M
Condition monitoring
Circuit-breaker condition monitoring SSCBR1 CBCM CBCM
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Runtime counter for machines and devices MDSOPT1 OPTS OPTM
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement, instance 1 CMMXU1 3I 3I
Three-phase current measurement, instance 2 CMMXU2 3I(B) 3I(B)
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement, instance 2 RESCMMXU2 Io(B) In(B)
RTD/mA measurement XRGGIO130 X130 (RTD) X130 (RTD)

3.5.2.1 Default I/O connections


Table 19: Default connections for binary inputs
Binary input Description Connector pins
X110-BI1 Blocking of O/C high stage (high voltage) and X110-1,2
instantaneous stage (low voltage)
X110-BI2 External protection trip X110-3,4
X110-BI3 Circuit breaker low gas pressure indication X110-5,6
X110-BI4 Circuit breaker spring charged indication X110-7,6
X110-BI5 High-voltage side disconnector closed X110-8,9
X110-BI6 High-voltage side disconnector open X110-10,9
X110-BI7 High-voltage side circuit breaker closed X110-11,12
X110-BI8 High-voltage side circuit breaker open X110-13,12
X130-BI1 BCD sign bit (tap changer position) X130-1,2
X130-BI2 BCD bit 1 LSB X130-2,3
X130-BI3 BCD bit 2 X130-4,5
Table continues on next page

58 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Binary input Description Connector pins


X130-BI4 BCD bit 3 X130-5,6
X130-BI5 BCD bit 4 X130-7,8
X130-BI6 BCD bit 5 MSB X130-8,9

Table 20: Default connections for RDT/mA inputs


Binary input Description Connector pins
X130-AI1 X130-1,2
X130-AI2 X130-3,4
X130-AI3 Ambient temperature X130-5,6,11c
X130-AI4 X130-7,8,11c
X130-AI5 X130-9,10,11c
X130-AI6 X130-13,14,12c
X130-AI7 X130-15,16,12c
X130-AI8 X130-17,18,12c

Table 21: Default connections for binary outputs


Binary output Description Connector pins
X100-PO1 Close high-voltage circuit breaker X100-6,7
X100-PO2 Breaker failure backup trip to upstream breaker X100-8,9
X100-SO1 General start indication X100-10,11,(12)
X100-SO2 General operate indication X100-13,14
X100-PO3 Open circuit breaker/trip coil 1 high voltage X100-15-19
X100-PO4 Open circuit breaker/trip coil 2 low voltage X100-20-24
X110-SO1 Overcurrent operate alarm X110-14,15,16
X110-SO2 Differential protection operate alarm X110-17,18,19
X110-SO3 Earth fault operate alarm X110-20,21,22
X110-SO4 Thermal overload and negative phase-sequence X110-23,24
protection operate alarm

Table 22: Default connections for LEDs


LED Description
1 Transformer differential protection biased stage operate
2 Transformer differential protection instantaneous stage operate
3 Non-directional overcurrent protection operate
4 Restricted earth-fault protection operate
5 Earth fault protection operated
6 Circuit failure protection backup trip operated
7 NPS or thermal overload protection operated
Table continues on next page

RET615 59
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

LED Description
8 Disturbance recorder triggered
9 TCS, fuse failure, measuring circuit fault or circuit breaker supervision
10 Arc protection operate
11 Protection trip from external device

3.5.2.2 Default disturbance recorder settings

Table 23: Default analog channel selection and text settings


Channel Selection and text
1 IL1
2 IL2
3 IL3
4 IL1B
5 IL2B
6 IL3B
7 IoB
8 -
9 -
10 -
11 -
12 -

Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.

3.5.3 Functional diagrams


The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.

The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings.

The analog channels are assigned to different functions. The common signal
marked with 3I represents the three phase currents of the high-voltage side of the
transformer and 3IB represents the three phase currents of the low-voltage side of

60 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

the transformer. The signal marked with IoB represents the neutral current
measured between the start point of the transformer and grounding on the low
voltage side.

3.5.3.1 Functional diagrams for protection

The functional diagrams describe the IED’s protection functionality in detail and
picture the factory set default connections.

GUID-B811E0D7-9BFE-4C6A-B275-4AE76A09300A V2 EN

Figure 33: Stabilized and instantaneous differential protection for 2W–


transformers

The stabilized and instantaneous differential protection for 2W–transformers


(TR2PTDF1) provides protection of power transformer unit including, for
example, winding short-circuit and interturn faults. The IED compares the phase
currents on both sides of the object to be protected. If the differential current of the
phase currents in one of the phases exceed the setting of the stabilized operation
characteristic or the instantaneous protection stage of the function, the function
provides an operate signal.

For transformers having an on-line tap changer, the tap position information is
recommended to be used in differential protection, as the ratio difference of tap
changer movements can be corrected in TR2PTDF.

RET615 61
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

All operate signals are connected to the Master Trip 1 and 2 and also to the alarm
LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for
instantaneous high-stage of the differential protection.

GUID-1C4B6EFB-C39F-4D99-832A-F141FFBCBA9F V3 EN

Figure 34: Overcurrent and short-circuit protection

62 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Three stages for both high-voltage and low-voltage sides as a total of six
overcurrent stages are offered for overcurrent and short-circuit protection. The high-
voltage side high stage (PHHPTOC1) can be blocked by energizing the binary
input 1 (X110:1-2) or by starting the high stage of the low-voltage side
(PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by
activating the binary input (X110_BI1).

A selective backup overcurrent protection can be achieved by using blockings


between high-voltage side and low-voltage side overcurrent stages. This kind of
blocking scheme enables coordinated overlapping of overcurrent protection zones.

The operate of the overcurrent protection functions is connected to the output SO1
(X110:14-15-16). This output is used for giving a specific alarm of the overcurrent
protection operation.

GUID-BEF98714-E04C-4ABF-B846-F8B76D498FC9 V2 EN

Figure 35: Non-directional earth-fault protection

Two stages are offered for non-directional earth-fault protection. The earth-fault
protection measures the neutral current of the low-voltage side.

All operate signals are connected to the Master Trip as well as to the alarm LEDs.
LED 5 is used for non-directional earth-fault protection operate indication.

GUID-CF15BA10-B412-4F4B-8A67-99BB35C5BC46 V2 EN

Figure 36: Restricted low-impedance earth-fault protection

RET615 63
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

The configuration includes restricted low-impedance earth-fault protection function


for low-voltage side of two-winding power transformers (LREFPNDF1). The
numerical differential current stage operates exclusively on earth faults occurring
in the protected area, that is, in the area between the phase and neutral current
transformers. An earth fault in this area appears as a differential current between
the residual current of the phase currents and the neutral current of the conductor
between the star-point of the transformer and earth.

GUID-9A441D12-9499-40BA-BB9A-6BD00E3CC8AC V2 EN

Figure 37: Negative-sequence overcurrent protection

NSPTOC is designed for negative-phase sequence protection whenever the


operating characteristic is appropriate. It is applied for the protection of
transformers against thermal stress and damage.

NSPTOC1 measures negative-sequence current from the high-voltage side and


NSPTOC2 from the low-voltage side.

GUID-D4CC39C0-F782-4E80-9949-2084BD3DE5A1 V1 EN

Figure 38: Three-phase thermal overload protection for power transformers

Three-phase thermal overload protection for power transformers (T2PTTR1)


provides indication on overload situations. The operate signal of the thermal
overload protection is connected to the Master Trip 2. LED 7 is used for the

64 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

thermal overload protection alarm indication, the same as for negative-sequence


overcurrent protection operate indication.

GUID-C4825123-0299-4788-83FA-452FD7974E2D V1 EN

Figure 39: Circuit-breaker failure protection

The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input
by a number of different protection stages in the IED. CCBRBRF1 offers different
operating modes associated with the circuit-breaker position and the measured
phase and residual currents.

CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for retripping both the high-voltage and low-voltage side circuit
breakers through Master Trip 1 and 2. The TRBU operate output signal is
connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU)
operate indication.

RET615 65
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-42911654-7FC8-4A91-8E52-89E062039C69 V2 EN

Figure 40: Arc protection

Arc protection (ARCSARC1...3) is included as an optional function.

The arc protection offers individual function blocks for three arc sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.

66 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

3.5.3.2 Functional diagrams for disturbance recorder and supervision


functions

GUID-7F4CB02E-A271-480F-B2C7-968CED79DA13 V1 EN

Figure 41: Disturbance recorder

All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, the ARC protection
signals and the four binary inputs from X110 are also connected.

RET615 67
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-F8B12B36-DF24-4907-8288-814A7C34D70E V2 EN

Figure 42: Trip circuit supervision

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.

By default it is expected that there is no external resistor in the


circuit breaker tripping coil circuit connected parallel with circuit
breaker normally open auxiliary contact.

68 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

3.5.3.3 Functional diagrams for control and interlocking

GUID-0DB6F455-4206-4FE0-8E13-574312D34CED V1 EN

Figure 43: Master Trip

The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op are connected directly to the output PO3
(X100:15-19).

TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.

The external trip indication is connected also to the alarm LED 11.

RET615 69
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-0D5A94B8-8D06-4710-8B97-31D9C05FAAA4 V2 EN

Figure 44: Disconnector position indication

There are two types of disconnector and earthing switch blocks available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration logic. If controllable operation is preferred, the controllable
type of disconnector and earthing switch blocks can be used instead of the status
only type. The connection and configuration of the control blocks can be done
using PCM600.

The binary inputs 5 and 6 of the additional card X110 are used for busbar
disconnector (DCSXSWI1) or circuit-breaker truck position indication.

Table 24: Device positions indicated by binary inputs 5 and 6


Primary device position Input to be energized
Input 5 (X110:8-9) Input 6 (X110:10-9)
Busbar disconnector closed x
Busbar disconnector open x
Circuit breaker truck in service position x
Circuit breaker truck in test position x

The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
the disconnector position status and the statuses of the master trip logics and gas
pressure alarm and circuit-breaker spring charging. The OKPOS output from the
DCSXSWI block defines if the disconnector or the breaker truck is definitely either

70 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

open (in test position) or close (in service position). This, together with non-active
trip signal and non-active gas pressure alarm, activates the close-enable signal to
the circuit-breaker control function block. The open operation is always enabled.

The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.

If the ENA_CLOSE and BLK_CLOSE signals are completely


removed from the breaker control function block CBXCBR with
PCM600, the function assumes that the breaker close commands
are allowed continuously.

The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 9.

RET615 71
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-91CE1A30-0BFB-4609-B2D3-8D468C38BE1F V1 EN

Figure 45: Common alarm/indication 1 and 2

The signal outputs from the IED are connected to give dedicated information on:

• Start of any protection function SO1 (X100:10-12)


• Operation (trip) of any protection function SO2 (X100:13-15)
• Operation (trip) of any stage of the overcurrent protection function SO1
(X110:14-15-16)
• Operation (trip) of any differential protection function SO2 (X110:17-18-19)
• Operation (trip) of any stage of the earth-fault protection function SO3
(X110:20-21-22)
• Operation (trip) of thermal or current negative-sequence protection function
SO4 (X110:23-24)

TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining

72 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

ones not described in the functional diagram are available in PCM600 for
connection where applicable.

GUID-F78772E5-8513-4422-B928-5B6D7C97B828 V2 EN

Figure 46: Tap changer position indication

To increase the sensitivity of the stabilized differential function, the tap position
information from the tap changer is connected to the IED via the tap changer
position indication function TPOSSLTC1. TPOSSLTC1 is connected to the binary
inputs of the X130 BIO card or alternatively to the mA input of the RTD card.
TPOSSLTC1 uses binary-coded methods to generate the integer value of the tap
changer position.

3.6 Standard configuration C

3.6.1 Applications

The standard configuration includes three-phase transformer differential protection


for two-winding transformers and high impedance based restricted earth-fault
protection for the high-voltage (HV) side. The standard configuration is mainly
intended for protection of the power transformer between current transformers.

The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.

RET615 73
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.6.2 Functions

Table 25: Functions included in the standard configuration C


Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
PHLPTOC1 3I> (1) 51P-1 (1)
protection, low stage, instance 1
Three-phase non-directional overcurrent
PHLPTOC2 3I> (2) 51P-1 (2)
protection, low stage, instance 2
Three-phase non-directional overcurrent
PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent
PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent
PHIPTOC1 3I>>> (1) 50P/51P (1)
protection, instantaneous stage, instance 1
Three-phase non-directional overcurrent
PHIPTOC2 3I>>> (2) 50P/51P (2)
protection, instantaneous stage, instance 2
Non-directional earth-fault protection, low
EFLPTOC1 Io> (1) 51N-1 (1)
stage, instance 1
Non-directional earth-fault protection, high
EFHPTOC1 Io>> (1) 51N-2 (1)
stage, instance 1
Negative-sequence overcurrent protection,
NSPTOC1 I2> (1) 46 (1)
instance 1
Negative-sequence overcurrent protection,
NSPTOC2 I2> (2) 46 (2)
instance 2
Three-phase thermal overload protection for
T2PTTR1 3Ith>T 49T
power transformers, two time constants
Stabilized and instantaneous differential
TR2PTDF1 3dI>T 87T
protection for 2W –transformers
High impedance based restricted earth-fault
HREFPDIF1 dIoHi> 87NH
protection
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)
Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)
Multi-purpose protection, instance 1 MAPGAPC1 MAP (1) MAP (1)
Multi-purpose protection, instance 2 MAPGAPC2 MAP (2) MAP (2)
Multi-purpose protection, instance 3 MAPGAPC3 MAP (3) MAP (3)
Multi-purpose protection, instance 4 MAPGAPC4 MAP (4) MAP (4)
Multi-purpose protection, instance 5 MAPGAPC5 MAP (5) MAP (5)
Multi-purpose protection, instance 6 MAPGAPC6 MAP (6) MAP (6)
Control
Table continues on next page

74 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Function IEC 61850 IEC 60617 IEC-ANSI


Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
I <-> O DCC I <-> O DCC
Disconnector control, instance 1 DCXSWI1
(1) (1)
I <-> O DCC I <-> O DCC
Disconnector control, instance 2 DCXSWI2
(2) (2)
Earthing switch control ESXSWI1 I <-> O ESC I <-> O ESC
Disconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
Disconnector position indication, instance 3 DCSXSWI3 I <-> O DC (3) I <-> O DC (3)
Earthing switch indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
Earthing switch indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Tap changer position indication TPOSSLTC1 TPOSM 84M
Condition monitoring
Circuit-breaker condition monitoring SSCBR1 CBCM CBCM
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Runtime counter for machines and devices MDSOPT1 OPTS OPTM
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement, instance 1 CMMXU1 3I 3I
Three-phase current measurement, instance 2 CMMXU2 3I(B) 3I(B)
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement, instance 1 RESCMMXU1 Io In
RTD/mA measurement XRGGIO130 X130 (RTD) X130 (RTD)

3.6.2.1 Default I/O connections


Table 26: Default connections for binary inputs
Binary input Description Connector pins
X110-BI1 Blocking of O/C high stage (high voltage) and X110-1,2
instantaneous stage (low voltage)
X110-BI2 External protection trip X110-3,4
X110-BI3 Circuit breaker low gas pressure indication X110-5,6
X110-BI4 Circuit breaker spring charged indication X110-7,6
X110-BI5 High-voltage side disconnector closed X110-8,9
X110-BI6 High-voltage side disconnector open X110-10,9
X110-BI7 High-voltage side circuit breaker closed X110-11,12
X110-BI8 High-voltage side circuit breaker open X110-13,12
X130-BI1 BCD sign bit (tap changer position) X130-1,2
X130-BI2 BCD bit 1 LSB X130-2,3
Table continues on next page

RET615 75
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Binary input Description Connector pins


X130-BI3 BCD bit 2 X130-4,5
X130-BI4 BCD bit 3 X130-5,6
X130-BI5 BCD bit 4 X130-7,8
X130-BI6 BCD bit 5 MSB X130-8,9

Table 27: Default connections for RDT/mA inputs


Binary input Description Connector pins
X130-AI1 X130-1,2
X130-AI2 X130-3,4
X130-AI3 Ambient temperature X130-5,6,11c
X130-AI4 X130-7,8,11c
X130-AI5 X130-9,10,11c
X130-AI6 X130-13,14,12c
X130-AI7 X130-15,16,12c
X130-AI8 X130-17,18,12c

Table 28: Default connections for binary outputs


Binary output Description Connector pins
X100-PO1 Close high-voltage circuit breaker X100-6,7
X100-PO2 Breaker failure backup trip to upstream breaker X100-8,9
X100-SO1 General start indication X100-10,11,(12)
X100-SO2 General operate indication X100-13,14
X100-PO3 Open circuit breaker/trip coil 1 high voltage X100-15-19
X100-PO4 Open circuit breaker/trip coil 2 low voltage X100-20-24
X110-SO1 Overcurrent operate alarm X110-14,15,16
X110-SO2 Differential protection operate alarm X110-17,18,19
X110-SO3 Earth fault operate alarm X110-20,21,22
X110-SO4 Thermal overload and negative phase-sequence X110-23,24
protection operate alarm

Table 29: Default connections for LEDs


LED Description
1 Transformer differential protection biased stage operate
2 Transformer differential protection instantaneous stage operate
3 Non-directional overcurrent protection operate
4 Restricted earth-fault protection operate
5 Earth fault protection operated
6 Circuit failure protection backup trip operated
Table continues on next page

76 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

LED Description
7 NPS or thermal overload protection operated
8 Disturbance recorder triggered
9 TCS, fuse failure, measuring circuit fault or circuit breaker supervision
10 Arc protection operate
11 Protection trip from external device

3.6.2.2 Default disturbance recorder settings

Table 30: Default analog channel selection and text settings


Channel Selection and text
1 IL1
2 IL2
3 IL3
4 IL1B
5 IL2B
6 IL3B
7 Io
8 -
9 -
10 -
11 -
12 -

Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.

3.6.3 Functional diagrams


The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.

The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings.

The analog channels are assigned to different functions. The common signal
marked with 3I represents the three phase currents of the high-voltage side of the

RET615 77
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

transformer and 3IB represents the three phase currents of the low-voltage side of
the transformer. The signal marked with Io represents the neutral current measured
between the start point of the transformer and grounding on the high voltage side.

3.6.3.1 Functional diagrams for protection

The functional diagrams describe the IED’s protection functionality in detail and
picture the factory set default connections.

GUID-CE6678E5-8383-4CB0-9F75-C1BA8B3662D1 V2 EN

Figure 47: Stabilized and instantaneous differential protection for 2W–


transformers

The stabilized and instantaneous differential protection for 2W–transformers


(TR2PTDF1) provides protection of power transformer unit including, for
example, winding short-circuit and interturn faults. The IED compares the phase
currents on both sides of the object to be protected. If the differential current of the
phase currents in one of the phases exceed the setting of the stabilized operation
characteristic or the instantaneous protection stage of the function, the function
provides an operate signal.

For transformers having an on-line tap changer, the tap position information is
recommended to be used in differential protection, as the ratio difference of tap
changer movements can be corrected in TR2PTDF.

78 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

All operate signals are connected to the Master Trip 1 and 2 and also to the alarm
LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for
instantaneous high-stage of the differential protection.

GUID-1C4B6EFB-C39F-4D99-832A-F141FFBCBA9F V3 EN

Figure 48: Overcurrent and short-circuit protection

RET615 79
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Three stages for both high-voltage and low-voltage sides as a total of six
overcurrent stages are offered for overcurrent and short-circuit protection. The high-
voltage side high stage (PHHPTOC1) can be blocked by energizing the binary
input 1 (X110:1-2) or by starting the high stage of the low-voltage side
(PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by
activating the binary input (X110_BI1).

A selective backup overcurrent protection can be achieved by using blockings


between high-voltage side and low-voltage side overcurrent stages. This kind of
blocking scheme enables coordinated overlapping of overcurrent protection zones.

The operate of the overcurrent protection functions is connected to the output SO1
(X110:14-15-16). This output is used for giving a specific alarm of the overcurrent
protection operation.

GUID-405919EB-7FA4-45D9-BCCB-B876E72A6950 V2 EN

Figure 49: Non-directional earth-fault protection

Two stages are offered for non-directional earth-fault protection. The earth-fault
protection uses the residual current calculated from the high-voltage side phase
currents.

All operate signals are connected to the Master Trip 1 and also to the alarm LEDs.
LED 5 is used for non-directional earth-fault protection operate indication.

GUID-5CD36CE2-EE91-4A16-A93A-92786B73C331 V2 EN

Figure 50: Restricted high-impedance earth-fault protection

80 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

The configuration includes restricted high-impedance earth-fault protection


function for high-voltage side of two-winding power transformers (HREFPDIF1).
The restricted earth-fault current stage operates exclusively on earth faults
occurring in the protected area, that is, in the area between the phase and neutral
current transformers. An earth fault in this area appears as a differential current
between the residual current of the phase currents and the neutral current of the
conductor between the star-point of the transformer and earth.

GUID-9DCFCF0A-C00E-4642-AA74-CB18F9A2F755 V2 EN

Figure 51: Negative-sequence overcurrent protection

NSPTOC is designed for negative-phase sequence protection whenever the


operating characteristic is appropriate. It is applied for the protection of
transformers against thermal stress and damage.

NSPTOC1 measures negative-sequence current from the high-voltage side and


NSPTOC2 from the low-voltage side.

GUID-AE2AD913-A841-4CF8-BD23-DD79CDC10BB4 V1 EN

Figure 52: Three-phase thermal overload protection for power transformers

Three-phase thermal overload protection for power transformers (T2PTTR1)


provides indication on overload situations. The operate signal of the thermal

RET615 81
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

overload protection is connected to the Master Trip 2. LED 7 is used for the
thermal overload protection alarm indication, the same as for negative-sequence
overcurrent protection operate indication.

GUID-5BF71150-B75E-405A-91CF-87CDF86639BE V2 EN

Figure 53: Circuit-breaker failure protection

The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input
by a number of different protection stages in the IED. CCBRBRF1 offers different
operating modes associated with the circuit-breaker position and the measured
phase and residual currents.

CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for retripping both the high-voltage and low-voltage side circuit
breakers through Master Trip 1 and 2. The TRBU operate output signal is
connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU)
operate indication.

82 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-42911654-7FC8-4A91-8E52-89E062039C69 V2 EN

Figure 54: Arc protection

Arc protection (ARCSARC1...3) is included as an optional function.

The arc protection offers individual function blocks for three arc sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.

RET615 83
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.6.3.2 Functional diagrams for disturbance recorder and supervision


functions

GUID-96BB51D1-DB86-49BE-A5FE-25B304403C59 V2 EN

Figure 55: Disturbance recorder

All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, the ARC protection
signals and the four binary inputs from X110 are also connected.

84 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-F8B12B36-DF24-4907-8288-814A7C34D70E V2 EN

Figure 56: Trip circuit supervision

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.

By default it is expected that there is no external resistor in the


circuit breaker tripping coil circuit connected parallel with circuit
breaker normally open auxiliary contact.

RET615 85
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.6.3.3 Functional diagrams for control and interlocking

GUID-FCB8739C-C3C7-4994-BAC6-18BA323962F7 V2 EN

Figure 57: Master Trip

The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op are connected directly to the output PO3
(X100:15-19).

TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.

The external trip indication is connected also to the alarm LED 11.

86 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-0D5A94B8-8D06-4710-8B97-31D9C05FAAA4 V2 EN

Figure 58: Disconnector position indication

There are two types of disconnector and earthing switch blocks available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration logic. If controllable operation is preferred, the controllable
type of disconnector and earthing switch blocks can be used instead of the status
only type. The connection and configuration of the control blocks can be done
using PCM600.

The binary inputs 5 and 6 of the additional card X110 are used for busbar
disconnector (DCSXSWI1) or circuit-breaker truck position indication.

Table 31: Device positions indicated by binary inputs 5 and 6


Primary device position Input to be energized
Input 5 (X110:8-9) Input 6 (X110:10-9)
Busbar disconnector closed x
Busbar disconnector open x
Circuit breaker truck in service position x
Circuit breaker truck in test position x

The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
the disconnector position status and the statuses of the master trip logics and gas
pressure alarm and circuit-breaker spring charging. The OKPOS output from the
DCSXSWI block defines if the disconnector or the breaker truck is definitely either

RET615 87
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

open (in test position) or close (in service position). This, together with non-active
trip signal and non-active gas pressure alarm, activates the close-enable signal to
the circuit-breaker control function block. The open operation is always enabled.

The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.

If the ENA_CLOSE and BLK_CLOSE signals are completely


removed from the breaker control function block CBXCBR with
PCM600, the function assumes that the breaker close commands
are allowed continuously.

The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 9.

88 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-EF27034F-786A-460C-9350-6A2E02C4A3BC V3 EN

Figure 59: Common alarm/indication 1 and 2

The signal outputs from the IED are connected to give dedicated information on:

• Start of any protection function SO1 (X100:10-12)


• Operation (trip) of any protection function SO2 (X100:13-15)
• Operation (trip) of any stage of the overcurrent protection function SO1
(X110:14-15-16)
• Operation (trip) of differential protection function SO2 (X110:17-18-19)
• Operation (trip) of any stage of the earth-fault protection function SO3
(X110:20-21-22)
• Operation (trip) of thermal or current negative-sequence protection function
SO4 (X110:23-24)

TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining

RET615 89
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

ones not described in the functional diagram are available in PCM600 for
connection where applicable.

GUID-F78772E5-8513-4422-B928-5B6D7C97B828 V2 EN

Figure 60: Tap changer position indication

To increase the sensitivity of the stabilized differential function, the tap position
information from the tap changer is connected to the IED via the tap changer
position indication function TPOSSLTC1. TPOSSLTC1 is connected to the binary
inputs of the X130 BIO card or alternatively to the mA input of the RTD card.
TPOSSLTC1 uses binary-coded methods to generate the integer value of the tap
changer position.

3.7 Standard configuration D

3.7.1 Applications

The standard configuration includes three-phase transformer differential protection


for two-winding transformers and high impedance based restricted earth-fault
protection for the low-voltage (LV) side. The standard configuration is mainly
intended for protection of the power transformer between current transformers.

The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.

90 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

3.7.2 Functions

Table 32: Functions included in the standard configuration D


Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
PHLPTOC1 3I> (1) 51P-1 (1)
protection, low stage, instance 1
Three-phase non-directional overcurrent
PHLPTOC2 3I> (2) 51P-1 (2)
protection, low stage, instance 2
Three-phase non-directional overcurrent
PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent
PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent
PHIPTOC1 3I>>> (1) 50P/51P (1)
protection, instantaneous stage, instance 1
Three-phase non-directional overcurrent
PHIPTOC2 3I>>> (2) 50P/51P (2)
protection, instantaneous stage, instance 2
Non-directional earth-fault protection, low
EFLPTOC2 Io> (2) 51N-1 (2)
stage, instance 2
Non-directional earth-fault protection, high
EFHPTOC2 Io>> (2) 51N-2 (2)
stage, instance 2
Negative-sequence overcurrent protection,
NSPTOC1 I2> (1) 46 (1)
instance 1
Negative-sequence overcurrent protection,
NSPTOC2 I2> (2) 46 (2)
instance 2
Three-phase thermal overload protection for
T2PTTR1 3Ith>T 49T
power transformers, two time constants
Stabilized and instantaneous differential
TR2PTDF1 3dI>T 87T
protection for 2W –transformers
High impedance based restricted earth-fault
HREFPDIF1 dIoHi> 87NH
protection
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)
Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)
Multi-purpose protection, instance 1 MAPGAPC1 MAP (1) MAP (1)
Multi-purpose protection, instance 2 MAPGAPC2 MAP (2) MAP (2)
Multi-purpose protection, instance 3 MAPGAPC3 MAP (3) MAP (3)
Multi-purpose protection, instance 4 MAPGAPC4 MAP (4) MAP (4)
Multi-purpose protection, instance 5 MAPGAPC5 MAP (5) MAP (5)
Multi-purpose protection, instance 6 MAPGAPC6 MAP (6) MAP (6)
Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
Table continues on next page

RET615 91
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Function IEC 61850 IEC 60617 IEC-ANSI


I <-> O DCC I <-> O DCC
Disconnector control, instance 1 DCXSWI1
(1) (1)
I <-> O DCC I <-> O DCC
Disconnector control, instance 2 DCXSWI2
(2) (2)
Earthing switch control ESXSWI1 I <-> O ESC I <-> O ESC
Disconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
Disconnector position indication, instance 3 DCSXSWI3 I <-> O DC (3) I <-> O DC (3)
Earthing switch indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
Earthing switch indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Tap changer position indication TPOSSLTC1 TPOSM 84M
Condition monitoring
Circuit-breaker condition monitoring SSCBR1 CBCM CBCM
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Runtime counter for machines and devices MDSOPT1 OPTS OPTM
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement, instance 1 CMMXU1 3I 3I
Three-phase current measurement, instance 2 CMMXU2 3I(B) 3I(B)
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement, instance 2 RESCMMXU2 Io(B) In(B)
RTD/mA measurement XRGGIO130 X130 (RTD) X130 (RTD)

3.7.2.1 Default I/O connections


Table 33: Default connections for binary inputs
Binary input Description Connector pins
X110-BI1 Blocking of O/C high stage (high voltage) and X110-1,2
instantaneous stage (low voltage)
X110-BI2 External protection trip X110-3,4
X110-BI3 Circuit breaker low gas pressure indication X110-5,6
X110-BI4 Circuit breaker spring charged indication X110-7,6
X110-BI5 High-voltage side disconnector closed X110-8,9
X110-BI6 High-voltage side disconnector open X110-10,9
X110-BI7 High-voltage side circuit breaker closed X110-11,12
X110-BI8 High-voltage side circuit breaker open X110-13,12
X130-BI1 BCD sign bit (tap changer position) X130-1,2
X130-BI2 BCD bit 1 LSB X130-2,3
X130-BI3 BCD bit 2 X130-4,5
Table continues on next page

92 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Binary input Description Connector pins


X130-BI4 BCD bit 3 X130-5,6
X130-BI5 BCD bit 4 X130-7,8
X130-BI6 BCD bit 5 MSB X130-8,9

Table 34: Default connections for RDT/mA inputs


Binary input Description Connector pins
X130-AI1 X130-1,2
X130-AI2 X130-3,4
X130-AI3 Ambient temperature X130-5,6,11c
X130-AI4 X130-7,8,11c
X130-AI5 X130-9,10,11c
X130-AI6 X130-13,14,12c
X130-AI7 X130-15,16,12c
X130-AI8 X130-17,18,12c

Table 35: Default connections for binary outputs


Binary output Description Connector pins
X100-PO1 Close high-voltage circuit breaker X100-6,7
X100-PO2 Breaker failure backup trip to upstream breaker X100-8,9
X100-SO1 General start indication X100-10,11,(12)
X100-SO2 General operate indication X100-13,14
X100-PO3 Open circuit breaker/trip coil 1 high voltage X100-15-19
X100-PO4 Open circuit breaker/trip coil 2 low voltage X100-20-24
X110-SO1 Overcurrent operate alarm X110-14,15,16
X110-SO2 Differential protection operate alarm X110-17,18,19
X110-SO3 Earth fault operate alarm X110-20,21,22
X110-SO4 Thermal overload and negative phase-sequence X110-23,24
protection operate alarm

Table 36: Default connections for LEDs


LED Description
1 Transformer differential protection biased stage operate
2 Transformer differential protection instantaneous stage operate
3 Non-directional overcurrent protection operate
4 Restricted earth-fault protection operate
5 Earth fault protection operated
6 Circuit failure protection backup trip operated
7 NPS or thermal overload protection operated
Table continues on next page

RET615 93
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

LED Description
8 Disturbance recorder triggered
9 TCS, fuse failure, measuring circuit fault or circuit breaker supervision
10 Arc protection operate
11 Protection trip from external device

3.7.2.2 Default disturbance recorder settings

Table 37: Default analog channel selection and text settings


Channel Selection and text
1 IL1
2 IL2
3 IL3
4 IL1B
5 IL2B
6 IL3B
7 IoB
8 -
9 -
10 -
11 -
12 -

Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.

3.7.3 Functional diagrams


The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.

The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings.

The analog channels are assigned to different functions. The common signal
marked with 3I represents the three phase currents of the high-voltage side of the
transformer and 3IB represents the three phase currents of the low-voltage side of

94 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

the transformer. The signal marked with IoB represents the neutral current
measured between the start point of the transformer and grounding on the low
voltage side.

3.7.3.1 Functional diagrams for protection

The functional diagrams describe the IED’s protection functionality in detail and
picture the factory set default connections.

GUID-99A6097A-7411-40E3-B6CE-694B1246D4B9 V3 EN

Figure 61: Stabilized and instantaneous differential protection for 2W-


transformers

The stabilized and instantaneous differential protection for 2W–transformers


(TR2PTDF1) provides protection of power transformer unit including, for
example, winding short-circuit and interturn faults. The IED compares the phase
currents on both sides of the object to be protected. If the differential current of the
phase currents in one of the phases exceed the setting of the stabilized operation
characteristic or the instantaneous protection stage of the function, the function
provides an operate signal.

For transformers having an on-line tap changer, the tap position information is
recommended to be used in differential protection, as the ratio difference of tap
changer movements can be corrected in TR2PTDF.

RET615 95
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

All operate signals are connected to the Master Trip 1 and 2 and also to the alarm
LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for
instantaneous high-stage of the differential protection.

GUID-1C4B6EFB-C39F-4D99-832A-F141FFBCBA9F V3 EN

Figure 62: Overcurrent and short-circuit protection

96 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Three stages for both high-voltage and low-voltage sides as a total of six
overcurrent stages are offered for overcurrent and short-circuit protection. The high-
voltage side high stage (PHHPTOC1) can be blocked by energizing the binary
input 1 (X110:1-2) or by starting the high stage of the low-voltage side
(PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by
activating the binary input (X110_BI1).

A selective backup overcurrent protection can be achieved by using blockings


between high-voltage side and low-voltage side overcurrent stages. This kind of
blocking scheme enables coordinated overlapping of overcurrent protection zones.

The operate of the overcurrent protection functions is connected to the output SO1
(X110:14-15-16). This output is used for giving a specific alarm of the overcurrent
protection operation.

GUID-9EA539DB-B9C7-4C3D-BFF4-810F66403743 V2 EN

Figure 63: Non-directional earth-fault protection

Two stages are offered for non-directional earth-fault protection. The earth-fault
protection uses the residual current calculated from the low-voltage side phase
currents.

All operate signals are connected to the Master Trip 2 and also to the alarm LEDs.
LED 5 is used for non-directional earth-fault protection operate indication.

GUID-5CD36CE2-EE91-4A16-A93A-92786B73C331 V2 EN

Figure 64: Restricted high-impedance earth-fault protection

RET615 97
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

The configuration includes restricted high-impedance earth-fault protection


function for low-voltage side of two-winding power transformers (HREFPDIF1).
The restricted earth-fault current stage operates exclusively on earth faults
occurring in the protected area, that is, in the area between the phase and neutral
current transformers. An earth fault in this area appears as a differential current
between the residual current of the phase currents and the neutral current of the
conductor between the star-point of the transformer and earth.

GUID-9DCFCF0A-C00E-4642-AA74-CB18F9A2F755 V2 EN

Figure 65: Negative-sequence overcurrent protection

NSPTOC is designed for negative-phase sequence protection whenever the


operating characteristic is appropriate. It is applied for the protection of
transformers against thermal stress and damage.

NSPTOC1 measures negative-sequence current from the high-voltage side and


NSPTOC2 from the low-voltage side.

GUID-34FCACA0-E981-42D3-9DCC-A6FD1E8DC214 V1 EN

Figure 66: Three-phase thermal overload protection for power transformers

Three-phase thermal overload protection for power transformers (T2PTTR1)


provides indication on overload situations. The operate signal of the thermal
overload protection is connected to the Master Trip 2. LED 7 is used for the

98 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

thermal overload protection alarm indication, the same as for negative-sequence


overcurrent protection operate indication.

GUID-429A2BA1-3C70-43BF-80EB-36503734D972 V1 EN

Figure 67: Circuit-breaker failure protection

The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input
by a number of different protection stages in the IED. CCBRBRF1 offers different
operating modes associated with the circuit-breaker position and the measured
phase and residual currents.

CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for retripping both the high-voltage and low-voltage side circuit
breakers through Master Trip 1 and 2. The TRBU operate output signal is
connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU)
operate indication.

RET615 99
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-42911654-7FC8-4A91-8E52-89E062039C69 V2 EN

Figure 68: Arc protection

Arc protection (ARCSARC1...3) is included as an optional function.

The arc protection offers individual function blocks for three arc sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.

100 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

3.7.3.2 Functional diagrams for disturbance recorder and supervision


functions

GUID-6942C970-C7A6-4B62-8466-2F4E8B7AA040 V1 EN

Figure 69: Disturbance recorder

All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, the ARC protection
signals and the four binary inputs from X110 are also connected.

RET615 101
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-F8B12B36-DF24-4907-8288-814A7C34D70E V2 EN

Figure 70: Trip circuit supervision

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.

By default it is expected that there is no external resistor in the


circuit breaker tripping coil circuit connected parallel with circuit
breaker normally open auxiliary contact.

102 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

3.7.3.3 Functional diagrams for control and interlocking

GUID-00B5279F-3CCB-44CC-A391-4E398782E7A5 V1 EN

Figure 71: Master Trip

The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op are connected directly to the output PO3
(X100:15-19).

TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.

The external trip indication is connected also to the alarm LED 11.

RET615 103
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-0D5A94B8-8D06-4710-8B97-31D9C05FAAA4 V2 EN

Figure 72: Disconnector position indication

There are two types of disconnector and earthing switch blocks available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration logic. If controllable operation is preferred, the controllable
type of disconnector and earthing switch blocks can be used instead of the status
only type. The connection and configuration of the control blocks can be done
using PCM600.

The binary inputs 5 and 6 of the additional card X110 are used for busbar
disconnector (DCSXSWI1) or circuit-breaker truck position indication.

Table 38: Device positions indicated by binary inputs 5 and 6


Primary device position Input to be energized
Input 5 (X110:8-9) Input 6 (X110:10-9)
Busbar disconnector closed x
Busbar disconnector open x
Circuit breaker truck in service position x
Circuit breaker truck in test position x

The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
the disconnector position status and the statuses of the master trip logics and gas
pressure alarm and circuit-breaker spring charging. The OKPOS output from the
DCSXSWI block defines if the disconnector or the breaker truck is definitely either

104 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

open (in test position) or close (in service position). This, together with non-active
trip signal and non-active gas pressure alarm, activates the close-enable signal to
the circuit-breaker control function block. The open operation is always enabled.

The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.

If the ENA_CLOSE and BLK_CLOSE signals are completely


removed from the breaker control function block CBXCBR with
PCM600, the function assumes that the breaker close commands
are allowed continuously.

The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 9.

RET615 105
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-861204B1-D644-41A1-9868-E28545574FF8 V1 EN

Figure 73: Common alarm/indication 1 and 2

The signal outputs from the IED are connected to give dedicated information on:

• Start of any protection function SO1 (X100:10-12)


• Operation (trip) of any protection function SO2 (X100:13-15)
• Operation (trip) of any stage of the overcurrent protection function SO1
(X110:14-15-16)
• Operation (trip) of differential protection function SO2 (X110:17-18-19)
• Operation (trip) of any stage of the earth-fault protection function SO3
(X110:20-21-22)
• Operation (trip) of thermal or current negative-sequence protection function
SO4 (X110:23-24)

TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining

106 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

ones not described in the functional diagram are available in PCM600 for
connection where applicable.

GUID-F78772E5-8513-4422-B928-5B6D7C97B828 V2 EN

Figure 74: Tap changer position indication

To increase the sensitivity of the stabilized differential function, the tap position
information from the tap changer is connected to the IED via the tap changer
position indication function TPOSSLTC1. TPOSSLTC1 is connected to the binary
inputs of the X130 BIO card or alternatively to the mA input of the RTD card.
TPOSSLTC1 uses binary-coded methods to generate the integer value of the tap
changer position.

3.8 Standard configuration E

3.8.1 Applications

The standard configuration includes three-phase transformer differential protection


for two-winding transformers and numerical restricted earth-fault protection for the
high-voltage (HV) side, phase-voltage based protection and measurement
functions. The standard configuration is mainly intended for protection of the
power transformer between current transformers.

The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.

RET615 107
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.8.2 Functions
Table 39: Functions included in the standard configuration E
Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
PHLPTOC1 3I> (1) 51P-1 (1)
protection, low stage, instance 1
Three-phase non-directional overcurrent
PHLPTOC2 3I> (2) 51P-1 (2)
protection, low stage, instance 2
Three-phase non-directional overcurrent
PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent
PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent
PHIPTOC1 3I>>> (1) 50P/51P (1)
protection, instantaneous stage, instance 1
Three-phase non-directional overcurrent
PHIPTOC2 3I>>> (2) 50P/51P (2)
protection, instantaneous stage, instance 2
Non-directional earth-fault protection, low
EFLPTOC1 Io> (1) 51N-1 (1)
stage, instance 1
Non-directional earth-fault protection, high
EFHPTOC1 Io>> (1) 51N-2 (1)
stage, instance 1
Negative-sequence overcurrent protection,
NSPTOC1 I2> (1) 46 (1)
instance 1
Negative-sequence overcurrent protection,
NSPTOC2 I2> (2) 46 (2)
instance 2
Residual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1)
Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2)
Three-phase undervoltage protection, instance
PHPTUV1 3U< (1) 27 (1)
1
Three-phase undervoltage protection, instance
PHPTUV2 3U< (2) 27 (2)
2
Three-phase overvoltage protection, instance 1 PHPTOV1 3U> (1) 59 (1)
Three-phase overvoltage protection, instance 2 PHPTOV2 3U> (2) 59 (2)
Three-phase thermal overload protection for
T2PTTR1 3Ith>T 49T
power transformers, two time constants
Stabilized and instantaneous differential
TR2PTDF1 3dI>T 87T
protection for 2W –transformers
Numerical stabilized low impedance restricted
LREFPNDF1 dIoLo> 87NL
earth-fault protection
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)
Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)
Control
Table continues on next page

108 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Function IEC 61850 IEC 60617 IEC-ANSI


Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
I <-> O DCC I <-> O DCC
Disconnector control, instance 1 DCXSWI1
(1) (1)
I <-> O DCC I <-> O DCC
Disconnector control, instance 2 DCXSWI2
(2) (2)
Earthing switch control ESXSWI1 I <-> O ESC I <-> O ESC
Disconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
Disconnector position indication, instance 3 DCSXSWI3 I <-> O DC (3) I <-> O DC (3)
Earthing switch indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
Earthing switch indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Tap changer position indication TPOSSLTC1 TPOSM 84M
Condition monitoring
Circuit-breaker condition monitoring SSCBR1 CBCM CBCM
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Fuse failure supervision SEQRFUF1 FUSEF 60
Runtime counter for machines and devices MDSOPT1 OPTS OPTM
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement, instance 1 CMMXU1 3I 3I
Three-phase current measurement, instance 2 CMMXU2 3I(B) 3I(B)
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement, instance 1 RESCMMXU1 Io In
Three-phase voltage measurement VMMXU1 3U 3U
Residual voltage measurement RESVMMXU1 Uo Vn
Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0
Three-phase power and energy measurement PEMMXU1 P, E P, E

3.8.2.1 Default I/O connections

Table 40: Default connections for binary inputs


Binary input Default usage Connector pins
X110-BI1 Blocking of O/C high stage (high voltage) and X110-1,2
instantaneous stage (low voltage)
X110-BI2 External protection trip X110-3,4
X110-BI3 Circuit breaker low gas pressure alarm X110-5,6
X110-BI4 Circuit breaker spring charged indication X110-7,6
X110-BI5 High voltage disconnector closed indication X110-8,9
X110-BI6 High voltage disconnector open indication X110-10,9
Table continues on next page

RET615 109
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Binary input Default usage Connector pins


X110-BI7 High voltage circuit breaker closed indication X110-11,12
X110-BI8 High voltage circuit breaker open indication X110-13,12
X130-BI1 Voltage transformer secondary MCB open X130-1,2
X130-BI2 Not assigned as default X130-3,4
X130-BI3 Not assigned as default X130-5,6
X130-BI4 Not assigned as default X130-7,8

Table 41: Default connections for binary outputs


Binary output Default usage Connector pins
X100-PO1 Close high-voltage circuit breaker X100-6,7
X100-PO2 Breaker failure backup trip to upstream breaker X100-8,9
X100-SO1 General start indication X100-10,11,(12)
X100-SO2 General operate indication X100-13,14
X100-PO3 Open circuit breaker/trip coil 1 HV X100-15-19
X100-PO4 Open circuit breaker/trip coil 2 LV X100-20-24
X110-SO1 Overcurrent operate alarm X110-14,15,16
X110-SO2 Differential protection operate alarm X110-17,18,19
X110-SO3 Earth fault operate alarm X110-20,21,22
X110-SO4 Combined protection operate alarm X110-23,24

Table 42: Default connections for LEDs


LED Default usage
1 Transformer differential protection biased stage operate
2 Transformer differential protection instantaneous stage operate
3 Overcurrent or earth fault protection operate
4 Restricted earth-fault protection operate
5 Voltage protection operated
6 Circuit failure protection back-up trip operated
7 NPS or thermal overload protection operated
8 Disturbance recorder triggered
9 Trip circuit supervision, fuse failure, measuring circuit fault or circuit breaker
supervision
10 Arc protection operate
11 Protection trip from external device

110 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

3.8.2.2 Default disturbance recorder settings


Table 43: Default analog channel selection and text settings
Channel Selection and text
1 IL1
2 IL2
3 IL3
4 IL1B
5 IL2B
6 IL3B
7 Io
8 Uo
9 U1
10 U2
11 U3
12 -

Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.

3.8.3 Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.

The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings.

The analog channels are assigned to different functions. The common signals
marked with 3I and 3U represent the three phase currents and voltages of the high-
voltage side of the transformer respectively, and 3IB represents the three phase
currents of the low-voltage side of the transformer. The signal marked with Io
represents the measured neutral current measured between the start point of the
transformer and grounding on the high voltage side. The signal marked with Uo
represents the measured residual voltage via open-delta connected voltage
transformers on the high voltage side.

RET615 111
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.8.3.1 Functional diagrams for protection

The functional diagrams describe the IED’s protection functionality in detail and
picture the factory set default connections.

GUID-B444DCDF-F010-467A-9B00-07C1E37207B9 V2 EN

Figure 75: Stabilized and instantaneous differential protection for 2W–


transformers

The stabilized and instantaneous differential protection for 2W–transformers


(TR2PTDF1) provides protection of power transformer unit including, for
example, winding short-circuit and interturn faults. The IED compares the phase
currents on both sides of the object to be protected. If the differential current of the
phase currents in one of the phases exceed the setting of the stabilized operation
characteristic or the instantaneous protection stage of the function, the function
provides an operate signal.

112 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

For transformers having an on-line tap changer, the tap position information is
recommended to be used in differential protection, as the ratio difference of tap
changer movements can be corrected in TR2PTDF.

All operate signals are connected to the Master Trip 1 and 2 and also to the alarm
LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for
instantaneous high-stage of the differential protection.

GUID-2AF3E8AD-2FB2-4C2B-9855-52DDE5B57495 V1 EN

Figure 76: Overcurrent and short-circuit protection

Three stages for both high-voltage and low-voltage sides as a total of six
overcurrent stages are offered for overcurrent and short-circuit protection. The high-
voltage side high stage (PHHPTOC1) can be blocked by energizing the binary
input 1 (X110:1-2) or by starting the high stage of the low-voltage side

RET615 113
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

(PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by


activating the binary input (X110_BI1).

A selective backup overcurrent protection can be achieved by using blockings


between high-voltage side and low-voltage side overcurrent stages. This kind of
blocking scheme enables coordinated overlapping of overcurrent protection zones.

The operate of the overcurrent protection functions is connected to the output SO1
(X110:14-15-16). This output is used for giving a specific alarm of the overcurrent
protection operation.

GUID-B50BF279-890D-479D-9E31-F71C6D852AA5 V1 EN

Figure 77: Non-directional earth-fault protection

Two stages are offered for non-directional earth-fault protection. The earth-fault
protection measures the neutral current of the low-voltage side.

All operate signals are connected to the Master Trip as well as to the alarm LEDs.
LED 3 is used for non-directional earth-fault protection operate indication.

GUID-9E516077-7D60-44B0-AE40-8A6C17B43B4B V1 EN

Figure 78: Restricted low-impedance earth-fault protection

The configuration includes restricted low-impedance earth-fault protection function


for high-voltage side of two-winding power transformers (LREFPNDF1). The
numerical differential current stage operates exclusively on earth faults occurring
in the protected area, that is, in the area between the phase and neutral current
transformers. An earth fault in this area appears as a differential current between
the residual current of the phase currents and the neutral current of the conductor
between the star-point of the transformer and earth.

114 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-CEDAF363-53D4-4C49-B570-C78AC13DDF82 V1 EN

Figure 79: Negative-phase sequence protection

NSPTOC is designed for negative-phase sequence protection whenever the


operating characteristic is appropriate. It is applied for the protection of
transformers against thermal stress and damage.

NSPTOC1 measures negative-sequence current from the high-voltage side and


NSPTOC2 from the low-voltage side.

GUID-6FC50ECB-7261-420F-9F79-F09F274A823D V2 EN

Figure 80: Thermal overload protection

Three-phase thermal overload protection for power transformers (T2PTTR1)


provides indication on overload situations. The operate signal of the thermal
overload protection is connected to the Master Trip 2. LED 7 is used for the
thermal overload protection alarm indication, the same as for negative-sequence
overcurrent protection operate indication.

RET615 115
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-F10B950D-2141-44DC-9107-3983DD3234EA V1 EN

Figure 81: Overvoltage and undervoltage protection

Two overvoltage and undervoltage protection stages (PHxPTOV and PHxPTUV)


offer protection against abnormal phase voltage conditions. The operation of
voltage functions is connected to alarm LED 5. A failure in the voltage measuring
circuit is detected by the fuse failure function and the activation is connected to
undervoltage protection functions to avoid faulty undervoltage tripping.

GUID-C53C6AD2-061B-4483-9931-A227EFF66AA8 V2 EN

Figure 82: Residual overvoltage protection

116 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

The residual overvoltage protection (ROVPTOV) provides earth-fault protection


by detecting abnormal level of residual voltage. The operation signal is connected
to alarm LED 3.

GUID-0D218E13-46B7-4299-A30C-793B72E43572 V1 EN

Figure 83: Circuit-breaker failure protection

The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input
by a number of different protection stages in the IED. CCBRBRF1 offers different
operating modes associated with the circuit-breaker position and the measured
phase and residual currents.

CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for retripping both the high-voltage and low-voltage side circuit
breakers through Master Trip 1 and 2. The TRBU operate output signal is
connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU)
operate indication.

GUID-3AEB5B1A-9FE5-40E3-A199-F976B4127C87 V1 EN

Figure 84: Arc protection

RET615 117
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Arc protection (ARCSARC1...3) is included as an optional function.

The arc protection offers individual function blocks for three arc sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.

3.8.3.2 Functional diagram for disturbance recorder and supervision functions

GUID-8A18CD3E-F811-4A8A-B01B-BC38004F1891 V1 EN

Figure 85: Disturbance recorder

All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, the ARC protection
signals and the four binary inputs from X110 are also connected.

118 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-2D158BA9-0D4F-4389-8D6A-FE415C4EDD91 V1 EN

Figure 86: Trip circuit supervision

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.

By default it is expected that there is no external resistor in the


circuit breaker tripping coil circuit connected parallel with circuit
breaker normally open auxiliary contact.

GUID-5495E5E0-2282-4370-A0BA-D8B4649B9E22 V2 EN

Figure 87: Fuse failure supervision and runtime counter

The fuse failure supervision SEQRFUF1 detects failures in voltage measurement


circuits. Failures, such as open miniature circuit breaker, are detected and the alarm
is connected to supervision alarm LED 9.

The generic operation time counter function MDSOPT calculates accumulated


operation time of the transformer. The alarm is connected to the alarm LED 9.

RET615 119
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.8.3.3 Functional diagrams for control and interlocking

GUID-EC39937B-DB3E-4F77-A4FA-6949E5EF777A V1 EN

Figure 88: Master Trip

The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op are connected directly to the output PO3
(X100:15-19).

TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.

The external trip indication is connected also to the alarm LED 11.

120 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-D85EB0CA-9C9F-4847-ABB7-3CA9C740EC80 V2 EN

Figure 89: Circuit breaker control and disconnector position indication

There are two types of disconnector and earthing switch blocks available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration logic. If controllable operation is preferred, the controllable
type of disconnector and earthing switch blocks can be used instead of the status
only type. The connection and configuration of the control blocks can be done
using PCM600.

The binary inputs 5 and 6 of the additional card X110 are used for busbar
disconnector (DCSXSWI1) or circuit-breaker truck position indication.

Table 44: Device positions indicated by binary inputs 5 and 6


Primary device position Input to be energized
Input 5 (X110:8-9) Input 6 (X110:10-9)
Busbar disconnector closed x
Busbar disconnector open x
Circuit breaker truck in service position x
Circuit breaker truck in test position x

The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
the disconnector position status and the statuses of the master trip logics and gas
pressure alarm and circuit-breaker spring charging. The OKPOS output from the
DCSXSWI block defines if the disconnector or the breaker truck is definitely either

RET615 121
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

open (in test position) or close (in service position). This, together with non-active
trip signal and non-active gas pressure alarm, activates the close-enable signal to
the circuit-breaker control function block. The open operation is always enabled.

The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.

If the ENA_CLOSE and BLK_CLOSE signals are completely


removed from the breaker control function block CBXCBR with
PCM600, the function assumes that the breaker close commands
are allowed continuously.

The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 9.

122 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-3FBEA8E7-F72F-43CD-B4E5-68582DAC6B7E V2 EN

Figure 90: Common alarm/indication 1 and 2

The signal outputs from the IED are connected to give dedicated information on:

• Start of any protection function SO1 (X100:10-12)


• Operation (trip) of any protection function SO2 (X100:13-15)
• Operation (trip) of any stage of the overcurrent protection function SO1
(X110:14-15-16)

RET615 123
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

• Operation (trip) of differential protection function SO2 (X110:17-18-19)


• Operation (trip) of any stage of the earth-fault protection function SO3
(X110:20-21-22)
• Operation (trip) of thermal or current negative-sequence protection function
SO4 (X110:23-24)

TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for
connection where applicable.

3.9 Standard configuration F

3.9.1 Applications

The standard configuration includes three-phase transformer differential protection


for two-winding transformers, numerical restricted earth-fault protection for the low-
voltage (LV) side, phase-voltage based protection and measurement functions. The
standard configuration is mainly intended for protection of the power transformer
between current transformers.

The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.

3.9.2 Functions
Table 45: Functions included in the standard configuration F
Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
PHLPTOC1 3I> (1) 51P-1 (1)
protection, low stage, instance 1
Three-phase non-directional overcurrent
PHLPTOC2 3I> (2) 51P-1 (2)
protection, low stage, instance 2
Three-phase non-directional overcurrent
PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent
PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent
PHIPTOC1 3I>>> (1) 50P/51P (1)
protection, instantaneous stage, instance 1
Three-phase non-directional overcurrent
PHIPTOC2 3I>>> (2) 50P/51P (2)
protection, instantaneous stage, instance 2
Table continues on next page

124 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Function IEC 61850 IEC 60617 IEC-ANSI


Non-directional earth-fault protection, low
EFLPTOC2 Io> (2) 51N-1 (2)
stage, instance 2
Non-directional earth-fault protection, high
EFHPTOC2 Io>> (2) 51N-2 (2)
stage, instance 2
Negative-sequence overcurrent protection,
NSPTOC1 I2> (1) 46 (1)
instance 1
Negative-sequence overcurrent protection,
NSPTOC2 I2> (2) 46 (2)
instance 2
Residual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1)
Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2)
Three-phase undervoltage protection, instance
PHPTUV1 3U< (1) 27 (1)
1
Three-phase undervoltage protection, instance
PHPTUV2 3U< (2) 27 (2)
2
Three-phase overvoltage protection, instance 1 PHPTOV1 3U> (1) 59 (1)
Three-phase overvoltage protection, instance 2 PHPTOV2 3U> (2) 59 (2)
Three-phase thermal overload protection for
T2PTTR1 3Ith>T 49T
power transformers, two time constants
Stabilized and instantaneous differential
TR2PTDF1 3dI>T 87T
protection for 2W –transformers
Numerical stabilized low impedance restricted
LREFPNDF1 dIoLo> 87NL
earth-fault protection
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)
Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)
Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
I <-> O DCC I <-> O DCC
Disconnector control, instance 1 DCXSWI1
(1) (1)
I <-> O DCC I <-> O DCC
Disconnector control, instance 2 DCXSWI2
(2) (2)
Earthing switch control ESXSWI1 I <-> O ESC I <-> O ESC
Disconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
Disconnector position indication, instance 3 DCSXSWI3 I <-> O DC (3) I <-> O DC (3)
Earthing switch indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
Earthing switch indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Tap changer position indication TPOSSLTC1 TPOSM 84M
Condition monitoring
Circuit-breaker condition monitoring SSCBR1 CBCM CBCM
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Table continues on next page

RET615 125
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Function IEC 61850 IEC 60617 IEC-ANSI


Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Fuse failure supervision SEQRFUF1 FUSEF 60
Runtime counter for machines and devices MDSOPT1 OPTS OPTM
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement, instance 1 CMMXU1 3I 3I
Three-phase current measurement, instance 2 CMMXU2 3I(B) 3I(B)
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement, instance 2 RESCMMXU2 Io(B) In(B)
Three-phase voltage measurement VMMXU1 3U 3U
Residual voltage measurement RESVMMXU1 Uo Vn
Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0
Three-phase power and energy measurement PEMMXU1 P, E P, E

3.9.2.1 Default I/O connections

Table 46: Default connections for binary inputs


Binary input Default usage Connector pins
X110-BI1 Blocking of O/C high stage (high voltage) and X110-1,2
instantaneous stage (low voltage)
X110-BI2 External protection trip X110-3,4
X110-BI3 Circuit breaker low gas pressure alarm X110-5,6
X110-BI4 Circuit breaker spring charged indication X110-7,6
X110-BI5 High voltage disconnector closed indication X110-8,9
X110-BI6 High voltage disconnector open indication X110-10,9
X110-BI7 High voltage circuit breaker closed indication X110-11,12
X110-BI8 High voltage circuit breaker open indication X110-13,12
X130-BI1 Voltage transformer secondary MCB open X130-1,2
X130-BI2 Not assigned as default X130-3,4
X130-BI3 Not assigned as default X130-5,6
X130-BI4 Not assigned as default X130-7,8

Table 47: Default connections for binary outputs


Binary output Default usage Connector pins
X100-PO1 Close high-voltage circuit breaker X100-6,7
X100-PO2 Breaker failure backup trip to upstream breaker X100-8,9
X100-SO1 General start indication X100-10,11,(12)
X100-SO2 General operate indication X100-13,14
Table continues on next page

126 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Binary output Default usage Connector pins


X100-PO3 Open circuit breaker/trip coil 1 HV X100-15-19
X100-PO4 Open circuit breaker/trip coil 2 LV X100-20-24
X110-SO1 Overcurrent operate alarm X110-14,15,16
X110-SO2 Differential protection operate alarm X110-17,18,19
X110-SO3 Earth fault operate alarm X110-20,21,22
X110-SO4 Combined protection operate alarm X110-23,24

Table 48: Default connections for LEDs


LED Default usage
1 Transformer differential protection biased stage operate
2 Transformer differential protection instantaneous stage operate
3 Overcurrent or earth-fault protection operate
4 Restricted earth-fault protection operate
5 Voltage protection operated
6 Circuit failure protection back-up trip operated
7 NPS or thermal overload protection operated
8 Disturbance recorder triggered
9 Trip circuit supervision, fuse failure, measuring circuit fault or circuit breaker
supervision
10 Arc protection operate
11 Protection trip from external device

3.9.2.2 Default disturbance recorder settings

Table 49: Default analog channel selection and text settings


Channel Selection and text
1 IL1
2 IL2
3 IL3
4 IL1B
5 IL2B
6 IL3B
7 IoB
8 Uo
9 U1
10 U2
11 U3
12 -

RET615 127
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.

3.9.3 Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.

The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings.

The analog channels are assigned to different functions. The common signals
marked with 3I and 3U represent the three phase currents and voltages of the high-
voltage side of the transformer respectively, and 3IB represents the three phase
currents of the low-voltage side of the transformer. The signal marked with IoB
represents the neutral current measured between the start point of the transformer
and grounding on the low voltage side. The signal marked with Uo represents the
measured residual voltage via open-delta connected voltage transformers on the
high voltage side.

3.9.3.1 Functional diagrams for protection

The functional diagrams describe the IED’s protection functionality in detail and
picture the factory set default connections.

128 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-049BD680-D526-4585-9682-7A11A034434A V2 EN

Figure 91: Stabilized and instantaneous differential protection for 2W–


transformers

The stabilized and instantaneous differential protection for 2W–transformers


(TR2PTDF1) provides protection of power transformer unit including, for
example, winding short-circuit and interturn faults. The IED compares the phase
currents on both sides of the object to be protected. If the differential current of the
phase currents in one of the phases exceed the setting of the stabilized operation
characteristic or the instantaneous protection stage of the function, the function
provides an operate signal.

For transformers having an on-line tap changer, the tap position information is
recommended to be used in differential protection, as the ratio difference of tap
changer movements can be corrected in TR2PTDF.

RET615 129
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

All operate signals are connected to the Master Trip 1 and 2 and also to the alarm
LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for
instantaneous high-stage of the differential protection.

GUID-41BDB2C0-0742-4475-8348-A0B65198AAD7 V2 EN

Figure 92: Overcurrent and short-circuit protection

130 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Three stages for both high-voltage and low-voltage sides as a total of six
overcurrent stages are offered for overcurrent and short-circuit protection. The high-
voltage side high stage (PHHPTOC1) can be blocked by energizing the binary
input 1 (X110:1-2) or by starting the high stage of the low-voltage side
(PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by
activating the binary input (X110_BI1).

A selective backup overcurrent protection can be achieved by using blockings


between high-voltage side and low-voltage side overcurrent stages. This kind of
blocking scheme enables coordinated overlapping of overcurrent protection zones.

The operate of the overcurrent protection functions is connected to the output SO1
(X110:14-15-16). This output is used for giving a specific alarm of the overcurrent
protection operation.

GUID-D2C7FF7C-75CF-40CA-85A4-D59967FD7E85 V1 EN

Figure 93: Non-directional earth-fault protection

Two stages are offered for non-directional earth-fault protection. The earth-fault
protection measures the neutral current of the low-voltage side.

All operate signals are connected to the Master Trip as well as to the alarm LEDs.
LED 3 is used for non-directional earth-fault protection operate indication.

GUID-3EC397CB-3B6C-4F34-88B2-184F75F355AD V1 EN

Figure 94: Restricted low-impedance earth-fault protection

The configuration includes restricted low-impedance earth-fault protection function


for low-voltage side of two-winding power transformers (LREFPNDF1). The
numerical differential current stage operates exclusively on earth faults occurring
in the protected area, that is, in the area between the phase and neutral current

RET615 131
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

transformers. An earth fault in this area appears as a differential current between


the residual current of the phase currents and the neutral current of the conductor
between the star-point of the transformer and earth.

GUID-6CADBBD9-E389-48FA-B63E-DCE207E3AC11 V1 EN

Figure 95: Negative-phase sequence protection

NSPTOC is designed for negative-phase sequence protection whenever the


operating characteristic is appropriate. It is applied for the protection of
transformers against thermal stress and damage.

NSPTOC1 measures negative-sequence current from the high-voltage side and


NSPTOC2 from the low-voltage side.

GUID-4A274797-A978-427C-A646-19421DB3AC6A V2 EN

Figure 96: Thermal overload protection

Three-phase thermal overload protection for power transformers (T2PTTR1)


provides indication on overload situations. The operate signal of the thermal
overload protection is connected to the Master Trip 2. LED 7 is used for the
thermal overload protection alarm indication, the same as for negative-sequence
overcurrent protection operate indication.

132 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-B1AE475D-8F14-4510-B9EC-D84AA7EC66E6 V1 EN

Figure 97: Overvoltage and undervoltage protection

Two overvoltage and undervoltage protection stages (PHxPTOV and PHxPTUV)


offer protection against abnormal phase voltage conditions. The operation of
voltage functions is connected to alarm LED 5. A failure in the voltage measuring
circuit is detected by the fuse failure function and the activation is connected to
undervoltage protection functions to avoid faulty undervoltage tripping.

GUID-6D0DF1EB-1B51-40A1-A973-E53F30969D4A V2 EN

Figure 98: Residual overvoltage protection

RET615 133
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

The residual overvoltage protection (ROVPTOV) provides earth-fault protection


by detecting abnormal level of residual voltage. The operation signal is connected
to alarm LED 3.

GUID-704C8BBA-751D-443F-91FF-0508874DA792 V1 EN

Figure 99: Circuit-breaker failure protection

The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input
by a number of different protection stages in the IED. CCBRBRF1 offers different
operating modes associated with the circuit-breaker position and the measured
phase and residual currents.

CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for retripping both the high-voltage and low-voltage side circuit
breakers through Master Trip 1 and 2. The TRBU operate output signal is
connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU)
operate indication.

GUID-941081CB-1566-42DA-83EA-06B53C531D88 V1 EN

Figure 100: Arc protection

134 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Arc protection (ARCSARC1...3) is included as an optional function.

The arc protection offers individual function blocks for three arc sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.

3.9.3.2 Functional diagram for disturbance recorder and supervision functions

GUID-6A46C2D2-1109-4E77-99AE-D47F6BB4B375 V1 EN

Figure 101: Disturbance recorder

All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, the ARC protection
signals and the four binary inputs from X110 are also connected.

RET615 135
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-3F90CE14-EF57-48E1-81F0-85F37C06B26B V1 EN

Figure 102: Trip circuit supervision

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.

By default it is expected that there is no external resistor in the


circuit breaker tripping coil circuit connected parallel with circuit
breaker normally open auxiliary contact.

GUID-9A8E1D37-4EE6-489B-B930-1DE6BB24978B V2 EN

Figure 103: Fuse failure supervision and runtime counter

The fuse failure supervision SEQRFUF1 detects failures in voltage measurement


circuits. Failures, such as open miniature circuit breaker, are detected and the alarm
is connected to supervision alarm LED 9.

The generic operation time counter function MDSOPT calculates accumulated


operation time of the transformer. The alarm is connected to the alarm LED 9.

136 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

3.9.3.3 Functional diagrams for control and interlocking

GUID-A3B7EF01-A345-4D54-8BA0-7E370EE20E2B V1 EN

Figure 104: Master Trip

The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op are connected directly to the output PO3
(X100:15-19).

TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.

The external trip indication is connected also to the alarm LED 11.

RET615 137
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-D53DC028-0381-4E85-BCCC-08B0E168B6D2 V2 EN

Figure 105: Circuit breaker control and disconnector position indication

There are two types of disconnector and earthing switch blocks available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration logic. If controllable operation is preferred, the controllable
type of disconnector and earthing switch blocks can be used instead of the status
only type. The connection and configuration of the control blocks can be done
using PCM600.

The binary inputs 5 and 6 of the additional card X110 are used for busbar
disconnector (DCSXSWI1) or circuit-breaker truck position indication.

Table 50: Device positions indicated by binary inputs 5 and 6


Primary device position Input to be energized
Input 5 (X110:8-9) Input 6 (X110:10-9)
Busbar disconnector closed x
Busbar disconnector open x
Circuit breaker truck in service position x
Circuit breaker truck in test position x

The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
the disconnector position status and the statuses of the master trip logics and gas
pressure alarm and circuit-breaker spring charging. The OKPOS output from the
DCSXSWI block defines if the disconnector or the breaker truck is definitely either

138 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

open (in test position) or close (in service position). This, together with non-active
trip signal and non-active gas pressure alarm, activates the close-enable signal to
the circuit-breaker control function block. The open operation is always enabled.

The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.

If the ENA_CLOSE and BLK_CLOSE signals are completely


removed from the breaker control function block CBXCBR with
PCM600, the function assumes that the breaker close commands
are allowed continuously.

The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 9.

RET615 139
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-FA535501-759C-48BA-A909-76336E08EED8 V2 EN

Figure 106: Common alarm/indication 1 and 2

The signal outputs from the IED are connected to give dedicated information on:

• Start of any protection function SO1 (X100:10-12)


• Operation (trip) of any protection function SO2 (X100:13-15)
• Operation (trip) of any stage of the overcurrent protection function SO1
(X110:14-15-16)

140 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

• Operation (trip) of differential protection function SO2 (X110:17-18-19)


• Operation (trip) of any stage of the earth-fault protection function SO3
(X110:20-21-22)
• Operation (trip) of thermal or current negative-sequence protection function
SO4 (X110:23-24)

TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for
connection where applicable.

3.10 Standard configuration G

3.10.1 Applications

The standard configuration includes three-phase differential, short-circuit,


overcurrent, earth-fault, thermal overload, voltage and negative-phase sequence
protection in power transformer feeders. The standard configuration is mainly
intended for protection of the power transformer between current transformers.

The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.

3.10.2 Functions
Table 51: Functions included in the standard configuration G
Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
PHLPTOC1 3I> (1) 51P-1 (1)
protection, low stage, instance 1
Three-phase non-directional overcurrent
PHLPTOC2 3I> (2) 51P-1 (2)
protection, low stage, instance 2
Three-phase non-directional overcurrent
PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent
PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent
PHIPTOC1 3I>>> (1) 50P/51P (1)
protection, instantaneous stage, instance 1
Three-phase non-directional overcurrent
PHIPTOC2 3I>>> (2) 50P/51P (2)
protection, instantaneous stage, instance 2
Non-directional earth-fault protection, low
EFLPTOC1 Io> (1) 51N-1 (1)
stage, instance 1
Table continues on next page

RET615 141
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Function IEC 61850 IEC 60617 IEC-ANSI


Non-directional earth-fault protection, high
EFHPTOC1 Io>> (1) 51N-2 (1)
stage, instance 1
Negative-sequence overcurrent protection,
NSPTOC1 I2> (1) 46 (1)
instance 1
Negative-sequence overcurrent protection,
NSPTOC2 I2> (2) 46 (2)
instance 2
Residual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1)
Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2)
Three-phase undervoltage protection, instance
PHPTUV1 3U< (1) 27 (1)
1
Three-phase undervoltage protection, instance
PHPTUV2 3U< (2) 27 (2)
2
Three-phase overvoltage protection, instance 1 PHPTOV1 3U> (1) 59 (1)
Three-phase overvoltage protection, instance 2 PHPTOV2 3U> (2) 59 (2)
Three-phase thermal overload protection for
T2PTTR1 3Ith>T 49T
power transformers, two time constants
Stabilized and instantaneous differential
TR2PTDF1 3dI>T 87T
protection for 2W –transformers
High impedance based restricted earth-fault
HREFPDIF1 dIoHi> 87NH
protection
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)
Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)
Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
I <-> O DCC I <-> O DCC
Disconnector control, instance 1 DCXSWI1
(1) (1)
I <-> O DCC I <-> O DCC
Disconnector control, instance 2 DCXSWI2
(2) (2)
Earthing switch control ESXSWI1 I <-> O ESC I <-> O ESC
Disconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
Disconnector position indication, instance 3 DCSXSWI3 I <-> O DC (3) I <-> O DC (3)
Earthing switch indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
Earthing switch indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Tap changer position indication TPOSSLTC1 TPOSM 84M
Condition monitoring
Circuit-breaker condition monitoring SSCBR1 CBCM CBCM
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Table continues on next page

142 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Function IEC 61850 IEC 60617 IEC-ANSI


Fuse failure supervision SEQRFUF1 FUSEF 60
Runtime counter for machines and devices MDSOPT1 OPTS OPTM
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement, instance 1 CMMXU1 3I 3I
Three-phase current measurement, instance 2 CMMXU2 3I(B) 3I(B)
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement, instance 1 RESCMMXU1 Io In
Three-phase voltage measurement VMMXU1 3U 3U
Residual voltage measurement RESVMMXU1 Uo Vn
Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0
Three-phase power and energy measurement PEMMXU1 P, E P, E

3.10.2.1 Default I/O connections


Table 52: Default connections for binary inputs
Binary input Description Connector pins
X110-BI1 Blocking of O/C high stage (high voltage) and X110-1,2
instantaneous stage (low voltage)
X110-BI2 External protection trip X110-3,4
X110-BI3 Circuit breaker low gas pressure alarm X110-5,6
X110-BI4 Circuit breaker spring charged indication X110-7,6
X110-BI5 High-voltage side disconnector closed X110-8,9
X110-BI6 High-voltage side disconnector open X110-10,9
X110-BI7 High-voltage side circuit breaker closed X110-11,12
X110-BI8 High-voltage side circuit breaker open X110-13,12
X130-BI1 Voltage transformer secondary MCB open X130-1,2
X130-BI2 Not assigned as default X130-3,4
X130-BI3 Not assigned as default X130-5,6
X130-BI4 Not assigned as default X130-7,8

Table 53: Default connections for binary outputs


Binary output Description Connector pins
X100-PO1 Close high-voltage circuit breaker X100-6,7
X100-PO2 Breaker failure backup trip to upstream breaker X100-8,9
X100-SO1 General start indication X100-10,11,(12)
X100-SO2 General operate indication X100-13,14
X100-PO3 Open circuit breaker/trip coil 1 high voltage X100-15-19
X100-PO4 Open circuit breaker/trip coil 2 low voltage X100-20-24
Table continues on next page

RET615 143
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Binary output Description Connector pins


X110-SO1 Overcurrent operate alarm X110-14,15,16
X110-SO2 Differential protection operate alarm X110-17,18,19
X110-SO3 Earth fault operate alarm X110-20,21,22
X110-SO4 Combined protection operate alarm X110-23,24

Table 54: Default connections for LEDs


LED Default usage
1 Transformer differential protection biased stage operate
2 Transformer differential protection instantaneous stage operate
3 Overcurrent or earth-fault protection operate
4 Restricted earth-fault protection operate
5 Voltage protection operated
6 Circuit failure protection back-up trip operated
7 NPS or thermal overload protection operated
8 Disturbance recorder triggered
9 TCS, fuse failure, measuring circuit fault or circuit breaker supervision
10 Arc protection operate
11 Protection trip from external device

3.10.2.2 Default disturbance recorder settings

Table 55: Default analog channel selection and text settings


Channel Selection and text
1 IL1
2 IL2
3 IL3
4 IL1B
5 IL2B
6 IL3B
7 Io
8 Uo
9 U1
10 U2
11 U3
12 -

Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the

144 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.

3.10.3 Functional diagrams


The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.

The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings.

The analog channels are assigned to different functions. The common signals
marked with 3I and 3U represent the three phase currents and voltages of the high-
voltage side of the transformer respectively, and 3IB represents the three phase
currents of the low-voltage side of the transformer. The signal marked with Io
represents the measured neutral current measured between the start point of the
transformer and grounding on the high voltage side. The signal marked with Uo
represents the measured residual voltage via open-delta connected voltage
transformers on the high voltage side.

3.10.3.1 Functional diagrams for protection

The functional diagrams describe the IED’s protection functionality in detail and
picture the factory set default connections.

RET615 145
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-56FA9AE4-C0DC-4E61-9BA2-D01B4DE65687 V2 EN

Figure 107: Stabilized and instantaneous differential protection for 2W


transformers

The stabilized and instantaneous differential protection for 2W–transformers


(TR2PTDF1) provides protection of power transformer unit including, for
example, winding short-circuit and interturn faults. The IED compares the phase
currents on both sides of the object to be protected. If the differential current of the
phase currents in one of the phases exceed the setting of the stabilized operation
characteristic or the instantaneous protection stage of the function, the function
provides an operate signal.

For transformers having an on-line tap changer, the tap position information is
recommended to be used in differential protection, as the ratio difference of tap
changer movements can be corrected in TR2PTDF.

146 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

All operate signals are connected to the Master Trip 1 and 2 and also to the alarm
LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for
instantaneous high-stage of the differential protection.

GUID-D8FD1F06-95D6-427E-9975-B41130865CFF V2 EN

Figure 108: Overcurrent and short-circuit protection

RET615 147
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Three stages for both high-voltage and low-voltage sides as a total of six
overcurrent stages are offered for overcurrent and short-circuit protection. The high-
voltage side high stage (PHHPTOC1) can be blocked by energizing the binary
input 1 (X110:1-2) or by starting the high stage of the low-voltage side
(PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by
activating the binary input (X110_BI1).

A selective backup overcurrent protection can be achieved by using blockings


between high-voltage side and low-voltage side overcurrent stages. This kind of
blocking scheme enables coordinated overlapping of overcurrent protection zones.

The operate of the overcurrent protection functions is connected to the output SO1
(X110:14-15-16). This output is used for giving a specific alarm of the overcurrent
protection operation.

GUID-B2CBE815-01C2-4856-8BC1-426815374D99 V1 EN

Figure 109: Non-directional earth-fault protection

Two stages are offered for non-directional earth-fault protection. The earth-fault
protection measures the neutral current of the low-voltage side.

All operate signals are connected to the Master Trip as well as to the alarm LEDs.
LED 3 is used for non-directional earth-fault protection operate indication.

GUID-E2C14CE9-1974-4C13-8AE2-7A062ADF68A0 V1 EN

Figure 110: Restricted high-impedance earth-fault protection

The configuration includes restricted high-impedance earth-fault protection


function for high-voltage side of two-winding power transformers (HREFPDIF1).
The restricted earth-fault current stage operates exclusively on earth faults

148 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

occurring in the protected area, that is, in the area between the phase and neutral
current transformers. An earth fault in this area appears as a differential current
between the residual current of the phase currents and the neutral current of the
conductor between the star-point of the transformer and earth.

GUID-AAA89F5C-737E-460E-8B01-A45F56A945C7 V1 EN

Figure 111: Negative sequence protection

NSPTOC is designed for negative-phase sequence protection whenever the


operating characteristic is appropriate. It is applied for the protection of
transformers against thermal stress and damage.

NSPTOC1 measures negative-sequence current from the high-voltage side and


NSPTOC2 from the low-voltage side.

GUID-CA2DCDB9-3DFA-4CAE-BE98-5EA5923BDB0D V2 EN

Figure 112: Three-phase thermal overload protection for power transformers

Three-phase thermal overload protection for power transformers (T2PTTR1)


provides indication on overload situations. The operate signal of the thermal
overload protection is connected to the Master Trip 2. LED 7 is used for the
thermal overload protection alarm indication, the same as for negative-sequence
overcurrent protection operate indication.

RET615 149
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-8C4ECD1A-D84A-4B87-BAE8-54A1686E161E V1 EN

Figure 113: Overvoltage and undervoltage protection

Two overvoltage and undervoltage protection stages (PHxPTOV and PHxPTUV)


offer protection against abnormal phase voltage conditions. The operation of
voltage functions is connected to alarm LED 5. A failure in the voltage measuring
circuit is detected by the fuse failure function and the activation is connected to
undervoltage protection functions to avoid faulty undervoltage tripping.

GUID-724B9856-A0F8-4711-AD17-B458C4265512 V2 EN

Figure 114: Residual overvoltage protection

150 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

The residual overvoltage protection (ROVPTOV) provides earth-fault protection


by detecting abnormal level of residual voltage. The operation signal is connected
to alarm LED 3.

Figure 115: Circuit-breaker failure protection

The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input
by a number of different protection stages in the IED. CCBRBRF1 offers different
operating modes associated with the circuit-breaker position and the measured
phase and residual currents.

CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for retripping both the high-voltage and low-voltage side circuit
breakers through Master Trip 1 and 2. The TRBU operate output signal is
connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU)
operate indication.

GUID-17B182C7-7A27-4F4D-BB00-6980945E453E V1 EN

Figure 116: Arc protection

Arc protection (ARCSARC1...3) is included as an optional function.

The arc protection offers individual function blocks for three arc sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.

RET615 151
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.10.3.2 Functional diagram for disturbance recorder and trip circuit supervision

GUID-D068A0A3-49B4-4D02-95D1-3DF5F46EAB74 V1 EN

Figure 117: Disturbance recorder

All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, the ARC protection
signals and the four binary inputs from X110 are also connected.

GUID-696685EC-212D-4526-825C-91DCCF4A7134 V1 EN

Figure 118: Trip circuit supervision

152 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.

By default it is expected that there is no external resistor in the


circuit breaker tripping coil circuit connected parallel with circuit
breaker normally open auxiliary contact.

GUID-0A88DBE8-B765-4A96-8BBB-BD824159B0AF V2 EN

Figure 119: Fuse failure supervision and run time counter

The fuse failure supervision SEQRFUF1 detects failures in voltage measurement


circuits. Failures, such as open miniature circuit breaker, are detected and the alarm
is connected to supervision alarm LED 9.

The generic operation time counter function MDSOPT calculates accumulated


operation time of the transformer. The alarm is connected to the alarm LED 9.

RET615 153
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.10.3.3 Functional diagrams for control and interlocking

GUID-1EC3ED90-6920-4B83-B947-B4DFDFC83D59 V1 EN

Figure 120: Master Trip

The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op are connected directly to the output PO3
(X100:15-19).

TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.

The external trip indication is connected also to the alarm LED 11.

154 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-42E5CCDE-2D8E-4E27-83C9-65C3707B10AC V2 EN

Figure 121: Circuit breaker control and disconnector position indication

There are two types of disconnector and earthing switch blocks available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration logic. If controllable operation is preferred, the controllable
type of disconnector and earthing switch blocks can be used instead of the status
only type. The connection and configuration of the control blocks can be done
using PCM600.

The binary inputs 5 and 6 of the additional card X110 are used for busbar
disconnector (DCSXSWI1) or circuit-breaker truck position indication.

Table 56: Device positions indicated by binary inputs 5 and 6


Primary device position Input to be energized
Input 5 (X110:8-9) Input 6 (X110:10-9)
Busbar disconnector closed x
Busbar disconnector open x
Circuit breaker truck in service position x
Circuit breaker truck in test position x

The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
the disconnector position status and the statuses of the master trip logics and gas
pressure alarm and circuit-breaker spring charging. The OKPOS output from the
DCSXSWI block defines if the disconnector or the breaker truck is definitely either

RET615 155
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

open (in test position) or close (in service position). This, together with non-active
trip signal and non-active gas pressure alarm, activates the close-enable signal to
the circuit-breaker control function block. The open operation is always enabled.

The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.

If the ENA_CLOSE and BLK_CLOSE signals are completely


removed from the breaker control function block CBXCBR with
PCM600, the function assumes that the breaker close commands
are allowed continuously.

The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 9.

156 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-8C2D5158-3D5A-4E47-9909-25903815F026 V2 EN

Figure 122: Common alarm indication 1 and 2

The signal outputs from the IED are connected to give dedicated information on:

• Start of any protection function SO1 (X100:10-12)


• Operation (trip) of any protection function SO2 (X100:13-15)
• Operation (trip) of any stage of the overcurrent protection function SO1
(X110:14-15-16)

RET615 157
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

• Operation (trip) of differential protection function SO2 (X110:17-18-19)


• Operation (trip) of any stage of the earth-fault protection function SO3
(X110:20-21-22)
• Operation (trip) of thermal or current negative-sequence protection function
SO4 (X110:23-24)

TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for
connection where applicable.

3.11 Standard configuration H

3.11.1 Applications

The standard configuration includes three-phase transformer differential protection


for two-winding transformers, high impedance based restricted earth-fault
protection for the low-voltage (LV) side, phase voltage based protection and
measurement functions. The standard configuration is mainly intended for
protection of the power transformer between current transformers.

The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.

3.11.2 Functions
Table 57: Functions included in the standard configuration H
Function IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent
PHLPTOC1 3I> (1) 51P-1 (1)
protection, low stage, instance 1
Three-phase non-directional overcurrent
PHLPTOC2 3I> (2) 51P-1 (2)
protection, low stage, instance 2
Three-phase non-directional overcurrent
PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent
PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent
PHIPTOC1 3I>>> (1) 50P/51P (1)
protection, instantaneous stage, instance 1
Three-phase non-directional overcurrent
PHIPTOC2 3I>>> (2) 50P/51P (2)
protection, instantaneous stage, instance 2
Table continues on next page

158 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Function IEC 61850 IEC 60617 IEC-ANSI


Non-directional earth-fault protection, low
EFLPTOC2 Io> (2) 51N-1 (2)
stage, instance 2
Non-directional earth-fault protection, high
EFHPTOC2 Io>> (2) 51N-2 (2)
stage, instance 2
Negative-sequence overcurrent protection,
NSPTOC1 I2> (1) 46 (1)
instance 1
Negative-sequence overcurrent protection,
NSPTOC2 I2> (2) 46 (2)
instance 2
Residual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1)
Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2)
Three-phase undervoltage protection, instance
PHPTUV1 3U< (1) 27 (1)
1
Three-phase undervoltage protection, instance
PHPTUV2 3U< (2) 27 (2)
2
Three-phase overvoltage protection, instance 1 PHPTOV1 3U> (1) 59 (1)
Three-phase overvoltage protection, instance 2 PHPTOV2 3U> (2) 59 (2)
Three-phase thermal overload protection for
T2PTTR1 3Ith>T 49T
power transformers, two time constants
Stabilized and instantaneous differential
TR2PTDF1 3dI>T 87T
protection for 2W –transformers
High impedance based restricted earth-fault
HREFPDIF1 dIoHi> 87NH
protection
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)
Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)
Control
Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB
I <-> O DCC I <-> O DCC
Disconnector control, instance 1 DCXSWI1
(1) (1)
I <-> O DCC I <-> O DCC
Disconnector control, instance 2 DCXSWI2
(2) (2)
Earthing switch control ESXSWI1 I <-> O ESC I <-> O ESC
Disconnector position indication, instance 1 DCSXSWI1 I <-> O DC (1) I <-> O DC (1)
Disconnector position indication, instance 2 DCSXSWI2 I <-> O DC (2) I <-> O DC (2)
Disconnector position indication, instance 3 DCSXSWI3 I <-> O DC (3) I <-> O DC (3)
Earthing switch indication, instance 1 ESSXSWI1 I <-> O ES (1) I <-> O ES (1)
Earthing switch indication, instance 2 ESSXSWI2 I <-> O ES (2) I <-> O ES (2)
Tap changer position indication TPOSSLTC1 TPOSM 84M
Condition monitoring
Circuit-breaker condition monitoring SSCBR1 CBCM CBCM
Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)
Table continues on next page

RET615 159
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Function IEC 61850 IEC 60617 IEC-ANSI


Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)
Fuse failure supervision SEQRFUF1 FUSEF 60
Runtime counter for machines and devices MDSOPT1 OPTS OPTM
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement, instance 1 CMMXU1 3I 3I
Three-phase current measurement, instance 2 CMMXU2 3I(B) 3I(B)
Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0
Residual current measurement, instance 2 RESCMMXU2 Io(B) In(B)
Three-phase voltage measurement VMMXU1 3U 3U
Residual voltage measurement RESVMMXU1 Uo Vn
Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0
Three-phase power and energy measurement PEMMXU1 P, E P, E

3.11.2.1 Default I/O connections

Table 58: Default connections for binary inputs


Binary input Default usage Connector pins
X110-BI1 Blocking of O/C high stage (high voltage) and X110-1,2
instantaneous stage (low voltage)
X110-BI2 External protection trip X110-3,4
X110-BI3 Circuit breaker low gas pressure alarm X110-5,6
X110-BI4 Circuit breaker spring charged indication X110-7,6
X110-BI5 High voltage disconnector closed indication X110-8,9
X110-BI6 High voltage disconnector open indication X110-10,9
X110-BI7 High voltage circuit breaker closed indication X110-11,12
X110-BI8 High voltage circuit breaker open indication X110-13,12
X130-BI1 Voltage transformer secondary MCB open X130-1,2
X130-BI2 Not assigned as default X130-3,4
X130-BI3 Not assigned as default X130-5,6
X130-BI4 Not assigned as default X130-7,8

Table 59: Default connections for binary outputs


Binary output Default usage Connector pins
X100-PO1 Close high-voltage circuit breaker X100-6,7
X100-PO2 Breaker failure backup trip to upstream breaker X100-8,9
X100-SO1 General start indication X100-10,11,(12)
X100-SO2 General operate indication X100-13,14
Table continues on next page

160 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Binary output Default usage Connector pins


X100-PO3 Open circuit breaker/trip coil 1 HV X100-15-19
X100-PO4 Open circuit breaker/trip coil 2 LV X100-20-24
X110-SO1 Overcurrent operate alarm X110-14,15,16
X110-SO2 Differential protection operate alarm X110-17,18,19
X110-SO3 Earth fault operate alarm X110-20,21,22
X110-SO4 Combined protection operate alarm X110-23,24

Table 60: Default connections for LEDs


LED Default usage
1 Transformer differential protection biased stage operate
2 Transformer differential protection instantaneous stage operate
3 Overcurrent or earth-fault protection operate
4 Restricted earth-fault protection operate
5 Voltage protection operated
6 Circuit failure protection back-up trip operated
7 NPS or thermal overload protection operated
8 Disturbance recorder triggered
9 Trip circuit supervision, fuse failure, measuring circuit fault or circuit breaker
supervision
10 Arc protection operate
11 Protection trip from external device

3.11.2.2 Default disturbance recorder settings

Table 61: Default analog channel selection and text settings


Channel Selection and text
1 IL1
2 IL2
3 IL3
4 IL1B
5 IL2B
6 IL3B
7 IoB
8 Uo
9 U1
10 U2
11 U3
12 -

RET615 161
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.

3.11.3 Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.

The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings.

The analog channels are assigned to different functions. The common signal
marked with 3I represents the three phase currents of the high-voltage side of the
transformer and 3IB represents the three phase currents of the low-voltage side of
the transformer. The signal marked with IoB represents the neutral current
measured between the start point of the transformer and grounding on the low
voltage side. The signal marked with Uo represents the measured residual voltage
via open-delta connected voltage transformers on the high voltage side.

3.11.3.1 Functional diagrams for protection

The functional diagrams describe the IED’s protection functionality in detail and
picture the factory set default connections.

162 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-1603E90A-FED5-4063-9307-8D4F62D42921 V2 EN

Figure 123: Stabilized and instantaneous differential protection for 2W–


transformers

The stabilized and instantaneous differential protection for 2W–transformers


(TR2PTDF1) provides protection of power transformer unit including, for
example, winding short-circuit and interturn faults. The IED compares the phase
currents on both sides of the object to be protected. If the differential current of the
phase currents in one of the phases exceed the setting of the stabilized operation
characteristic or the instantaneous protection stage of the function, the function
provides an operate signal.

For transformers having an on-line tap changer, the tap position information is
recommended to be used in differential protection, as the ratio difference of tap
changer movements can be corrected in TR2PTDF.

RET615 163
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

All operate signals are connected to the Master Trip 1 and 2 and also to the alarm
LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for
instantaneous high-stage of the differential protection.

GUID-9FF363C0-C581-47D7-9218-36121D6B5285 V2 EN

Figure 124: Overcurrent and short-circuit protection

164 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Three stages for both high-voltage and low-voltage sides as a total of six
overcurrent stages are offered for overcurrent and short-circuit protection. The high-
voltage side high stage (PHHPTOC1) can be blocked by energizing the binary
input 1 (X110:1-2) or by starting the high stage of the low-voltage side
(PHHPTOC2). Also the low-voltage side instantaneous stage is blocked by
activating the binary input (X110_BI1).

A selective backup overcurrent protection can be achieved by using blockings


between high-voltage side and low-voltage side overcurrent stages. This kind of
blocking scheme enables coordinated overlapping of overcurrent protection zones.

The operate of the overcurrent protection functions is connected to the output SO1
(X110:14-15-16). This output is used for giving a specific alarm of the overcurrent
protection operation.

GUID-0030A115-1F44-480C-9D60-7DC6DC91D081 V1 EN

Figure 125: Non-directional earth-fault protection

Two stages are offered for non-directional earth-fault protection. The earth-fault
protection measures the neutral current of the low-voltage side.

All operate signals are connected to the Master Trip as well as to the alarm LEDs.
LED 3 is used for non-directional earth-fault protection operate indication.

GUID-9D9E76F8-547A-4D73-930F-D2DB10081970 V1 EN

Figure 126: Restricted high-impedance earth-fault protection

The configuration includes restricted high-impedance earth-fault protection


function for low-voltage side of two-winding power transformers (HREFPDIF1).
The restricted earth-fault current stage operates exclusively on earth faults
occurring in the protected area, that is, in the area between the phase and neutral
current transformers. An earth fault in this area appears as a differential current

RET615 165
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

between the residual current of the phase currents and the neutral current of the
conductor between the star-point of the transformer and earth.

GUID-6EF3B245-3E4E-4D0B-8F72-384C074F85CE V1 EN

Figure 127: Negative-phase sequence protection

NSPTOC is designed for negative-phase sequence protection whenever the


operating characteristic is appropriate. It is applied for the protection of
transformers against thermal stress and damage.

NSPTOC1 measures negative-sequence current from the high-voltage side and


NSPTOC2 from the low-voltage side.

GUID-FB2F2B5B-9009-4903-8A73-6225E8DF03DE V2 EN

Figure 128: Thermal overload protection

Three-phase thermal overload protection for power transformers (T2PTTR1)


provides indication on overload situations. The operate signal of the thermal
overload protection is connected to the Master Trip 2. LED 7 is used for the
thermal overload protection alarm indication, the same as for negative-sequence
overcurrent protection operate indication.

166 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-DFAAC066-D9D5-4188-B371-1A2DE2CACF4B V1 EN

Figure 129: Overvoltage and undervoltage protection

Two overvoltage and undervoltage protection stages (PHxPTOV and PHxPTUV)


offer protection against abnormal phase voltage conditions. The operation of
voltage functions is connected to alarm LED 5. A failure in the voltage measuring
circuit is detected by the fuse failure function and the activation is connected to
undervoltage protection functions to avoid faulty undervoltage tripping.

GUID-3A11CB90-5E73-488A-8D9B-362487AE218B V2 EN

Figure 130: Residual overvoltage protection

RET615 167
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

The residual overvoltage protection (ROVPTOV) provides earth-fault protection


by detecting abnormal level of residual voltage. The operation signal is connected
to alarm LED 3.

GUID-98E5309A-F88B-4BDB-9EFA-DF9D1E2C8A7C V1 EN

Figure 131: Circuit-breaker failure protection

The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input
by a number of different protection stages in the IED. CCBRBRF1 offers different
operating modes associated with the circuit-breaker position and the measured
phase and residual currents.

CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for retripping both the high-voltage and low-voltage side circuit
breakers through Master Trip 1 and 2. The TRBU operate output signal is
connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU)
operate indication.

GUID-D3FFC16D-D97F-4EB5-B851-677E2E41CE9E V1 EN

Figure 132: Arc protection

168 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Arc protection (ARCSARC1...3) is included as an optional function.

The arc protection offers individual function blocks for three arc sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.

3.11.3.2 Functional diagram for disturbance recorder and supervision functions

GUID-A788BFC0-0EBA-4451-AC0B-6D56B37ADEB4 V1 EN

Figure 133: Disturbance recorder

All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, the ARC protection
signals and the four binary inputs from X110 are also connected.

RET615 169
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-29073B9E-44C7-4622-AB1E-6ECBBF6FAF0F V1 EN

Figure 134: Trip circuit supervision

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.

By default it is expected that there is no external resistor in the


circuit breaker tripping coil circuit connected parallel with circuit
breaker normally open auxiliary contact.

GUID-F6B3D3D0-6A64-4852-8533-6491AC0D8DB5 V2 EN

Figure 135: Fuse failure supervision and runtime counter

The fuse failure supervision SEQRFUF1 detects failures in voltage measurement


circuits. Failures, such as open miniature circuit breaker, are detected and the alarm
is connected to supervision alarm LED 9.

The generic operation time counter function MDSOPT calculates accumulated


operation time of the transformer. The alarm is connected to the alarm LED 9.

170 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

3.11.3.3 Functional diagrams for control and interlocking

GUID-B306F9D8-14BC-42A3-9C3D-2190AB0468FB V1 EN

Figure 136: Master Trip

The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op are connected directly to the output PO3
(X100:15-19).

TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.

The external trip indication is connected also to the alarm LED 11.

RET615 171
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-8335EE7E-3951-434C-8B1D-D19DD3FEF1C6 V2 EN

Figure 137: Circuit breaker control and disconnector position indication

There are two types of disconnector and earthing switch blocks available.
DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and
ESXSWI1 are controllable type. By default, the status only blocks are connected in
standard configuration logic. If controllable operation is preferred, the controllable
type of disconnector and earthing switch blocks can be used instead of the status
only type. The connection and configuration of the control blocks can be done
using PCM600.

The binary inputs 5 and 6 of the additional card X110 are used for busbar
disconnector (DCSXSWI1) or circuit-breaker truck position indication.

Table 62: Device positions indicated by binary inputs 5 and 6


Primary device position Input to be energized
Input 5 (X110:8-9) Input 6 (X110:10-9)
Busbar disconnector closed x
Busbar disconnector open x
Circuit breaker truck in service position x
Circuit breaker truck in test position x

The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
the disconnector position status and the statuses of the master trip logics and gas
pressure alarm and circuit-breaker spring charging. The OKPOS output from the
DCSXSWI block defines if the disconnector or the breaker truck is definitely either

172 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

open (in test position) or close (in service position). This, together with non-active
trip signal and non-active gas pressure alarm, activates the close-enable signal to
the circuit-breaker control function block. The open operation is always enabled.

The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.

If the ENA_CLOSE and BLK_CLOSE signals are completely


removed from the breaker control function block CBXCBR with
PCM600, the function assumes that the breaker close commands
are allowed continuously.

The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 9.

RET615 173
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-81A0A8A4-B3F6-4571-AE68-1B5B24260E95 V2 EN

Figure 138: Common alarm/indication 1 and 2

The signal outputs from the IED are connected to give dedicated information on:

• Start of any protection function SO1 (X100:10-12)


• Operation (trip) of any protection function SO2 (X100:13-15)
• Operation (trip) of any stage of the overcurrent protection function SO1
(X110:14-15-16)

174 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

• Operation (trip) of differential protection function SO2 (X110:17-18-19)


• Operation (trip) of any stage of the earth-fault protection function SO3
(X110:20-21-22)
• Operation (trip) of thermal or current negative-sequence protection function
SO4 (X110:23-24)

TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for
connection where applicable.

3.12 Standard configuration J

3.12.1 Applications

The standard configuration J provides mainly three-phase differential protection


and non-electrical protection for power transformer feeders. The standard
configuration is mainly intended for protection of the power transformer between
current transformers.

The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.

3.12.2 Functions

Table 63: Functions included in the standard configuration J


Functionality IEC 61850 IEC 60617 IEC-ANSI
Protection
Stabilized and instantaneous differential TR2PTDF1 3dI>T 87T
protection for two-winding transformers
High impedance-based restricted earth- HREFPDIF1 dI0Hi> 87NH
fault
Circuit breaker failure protection (HV side) CCBRBRF1 3I>/Io>BF 51BF/51NBF
Arc protection (LV side) ARCSARC1 ARC(1) 50L/50NL(1)
ARCSARC2 ARC(2) 50L/50NL(2)
ARCSARC3 ARC(3) 50L/50NL(3)
Multi-purpose protection, instance 1 MAPGAPC1 MAP (1) MAP (1)
Multi-purpose protection, instance 2 MAPGAPC1 MAP (2) MAP (2)
Control
Table continues on next page

RET615 175
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Functionality IEC 61850 IEC 60617 IEC-ANSI


Circuit-breaker control CBXCBR1 I ↔ O CB I ↔ O CB
Disconnector position indication DCSXSWI1 I ↔ O DC(1) I ↔ O DC(1)
DCSXSWI 2 I ↔ O DC(2) I ↔ O DC(2)
DCSXSWI 3 I ↔ O DC(3) I ↔ O DC(3)
Earthing switch indication ESSXSWI1 I ↔ O ES I ↔ O ES
Tap changer position indication TPOSSLTC1 TPOSM 84M
Condition monitoring
Circuit breaker condition monitoring (HV SSCBR1 CBCM CBCM
side)
Trip circuit supervision TCSSCBR1 TCS(1) TCM(1)
TCSSCBR2 TCS(2) TCM(2)
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement (HV CMMXU1 3I 3I
side)
Three-phase current measurement (LV CMMXU2 3I(B) 3I(B)
side)
Sequence current measurement (HV side) CSMSQI1 I1,I2,I0 I1,I2,I0
Sequence current measurement (LV side) CSMSQI2 I1,I2,I0(B) I1,I2,I0(B)

3.12.2.1 Default I/O connections

Table 64: Default connections for binary inputs


Binary input Description Connector pins
X110-BI1 External protection trip 1 X110-1,2
X110-BI2 External protection trip 2 X110-3,4
X110-BI3 Low-voltage side circuit breaker closed X110-5,6
X110-BI4 Circuit breaker spring charged X110-7,6
X110-BI5 External protection alarm 1 X110-8,9
X110-BI6 External protection alarm 2 X110-10,9
X110-BI7 High-voltage side circuit breaker closed X110-11,12
X110-BI8 High-voltage side circuit breaker open X110-13,12
X130-BI1 BCD sign bit (tap changer position) X130-1,2
X130-BI2 BCD bit 1, LSB X130-3,2
X130-BI3 BCD bit 2 X130-4,5
X130-BI4 BCD bit 3 X130-6,5
X130-BI5 BCD bit 4 X130-7,8
X130-BI6 BCD bit 5, MSB X130-9,8

176 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Table 65: Default connections for binary outputs


Binary output Description Connector pins
X100-PO1 Close high-voltage circuit breaker X100-6,7
X100-PO2 Breaker failure backup trip to upstream breaker X100-8,9
X100-SO1 General start indication X100-10,11,(12)
X100-SO2 General operate indication X100-13,14
X100-PO3 Open circuit breaker/trip coil 1 high voltage X100-15-19
X100-PO4 Open circuit breaker/trip coil 2 low voltage X100-20-24
X110-SO1 Differential protection operate alarm X110-14,15,16
X110-SO2 High impedance-based restricted earth-fault X110-17,18,19
protection operate alarm
X110-SO3 External protection trip X110-20,21,22
X110-SO4 External protection alarm X110-23,24

Table 66: Default connections for LEDs


LED Default usage
1 Transformer differential protection biased stage operate
2 Transformer differential protection instantaneous stage operate
3 High impedance-based restricted earth-fault protection operate
4 External protection trip 1
5 External protection trip 2
6 Circuit failure protection backup trip operated
7 Disturbance recorder triggered
8 Circuit breaker condition monitoring
9 Trip circuit supervision, measuring circuit fault or circuit breaker supervision
10 External protection alarm 1
11 External protection alarm 2

3.12.2.2 Default disturbance recorder settings

Table 67: Default analog channel selection and text settings


Channel Selection and text
1 IL1
2 IL2
3 IL3
4 IL1B
5 IL2B
6 IL3B
7 Io
Table continues on next page

RET615 177
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Channel Selection and text


8 -
9 -
10 -
11 -
12 -

Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.

3.12.3 Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.

The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings.

The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with 3I_A represents the three phase
currents of the high-voltage side of the transformer and 3I_B represents the three
phase currents of the low-voltage side of the transformer. The signal marked with
Io_difA represents the dedicated differential neutral current measured between the
start point of the transformer and grounding on the high-voltage side, and Io_difB
represents the current on the low-voltage side.

3.12.3.1 Functional diagrams for protection

The functional diagrams describe the IED’s protection functionality in detail and
picture the factory set default connections.

178 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-86C475D1-77C5-4483-8B3E-EE1AC79E347D V1 EN

Figure 139: Stabilized and instantaneous differential protection for 2W–


transformers (HREFPDIF for high-voltage side)

RET615 179
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-F2337257-97CE-491D-9A1D-C8879763324A V1 EN

Figure 140: Stabilized and instantaneous differential protection for 2W–


transformers (HREFPDIF for low-voltage side)

The stabilized and instantaneous differential protection for 2W–transformers


(TR2PTDF1) provides protection of power transformer unit including, for
example, winding short-circuit and interturn faults. The IED compares the phase
currents on both sides of the object to be protected. If the differential current of the
phase currents in one of the phases exceed the setting of the stabilized operation
characteristic or the instantaneous protection stage of the function, the function
provides an operate signal.

For transformers having an on-line tap changer, the tap position information is
recommended to be used in differential protection, as the ratio difference of tap
changer movements can be corrected in TR2PTDF.

All operate signals are connected to the Master Trip 1 and 2 and also to the alarm
LEDs. LED 1 is used for biased low-stage operate indication and LED 2 for
instantaneous high-stage of the differential protection.

180 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

RESTRICTED EARTH-FAULT

HREFPDIF(1)
I0 Hi>

87NH
I0_difA I0 START REF_START
(I0_difB)
BLOCK OPERATE REF_OPERATE

LED3

GUID-A4AF8DDC-F04C-4AEE-A2BD-F387065357BF V1 EN

Figure 141: Restricted high-impedance earth-fault protection

The configuration includes restricted high-impedance earth-fault protection


function for two-winding power transformers (HREFPDIF1). HREFPDIF could be
used for either high-voltage side or low-voltage side, depending on the differential
residual current provided for the analog channel Io.

The earth-fault current stage operates exclusively on earth faults occurring in the
protected area, that is, in the area between the phase and neutral current
transformers. An earth fault in this area appears as a differential current between
the residual current of the phase currents and the neutral current of the conductor
between the star-point of the transformer and earth.

GUID-E8BAFEE3-2965-432A-A1C5-1FDDDC54C4FD V1 EN

Figure 142: Circuit-breaker failure protection

The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input
by a number of different protection stages in the IED. CCBRBRF1 offers different
operating modes associated with the circuit-breaker position and the measured
phase and residual currents. CCBRBRF1 has two operating outputs: TRRET and

RET615 181
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

TRBU. The TRRET operate output is used for retripping both the high-voltage and
low-voltage side circuit breakers through Master Trip 1 and 2. The TRBU operate
output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for backup
(TRBU) operate indication.

GUID-2F782865-C844-474E-ABF6-B6842E8E780D V1 EN

Figure 143: Arc protection

Arc protection (ARCSARC1...3) is included as an optional function. The arc


protection offers individual function blocks for three arc sensors that can be
connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip.

182 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

3.12.3.2 Functional diagrams for disturbance recorder and supervision

GUID-CBC72B54-EA6E-495A-B669-286ED9C88ED2 V1 EN

Figure 144: Disturbance recorder

The disturbance recorder has 64 digital inputs out of which 19 are connected as a
default. All start and operate signals from the protection stages are routed to trigger
the disturbance recorder or alternatively only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, the arc protection
signals and seven binary inputs from X110 are also connected.

RET615 183
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-0DF909DC-BD57-45F9-8542-CDB931202409 V1 EN

Figure 145: Trip circuit supervision

Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). TCSSCBR1 is blocked
when high-voltage side circuit breaker is not closed and also blocked by Master
trip 1 (TRPPTRC1). TCSSCBR2 is blocked when low-voltage side circuit breaker
is not closed and also blocked by Master trip 2 (TRPPTRC2). The TCS alarm
indication is connected to LED 9.

3.12.3.3 Functional diagrams for control and interlocking

MVGAPC1
I1 Q1 MVGAPC1 Q1
I2 Q2 MVGAPC1 Q 2
I3 Q3 MVGAPC1 Q 3
I4 Q4 MVGAPC1 Q 4

GUID-167B5ADF-B97A-4A39-A055-334C03B62A32 V1 EN

Figure 146: Master Trip

184 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op are connected directly to the output PO3
(X100:15-19).

TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.

The external protection trip and alarm signals for non-electrical protection are also
connected to LED 4, LED 5, LED 10 and LED 11.

GUID-6D44365E-82E7-40B8-B098-CB80F7E4B220 V1 EN

Figure 147: Circuit breaker control

There are three disconnector status blocks (DCSXSWI1…3) available in the IED.
They are available in PCM600 for connection where applicable.

The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
the statuses of the master trip logic and circuit-breaker spring charging. The open
operation is always enabled.

The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.

RET615 185
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 8.

MVGAPC1 Q1

MVGAPC1 Q 2

MVGAPC1 Q 3
MVGAPC1 Q 4

GUID-0A5EAAE3-FA87-4FCB-814C-7586BC05DC10 V1 EN

Figure 148: Common alarm/indication 1 and 2

The signal outputs from the IED are connected to give dedicated information on:

• Start of any protection function SO1 (X100:10-12)


• Operation (trip) of any protection function SO2 (X100:13-14)
• Operation (trip) of differential protection function SO1 (X110:14-15-16)
• Operation (trip) of high impedance restricted earth fault protection function
SO2(X110:17-18-19)
• External protection trip signals SO3 (X110:20-21-22)
• External protection alarm signals SO4 (X110:23-24)

186 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for
connection where applicable.

GUID-43684E97-B173-4BBB-B7F4-219AA9A2E8B4 V1 EN

Figure 149: Tap changer position indication

To increase the sensitivity of the stabilized differential function, the tap position
information from the tap changer is connected to the IED via the tap changer
position indication function TPOSSLTC1. TPOSSLTC1 is connected to the binary
inputs of the X130 BIO card or alternatively to the mA input of the RTD card.
TPOSSLTC1 uses binary-coded methods to generate the integer value of the tap
changer position.

3.13 Standard configuration K

3.13.1 Applications

The standard configuration K, with three-phase short-circuits, overcurrent, earth-


fault, thermal overload and negative-phase sequence protection functions, provides
backup protection for the power transformer.

The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.

RET615 187
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.13.2 Functions
Table 68: Functions included in the standard configuration K
Functionality IEC 61850 IEC 60617 IEC-ANSI
Protection
Three-phase non-directional overcurrent PHLPTOC1 3I>(1) 51P-1(1)
protection, low stage (HV side)
Three-phase non-directional overcurrent PHLPTOC2 3I> (2) 51P-1(2)
protection, low stage (LV side)
Three-phase non-directional overcurrent PHHPTOC1 3I>>(1) 51P-2(1)
protection, high stage (HV side)
Three-phase non-directional overcurrent PHHPTOC2 3I>>(2) 51P-2(2)
protection, high stage (LV side)
Three-phase non-directional overcurrent PHIPTOC1 3I>>>(1) 50P/51P(1)
protection, instantaneous stage (HV side)
Three-phase non-directional overcurrent PHIPTOC2 3I>>>(2) 50P/51P(2)
protection, instantaneous stage (LV side)
Non-directional earth-fault protection, low EFLPTOC1 I0>(1) 51N-1(1)
stage (HV side)
Non-directional earth-fault protection, low EFLPTOC2 I0>(2) 51N-1(2)
stage, using calculated Io (LV side)
Non-directional earth-fault protection, high EFHPTOC1 I0>>(1) 51N-2(1)
stage (HV side)
Non-directional earth-fault protection, high EFHPTOC2 I0>>(2) 51N-2(2)
stage, using calculated Io (LV side)
Negative-sequence overcurrent NSPTOC1 I2>(1) 46(1)
protection, instance 1 (HV side)
Negative-sequence overcurrent NSPTOC2 I2>(2) 46(2)
protection, instance 2 (LV side)
Negative-sequence overcurrent NSPTOC3 I2>(3) 46(3)
protection, instance 3 (HV side)
Negative-sequence overcurrent NSPTOC4 I2>(4) 46(4)
protection, instance 4 (LV side)
Three phase over voltage protection, PHPTOV1 3U>(1) 59(1)
instance 1
Three phase over voltage protection, PHPTOV2 3U>(2) 59(2)
instance 2
Three phase under voltage protection, PHPTUV1 3U<(1) 27(1)
instance 1
Three phase under voltage protection, PHPTUV2 3U<(2) 27(2)
instance 2
Residual over voltage protection, instance ROVPTOV1 U0>(1) 59G(1)
1
Residual over voltage protection, instance ROVPTOV2 U0>(2) 59G(2)
2
Low impedance-based restricted earth- LREFPNDF1 dI0Lo> 87NL
fault
Three-phase thermal protection for power T2PTTR1 3Ith>T 49T
transformers, two time constants (HV side)
Table continues on next page

188 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

Functionality IEC 61850 IEC 60617 IEC-ANSI


Circuit breaker failure protection (HV side) CCBRBRF1 3I>/Io>BF 51BF/51NBF
Arc protection (LV side) ARCSARC1 ARC(1) 50L/50NL(1)
ARCSARC2 ARC(2) 50L/50NL(2)
ARCSARC3 ARC(3) 50L/50NL(3)
Control
Circuit-breaker control CBXCBR1 I ↔ O CB I ↔ O CB
Disconnector position indication DCSXSWI1 I ↔ O DC(1) I ↔ O DC(1)
DCSXSWI 2 I ↔ O DC(2) I ↔ O DC(2)
DCSXSWI 3 I ↔ O DC(3) I ↔ O DC(3)
Earthing switch indication ESSXSWI1 I ↔ O ES I ↔ O ES
Condition monitoring
Circuit breaker condition monitoring (HV SSCBR1 CBCM CBCM
side)
Fuse failure supervision SEQRFUF1 FUSEF 60
Trip circuit supervision TCSSCBR1 TCS(1) TCM(1)
TCSSCBR2 TCS(2) TCM(2)
Measurement
Disturbance recorder RDRE1 - -
Three-phase current measurement (HV CMMXU1 3I 3I
side)
Three-phase current measurement (LV CMMXU2 3I(B) 3I(B)
side)
Sequence current measurement (HV side) CSMSQI1 I1,I2,I0 I1,I2,I0
Sequence current measurement (LV side) CSMSQI2 I1,I2,I0(B) I1,I2,I0(B)
Tap changer position indication TPOSSLTC1 TPOSM 84M

3.13.2.1 Default I/O connections

Table 69: Default connections for binary inputs


Binary input Description Connector pins
X110-BI1 Backup X110-1,2
X110-BI2 Backup X110-3,4
X110-BI3 High-voltage side circuit breaker closed X110-5,6
X110-BI4 Circuit breaker spring charged X110-7,6
X110-BI5 Backup X110-8,9
X110-BI6 Backup X110-10,9
X110-BI7 Low-voltage side circuit breaker closed X110-11,12
X110-BI8 Low-voltage side circuit breaker open X110-13,12
X130-BI1 Backup X130-1,2
Table continues on next page

RET615 189
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

Binary input Description Connector pins


X130-BI2 Backup X130-3,4
X130-BI3 Backup X130-5,6
X130-BI4 Backup X130-7,8

Table 70: Default connections for binary outputs


Binary output Description Connector pins
X100-PO1 Close low-voltage circuit breaker X100-6,7
X100-PO2 Breaker failure backup trip to upstream breaker X100-8,9
X100-SO1 General start indication X100-10,11,(12)
X100-SO2 General operate indication X100-13,14
X100-PO3 Open circuit breaker/trip coil 1 high voltage X100-15-19
X100-PO4 Open circuit breaker/trip coil 2 low voltage X100-20-24
X110-SO1 Low impedance-based restricted earth-fault protection X110-14,15,16
operate alarm
X110-SO2 Overcurrent operate alarm X110-17,18,19
X110-SO3 Earth fault operate alarm X110-20,21,22
X110-SO4 Negative sequence overcurrent operate alarm X110-23,24

Table 71: Default connections for LEDs


LED Default usage
1 Low impedance-based restricted earth-fault protection operate
2 Non-directional overcurrent protection operate
3 Earth fault protection operate
4 Negative sequence overcurrent operate
5 Thermal overload alarm
6 Circuit failure protection backup trip operate
7 Disturbance recorder triggered
8 Circuit breaker condition monitoring
9 Circuit supervision alarm
10 Voltage protection operate
11 Arc protection operate

190 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

3.13.2.2 Default disturbance recorder settings


Table 72: Default analog channel selection and text settings
Channel Selection and text
1 IL1
2 IL2
3 IL3
4 IL1B
5 IL2B
6 IL3B
7 Io
8 U1
9 U2
10 U3
11 -
12 -

Additionally, all the digital inputs that are connected by default are also enabled
with the setting. Default triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to
trigger the disturbance recorded by default.

3.13.3 Functional diagrams

The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.

The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings.

The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with 3I_A represents the three phase
currents of the high-voltage side of the transformer and 3I_B represents the three
phase currents of the low-voltage side of the transformer. The signal marked with
Io_A represents the neutral current measured between the start point of the
transformer and grounding on the high-voltage side and Io_B represents the
calculated residual current of low-voltage side.

RET615 191
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

3.13.3.1 Functional diagrams for protection

The functional diagrams describe the IED’s protection functionality in detail and
picture the factory set default connections.

GUID-C4311413-47DB-4C34-99B2-5E16F18E6DD3 V1 EN

Figure 150: Overcurrent and short-circuit protection

Three stages for both high-voltage and low-voltage sides as a total of six
overcurrent stages are offered for overcurrent and short-circuit protection.

LED 2 is used for overcurrent and short-current protection operate alarm.

The operate output of the overcurrent protection functions is connected to the


output SO2 (X110:17-18-19). This output is used for giving a specific alarm of the
overcurrent protection operation.

192 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-45FCFD7A-0916-47D4-9EB1-C3E99963439A V1 EN

Figure 151: Non-directional earth-fault protection

Two stages for both high-voltage and low-voltage sides (as a total of four stages)
are offered for earth-fault protection.

The high-voltage side earth-fault protections measure the neutral current of the high-
voltage side, and the low-voltage side earth-fault protections are based on the
calculated residual current.

All operate signals are connected to the Master Trip and to the alarm LEDs. LED 3
is used for non-directional earth-fault protection operate indication.

RET615 193
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

RESTRICTED EARTH_FAULT

LREFPNDF(1)
I0 L0>

87NL
3I_A 3I START REF_START
I0_A I0
OPERATE REF_OPERATE
BLOCK

LED1

GUID-D36B26FE-1DE8-4F3C-92EC-73D93D10C021 V1 EN

Figure 152: Restricted low-impedance earth-fault protection

The configuration includes restricted low-impedance earth-fault protection function


for high-voltage side of two-winding power transformers (LREFPNDF1). The
numerical differential current stage operates exclusively on earth faults occurring
in the protected area, that is, in the area between the phase and neutral current
transformers. An earth fault in this area appears as a differential current between
the residual current of the phase currents and the neutral current of the conductor
between the star-point of the transformer and earth. LED 1 is used for low-
impedance earth-fault protection operate alarm.

194 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

GUID-41899556-D0E8-404B-8BFC-B569E30FCEE5 V1 EN

Figure 153: Negative-sequence overcurrent protection

NSPTOC is designed for negative-phase sequence protection whenever the


operating characteristic is appropriate. It is applied for the protection of
transformers against thermal stress and damage.

RET615 195
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

NSPTOC1 and NSPTOC3 measure negative-sequence current from the high-


voltage side and NSPTOC2 and NSPTOC4 from the low-voltage side.

LED4 is used for negative sequence overcurrent protection operate alarm.

PHPTOV1
3U> (1)

59(1)
3U START
BLOCK OPERATE

PHPTOV2
3U> (2)

59(2)
3U START
BLOCK OPERATE

PHPTUV1
3U< (1)
OR
27(1)
3U START LED10
(Voltage Protection Operate)
SEQRFUF_FUSEF_U BLOCK OPERATE

PHPTUV2
3U< (2)

27(2)
3U START
SEQRFUF_FUSEF_U BLOCK OPERATE

ROVPTOV1
U0> (1)
OR

59G(1) LED3
U0 START (EF Operate)
BLOCK OPERATE

ROVPTOV2
U0> (2)

59G(2)
U0 START
BLOCK OPERATE

GUID-077F070B-DB7B-4C22-992E-7EEB7AC91E4E V1 EN

Figure 154: Voltage protection

Two overvoltage and undervoltage protection stages (PHxPTOV and PHxPTUV)


offer protection against abnormal phase voltage conditions. The operation of
voltage functions is connected to alarm LED 10. A failure in the voltage measuring

196 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

circuit is detected by the fuse failure function and the activation is connected to
undervoltage protection functions to avoid faulty undervoltage tripping.

The residual overvoltage protection (ROVPTOV) provides earth-fault protection


by detecting abnormal level of residual voltage. The operation signal is connected
to alarm LED 3.

GUID-AC33B856-5FF6-4C72-A281-0BF53AD0374E V1 EN

Figure 155: Three-phase thermal overload protection for power transformers

Three-phase thermal overload protection for power transformers (T2PTTR1)


provides indication on overload situations. The operate signal of the thermal
overload protection is connected to the Master Trip 1. LED 5 is used for the
thermal overload protection alarm indication.

GUID-F48180D9-E410-4BED-B729-46D0BD7A7E2B V1 EN

Figure 156: Circuit-breaker failure protection

The circuit-breaker failure protection (CCBRBRF1) is initiated via the start input
by a number of different protection stages in the IED. CCBRBRF1 offers different
operating modes associated with the circuit breaker position and the measured
phase and residual currents.

CCBRBRF1 has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for retripping both the high-voltage and low-voltage side circuit
breakers through Master Trip 1 and 2. The TRBU operate output signal is
connected to the output PO2 (X100: 8-9). LED 6 is used for backup (TRBU)
operate indication.

RET615 197
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-2229E3AF-85E6-41A8-A9B6-B29BBD9E36A5 V1 EN

Figure 157: Arc protection

Arc protection (ARCSARC1...3) is included as an optional function. The arc


protection offers individual function blocks for three arc sensors that can be
connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip.

198 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

3.13.3.2 Functional diagrams for disturbance recorder and supervision

DISTURBANCE RECORDER

RDRE
PHLPTOC1_START C1 TRIGGERED LED7
PHHPTOC1_START C2
PHIPTOC1_START C3
PHLPTOC2_START C4
PHHPTOC2_START C5
PHIPTOC2_START C6
EFLPTOC1_START C7
EFHPTOC1_START C8
EFLPTOC2_START C9
EFHPTOC2_START C10
NSPTOC1_START C11
NSPTOC3_START C12
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE OR NSPTOC2_START C13
PHIPTOC1_OPERATE NSPTOC4_START C14
REF_START C15
PHLPTOC2_OPERATE T2PTTR1_START C16
PHHPTOC2_OPERATE OR C17
CCBRBRF1_TRRET
PHIPTOC2_OPERATE CCBRBRF1_TRBU C18
C19
EFLPTOC1_OPERATE OR C20
EFHPTOC1_OPERATE
C21
EFLPTOC2_OPERATE OR C22
EFHPTOC2_OPERATE
C23
C24
NSPTOC1_OPERATE REF_OPERATE C25
OR T2PTTR1_ALARM C26
NSPTOC3_OPERATE
T2PTTR1_OPERATE C27
NSPTOC2_OPERATE
OR T2PTTR1_BLK_CLOSE C28
NSPTOC4_OPERATE
C29
ARCSARC1_ARC_FLT_DET
ARCSARC2_ARC_FLT_DET C30
OR X110_BI7(LV CB CLOSED) C31
ARCSARC3_ARC_FLT_DET X110_BI8(LV CB OPEN) C32
ARCSARC1_OPERATE X110_BI3(HV CB CLOSED) C33
ARCSARC2_OPERATE OR ROVPTOV1_START C34
ARCSARC3_OPERATE ROVPTOV2_START C35
PHPTOV1_START C36
PHPTOV2_START C37
PHPTUV1_START C38
PHPTUV2_START C39
ROVPTOV1_OPERATE OR C40
ROVPTOV2_OPERATE
C41
PHPTOV1_OPERATE C42
OR
PHPTOV2_OPERATE SEQRFUF1_FUSEF_3PH C43
PHPTUV1_OPERATE SEQRFUF1_FUSEF_U C44
OR
PHPTUV2_OPERATE MDSOPT_ALARM C45
C46
C47
C48
C49
C50
C51
C52
C53
C54
C55
C56
C57
C58
C59
C60
C61
C62
C63
C64

GUID-5186BB2A-AA2D-47D6-83A5-84C2139D91A7 V1 EN

Figure 158: Disturbance recorder

The disturbance recorder has 64 digital inputs out of which 45 are connected as a
default. All start and operate signals from the protection stages are routed to trigger
the disturbance recorder or alternatively only to be recorded by the disturbance
recorder depending on the parameter settings. Additionally, the arc protection
signals and three binary inputs from X110 are also connected.

LED 7 is used as indication when disturbance recorder is triggered.

RET615 199
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

SUPERVISION

TRPPTRC1_TRIP
X110_BI3
(HV CB Closed)

TRPPTRC2_TRIP
X110_BI7
(LV CB Closed)

X110_BI3
(HV CB Closed)

GUID-8B608345-E898-4AA8-BD1C-15E0F18518AA V1 EN

Figure 159: Circuit supervision

Two separate trip circuit supervision functions are included: TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). TCSSCBR1 is blocked
when high-voltage side circuit breaker is not closed. TCSSCBR1 is also blocked by
Master trip 1 (TRPPTRC1). TCSSCBR2 is blocked when low-voltage side circuit
breaker is not closed. TCSSCBR2 is also blocked by Master trip 2 (TRPPTRC2).
The TCS alarm indication is connected to LED 9.

The fuse failure supervision function SEQRFUF1 is used to block the voltage
measuring functions at failures in the secondary circuits between the voltage
transformer and the IED to avoid unwanted operations that might occur otherwise.
The fuse failure alarm of SEQRFUF1 is also connected to LED 9.

200 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

3.13.3.3 Functional diagrams for control and interlocking

REF_OPERATE
PHIPTOC1_OPERATE
PHHPTOC1_OPERATE
PHLPTOC1_OPERATE
EFHPTOC1_OPERATE
EFLPTOC1_OPERATE OR
NSPTOC1_OPERATE
TRPPTRC1_TRIP
NSPTOC3_OPERATE
X100
CCBRBRF1_TRRET RST_LKOUT +
With lock-out mode 16
ROVPTOV1_OPERATE Open HV
selection PO3
ROVPTOV2_OPERATE CB/
PHPTOV1_OPERATE 17
Trip coil 1
PHPTOV2_OPERATE 15
19
PHPTUV1_OPERATE TCS1 18
PHPTUV2_OPERATE

REF_OPERATE
PHIPTOC1_OPERATE MASTER TRIP 2(LV SIDE)
PHHPTOC1_OPERATE
PHLPTOC1_OPERATE
EFHPTOC1_OPERATE
EFLPTOC1_OPERATE
PHIPTOC2_OPERATE TRPPTRC2
PHHPTOC2_OPERATE BLOCK TRIP TRPPTRC2_TRIP X100
PHLPTOC2_OPERATE OR OPERATE CL_LKOUT
+
EFHPTOC2_OPERATE RST_LKOUT 20
EFLPTOC2_OPERATE
With lock-out mode
22
selection Open LV
NSPTOC1_OPERATE PO4
CB/
NSPTOC2_OPERATE 21 Trip coil 2
NSPTOC3_OPERATE OR 23
NSPTOC4_OPERATE 24
ARCSAC1_OPERATE TCS2
CBXCBR_EXE_OP
ARCSAC2_OPERATE
ARCSAC3_OPERATE
T2PTTR1_OPERATE
ROVPTOV1_OPERATE
ROVPTOV2_OPERATE
PHPTOV1_OPERATE
PHPTOV2_OPERATE
PHPTUV1_OPERATE
PHPTUV2_OPERATE

GUID-674D65F9-D71D-4C52-861E-891CD5AA7D29 V1 EN

Figure 160: Master trip

The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op are connected directly to the output PO4
(X100:20-24).

TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.

RET615 201
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

GUID-C3F3BDA2-5149-4A98-B0F9-106D98B7BD4C V1 EN

Figure 161: Circuit breaker control

There are three disconnector status blocks (DCSXSWI1…3) available in the IED.
They are available in PCM600 for connection where applicable.

The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
the statuses of the master trip logic and circuit-breaker spring charging. The open
operation is always enabled.

The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.

The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 8.

202 RET615
Application Manual
1YHT530003D05 C Section 3
RET615 standard configurations

COMMON ALARM/INDICATION 1&2

PHIPTOC1_START
PHHPTOC1_START
PHLPTOC1_START
PHIPTOC2_START
PHHPTOC2_START
PHLPTOC2_START
EFHPTOC1_START
EFLPTOC1_START
EFHPTOC2_START
EFLPTOC2_START
NSPTOC1_START
NSPTOC3_START OR
NSPTOC2_START
NSPTOC4_START
REF_START
T2PTTR1_START
ROVPTOV1_START + X100
ROVPTOV2_START
PHPTOV1_START 10
Start
PHPTOV2_START SO1
Indication
PHPTUV1_START 11
PHPTUV2_START TPGAPC1 12
IN1 OUT1
+
PHIPTOC1_OPERATE IN2 OUT2
PHHPTOC1_OPERATE
13 Operate
PHLPTOC1_OPERATE SO2 Indication
PHIPTOC2_OPERATE 14
PHHPTOC2_OPERATE
PHLPTOC2_OPERATE
EFHPTOC1_OPERATE
EFLPTOC1_OPERATE
EFHPTOC2_OPERATE
EFLPTOC2_OPERATE
NSPTOC1_OPERATE OR
NSPTOC3_OPERATE
NSPTOC2_OPERATE
NSPTOC4_OPERATE
REF_OPERATE
T2PTTR1_OPERATE
ARCSARC1_OPERATE
ARCSARC2_OPERATE
ARCSARC3_OPERATE
ROVPTOV1_OPERATE
ROVPTOV2_OPERATE
PHPTOV1_OPERATE
PHPTOV2_OPERATE
PHPTUV1_OPERATE
PHPTUV2_OPERATE X110
+
SO1 14
REF
REF_OPERATE Operate
TPGAPC2 16 Alarm
15
IN1 OUT1

PHIPTOC1_OPERATE IN2 OUT2


+
PHHPTOC1_OPERATE
PHLPTOC1_OPERATE SO2 17 Overcurrent
OR
PHIPTOC2_OPERATE Operate
PHHPTOC2_OPERATE 19 Alarm
PHLPTOC2_OPERATE 18

EFHPTOC1_OPERATE +
EFLPTOC1_OPERATE OR SO3 20
EFHPTOC2_OPERATE Earth Fault
EFLPTOC2_OPERATE TPGAPC3 Operate
22 Alarm
IN1 OUT1
21
IN2 OUT2

NSPTOC1_OPERATE
NSPTOC3_OPERATE +
NSPTOC2_OPERATE OR
NSPTOC4_OPERATE SO4 23 Negative
Sequence
24
Overcurrent
Operate Alarm

GUID-8D9B3FA1-4422-486F-80EF-884410E38296 V1 EN

Figure 162: Common alarm/indication 1 and 2

The signal outputs from the IED are connected to give dedicated information on:

• Start of any protection function SO1 (X100:10-12)


• Operation (trip) of any protection function SO2 (X100:13-14)
• Operation (trip) low impedance restricted earth fault SO1 (X110:14-15-16)
RET615 203
Application Manual
Section 3 1YHT530003D05 C
RET615 standard configurations

• Operation (trip) of any stage of the overcurrent protection function SO2


(X110:17-18-19)
• Operation (trip) of any stage of the earth-fault protection function SO3
(X110:20-21-22)
• Operation (trip) of current negative-sequence protection function SO4
(X110:23-24)

TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for
connection where applicable.

204 RET615
Application Manual
1YHT530003D05 C Section 4
Requirements for measurement transformers

Section 4 Requirements for measurement


transformers

4.1 Current transformers

4.1.1 Current transformer requirements for non-directional


overcurrent protection
For reliable and correct operation of the overcurrent protection, the CT has to be
chosen carefully. The distortion of the secondary current of a saturated CT may
endanger the operation, selectivity, and co-ordination of protection. However,
when the CT is correctly selected, a fast and reliable short circuit protection can be
enabled.

The selection of a CT depends not only on the CT specifications but also on the
network fault current magnitude, desired protection objectives, and the actual CT
burden. The protection settings of the IED should be defined in accordance with
the CT performance as well as other factors.

4.1.1.1 Current transformer accuracy class and accuracy limit factor

The rated accuracy limit factor (Fn) is the ratio of the rated accuracy limit primary
current to the rated primary current. For example, a protective current transformer
of type 5P10 has the accuracy class 5P and the accuracy limit factor 10. For
protective current transformers, the accuracy class is designed by the highest
permissible percentage composite error at the rated accuracy limit primary current
prescribed for the accuracy class concerned, followed by the letter "P" (meaning
protection).

Table 73: Limits of errors according to IEC 60044-1 for protective current transformers
Accuracy class Current error at Phase displacement at rated primary Composite error at
rated primary current rated accuracy limit
current (%) minutes centiradians primary current (%)
5P ±1 ±60 ±1.8 5
10P ±3 - - 10

The accuracy classes 5P and 10P are both suitable for non-directional overcurrent
protection. The 5P class provides a better accuracy. This should be noted also if
there are accuracy requirements for the metering functions (current metering,
power metering, and so on) of the IED.

RET615 205
Application Manual
Section 4 1YHT530003D05 C
Requirements for measurement transformers

The CT accuracy primary limit current describes the highest fault current
magnitude at which the CT fulfils the specified accuracy. Beyond this level, the
secondary current of the CT is distorted and it might have severe effects on the
performance of the protection IED.

In practise, the actual accuracy limit factor (Fa) differs from the rated accuracy
limit factor (Fn) and is proportional to the ratio of the rated CT burden and the
actual CT burden.

The actual accuracy limit factor is calculated using the formula:

Sin + Sn
Fa ≈ Fn ×
Sin + S
A071141 V1 EN

Fn the accuracy limit factor with the nominal external burden Sn

Sin the internal secondary burden of the CT

S the actual external burden

4.1.1.2 Non-directional overcurrent protection

The current transformer selection


Non-directional overcurrent protection does not set high requirements on the
accuracy class or on the actual accuracy limit factor (Fa) of the CTs. It is, however,
recommended to select a CT with Fa of at least 20.

The nominal primary current I1n should be chosen in such a way that the thermal
and dynamic strength of the current measuring input of the IED is not exceeded.
This is always fulfilled when

I1n > Ikmax / 100,

Ikmax is the highest fault current.

The saturation of the CT protects the measuring circuit and the current input of the
IED. For that reason, in practice, even a few times smaller nominal primary current
can be used than given by the formula.

Recommended start current settings


If Ikmin is the lowest primary current at which the highest set overcurrent stage is to
operate, the start current should be set using the formula:

Current start value < 0.7 x (Ikmin / I1n)

I1n is the nominal primary current of the CT.

206 RET615
Application Manual
1YHT530003D05 C Section 4
Requirements for measurement transformers

The factor 0.7 takes into account the protection IED inaccuracy, current
transformer errors, and imperfections of the short circuit calculations.

The adequate performance of the CT should be checked when the setting of the
high set stage overcurrent protection is defined. The operate time delay caused by
the CT saturation is typically small enough when the overcurrent setting is
noticeably lower than Fa.

When defining the setting values for the low set stages, the saturation of the CT
does not need to be taken into account and the start current setting is simply
according to the formula.

Delay in operation caused by saturation of current transformers


The saturation of CT may cause a delayed IED operation. To ensure the time
selectivity, the delay must be taken into account when setting the operate times of
successive IEDs.

With definite time mode of operation, the saturation of CT may cause a delay that
is as long as the time the constant of the DC component of the fault current, when
the current is only slightly higher than the starting current. This depends on the
accuracy limit factor of the CT, on the remanence flux of the core of the CT, and
on the operate time setting.

With inverse time mode of operation, the delay should always be considered as
being as long as the time constant of the DC component.

With inverse time mode of operation and when the high-set stages are not used, the
AC component of the fault current should not saturate the CT less than 20 times the
starting current. Otherwise, the inverse operation time can be further prolonged.
Therefore, the accuracy limit factor Fa should be chosen using the formula:

Fa > 20*Current start value / I1n

The Current start value is the primary pickup current setting of the IED.

4.1.1.3 Example for non-directional overcurrent protection

The following figure describes a typical medium voltage feeder. The protection is
implemented as three-stage definite time non-directional overcurrent protection.

RET615 207
Application Manual
Section 4 1YHT530003D05 C
Requirements for measurement transformers

A071142 V1 EN

Figure 163: Example of three-stage overcurrent protection

The maximum three-phase fault current is 41.7 kA and the minimum three-phase
short circuit current is 22.8 kA. The actual accuracy limit factor of the CT is
calculated to be 59.

The start current setting for low-set stage (3I>) is selected to be about twice the
nominal current of the cable. The operate time is selected so that it is selective with
the next IED (not visible in the figure above). The settings for the high-set stage
and instantaneous stage are defined also so that grading is ensured with the
downstream protection. In addition, the start current settings have to be defined so
that the IED operates with the minimum fault current and it does not operate with
the maximum load current. The settings for all three stages are as in the figure above.

For the application point of view, the suitable setting for instantaneous stage (I>>>)
in this example is 3 500 A (5.83 x I2n). For the CT characteristics point of view, the
criteria given by the current transformer selection formula is fulfilled and also the
IED setting is considerably below the Fa. In this application, the CT rated burden
could have been selected much lower than 10 VA for economical reasons.

208 RET615
Application Manual
1YHT530003D05 C Section 5
IED physical connections

Section 5 IED physical connections

5.1 Inputs

5.1.1 Energizing inputs

5.1.1.1 Phase currents

The IED can also be used in single or two-phase applications by


leaving one or two energizing inputs unoccupied. However, at least
terminals X120/7-8 must be connected.

Table 74: Phase current inputs


Terminal Description
X120-1, 2 IL1B1)
X120-3, 4 IL2B1)
X120-5, 6 IL3B1)
X120-7, 8 IL1
X120-9, 10 IL2
X120-11, 12 IL3

1) Dedicated for current measurement in configuration J

5.1.1.2 Residual current


Table 75: Residual current input
Terminal Description
X120-13, 14 Io

5.1.1.3 Phase voltages


Table 76: Phase voltage inputs included in configurations E, F, G, H and K
Terminal Description
X130-11, 12 U1
X130-13, 14 U2
X130-15, 16 U3

RET615 209
Application Manual
Section 5 1YHT530003D05 C
IED physical connections

5.1.1.4 Residual voltage


Table 77: Residual voltage input included in configurations E, F, G, H and K
Terminal Description
X130-17, 18 Uo

5.1.2 RTD/mA inputs


RTD/mA inputs are optional for configurations A, B, C and D.

Table 78: RTD/mA inputs


Terminal Description
X130-1 mA1 (AI1), +
X130-2 mA1 (AI1), -
X130-3 mA2 (AI2), +
X130-4 mA2 (AI2), -
X130-5 RTD1 (AI3), +
X130-6 RTD1 (AI3), -
X130-7 RTD2 (AI4), +
X130-8 RTD2 (AI4), -
X130-9 RTD3 (AI5), +
X130-10 RTD3 (AI5), -

X130-11 Common1)

X130-12 Common2)
X130-13 RTD4 (AI6), +
X130-14 RTD4 (AI6), -
X130-15 RTD5 (AI7), +
X130-16 RTD5 (AI7), -
X130-17 RTD6 (AI8), +
X130-18 RTD6 (AI8), -

1) Common ground for RTD channels 1-3.


2) Common ground for RTD channels 4-6.

5.1.3 Auxiliary supply voltage input


The auxiliary voltage of the IED is connected to terminals X100/1-2. At DC
supply, the positive lead is connected to terminal X100-1. The permitted auxiliary
voltage range (AC/DC or DC) is marked on the top of the LHMI of the IED.

Table 79: Auxiliary voltage supply


Terminal Description
X100-1 + Input
X100-2 - Input

210 RET615
Application Manual
1YHT530003D05 C Section 5
IED physical connections

5.1.4 Binary inputs


The binary inputs can be used, for example, to generate a blocking signal, to
unlatch output contacts, to trigger the disturbance recorder or for remote control of
IED settings.

Table 80: Binary input terminals X110-1...13


Terminal Description
X110-1 BI1, +
X110-2 BI1, -
X110-3 BI2, +
X110-4 BI2, -
X110-5 BI3, +
X110-6 BI3, -
X110-6 BI4, -
X110-7 BI4, +
X110-8 BI5, +
X110-9 BI5, -
X110-9 BI6, -
X110-10 BI6, +
X110-11 BI7, +
X110-12 BI7, -
X110-12 BI8, -
X110-13 BI8, +

Binary inputs of slot X130 are optional for configurations A, B, C, D and J.

Table 81: Binary input terminals X130-1...9


Terminal Description
X130-1 BI1, +
X130-2 BI1, -
X130-2 BI2, -
X130-3 BI2, +
X130-4 BI3, +
X130-5 BI3, -
X130-5 BI4, -
X130-6 BI4, +
X130-7 BI5, +
X130-8 BI5, -
X130-8 BI6, -
X130-9 BI6, +

RET615 211
Application Manual
Section 5 1YHT530003D05 C
IED physical connections

Binary inputs of slot X130 are available with configurations E, F, G, H and K.

Table 82: Binary input terminals X130-1...8


Terminal Description
X130-1 BI1, +
X130-2 BI1, -
X130-3 BI2, +
X130-4 BI2, -
X130-5 BI3, +
X130-6 BI3, -
X130-7 BI4, +
X130-8 BI4, -

5.1.5 Optional light sensor inputs


If the IED is provided with the optional communication module with light sensor
inputs, the pre-manufactured lens-sensor fibres are connected to inputs X13, X14
and X15, see the terminal diagrams.For further information, see arc protection.

The IED is provided with connection sockets X13, X14 and X15
only if the optional communication module with light sensor inputs
has been installed. If the arc protection option is selected when
ordering an IED, the light sensor inputs are included in the
communication module.

Table 83: Light sensor input connectors


Terminal Description
X13 Input Light sensor 1
X14 Input Light sensor 2
X15 Input Light sensor 3

5.2 Outputs

5.2.1 Outputs for tripping and controlling


Output contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable of
controlling most circuit breakers. On delivery from the factory, the trip signals
from all the protection stages are routed to PO3 and PO4.

212 RET615
Application Manual
1YHT530003D05 C Section 5
IED physical connections

Table 84: Output contacts


Terminal Description
X100-6 PO1, NO
X100-7 PO1, NO
X100-8 PO2, NO
X100-9 PO2, NO
X100-15 PO3, NO (TCS resistor)
X100-16 PO3, NO
X100-17 PO3, NO
X100-18 PO3 (TCS1 input), NO
X100-19 PO3 (TCS1 input), NO
X100-20 PO4, NO (TCS resistor)
X100-21 PO4, NO
X100-22 PO4, NO
X100-23 PO4 (TCS2 input), NO
X100-24 PO4 (TCS2 input), NO

5.2.2 Outputs for signalling


Output contacts SO1 and SO2 in slot X100 or SO1, SO2, SO3 and SO4 in slot
X110 or SO1, SO2 and SO3 in slot X130 (optional) can be used for signalling on
start and tripping of the IED. On delivery from the factory, the start and alarm
signals from all the protection stages are routed to signalling outputs.

Table 85: Output contacts X100-10...14


Terminal Description
X100-10 SO1, common
X100-11 SO1, NC
X100-12 SO1, NO
X100-13 SO2, NO
X100-14 SO2, NO

Table 86: Output contacts X110-14...24


Terminal Description
X110-14 SO1, common
X110-15 SO1, NO
X110-16 SO1, NC
X110-17 SO2, common
X110-18 SO2, NO
X110-19 SO2, NC
X110-20 SO3, common
Table continues on next page

RET615 213
Application Manual
Section 5 1YHT530003D05 C
IED physical connections

Terminal Description
X110-21 SO3, NO
X110-22 SO3, NC
X110-23 SO4, common
X110-24 SO4, NO

Output contacts of slot X130 are available in the optional BIO module BIOB02A
for configurations A, B, C, D and J.

Table 87: Output contacts X130-10...18


Terminal Description
X130-10 SO1, common
X130-11 SO1, NO
X130-12 SO1, NC
X130-13 SO2, common
X130-14 SO2, NO
X130-15 SO2, NC
X130-16 SO3, common
X130-17 SO3, NO
X130-18 SO3, NC

5.2.3 IRF
The IRF contact functions as an output contact for the self-supervision system of
the protection IED. Under normal operating conditions, the IED is energized and
the contact is closed (X100/3-5). When a fault is detected by the self-supervision
system or the auxiliary voltage is disconnected, the output contact drops off and the
contact closes (X100/3-4).

Table 88: IRF contact


Terminal Description
X100-3 IRF, common
X100-4 Closed; IRF, or Uaux disconnected

X100-5 Closed; no IRF, and Uaux connected

214 RET615
Application Manual
1YHT530003D05 C Section 6
Glossary

Section 6 Glossary

ANSI American National Standards Institute


ASCII American Standard Code for Information Interchange
CT Current transformer
DANP Doubly attached node with PRP
DPC Double-point control
EMC Electromagnetic compatibility
Ethernet A standard for connecting a family of frame-based
computer networking technologies into a LAN
FIFO First in, first out
GOOSE Generic Object-Oriented Substation Event
HMI Human-machine interface
HSR High-availability seamless redundancy
I/O Input/output
IEC International Electrotechnical Commission
IEC 60870-5-103 1. Communication standard for protective equipment
2. A serial master/slave protocol for point-to-point
communication
IEC 61850 International standard for substation communication
and modeling
IEC 61850-8-1 A communication protocol based on the IEC 61850
standard series
IED Intelligent electronic device
IP address A set of four numbers between 0 and 255, separated
by periods. Each server connected to the Internet is
assigned a unique IP address that specifies the
location for the TCP/IP protocol.
LAN Local area network
LC Connector type for glass fibre cable
LCD Liquid crystal display
LED Light-emitting diode
LHMI Local human-machine interface

RET615 215
Application Manual
Section 6 1YHT530003D05 C
Glossary

Modbus A serial communication protocol developed by the


Modicon company in 1979. Originally used for
communication in PLCs and RTU devices.
Modbus TCP/IP Modbus RTU protocol which uses TCP/IP and
Ethernet to carry data between devices
PCM600 Protection and Control IED Manager
PO Power output
PRP Parallel redundancy protocol
RIO600 Remote I/O unit
RJ-45 Galvanic connector type
RSTP Rapid spanning tree protocol
RTU Remote terminal unit
SAN Singly attached node
Single-line Simplified notation for representing a three-phase
diagram power system. Instead of representing each of three
phases with a separate line or terminal, only one
conductor is represented.
SLD Single-line diagram
TCS Trip-circuit supervision
WAN Wide area network
WHMI Web human-machine interface

216 RET615
Application Manual
217
Contact us

1YHT530003D05 C © Copyright 2014 ABB. All rights reserved.


ABB
Nanjing SAC Power Grid Automation
Co., Ltd.
No. 11 Phoenix Road, Jiangning
Development Zone
211100 Nanjing, China
Phone +86 25 51183000
Fax +86 25 51183883

www.abb.com/substationautomation

You might also like