Professional Documents
Culture Documents
DIESEL GENSET 1250kVA (Prime Power) : Engine Specs
DIESEL GENSET 1250kVA (Prime Power) : Engine Specs
TNK1250P
1250kVA
50Hz
Specification, picture, dimension may change without notice due to product improvement.
Engine Specs
Type : Perkins 4012-46TWG2A
Power Output [kW] : 1000
Electrical Output [kVA] : 1250
Speed [Rpm] : 1500
Frequency [Hz] : 50
No of cylinders : 12V
Displacement [l] : 45.842
Bore/Stroke [mm] : 160 / 190
Compression Ratio : 13.6 : 1
Governor : Electrical
Cooling System : Water cooling with Radiator
Fuel Consumption [l/h] : 259 (100% Load)
Oil Capacity [l] : 177
Alternator Specs
Type [3 Phases, Single Bearing] : STAMFORD PI734A / LVI634G
Rated Output [kVA] : 1250
Standby AMP : 1987
Speed [Rpm] / Frequency [Hz] : 1500 / 50
Voltage [V] : 400/230
Insulation : Class H
Protection : IP 23
Accessories
Radiator Cooling : as PERKINS standard
: 50˚ max with coolant cap
Coolant Capacity : 201 L
Digital Control Panel, consist of : DEEP SEA ELECTRONICS (DSE 7320 or depend
on request) Module, parameter : •Volt meter,
•Auto Start Control (AMF), •Hour meter,
•Speed Control,
•Engine lube oil pressure gauge, •Engine coolant
Temperature gauge) ,
: Ampere meter
: Start key switch
: Charging control lamp
: Control fuse
: Emergency Stop Button
System Volt : 24Volts
: Set of Connection cables and Cable terminals
Exhaust System : Industrial exhaust silencer
Air Filter : Dry Type
Baseframe : Steel Channel construction
Engine and Alternator Mounting : Rubber metal elements
Set of Operation books : User’s Manual
According to ISO 8528-5. Continuous Power: No time limitation, plus 10% addictional, power for governing purpose only. Prime Power: Average output ≤ 80%, no time limitation, plus 5%
addictional power for governing purpose only. Limited Time Running Power: for up to 500 h/year, thereof a maximum of 300 h/year continuous running. In consideration of a generator
efficiency level of 89% - 90% and a power factor of 0.8