Model ESFR-17
16.8 K-factor Upright Sprinkler
Early Suppression, Fast Response
General when sizing system piping and posi-
tioning the system piping with respect
Description to the ceiling.
Applications for the TYCO ESFR Sprin-
TYCO Model ESFR-17 Upright Sprin- klers are expanding beyond currently
klers are Early Suppression, Fast recognized installation standards. For
Response (ESFR) sprinklers having a information on research fire tests that
nominal K-factor of 16.8 (Ref. Figure 1). may be acceptable to an authority
They are suppression mode sprinklers having jurisdiction, contact Tyco Fire
that are especially advantageous as a Protection Products (TFPP) Technical
means of eliminating in-rack sprinklers Services.
when protecting high-piled storage.
Model ESFR-17 Sprinklers are primarily NOTICE
used for ceiling-only sprinkler protec- The Model ESFR-17 Upright Sprinklers
tion of (but not limited to) the following described herein must be installed and
storage applications: maintained in compliance with this doc-
ument, as well as with the applicable
• most encapsulated or non-encap-
standards of the National Fire Protec-
sulated common materials including
tion Association (NFPA), in addition to
cartoned, unexpanded plastics
the standards of any authorities having
• cartoned, expanded plastics
• some storage arrangements of
jurisdiction (e.g., FM Global). Failure to
do so may impair the performance of Technical
rubber tires and roll paper these devices.
The owner is responsible for main-
Data
For more specific criteria, refer to Table Approvals
A in this technical data sheet as well as taining their fire protection system
and devices in proper operating con- FM Approved
the applicable design standard. CE Certified (Certificate of Conformity
dition. Contact the installing contrac-
The Model ESFR-17 Upright Sprin- 1725-CPD-H0012)
tor or product manufacturer with any
klers provide the system designer with questions. Maximum Working Pressure
an upright option to the traditional 175 psi (12,1 bar)
pendent ESFR Sprinklers. With a K-fac- In all cases, the appropriate NFPA or
FM Global installation standard must Pipe Thread Connections
tor of 16.8, Model ESFR-17 Sprinklers 3/4 Inch NPT or ISO 7-R 3/4
provide system designers with hydrau- be referenced to ensure applicabil-
lic and sprinkler placement options not ity and to obtain complete installa- Discharge Coefficient
presently available to traditional ESFR tion guidelines. The general guidelines K=16.8 gpm/psi1/2 (241,9 lpm/bar1/2)
Sprinklers having a K-factor of 14.0. In in this data sheet are not intended to Temperature Ratings
particular, the Model ESFR-17 Upright provide complete installation criteria. 165°F (74°C) and 212°F (100°C)
Sprinklers are designed to operate at
substantially lower-end head pressures
compared to ESFR Sprinklers with 14.0
Sprinkler Finish
Natural Brass
K-factors. This feature offers flexibility Identification Physical Characteristics
Frame ���������������������������������������������������������Brass
2-9/16" DIA.
(65,0 mm)
10 TEMPERATURE
RATING
Components: 2
1 - Frame
2 - Deflector 3
3 - Compression
WRENCH
Screw
4 FLATS
4 - Hook THERMAL
5 - Strut 3-5/8" SENSING
6 - Link Assembly 5 (92,1 mm) ELEMENT
7 - Button
8 - Sealing
Assembly 6 1/2"
9 (12,7 mm)
9 - Ejection Spring
10 - Deflector Nut NOMINAL 1-5/8"
8 MAKE-IN (41,3 mm)
7 3/4" NPT
FIGURE 1
MODEL ESFR-17 UPRIGHT SPRINKLER, 16.8K
EARLY SUPPRESSION, FAST RESPONSE
Criteria
Element-to-Ceiling Distance
Roof Construction Refer to FM Global 2-0 for Storage
Unobstructed or obstructed construc- Sprinklers.
The following general guidelines pro- tion (e.g., smooth ceiling, bar joists,
vided for the TYCO Model ESFR-17 beam and girder, and so forth) Obstructions below Upright ESFR
Upright Sprinklers may be used for Sprinklers, Including Branchlines
Where the depths of the solid struc- Per the requirements of FM, obstruc-
quick reference.
tural members (e.g., beams and stem) tions below upright ESFR Sprinklers
The National Fire Protection Associa- exceed 12 inches (302 mm), install can be ignored as follows
tion (NFPA) and FM Global (FM Approv- ESFR Sprinklers in each channel
als) provide installation standards that formed by the structural members. • open-web bar joists or trusses
must be used to properly design an having chords no more than 4
automatic sprinkler system utilizing Ceiling Slope inches (102 mm) wide
Early Suppression, Fast Response Maximum 2 inch rise for 12 inch run
(16.7%) • bridging or wind bracing no more
(ESFR) Sprinklers. The guidelines pro- than 4 inches (102 mm) wide
vided by NFPA and FM Global may Maximum Coverage Area
differ; consequently, the appropriate 100 ft.2 (9,3 m2) • individual pipes and conduit 4 inches
standard must be used for a given (102 mm) diameter or less 3 inch
installation. In some cases, the installation stan- [DN80] pipe size or less will not
dards permit a greater coverage area. require sprigs)
In all cases, the appropriate NFPA or
FM Global installation standard must Minimum Coverage Area • individual groups of smaller pipe
be referenced to ensure applicabil- 64 ft.2 (5,8 m2) per or conduit having a total width of 4
ity and to obtain complete installation NFPA 13 / FM Global 2-0 inches or less
guidelines, since the following general Maximum Spacing
guidelines are not intended to provide
complete installation criteria.
12 feet (3,7 m) for building heights
up to 30 feet (9,1 m)
Operation
The fusible link assembly is com-
In addition to this technical data sheet, 10 feet (3,1 m) for building heights prised of two link halves that are joined
the following data sheets describe greater than 30 feet (9,1 m) together by a thin layer of solder. When
other TYCO ESFR Sprinklers: the rated temperature is reached, the
Minimum Spacing
• TFP312 8 feet (2,4 m) solder melts and the two link halves
Model ESFR-25 (TY9226) separate, activating the sprinkler and
K=25.2 Pendent Sprinkler Minimum Clearance to Commodity flowing water.
36 inches (914 mm)
• TFP315
Model ESFR-17 (TY7226) NFPA 13
K=16.8 Pendent Sprinkler Deflector-to-Ceiling Distance
3 to 12 inches (76,2 to 304 mm)
• TFP318
Model ESFR-1 (TY6226)
K=14.0 Pendent Sprinkler
TFP316