Wastewater Standard Details
Wastewater Standard Details
Wastewater Standard Details
Standard Details
Connections and Developer Services
Construction Requirements for Self-Lay Developments
December 2017 (Revision 03)
Document IW-CDS-5030-01
IW-CDS-5030-01
Revision Log
Date Details of Revision Revision Author Approver
April 2016 General revisions 01 T’OC M’OD
August 2016 General revisions & 02 TO’C MO’D
drawing added
December 2017 General revisions & 03 TO’C MO’D
drawing added
IW-CDS-5030-01 Rev. 03 December 2017
Background
Technical Documentation has been developed by Irish Water’s Connections and
Developer Services which outlines the requirements for wastewater services
infrastructure within developments.
These standard details have been developed to outline to developers Irish Water’s
requirements for the provision of wastewater infrastructure that is to be installed in
developments and that would be connected to Irish Water’s networks and subsequently
vested in Irish Water.
The standard details are based on best practice within the water industry. They take
account of the experience of Local Authorities in the provision of these services to new
developments. They have been successfully used by Irish Water’s own internal
functions for a variety of projects and they are in line with water utility industry norms.
There are 36 No Standard Details dealing with wastewater infrastructure covering all
aspects of such infrastructure.
The use of the standard details is mandatory in all new Irish Water Connection
Agreement Offers issued after 1st June 2016.
.
IW-CDS-5030-01 Rev. 03 December 2017
Standard Details for Wastewater Networks
Index Sheet
These Standard Details show the acceptable typical details and outline the minimum standards that are required by Irish Water for the
provision of wastewater pipes and related infrastructure which are to be connected to the Irish Water Network. They shall be used in
conjunction with the associated Design Risk Assessments that have been developed which identify the risks that designers shall take into
account in the detailed design of the wastewater pipes and related infrastructure to be connected to the Irish Water Network. The pipes
and related infrastructure to be put in place within developments shall comply fully with these Standard Details. Ultimate responsibility
(including, but not limited to, any losses, costs, demands, damages, actions, expenses, negligence and claims) for the detailed design,
construction and provision of such pipes and related infrastructure shall rest entirely with the Developer, his/her Designer(s), Contractor(s)
or other connected party. Irish Water assumes no responsibility for and gives no guarantees, undertakings or warranties in relation to the
pipes and related infrastructure to be provided in accordance with these Standard Details.
No part of the Standard Details shall be reproduced or transmitted in any form or stored in any retrieval system of any nature without the
prior written permission of Irish Water as copyright holder, except as agreed for use.
These Standard Details shall be used in conjunction with current Irish Water Codes of Practice, which will take precedence over the
Standard Details.
These Standard Details may also be used for the installation of wastewater infrastructure for Asset Delivery Works & Capital Project
Works Programmes at the discretion of Irish Water.
DEC. 2017
IW-CDS-5030-01 Rev. 03 December 2017
VENT STACK
CUSTOMER PROPERTY
SEE NOTE 2 ON
STD-WW-03
PROPERTY BOUNDARY
WITHIN
1m OF
BOUNDARY
FOOTPATH
ROAD
SEWER
( IRISH WATER RESPONSIBILITY )
A/B C D
MAINTENANCE
RESPONSIBILITY
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
WASTEWATER SERVICE
1 11/'17 JMC TOC Note reference added MOD CONNECTION RESPONSIBILITY STD-WW- 01 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
1. THE MINIMUM SIZE FOR A GRAVITY FOUL SERVICE CONNECTION SHALL BE 100mm DIAMETER.
2. THE MINIMUM SIZE OF GRAVITY FOUL SEWER SHALL BE 225mm DIAMETER IN GENERAL. GRAVITY SEWERS ON BRANCHES SERVING LESS THAN 20 PROPERTIES MAY BE 150mm DIAMETER SUBJECT TO
AGREEMENT WITH IRISH WATER.
3. THE MINIMUM SIZE FOR RISING MAINS SHALL NOT BE LESS THAN 80mm & THE DESIRED MINIMUM SIZE OF RISING MAIN SHALL BE 100mm DIAMETER.
4. EACH PROPERTY SHALL HAVE A SEPARATE WASTE WATER SERVICE CONNECTION. A CONNECTION SHALL NOT BE TAKEN FROM AN EXISTING SERVICE CONNECTION.
LEGEND
PROPOSED SEWER
PROPOSED MANHOLE
PROPOSED INSPECTION CHAMBER
EXISTING SEWER
EXISTING MANHOLE
TELECOMMUNICATIONS
STORM WATER
ELECTRICITY
WATER MAIN
FOUL SEWER
CABLE TV
GAS MAIN
BUILDING
ROAD
KERB
FOOTPATH
BOUNDARY
RESPONSIBILITY RESPONSIBILITY
WITHIN 1000mm
(SEE NOTE 2)
FOOTPATH
ROAD
MAX.150mm
VARIES
VARIES
SLIDING COUPLING
45° BEND
CONNECTION PIPE
100 1 : 60
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
1 11/'17 JMC TOC Updated Notes MOL DRAIN AND SERVICE CONNECTION PIPEWORK STD-WW- 03 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
90°
°
45
SEE NOTE 7
CONNECTION PIPE
A
AC RAN
CE GE
PT
AB
LE
SEWER
FLOW
0°
CROSS-SECTIONAL VIEW IN
VIEW OF SEWER DIRECTION OF ARROW A
90°
°
60
SEE NOTE 7
°
45
CONNECTION PIPE
A
AC RAN
CE GE
PT
AB
LE
SEWER
FLOW
0°
CROSS-SECTIONAL VIEW IN
VIEW OF SEWER DIRECTION OF ARROW A
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
TYPICAL SEWER / SERVICE PIPE
1 11/'17 JMC TOC Updated connection detail & notes MOD CONNECTION STD-WW- 04 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
2. SPECIFIC SEPARATION CLEARANCE DISTANCES IN EXCESS OF THESE MINIMA SHALL BE PROVIDED FOR
SERVICES SUCH AS GAS, ELECTRICITY, FIBRE-OPTIC OR OIL FILLED CABLES AS THE CASE MAY BE.
THE PARTICULAR UTILITY PROVIDERS SHALL BE CONSULTED TO DETERMINE THESE MINIMUM SEPARATION
DISTANCES AND EVIDENCE OF THIS CONSULTATION, WITH THE SPECIFIED SEPARATION DISTANCES,
SHALL BE PROVIDED TO IRISH WATER AT DESIGN STAGE.
3. NOTIFICATION IN WRITING IS REQUIRED SHOULD WORKS BE WITHIN THE FOLLOWING DISTANCES FROM AN EXISTING WATER MAIN OR WASTEWATER RISING MAIN:-
HORIZONTAL
1m AT EITHER SIDE OF AN EXISTING MAIN LESS THAN 200mm IN DIAMETER.
2m AT EITHER SIDE OF AN EXISTING MAIN OF 200mm TO 350mm IN DIAMETER.
5m AT EITHER SIDE OF AN EXISTING MAIN OF 350mm OR GREATER IN DIAMETER.
WHERE DUCTS OR PIPES ARE TO BE LAID CLOSE TO AN EXISTING WATERMAIN OR SEWER IN THE OWNERSHIP OF IRISH WATER,
NOTIFICATION IN WRITING SHALL BE PROVIDED A MINIMUM OF 10 DAYS AHEAD OF ADVANCEMENT OF THE WORK.
NOTIFICATION IN WRITING IS REQUIRED SHOULD WORKS BE WITHIN 1.5m DISTANCE OF A WASTEWATER SEWER.
REQUIREMENTS SHALL ALSO APPLY TO TRIAL HOLES OR SLIT TRENCHES TO LOCATE THE MAIN OR GAIN GROUND INFO DATA.
LARGER DIAMETERS >350mm DISTRIBUTION AND TRUNK MAINS, IRISH WATER MUST BE NOTIFIED AT LEAST 1 MONTH IN ADVANCE.
DEVELOPERS SHALL ALSO COMPLY WITH ANY NOTIFICATION REQUIREMENTS OF OTHER UTILITY PROVIDERS (ESB, GAS MAIN, TELECOMMUNICATION ETC.).
4. DETAILED PROPOSALS, INCLUDING WORK METHOD STATEMENTS, INSURANCE CONFIRMATION AND DETAILS OF WORK COMPLETED OF A SIMILAR NATURE MUST
BE SUBMITTED TO IRISH WATER FOR ITS CONSIDERATION BEFORE AGREEMENT WILL ISSUE.ALL SUCH WORKS IN THE VICINITY OF ARTERIAL WATER MAINS AND SEWERS
(MAINS GREATER THAN 400mm) SHALL BE SUBJECT TO WRITTEN AGREEMENT WITH IRISH WATER BEFORE CONSTRUCTION COMMENCES ON SITE. THIS AGREEMENT
SHALL ALSO INCLUDE ANY NECESSARY PROTECTION FOR WATER MAINS.
5. ANY DAMAGE SHALL BE NOTIFIED IMMEDIATELY TO IRISH WATER. THE PERSON WHO CAUSES THE DAMAGE TO A SEWER MAIN OR FITTING WILL BE DEEMED TO HAVE
COMMITTED AN OFFENCE UNDER SECTION 45 OF THE WATER SERVICES ACT 2007.
6. UNDER NO CIRCUMSTANCES WILL IRISH WATER ACCEPT SEWER MAIN INSTALLATIONS UNDER STRUCTURES, EXISTING OR PROPOSED, OR IN CLOSE PROXIMITY TO
ANY EXISTING STRUCTURES OR FEATURES THAT WILL INHIBIT ACCESS FOR POST INSTALLATION MAINTENANCE AND ACCESS.
7. THE MINIMUM CLEAR DISTANCE WILL BE INCREASED IF THE SEWER IS GREATER THAN 3m DEEP OR IF THE DIAMETER IS GREATER THAN 375mm. THE MINIMUM CLEAR DISTANCE
IN THESE SITUATIONS SHALL BE > DEPTH TO INVERT OR 10 TIMES THE SEWER DIAMETER, WHICH EVER IS GREATER.
8. THE EXTERNAL FACES OF MANHOLE SHALL BE AT LEAST 0.5m FROM KERB LINE.
9. WHERE DESIGN DEVIATES FROM TYPICAL DETAILS, THE LAYOUT IS SUBJECT TO REVIEW BY IRISH WATER.
3000mm MINIMUM
BUILDING
CABLE TV
TELECOMMUNICATIONS
MINIMUM 1200mm
ELECTRICITY
WATER MAIN
FOUNDATION
GAS MAIN
ELECTRICAL CORRIDOR
( DEPTH AND LAYOUT STORM WATER
REQUIREMENTS TO BE
CONFIRMED WITH SERVICE MIN. 1000mm
PROVIDER )
FOUL SEWER
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
TYPICAL SERVICE LAYOUT INDICATING
1 11/'17 JMC TOC Updated notes MOD SEPARATION DISTANCES STD-WW- 05 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
METHOD STATEMENTS:
ALL WORKS SHALL BE CARRIED
OUT IN ACCORDANCE WITH BS 5837 AND INFORMED BY
NJUG VOLUME 4
PRECAUTION AREA:
EXCLUSION AREA:
PREVENTION MEASURES
REQUIRED IN LINE WITH
LANDSCAPING DESIGN & SPECIAL
GIRTH x 4
PROTECTION REQUIRED. (e.g. BY NO WORKS PERMITTED
USE OF APPROPRIATE BARRIERS,
HIGH PERFORMANCE JOINTS, OR
BY USE OF POLYETHYLENE WITH
WELDED JOINTS). THE LANDSCAPE
DESIGN AND DETAILS OF THE
SPECAIL PROTECTION MEASURES
MUST BE AGREED WITH IRISH
EXISTING PLANTING:
WATER
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
RESTRICTIONS ON WASTEWATER
2 11/'17 JMC TOC Revised to suit ILI recommendations MOD
1 08/'16 JMC TOC Added new section & notes MOD INFRASTRUCTURE WORKS STD-WW- 06 2
0 09/'15 JMC TOC Initial Issue SL ADJACENT TO TREES
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
PLEASE NOTE THAT TABLE A.1. OF BS 5837 (BELOW) IS TO BE USED TO CALCULATE THE ABSOLUTE MIMIMUM DISTANCE BETWEEN NEW TREE PLANTING
FROM THE WASTEWATER INFRASTRUCTURE (THE SERVICES). THE DISTANCE IS REQUIRED TO AVOID DIRECT DAMAGE TO THE INFRASTRUCTURE FROM
FUTURE GROWTH. THE DISTANCE IS A FUNCTION OF THE DEPTH OF THE SERVICES AND THE (FINAL EXPECTED) STEM DIAMETER OF THE TREE AT
MATURITY (i.e. FINAL EXPECTED GROWTH).
TABLE A.1. Minimum distance between young trees or new planting & structures, in metres (m)
BS 5837 Final stem dia. < 300mm Final stem dia. 300mm to 600mm Final stem dia. > 600mm
Services
< 1m deep 0.5 1.5 3.0
> 1m deep -- 1.0 2.0
THUS FOR EXAMPLE:
- FOR A SERVICE LESS THAN 1 METRE DEEP, THE MINIMUM DISTANCE IS TO BE 1.5m FOR A TREE BETWEEN 300 AND 600mm STEM DIAMETER AT MATURITY.
- FOR A SERVICE GREATER THAN 1 METRE DEEP, THE MINIMUM DISTANCE IS TO BE 1.0m FOR A TREE BETWEEN 300 AND 600mm STEM DIAMETER AT MATURITY.
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WATER NOT TO SCALE JUL. 2017
TITLE DRAWING No. REV
100 500
150 600
300 750
350 750
400 900
450 900
'C'
1 11/'17 JMC TOC Updated & Added Notes MOD TRENCH BACKFILL AND BEDDING STD-WW- 07 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
IW-CDS-5030-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. SOLID BLOCKWORK TO BE OF HIGH STRENGTH (20N/mm²) TO IS EN 771.
3. MAXIMUM DEPTH OF BLOCK WORK MANHOLE IS 1.20m (THE USE OF BLOCK
WORK IN DEEPER MANHOLES WILL BE CONSIDERED BUT SUCH USE WILL
REQUIRE DETAILED STRUCTURAL DESIGN AND BE SUBJECT TO IRISH WATER
REVIEW).
4. WALLS TO BE FLUSH POINTED AND NOT PLASTERED INTERNALLY, INTERNAL
LINING OF ENGINEERING BRICK TO IS EN 771-1 TO A HEIGHT OF 1m ABOVE
MANHOLE COVER AND FRAME SHALL COMPLY BENCHING. ENGINEERING BRICK TO BE BONDED TO BLOCKWORK USING
TO IS EN 124 AND BS 7903 (ALL CLASS D400 ENGLISH GARDEN WALL BOND.
COVERS SHALL HAVE MIN. FRAME DEPTH 100 5. STRUCTURAL DESIGN AND REINFORCEMENT DETAILS FOR ROOF AND BASE
OR 150mm) MIN. OPE. 600 x 600mm SLABS TO BE PROVIDED BY THE DEVELOPER AND SUBMITTED TO IRISH WATER
SEE NOTES 10, 11 & 12. FOR REVIEW. MANHOLE ROOFS SHALL CONSIST OF A REINFORCED CONCRETE
SLAB OF IN-SITU CONCRETE, C30/37, WITH A MINIMUM THICKNESS OF 225mm
COVER TO BE SET IN
DESIGNED TO CARRY ALL LIVE AND DEAD LOADS. ALTERNATIVELY, APPROVED
C50\60 MORTAR
FINISHED GROUND LEVEL PRE-CAST CONCRETE ROOF SLABS MAY BE USED SUBJECT TO IRISH WATER
REVIEW AND COMPLIANCE WITH BS 5911 PART 4: 2002.
1 No. COURSE MIN. 6. COVERS AND FRAMES SHALL BE SUITABLE FOR ROAD AND TRAFFIC
3 No. COURSES MAX OF CLASS CONDITIONS SUBJECT TO REVIEW FROM IRISH WATER.
B ENGINEERING BRICKS SET IN 7. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN
C50/60 MORTAR GREEN AREAS.
225
8. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED ON
675mm MAX. TO FIRST STEP GROUND CONDITIONS WITHIN THE SITE. SHOULD ANTI FLOATATION MEASURES
20N/mm² CONCRETE BE REQUIRED THEY SHALL BE SUBJECT TO REVIEW BY IRISH WATER.
9. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206 : 2013.
BLOCKS TO COMPLY
WITH IS EN 771-3 10. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S
ENGINEERING
REQUIREMENTS.
BRICK WORK LINING 1:3 SAND:CEMENT MORTAR 11. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
300 c/c's
1000mm ABOVE BENCHING WITH STEEL TROWEL FINISH 12. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR
AT A 1:30 SLOPE TOWARDS MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF TRANSPORT, TOURISM & SPORT, OR
THE CHANNEL TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
FLEXIBLE JOINT
FLEXIBLE JOINT
Flow Flow
50
Max. 600 Max. 600
225
ROCKER PIPE
ROCKER PIPE (SEE TABLE OVER)
(SEE TABLE OVER)
225
REINFORCED CONCRETE
BASE GRADE C30/37 SECTION B-B
75mm GRADE C12/15
BLINDING CONCRETE
B
1760
215 1200 215
215
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
Added rocker pipe table,
2 11/'17 JMC TOC added & updated notes MOD TITLE DRAWING No. REV
225
OF CLASS B 10. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED
ENGINEERING BRICKS MIN. 600 ON GROUND CONDITIONS WITHIN THE SITE. SHOULD ANTI FLOATATION
SET IN C50/60 MORTAR MEASURES BE REQUIRED THEY SHALL BE SUBJECT TO REVIEW
BY IRISH WATER.
PRECAST CONCRETE 11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206 : 2013.
MANHOLE RINGS TO 12. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD
IS 420 IN CONJUNCTION AUTHORITY'S REQUIREMENTS.
WITH IS EN 1917 : 2004 120 13. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
14. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR
MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF TRANSPORT, TOURISM & SPORT,
ELASTOMETRIC JOINT SEAL OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
300 c/c's
TO EN 681 15. IF DEPTH FROM GROUND TO PIPE SOFFIT IS GREATER THAN 6m DEEP, A SITE SPECIFIC
ENGINEERED SOLUTION FOR ACCESS SHALL BE PROVIDED.
MANHOLE STEPS TO COMPLY WITH IS 16. PROPRIETARY WATERTIGHT PCC MANHOLE RING SYSTEMS WITH A WALL THICKNESS >
150mm GRADE C16/20 125mm, & A WATER TIGHT JOINT SEALING SYSTEM, MAY BE USED WITHOUT CONCRETE
EN 13101, TYPE D, CLASS 1,
IN-SITU CONCRETE SURROUND, SUBJECT TO THE GROUND WATER LEVEL AT THE MANHOLE BEING LOW, &
GALVANISED MILD STEEL & PLASTIC REFER TO TABLE FOR
SURROUND SUBJECT TO REVIEW BY IRISH WATER.
ENCAPSULATED. STEPS ARE REQUIRED PRE-CAST RING DIAMETER
IN MANHOLES UP TO A GROUND TO PIPE
SOFFIT DEPTH OF LESS THAN 3.0m. BOTTOM PRECAST SECTION
MAX. 300
225
MIN. 50mm TO MAX. 300mm MIN. 600
FIRST RING SUNK INTO
SELF CLEANING TOE HOLES TO BE IN-SITU CONCRETE BASE 1200mm SHAFT Ø
PROVIDED WHERE CHANNEL 900mm MIN. CLEAR
REINFORCED CONCRETE
EXCEEDS 600mm WIDE ACCESS BEHIND
BASE GRADE C30/37
LADDER
INVERT SHOULD BE
STAINLESS STEEL CHAIN IN "DOWN" PCC REDUCING SLAB
FORMED WITH CAST
POSITION SECURED TO RESTRAINING IN-SITU CONCRETE
225
2000 MIN.
75mm GRADE C12/15 STRINGER
BLINDING CONCRETE
SECTION A-A LADDERS IN
MANHOLES TO
TO BARREL OF PIPE
COMPLY WITH
IS EN 14396
PLAN
MINIMUM MANHOLE DIAMETERS ROCKER PIPE LENGTH
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
Added rocker pipe table,
2 11/'17 JMC TOC deep manhole detail, MOD TITLE DRAWING No. REV
added & updated notes
Added steps & revised
1 08/'16 JMC TOC access ope & cover notes MOD PRE-CAST CONCRETE MANHOLE STD-WW- 10 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
MANHOLE COVER AND FRAME SHALL COMPLY TO IS EN 2. IN-SITU MANHOLES TO HAVE A MINIMUM WALL AND FLOOR THICKNESS OF
124 AND BS 7903 (ALL CLASS D400 COVERS SHALL 225mm FOR MANHOLE DEPTHS UP TO 3.0m AND 300mm OR MORE WHEN THE
HAVE MIN. FRAME DEPTH 100-150mm) MIN. OPE. MANHOLE DEPTH EXCEEDS 3.0m.
600x600mm 3. STRUCTURAL DESIGN & REINFORCEMENT DETAILS TO BE PROVIDED BY THE
COVER TO BE SET DEVELOPER AND SUBMITTED TO IRISH WATER FOR REVIEW. MANHOLE
IN C50\60 MORTAR ROOFS SHALL CONSIST OF A REINFORCED CONCRETE SLAB OF IN-SITU
SEE NOTES 9, 10 & 11. CONCRETE, C30/37, WITH A MINIMUM THICKNESS OF 225mm DESIGNED TO
CARRY ALL LIVE AND DEAD LOADS. ALTERNATIVELY, APPROVED PRE-CAST
FINISHED GROUND LEVEL CONCRETE ROOF SLABS MAY BE USED SUBJECT TO IRISH WATER
APPROVAL AND COMPLIANCE WITH BS 5911 PART 4: 2002.
4. MANHOLES GREATER THAN 3m IN DEPTH WILL REQUIRE A DETAILED
1 No. COURSE MIN. STRUCTURAL DESIGN AND BE SUBJECT TO IRISH WATER REVIEW.
3 No. COURSES MAX OF CLASS B 5. COVERS AND FRAMES SHALL BE SUITABLE FOR ROAD AND TRAFFIC
ENGINEERING BRICKS SET IN MIN. 600 CONDITIONS SUBJECT TO REVIEW BY IRISH WATER.
225
C50/60 MORTAR 6. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN
675mm MAX. GREEN AREAS.
TO FIRST STEP 25x25mm 7. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED ON
CHAMFER GROUND CONDITIONS WITHIN THE SITE. SHOULD ANTI-FLOATATION
MEASURES BE REQUIRED THEY SHALL BE SUBJECT TO REVIEW BY IRISH
WATER.
8. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206 : 2013.
120 9. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD
AUTHORITY'S REQUIREMENTS.
10. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
MANHOLE STEPS TO COMPLY WITH IS 11. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR
EN 13101, TYPE D, CLASS 1, GALVANISED MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF TRANSPORT, TOURISM & SPORT, OR
CONCRETE GRADE
MILD STEEL & PLASTIC ENCAPSULATED. TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
C30/37 IN ROOF,
STEPS ARE REQUIRED IN MANHOLES 12. IF DEPTH FROM GROUND TO PIPE SOFFIT EXCEEDS 6m, A SITE SPECIFIC ENGINEERED
300 c/c's
MIN. 600
225
225 D A 225
1200mm SHAFT
225
Flow Flow
2000 MIN.
230
MIN. 600
325
PLAN A
MIN. 600mm x
600mm
SQUARE OPE
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
Added rocker pipe table,
2 11/'17 JMC TOC deep manhole detail, MOD TITLE DRAWING No. REV
added & updated notes.
Added steps & revised
1 08/'16 JMC TOC access ope & cover notes MOD IN-SITU CONCRETE MANHOLE STD-WW- 11 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. RODDING EYE CHAMBER SHALL BE COVERED WITH APPROVED HEAVY
DUTY METAL COVERS TO IS 261 AND BS 5834. COVER AND FRAME SHALL
HEAVY DUTY COVER AND FRAME BE SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO
D400 (TO SUIT 150mm OPE.) REVIEW BY IRISH WATER.
3. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED
ON GROUND CONDITIONS WITHIN THE SITE. SHOULD ANTI FLOATATION
MEASURES BE REQUIRED THEY SHALL BE SUBJECT TO REVIEW BY IRISH
WATER.
4. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
5. MANHOLE DETAILS TO BE IN ACCORDANCE WITH STD-WW-09, 10 AND 11
STOPPER
Y - JUNCTION
90° BEND
225mm GRADE C25\30
CONCRETE SURROUND
TYPE No. 1
150mm - 450mm DIA. (INCL.) DROP GREATER THAN 1700mm
500mm - 900mm DIA. (INCL.) DROP GREATER THAN 2300mm
STOPPER
TEE JUNCTION 150
90° BEND
TYPE No. 2
150mm - 450mm DIA. (INCL.) DROP GREATER THAN 900 AND LESS THAN 1700mm
500mm - 900mm DIA. (INCL.) DROP GREATER THAN 1300mm AND LESS THAN 2300mm
Y - JUNCTION CHAIN
STOPPER
45° BEND
225mm GRADE C25\30
CONCRETE SURROUND
TYPE No. 3
150mm - 450mm DIA. (INCL.) DROP GREATER THAN 600mm AND LESS THAN 900m
500mm - 900mm DIA. (INCL.) DROP GREATER THAN 600mm AND LESS THAN 1300mm
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
SECTION
PRECAST UNITS
(REFER TO NOTE 7.)
BENCHING
100
FLOW FLOW
600
FLOOR PLAN
INSPECTION CHAMBER
(PRECAST CONCRETE CONSTRUCTION)
SEALED MANHOLE COVER
COVER TO BE SET AS PER TO SUIT IS EN 124 LOADING MINIMUM INTERNAL
MANUFACTURER'S MINIMUM 600mm x 600mm DIMENSIONS 600mm
SPECIFICATION CLEAR OPENING DIAMETER OR 600mm x 600mm
1 No. COURSE MIN.
3 No. COURSES MAX
OF CLASS B ENGINEERING BRICKS
PIPES BUILT INTO CHAMBER
WALL OR
JOINT FORMED WITH
WATERTIGHT SEALS 600
BENCHING
FLOW FLOW
600
IN ACCORDANCE WITH
IS EN 771-3
FLOOR PLAN
INSPECTION CHAMBER
(BLOCK WORK CONSTRUCTION)
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
E
STAINLESS STEEL
E
ANCHOR BOLTS
G/2
2
NTS
25x25mm CHAMFER
1000
G/2
50 MIN.
50 MIN.
50 MIN.
G/2
50 MIN. GRADE C25 / 30
0 MASS CONCRETE
100
G/2
90 DEGREE BEND NTS SUPPORT BLOCK
45 DEGREE BEND BEND WITH EXTENSION PIECES
E DOWEL BARS
20
VARIES 50 MIN.
0
C/2 C/2 D/2 D/2 TEE VARIES
E THRUST E
E
TE CONCRETE
E
WA IN TEE WITH EXTENSION PIECES PIPE PLINTH SUPPORT (ABOVE GROUND)
PLINTH
MA
F/2
GROUND
ROAD SURFACE
VARIES
SURFACE
50 MIN.
50 MIN.
DN x 2.5
REINFORCEMENT 300
PROFILE
F/2
TO DEVELOPER'S
DETAILS 300
200
VARIES
22.5 DEGREE BEND SECTIONAL ELEVATION FOR BEND OR TEE 100 DN x 2.5 100
11.25 DEGREE BEND
F/2
TRENCH
G/2
500
F/2
PIPE
150
TRENCH
200
300 INCLINED SLOPES, FOR PIPE
300
F/2
REQUIRED FOR PIPE DUCTILE IRON TO POLYETHYLENE CHANGE OVER
E
200
LENGTH > 3 METERS IN SLOPE.
H, J, or K
F/2
1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
300
100 DN x 2 100
C 2. CONCRETE THRUST BLOCKS (ANCHORAGE) SHALL BE POSITIONED
PLAN
H, J or K ELEVATION CROSS - SECTION SYMMETRICALLY WITH RESPECT TO THE CONNECTING PIPE & BENDS.
ELEVATION
PIPE SUPPORT DETAILS FOR INCLINED SLOPES TAPER 3. TRENCH DIMENSIONS : REFER TO DRAWING No's. STD-WW-07.
STEEL ELEVATION 4. THRUST BLOCKS SHALL BEAR ON UNDISTURBED SOIL.
ANCHOR SURFACE BOX ROAD SURFACE IF FOR ANY REASON THEY CANNOT THEN THE DEVELOPER SHALL
E 300
STRAPS NOTIFY IRISH WATER IMMEDIATELY WITH A PROPOSED SOLUTION.
TRENCH 5. THRUST BLOCK REINFORCEMENT REQUIRES SPECIFIC DESIGN.
G/2
BOTTOM 6. FOR TEST PRESSURES GREATER THAN 18 BAR, THRUST BLOCK
VARIES
PIPE
G/2
FLANGE
TRENCH
PRESSURE OF 100 KN/m (TYPICAL FOR SOFT CLAY) FOR OTHER
CONDITIONS. ACTUAL DIMENSIONS MAY BE ALTERED ON INSTRUCTIONS
F/2 F/2
H, J, or K
FROM IRISH WATER.
G/2
G/2
PLAN PLAN NOTE: PLAN 8. CONCRETE IN THRUST BLOCKS SHALL BE GRADE C20/25 IN ACCORDANCE
ANTI-TORQUE
300
CONCAVE BEND CONVEX BEND H FOR 45 DEGREE BEND J DEAD END 500
SUPPORT 300 WITH IS EN 206.
FOR 22.5 DEGREE BEND K PLAN 9. COMPRESSIBLE FILLER FOR CONCRETE PROTECTION TO BE IN
VERTICAL BENDS FOR 11.25 DEGREE BEND DEAD END THRUST BLOCK FOR SLUICE VALVE / GATE VALVE SECTION ACCORDANCE WITH BS EN 622-1 AND BS EN 622-4. BITUMINOUS
FOR VALVE BOX ARRANGEMENT MATERIAL SHALL NOT BE PUT IN CONTACT WITH PLASTIC PIPES.
THE THICKNESS OF COMPRESSIBLE FILLER FOR MAINS < 450mm IN
< 12 BAR TEST PRESSURE 12 BAR TO 15 BAR TEST PRESSURE 15 BAR TO 18 BAR TEST PRESSURE DIAMETER IS TO BE 18mm.
10. CONCRETE THRUST BLOCKS FOR POLYETHYLENE PIPE TO COMPLY
NOM. DIMENSIONS NOM. DIMENSIONS NOM. DIMENSIONS
DIA. WITH THE MANUFACTURER'S REQUIREMENTS.
DIA. DIA.
(mm) A B C D E F G H J K (mm) A B C D E F G H J K (mm) A B C D E F G H J K
100 600 330 160 80 200 350 390 700 600 400 100 700 380 190 100 200 350 510 750 600 400 100 750 400 205 100 220 400 530 800 650 400
TABLE OF DIMENSIONS FOR STEEPLY INCLINED PIPELINES
150 950 510 260 130 225 450 660 900 750 600 150 1135 620 320 160 225 450 760 950 750 600 150 1250 700 350 180 250 500 890 1000 850 650
200 1150 600 310 160 300 650 790 1050 900 700 200 1400 750 380 190 300 650 980 1150 950 700 200 1650 890 450 230 320 700 1170 1250 1000 800 GRADIENT SPACING
250 1350 750 380 200 300 800 970 1200 1000 750 250 1730 940 480 240 320 800 1210 1350 1050 850 250 1960 1060 540 270 350 900 1370 1450 1150 900
1 IN 2 & STEEPER 5.5m
300 1580 850 450 220 320 950 1110 1300 1100 850 300 2090 1130 580 300 380 950 1480 1500 1200 950 300 2300 1200 640 320 500 1100 1630 1650 1300 1050
350 2100 1150 570 290 450 1000 1450 1550 1200 900 350 2600 1410 720 360 500 1050 1840 1700 1350 1050 350 2930 1580 830 410 750 1200 2070 1850 1500 1150 BELOW 1 IN 2 TO 1 IN 4 11.0m
400 2550 1400 700 350 500 1050 1800 1700 1250 1000 400 2980 1610 820 420 750 1200 2110 1850 1500 1150 400 3510 1900 970 190* 1000 1300 2490 2000 1600 1250
450 3000 1630 830 420 680 1100 2130 1800 1450 1150 450 3400 1840 940 470 900 1300 2330 2000 1600 1250 450 3810 2270 1160 580 1000 1350 2970 2150 1700 1350 1 IN 4 TO 1 IN 5 16.6m
500 3590 1950 990 500 800 1200 2540 1950 1600 1250 500 4090 2210 1130 570 1000 1400 2890 2200 1750 1350 500 4340* 2380 1210 610 1000 1400 3700 2250 1750 1400
1 IN 5 TO 1 IN 6 22.0m
600 4100 2200 1120 570 850 1400 2880 2100 1700 1300 600 5010* 2710* 1380 700 1000 1500 3550* 2350 1900 1500 600 6370* 3450* 1760 890 1000 1500 4500* 2400 2050 1650
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
THRUST BLOCKS
Anti-torque support note & thrust
1 11/'17 JMC TOC MOD FOR RISING MAINS
flange added & note 6 updated STD-WW- 14 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. VALVE SURFACE BOX TO BE IN ACCORDANCE WITH IS 261 OR BS 5834. SCOUR CHAMBERS SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL COVERS TO IS EN
124 RATING D400. COVERS AND FRAMES SHALL BE SUITABLE FOR ROAD AND TRAFFIC CONDITIONS SUBJECT TO REVIEW BY IRISH WATER.
3. SLUICE VALVES SHALL BE DOUBLE FLANGED WITH DUCTILE IRON RESILIENT SEAL GATE VALVES, SUITABLE FOR USE IN RISING MAINS. THEY SHALL COMPLY WITH THE
REQUIREMENTS OF IS EN 1074 AND THEY SHALL HAVE THE APPROPRIATE CE MARKING.
4. SCOUR CHAMBER TO BE IN ACCORDANCE WITH BS EN 1992-3.
5. STRUCTURAL DESIGN AND REINFORCEMENT DETAILS TO BE PROVIDED BY THE DEVELOPER AND SUBMITTED TO IRISH WATER FOR REVIEW. ROOF SLABS SHALL BE
DESIGNED TO CARRY ALL LIVE LOADS & DEAD LOADS, & CONSIST OF A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM
THICKNESS OF 225mm. ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911 Part 4.
6. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-WW-14 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND PIPES AT
STEEP SLOPES.
7. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
8. ANTI CORROSION TAPE TO BE PROVIDED AROUND BURIED FLANGES.
9. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
10. ALL DUCTILE IRON PIPEWORK AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 598.
11. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED ON GROUND CONDITIONS WITHIN THE SITE. SHOULD ANTI FLOATATION MEASURES BE
REQUIRED THEY SHALL BE SUBJECT TO REVIEW BY IRISH WATER.
12. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD AUTHORITY'S REQUIREMENTS.
13. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
14. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF TRANSPORT,
TOURISM & SPORT, OR TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
225
WITH THRUST FLANGE
OF CLASS B
( LENGTH CUT TO SUIT) PRECAST CONSTRUCTION
DEPTH TO SUIT
MIN. 600 ENGINEERING BRICKS
AS PER STD-WW-10
D.I. PLAIN ENDED PIPE SET IN C50/60 MORTAR
( LENGTH CUT TO SUIT)
300 150 MANHOLE STEPS TO COMPLY WITH
IS EN 13101, TYPE D, CLASS 1,
ALL FLANGED
GALVANISED MILD STEEL &
LEVEL INVERT TEE
PLASTIC ENCAPSULATED.
200
300 200
300
500
200
BLIND SCOUR CHAMBER TO
LONG BODY TO BE EMPTIED BY VACUUM 200 300 400 300 400 x 400 x 200mm
D.I. SLUICE VALVE DEEP SUMP
FLEXIBLE JOINT TANKER
1350 DIA. REINFORCED CONCRETE
75mm CONCRETE GRADE
BASE SLAB C30 / 37
C12/15 BLINDING
SECTION A-A SECTION B-B
PRECAST CONSTRUCTION
D.I. SLUICE VALVE AS PER STD-WW-10
ALL FLANGED D.I. SLUICE VALVE D.I. SLUICE VALVE SEE DRAWING
LEVEL INVERT TEE SEE DRAWING STD-WW-16/17
STD-WW-16/17
ALL FLANGED LEVEL INVERT TEE
DIAMETER OF DIAMETER OF
RISING MAIN (mm) SCOUR (mm)
80 80
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
2 11/'17 JMC TOC Revised & added notes MOD SCOUR VALVE CHAMBER
Added steps, revised note
1 08/'16 JMC TOC 2, dims, cover & ope notes. MOD FOUL RISING MAIN (< 200mm DIA.) STD-WW- 15 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
GRADE C30/37, WITH A MINIMUM THICKNESS OF 150mm. ALTERNATIVELY, PRE-CAST CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-WW-07.
7. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206 : 2013.
8. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 598.
280
MAX.
300
300
FINISHED GROUND LEVEL & 17.
FINISHED GROUND LEVEL
COVER TO BE SET 1 No. COURSE MIN. COVER TO BE SET
IN C50\60 MORTAR 3 No. COURSES MAX. IN C50\60 MORTAR
OF CLASS B ENGINEERING BRICKS
CONCRETE ROOF SLAB SET IN C50/60 MORTAR
REFER TO NOTE 2 ON STD-WW-07
150
150
C30 / 37 REINFORCED SLAB CONCRETE ROOF SLAB
FOR MIN. DEPTH OF COVER
100
CONCRETE BEARING FLANGE DETAILS
SLAB
LOCALLY
LOCALLY
REFER TO STD-WW-07
MIN.
MIN.
150
150
FOR BEDDING AND
BACKFILLING DETAILS
LONG BODY FLANGED / PLAIN ENDED FLANGED / PLAIN ENDED FLANGED / PLAIN ENDED FLANGED / PLAIN ENDED
150
150
FLEXIBLE PIPE CUT TO SUIT PIPE CUT TO SUIT LONG BODY PIPE CUT TO SUIT PIPE CUT TO SUIT LONG BODY
COUPLING FLEXIBLE
FLANGED SLUICE VALVE DISMANTLING JOINT COUPLING FLANGED DISMANTLING JOINT FLEXIBLE
SLUICE VALVE CONCRETE ANTI-TORQUE SUPPORT COUPLING
CONCRETE ANTI-TORQUE
SUPPORT
SECTION SECTION
445
445
280
280
PRECAST
50
CONCRETE BLOCKWORK
100
IN ACCORDANCE WITH
IS EN 771-3
600
600
100
215
50
50
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
3 11/'17 JMC TOC Revised & Added Notes MOD SLUICE VALVE DETAILS FOR RISING MAINS
2 08/'16 JMC TOC Revised note 6 (Cl. 808) MOD
1 04/'16 JMC TOC Flexible couplings shown MOD DUCTILE IRON (D.I.) PIPE (< 200mm DIA.) STD-WW- 16 3
0 09/'15 JMC TOC Initial Issue SL (Sheet 1 of 2)
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. SLUICE VALVE CHAMBERS SHALL BE COVERED WITH APPROVED HEAVY DUTY METAL COVERS TO IS 261 AND BS 5834. COVER AND FRAME SHALL BE
SUITABLE FOR ROAD AND TRAFFIC CONDITIONS AND IS SUBJECT TO REVIEW BY IRISH WATER.
3. SLUICE VALVES SHALL BE DOUBLE FLANGED WITH DUCTILE IRON RESILIENT SEAL GATE VALVES, SUITABLE FOR USE IN RISING MAINS. THEY SHALL COMPLY
200 445 200 WITH THE REQUIREMENTS OF IS EN 1074 AND THEY SHALL HAVE THE APPROPRIATE CE MARKINGS.
4. ALL SLUICE VALVES SHALL BE CLOCKWISE CLOSING.
5. VALVE CHAMBER TO BE CONSTRUCTED OF PRECAST CONCRETE UNITS OR HIGH DENSITY BLOCKWORK. ALTERNATIVELY PROPRIETARY PREFABRICATED
CHAMBER UNITS MAY ALSO BE USED, SUBJECT TO REVIEW BY IRISH WATER. ROOF SLABS SHALL BE DESIGNED TO CARRY ALL LIVE LOADS & DEAD LOADS, &
200
CONSIST OF A REINFORCED CONCRETE SLAB OF IN-SITU CONCRETE, GRADE C30/37, WITH A MINIMUM THICKNESS OF 150mm. ALTERNATIVELY, PRE-CAST
CONCRETE ROOFS MAY BE USED, SUBJECT TO IRISH WATER REVIEW, & COMPLIANCE WITH BS 5911, Part 4.
6. CONCRETE CHAMBERS SHALL BE SURROUNDED BY A MINIMUM OF 150mm COMPACTED CLAUSE 808 MATERIAL AS PER STD-WW-07.
7. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
280
BULL NOSE 8. DUCTILE IRON PIPES AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 598.
FINISH 9. PE PIPES TO BE IN ACCORDANCE WITH IS EN 12201 : 2011.
10. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN GREEN AREAS.
11. THRUST BLOCKS (NOT SHOWN ON DRAWING), TO BE PROVIDED AS PER STANDARD DRAWING STD-WW-14 AT ALL TEES, BENDS, TAPERS, DEAD ENDS AND
PIPES AT STEEP SLOPES.
200
MAX.
IN C50\60 MORTAR 3 No. COURSES MAX.OF IN C50\60 MORTAR
300
300
CLASS B ENGINEERING BRICKS
SET IN C50/60 MORTAR CONCRETE ROOF SLAB
REFER TO NOTE 2 ON STD-WW-07
150
150
CONCRETE ROOF SLAB C30 / 37 REINFORCED SLAB
FOR MIN. DEPTH OF COVER
100
CONCRETE BEARING C25\30 PRECAST
SLAB CONCRETE BEARING SLAB
LOCALLY
LOCALLY
REFER TO STD-WW-07 REFER TO STD-WW-07
MIN.
MIN.
150
150
FOR BEDDING AND FOR BEDDING AND
BACKFILLING DETAILS BACKFILLING DETAILS
POLYETHYLENE POLYETHYLENE
(P.E.) PIPE (P.E.) PIPE
150
150
FUSION WELD FUSION WELD FUSION WELD
STUB FLANGE STUB FLANGE STUB FLANGE
WITH BACKING RING WITH BACKING RING WITH BACKING RING
DISMANTLING JOINT FLANGED
DISMANTLING JOINT
FLANGED SLUICE VALVE SLUICE VALVE
CONCRETE ANTI-TORQUE SUPPORT CONCRETE ANTI-TORQUE SUPPORT
SECTION SECTION
445
445
280
ROOF PLAN
ROOF PLAN
50 100 100 50 50 50
600 215 600 215
50
PRECAST
50
CONCRETE UNITS
(REFER TO NOTE 5.)
215
100
600
100
215
50
50
225 MIN.
HEAVY DUTY COVER AND
FRAME SHALL COMPLY WITH IS COVERS TO BE
CONCRETE ROOF SLAB EN 124 AND BS 7903, CLASS SET IN C50\60
C30/37 REINFORCED SLAB D400 (TO SUIT 900 SQ. OPE) MORTAR SEE NOTES 14, 15 & 16.
FLOW FLOW
MIN.
300
ROCKER PIPE
ROCKER PIPE
300
400
ROOF PLAN
2000
300
400 MIN. 400
1500
2000
FLOW FLOW
MIN.
300
THRUST FLANGE
250
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
AIR VALVE CHAMBER
2 11/'17 JMC TOC Revised & added notes MOD
1 08/'16 JMC TOC Revised note 5 & cover notes MOD (FOUL RISING MAIN < 200mm DIA.) STD-WW- 18 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
TO DUCTS
COVER
200
75
6. LONG RADIUS BENDS MAY BE USED FOR CHANGES IN DIRECTION OF UP TO 45°
DUCT CHAMBERS SHALL BE PROVIDED FOR ALL BENDS GREATER THAN 45°.
75
CABLE DUCTS
7. DUCT CHAMBERS TO BE LOCATED AT 50m INTERVALS MAXIMUM.
200
APPROVED SAND
8. APPROPRIATE MARKER TAPE SHALL BE LAID 200mm ABOVE THE EXTERNAL CROWN
OF THE DUCT AND SHOULD INCORPORATE REINFORCED TRACING WIRE.
TRACING WIRES SHALL BE CONNECTED ACROSS CHAMBERS.
ELECTRICAL MARKER TAPE TO BE USED IN ACCORDANCE WITH ESB SPECIFICATION.
11. ALL DUCTING TO BE INSTALLED WITH DRAW CORDS/ROPES, TO ALLOW THE PULL THROUGH
OF CABLES.
12. CABLE DUCT INTERFACE WITH CHAMBER WALL TO BE SEALED TO PREVENT INGRESS OF
GROUNDWATER TO CHAMBER.
C C
CABLE DUCT
1350
900
A A
1350
PLAN
75
150
150
225
1350 1350
SECTION A - A SECTION B - B
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
225
HANDRAILING MAY BE REQUIRED TO
DESIGNERS RISK ASSESSMENT
DEVELOPMENT
PUDDLE FLANGE
TO MATCH
DUCK BILL
CHECK VALVE
150
225
ROCKER PIPE
75 BLINDING C12/15
300
CONCRETE GRADE C 30/37
1000
SECTION
225
PUDDLE FLANGE
FLEXIBLE COUPLINGS
PIPE DIA.
+ 450
ROCKER PIPE
225
1
2
1000
PLAN
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
1 11/'17 JMC TOC Notes revised MOD EMERGENCY OVERFLOW STRUCTURE STD-WW- 20 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
4. ALL DUCTILE IRON PIPE WORK AND FITTINGS TO BE IN ACCORDANCE WITH IS EN 598.
6. ALL MANHOLES TO BE LOCATED A MINIMUM OF 5000mm FROM THE BANK EDGE TO ALLOW
FOR FUTURE ACCESS.
5000mm 5000mm
BANK EDGE
BANK EDGE
500mm MIN. OR TO REQUIREMENTS OF
RELEVANT AUTHORITY
BED OF STREAM
M.H. M.H.
FLEXIBLE JOINT
FULL CONCRETE
SEE DRAWING SURROUND 2x DIAMETER SEE DRAWING
STD-WW-10 AND GRADE C25/30 OR 1000mm MAX. STD-WW-10 AND
STD-WW-11 FOR DETAILS SEE STD-WW-11
FOR MANHOLE DRAWING STD-WW-08 FOR MANHOLE
DETAILS DETAILS
SECTION
5000mm
O.D. + 300mm
M.H. M.H.
PLAN
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
TYPICAL DITCH / STREAM CROSSING
1 11/'17 JMC TOC Updated pipe depth dimension MOD FOR GRAVITY MAIN STD-WW- 21 1
0 09/'15 JMC TOC Initial Issue SL (Sheet 1 of 2)
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
BANK EDGE
DETAILS REFER TO STD-WW-15
RELEVANT AUTHORITY
5000mm 5000mm
BED OF STREAM
REFER TO NOTE 3
FOR BENDS FUSION FUSION FLEXIBLE
WELD WELD COUPLING
FOR THRUST BLOCK DETAILS
REFER TO STD-WW-14
DI / PE PIPE
SEE NOTE 11
O.D. + 300mm
POLYETHYLENE
300 300 PIPEWORK 300 300 DI / PE PIPE
SEE NOTE 11
STUB FLANGE WITH CONCRETE SURROUND GRADE C 25/30. STUB FLANGE WITH
BACKING RING FOR FOR DETAILS SEE DRAWING STD-WW-08 BACKING RING FOR
DI/PE CONNECTION DI/PE CONNECTION
SECTION
SCOUR CHAMBER
PLAN
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
TYPICAL DITCH / STREAM CROSSING
Updated pipe depth dimension &
1 11/'17 JMC TOC note 10 revised MOD FOR RISING MAIN STD-WW- 22 1
0 09/'15 JMC TOC Initial Issue SL (Sheet 2 of 2)
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
BRIDGE PARAPET 1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
TAPPING WITH TRANSITION
32mm O.D. 150 150 2. AT BRIDGE CROSSING DUCTILE IRON PIPE WORK AND FITTINGS TO BE IN ACCORDANCE
90° ELBOW (MALE)
P.E. PIPE WITH IS EN 598.
150
5. THE DEVELOPER IS TO SEEK ADVICE FROM IRISH WATER AS TO WHETHER A DUPLICATE
RISING MAIN IS TO BE PROVIDED THROUGH THE BRIDGE CROSSING.
IF NECESSARY THE DEVELOPER WILL SUBMIT A DESIGN TO IRISH WATER FOR REVIEW.
SOCKET OUTLINE DUCTILE IRON
RISING MAIN 6. THRUST BLOCKS TO BE PROVIDED AS PER STD-WW-14 AT ALL TEES,
BENDS, TAPERS, DEAD ENDS AND PIPES ATE STEEP SLOPES.
7. THE QUALITY OF THE KIOSK CONSTRUCTION SHALL ENSURE THAT THE FOLLOWING IS ACHIEVED:
150
A) A THERMAL TRANSMITTANCE OF 1.5W PER m² K.
B) A FIRE RESISTANCE (RETENTION OF STABILITY, INTEGRITY AND INSULATION) EQUIVALENT TO
CLASS 2 OF BS 476, WHEN TESTED IN ACCORDANCE WITH BS 476 FOR A PERIOD EXCEEDING
30 MINUTES.
8. KIOSK (MIN. 600 HIGH x 450 WIDE x 300mm DEEP) TO BE CONSTRUCTED FROM THERMOSETTING U.V. &
WEATHER RESISTANT PLASTIC POWDER COATED & HOT DIPPED GALVANISED STEEL (MIN. 4mm
THICKNESS) TO BS EN 1461. STAINLESS STEEL OR NON-METALLIC MATERIALS, SUCH AS GLASS
REINFORCED PLASTIC (GRP), MAY BE USED AS AN ALTERNATIVE KIOSK MATERIAL, PARTICULARLY IN
SEVERE ENVIRONMENTS, SUBJECT TO AGREEMENT WITH IRISH WATER. COLOUR TO BE HOLLY
GREEN BS 4800 14 C 39, TO HAVE HINGED, LOCKABLE ACCESS DOOR (HINGES AND LOCKS TO BE
STAINLESS STEEL).
9. THE KIOSK SHALL BE LOCATED OFF THE FOOTPATH SO AS NOT TO IMPEDE PEDESTRIANS
AND POSITIONED SO AS TO FACILITATE SAFE ACCESS FOR MAINTENANCE PERSONNEL.
SECTION A - A 10. KIOSK TO BE FITTED WITH A VENT STACK TO MANUFACTURERS DETAIL IN SENSITIVE AREAS.
(AIR VALVE CONNECTION) 11. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
12. IN INSENSITIVE AREAS A VENT STACK IS NOT REQUIRED. LOUVRE VENT TO BE PROVIDED IN KIOSK.
KIOSK
(SEE NOTES 7, 8 & 9)
13. DETAIL FOR RISING MAIN FOR PE PIPEWORK TO BE AS PER THIS DETAIL. BRIDGE CROSSING
PIPEWORK TO BE DUCTILE IRON IN BOTH CASES.
AIR VALVE
14. THE LOCATION OF THE SCOUR CHAMBER MUST BE REVIEWED BY IRISH WATER & READILY
ACCESSIBLE BY ALL OPERATION & MAINTENANCE EQUIPMENT, INCLUDING A VACUUM TANKER.
EXPOSED PIPEWORK DUCTILE IRON
TO BE INSULATED PIPEWORK
32mm DIA. P.E. PIPE
USING PIPE LAGGING
ROAD LEVEL
CONCRETE SURROUND
TAPPING POINT TO GRADE C 25/30.
BE LOCATED AT SEE DRAWING STD-WW-10
HIGH POINT
FLEXIBLE JOINT
POLYETHYLENE
OR DUCTILE IRON FLEXIBLE POLYETHYLENE
FOR SCOUR VALVE / PIPEWORK JOINT OR DUCTILE IRON
CHAMBER DETAILS PIPEWORK
REFER TO STD-WW-15
SECTION
A
POLYETHYLENE POLYETHYLENE
OR DUCTILE IRON OR DUCTILE IRON
PIPEWORK PIPEWORK
POLYETHYLENE
SERVICE PIPE BRIDGE PARAPET
CONCRETE PLINTH
(150 HIGH x 600 LONG
KIOSK
(600 HIGH x 450 WIDE
A (32mm DIA. P.E.)
x 450 WIDE) x 300 DEEP)
PLAN
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
TYPICAL
1 11/'17 JMC TOC Notes 5 & 14 revised MOD BRIDGE CROSSING FOR RISING MAIN STD-WW- 23 1
0 09/'15 JMC TOC Initial Issue SL (Sheet 1 of 2)
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
1. ALL DIMENSIONS IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
RELEVANT AUTHORITY
FOR AIR VALVE / CHAMBER
DETAILS REFER TO STD-WW-18 14.THE LOCATION OF THE SCOUR CHAMBER MUST BE REVIEWED BY IRISH
AIR VALVE TO BE LOCATED WATER & READILY ACCESSIBLE BY ALL OPERATION & MAINTENANCE
BOTH SIDES OF CROSSING EQUIPMENT, INCLUDING A VACUUM TANKER.
BANK EDGE
BANK EDGE
FOR SCOUR VALVE / CHAMBER
DETAILS REFER TO STD-WW-15
5000mm
5000mm
O.D. COLLAR + 300mm
BED OF
STREAM
REFER TO NOTE 3
FOR BENDS
FLEXIBLE
FOR THRUST BLOCK JOINT
DETAILS REFER
TO STD-WW-14
POLYETHYLENE
OR DUCTILE IRON
PIPEWORK
300 300 POLYETHYLENE 300 300
PIPEWORK
POLYETHYLENE
FOR AIR VALVE / CHAMBER STUB FLANGE WITH FUSION FUSION STUB FLANGE WITH
CONCRETE SURROUND WELD OR DUCTILE IRON
DETAILS REFER TO STD-WW-18 BACKING RING WELD BACKING RING
GRADE C 25/30. FOR DETAILS PIPEWORK
AIR VALVE TO BE LOCATED
BOTH SIDES OF CROSSING SEE DRAWING STD-WW-08
SECTION
ROAD
BRIDGE PARAPET
POLYETHYLENE
OR DUCTILE IRON
PIPEWORK
O.D. COLLAR + 300mm
PLAN
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
TYPICAL
Updated pipe depth dimension &
1 11/'17 JMC TOC revised notes MOD BRIDGE CROSSING FOR RISING MAIN STD-WW- 24 1
0 09/'15 JMC TOC Initial Issue SL (Sheet 2 of 2)
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
2400
V-BEAM
REINFORCING PROFILE EACH GATE LEAF IN SUCH A WAY THAT THEY CANNOT BE REMOVED BUT ALLOW THE GATE
TO BE SECURED IN BOTH THE OPEN & CLOSED POSITION.
6. THE SECURITY RATING SHALL BE EITHER BASIC +, ENHANCED OR ENHANCED +. THE FENCE
STANDARD WILL BE BASED ON THE SECURITY RATING OF THE SITE & IS TO BE AGREED
WITH IRISH WATER.
ANTI-CLIMB &
ENHANCED + 50 x 50 Type: 868 4mm 2.4m
ANTI-BURROW
B
A
4000 mm MINIMUM
METAL PILLARS
RHS FRAME
LOCKABLE
SLIPBOLT
2400
RSA
SLAMPLATE
DROPBOLTS
GRADE C30/37
CONCRETE IN BASE
FOUNDATION DETAIL FOUNDATION DETAIL
TO MANUFACTURERS TO MANUFACTURERS 75mm CONCRETE
SPECIFICATION SPECIFICATION BLINDING, GRADE C12/15
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
APPROX. 8000mm
CONTROL
KIOSK GATES TO
OPEN INWARDS
2.4m HIGH PLASTIC COATED
WELDED MESH FENCE
INLET METER
IW-CDS-5030-01 Rev. 03 December 2017
PRECAST KERB
4000
SEWER
RISING MAIN
TANKER IMPERMEABLE
HARD STANDING
POWER
FOOTPATH
WATER
GRASS VERGE
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
675 (MAX.)
SEE NOTES 11, 12 & 13.
FINISHED GROUND LEVEL
FOR MIN. DEPTH OF COVER
ROCKER PIPE
ROCKER PIPE
D.I. FLANGED PLAIN
300
SECTION
2000
PE TO DI DETAIL
1 No. MIN.
3 No. COURSES MAX.OF CLASS B
ENGINEERING BRICKWORK
SET IN C50/60 MORTAR
CONCRETE ROOF SLAB
C30 / 37 REINFORCED CONCRETE SLAB
ROOF PLAN
2000
400
1500
300 400
MIN. WATER TIGHT SEAL
FLOW FLOW
M
MIN.
300
THRUST FLANGE
250
C30/37 CONCRETE TO
FLOOR PLAN WALLS AND BASE
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
2 11/'17 JMC TOC Revised & added notes MOD
A A 10. THE PUMPING STATION SHOULD NOT BE LOCATED IN AREAS THAT ARE
SUSCEPTIBLE TO FLOODING AT MORE THAN A 1:30 YEAR RECURRENCE.
THE PUMPING STATION FACILITY SHALL BE DESIGNED FOR INUNDATION.
THE FINISHED SLAB LEVEL SHALL BE POSITIONED ABOVE THE 1:100 YEAR
FLOOD LEVEL. ALL ELECTRICAL CONTROL EQUIPMENT SHALL BE WATER
RESISTANT AND POSITIONED ABOVE 1:200 YEAR FLOOD LEVEL.
11. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED
SEALED DUCTS
BAUER FITTING ON
GATE VALVE ON TEE EMERGENCY OVERFLOW (IF
3No.150 DIA. APPROVED) AND/OR 24 HOUR
TO ALLOW EMPTYING CABLE OPESØ100 PIPE FROM
OF THE RISING MAIN STORAGE TO BE PROVIDED
WASH DOWN
LOW LEVEL MECHANICAL
VENT OVERFLOW
HIGH SCREEN
LEVEL
100mm DIA. uPVC DRAIN VENT
FROM FLOW METER
CHAMBER TO VALVE MINIMUM 225mm DIA. EMERGENCY OVERFLOW PIPE
CHAMBER. OR SIZE TO MATCH CAPACITY OF INCOMING SEWER
IF ALLOWED.
FLAP VALVE
CONC. THRUST BLOCK VALVE CHAMBER
TO BEND (REFER TO DRAIN 80mm DIA
DRG. No. STD-WW-14 DUCTILE IRON
FOR DETAILS)
INCOMING FOUL SEWER (I.L. TO BE LOCATED
100mm ABOVE THE CUT-IN LEVEL OF THE PUMPS).
MAX.
GRADE C30/37
CONCRETE TO WALLS,
BASE AND ROOF
75mm BLINDING
GRADE C12/15
SECTION A-A
RISING MAIN
A A
CONC. THRUST BLOCK 150 DIA. CABLE OPE
TO BEND (REFER TO
DRG. No. STD-WW-14
FOR DETAILS)
1800 MINIMUM 1800 MINIMUM 1000 MINIMUM
REFER TO DRG. No.
STD-WW-09 FOR NON RETURN
PLAN
DETAILS TO STEP IRONS VALVE MINIMUM 225mm DIA. EMERGENCY OVERFLOW PIPE
OR SIZE TO MATCH CAPACITY OF INCOMING SEWER
IF ALLOWED.
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
2 11/'17 JMC TOC Revised notes 2,4,9 & 11 MOD TITLE DRAWING No. REV
Revised note 4, incoming
sewer note & added thrust MOD
1 08/'16 JMC TOC block & step irons to valve
chamber
INDICATIVE SUBMERSIBLE PUMPING STATION STD-WW- 28 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
APPROPRIATE LIFTING
DAVIT & SOCKET FOR
PUMP REMOVAL VALVE CHAMBER MAY BE
(SUBJECT TO REVIEW CONSTRUCTED WITH PRE-CAST
BY IRISH WATER) CONCRETE UNITS OF A SIZE TO
LIFT ASSISTED COVER ACCOMMODATE THE FITTINGS
WITH SAFETY GRID & SHOWN (MIN. 1800mmØ).
INCORPORATED
PUMPING STATION VALVE CHAMBER
HANDRAILS
LIFTING LIFT ASSISTED
ULTRA SONIC COVER
DAVIT
150
SENSOR
SEALED DUCTS SOCKET GL
FLEXIBLE
CHAMBER TO VALVE
COUPLINGS
CHAMBER.
FLAP VALVE ON VALVE CHAMBER GRADE C30/37 CONC. THRUST BLOCK
DRAIN 80mmØ DUCTILE IRON TO CONCRETETO IS 206 TOTO BEND (REFER TO
DISCHARGE ABOVE PUMP CUT-IN WALLS, BASE AND ROOFDRG. No. STD-WW-14
INCOMING FOUL SEWER LEVEL (AS PER PUMP SUPPLIER'S FOR DETAILS)
(I.L. TO BE LOCATED RECOMMENDATIONS)
ABOVE THE CUT-IN LEVEL 100mm
OF THE PUMPS). MAX. BOTTOM PRECAST SECTION TO BE
BUILT INTO BASE CONCRETE
MIN. 150mm GRADE MINIMUM 75mm
C20/25 IN-SITU FIRST RING BUILT INTO
CONCRETE IN-SITU CONCRETE BASE
SURROUND
REINFORCED CONCRETE
CONSTRUCTION BASE GRADE C30/37
300
JOINT
RISING MAIN
75mm GRADE C12/15 1800 (MIN.)
BLINDING CONCRETE TO SUIT PUMP INSTALLATION
1000
BENCHING 45°
MIN. SLOPE
SECTION A-A
VENTS FLANGE
350
BAUER FITTING ON
PROPOSED INLET 150 DIA. 150 DIA. GATE VALVE ON TEE
BAFFLE PLATE CABLE OPE CABLE OPE TO ALLOW EMPTYING
2500 MINIMUM
GATE VALVE
A INCOMING A
FOUL SEWER 150 DIA.
CABLE OPE
MIN. 150mm GRADE CONC. THRUST BLOCK
C20/25 IN-SITU CONCRETE TO BEND (REFER TO
SURROUND DRG. No. STD-WW-14
1800 MINIMUM
STAINLESS STEEL FOR DETAILS)
OVERFLOW BAFFLE
NON RETURN REFER TO DRG. No.
PLATE
VALVE STD-WW-09 FOR
EMERGENCY OVERFLOW (IF DETAILS TO STEP IRONS
APPROVED) AND/OR 24 HOUR
STORAGE TO BE PROVIDED
PLAN
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE JUL. 2016
TITLE DRAWING No. REV
INDICATIVE PRE-CAST CONCRETE
1 11/'17 JMC TOC Revised notes 2,4,9 & 11 MOD SUBMERSIBLE PUMPING STATION STD-WW- 28A 1
0 08/'16 JMC TOC Initial Issue MOD
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. PRE-CAST MANHOLES UNITS: COMPLYING WITH REQUIREMENTS OF
IS EN 1917 AND BS 5911-PART 3.
3. THICKER MANHOLE BASES REQUIRED FOR SEWERS IN EXCESS OF
3m DEEP WHERE THE SIZE IS GREATER THAN THE STANDARD MINIMUM SIZE.
4. PRE-CAST CONCRETE BASES MAY BE USED INCORPORATING
CHANNELS, BENCHING ETC. SUBJECT TO IRISH WATER REVIEW AND
COMPLYING WITH BS 5911-PART 4 2002.
5. STRUCTURAL DESIGN AND REINFORCEMENT DETAILS TO BE PROVIDED BY
THE DEVELOPER AND SUBMITTED TO IRISH WATER FOR REVIEW.
6. MANHOLE ROOFS SHOULD CONSIST OF A REINFORCED CONCRETE SLAB
OF IN-SITU CONCRETE, C30/37, WITH A MINIMUM THICKNESS OF 225mm
DESIGNED TO CARRY ALL LIVE AND DEAD LOADS, ALTERNATIVELY,
APPROVED PRE-CAST CONCRETE ROOF SLABS MAY BE USED SUBJECT
TO IRISH WATER REVIEW AND COMPLIANCE WITH BS 5911 PART 4: 2002.
7. COVERS AND FRAMES SHALL BE SUITABLE FOR ROAD AND TRAFFIC
CONDITIONS SUBJECT TO REVIEW BY IRISH WATER.
8. 200mm ALL AROUND, 100mm DEEP CONCRETE PLINTH AROUND COVERS IN
GREEN AREAS.
9. ALL CHAMBERS TO BE CHECKED FOR UPLIFT BY THE DEVELOPER BASED
ON GROUND CONDITIONS WITHIN THE SITE. SHOULD ANTI FLOATATION
COVER TO BE SET MEASURES BE REQUIRED THEY SHALL BE SUBJECT TO REVIEW BY
IN GRADE C50\60 IRISH WATER.
MORTAR 10. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
11. ANY SPECIAL ROAD REINSTATEMENT AROUND COVER & FRAME SHALL BE TO ROAD
COVER TO BE SEALED & LOCKABLE AUTHORITY'S REQUIREMENTS.
12. NEW ROAD CONSTRUCTION & SURFACE FINISH TO BE TO ROAD AUTHORITY REQUIREMENTS.
MANHOLE COVER AND FRAME SHALL 13. EXISTING ROAD REINSTATEMENT TO COMPLY WITH CURRENT VERSION OF "GUIDELINES FOR
COMPLY TO IS EN 124 AND BS 7903 SEE NOTES 11, 12 & 13. MANAGING OPENINGS IN PUBLIC ROADS" BY THE DEPT. OF TRANSPORT, TOURISM & SPORT, OR
TRANSPORT INFRASTRUCTURE IRELAND REQUIREMENTS.
(ALL CLASS D400 COVERS SHALL HAVE
MIN. FRAME DEPTH 100-150mm) MIN.
OPE. 600 x 600mm FINISHED GROUND LEVEL
1 No. MIN.,
3 No. MAX. OF CLASS B WATER TIGHT SEAL
225
ENGINEERING BRICK
SET IN C50/60 MORTAR 100mm Ø PIPE TO VENT STACK
150mm GRADE C16/20 IN-SITU MIN. 600 SEALED JOINT
CONCRETE SURROUND
ELASTOMERIC JOINTSEAL TO EN 681
500
ALL PRECAST CHAMBER RINGS TO BE REINFORCED
PRECAST CONCRETE MANHOLE RINGS TO IS 420 SLOPE 1:1 BOTTOM PRECAST SECTION TO BE BUILT INTO BASE
0
IN CONJUNCTION WITH IS EN 1917: 2004 CONCRETE MINIMUM 75 mm
BENCHING CONCRETE GRADE C25/30 FINISHED
WITH A 1:3 CEMENT SAND MORTAR
500
Flow
SLOPE
1:10
250
SECTION A-A
FLEXIBLE JOINT
Flow
ROCKER PIPE
(SEE TABLE BELOW)
Max. 600
PLAN
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
2 11/'17 JMC TOC Added rocker pipe table, MOD TITLE DRAWING No. REV
added & updated notes.
RISING MAIN
1 08/'16 JMC TOC Revised cover note & MOD DISCHARGE MANHOLE
access ope dim.
STD-WW- 29 2
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. KIOSKS TO BE CONSTRUCTED FROM THERMOSETTING U.V. & WEATHER RESISTANT PLASTIC POWDER COATED & HOT DIPPED GALVANISED MILD STEEL PLATE (MINIMUM 4mm THICKNESS) TO BS EN 1461. STAINLESS STEEL OR
NON-METALLIC MATERIALS, SUCH AS GLASS REINFORCED PLASTIC (GRP), MAY BE USED AS AN ALTERNATIVE KIOSK MATERIAL, PARTICULARLY IN SEVERE ENVIRONMENTS, SUBJECT TO AGREEMENT WITH IRISH WATER.
3. COLOUR TO BE HOLLY GREEN BS 4800 14 C39. INTERIOR FINISH TO BE WHITE UNLESS APPROVED BY IRISH WATER.
4. THE QUALITY OF KIOSK CONSTRUCTION SHALL ENSURE THAT THE FOLLOWING IS ACHIEVED:
A) A THERMAL TRANSMITTANCE OF 1.5W PER m²K
B) A FIRE RESISTANCE (RETENTION OF STABILITY, INTEGRITY AND INSULATION) EQUIVALENT TO CLASS 2 OF BS 476, WHEN TESTED IN ACCORDANCE WITH BS 476 FOR A PERIOD EXCEEDING 30 MINUTES.
C) AN IP RATING OF IP65 OR EQUIVALENT.
5. KIOSK TO HAVE SINGLE OR DOUBLE STEEL/GRP DOORS WITH MULTIPLE LOCKS TO LPS 1175 SR4 OR EN 1627. MINIMUM DOUBLE LOCKS WITH BOLTS THAT ENGAGE INTO THE SILL & HEADER AS WELL AS BETWEEN THE TWO
LEAVES OR LEAF & FRAME. LEADING EDGE OF LEAVES TO HAVE EITHER REBATED EDGES OR FITTED WITH ASTRAGALS.
6. KIOSK TO BE BOLTED TO THE PLINTH THROUGH A BOTTOM FLANGE WITH GALVANISED MILD STEEL OR STAINLESS STEEL ANCHOR BOLTS.
7. THE BOTTOM FLANGE SHALL BE SEATED ON A NEOPRENE GASKET AND SEALED WITH MASTIC.
8. REAR WALL SHALL BE REINFORCED WITH STAINLESS STEEL SECTIONS TO WHICH A MARINE PLY WOOD , 18mm THICK BOARD IS FIXED.
9. THE DEVELOPER SHALL BE RESPONSIBLE FOR THE ULTIMATE SIZING OF THE KIOSK TO ENSURE ADEQUATE SPACE REQUIREMENTS.
10. TELEMETRY DUCTING TO BE IN ACCORDANCE WITH BS 4660 AND BS EN 1401.
11. ELECTRICAL REQUIREMENTS TO BE IN ACCORDANCE WITH ESB SPECIFICATION.
12. THE ROOF OF THE KIOSK SHALL BE REMOVABLE (BOLTS) TO FACILITATE BACKBOARD REMOVAL.
13. ALL EXPOSED PIPEWORK TO BE ADEQUATELY INSULATED WITH PIPE LAGGING.
14. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
15. WATER TIGHT SEALS ARE TO BE PROVIDED WHERE DUCTING ENTERS DUCT CHAMBERS AND KIOSKS. ALL DUCTING TO BE INSTALLED WITH DRAW CORDS.
16. THE KIOSK SHALL NOT BE LOCATED IN AREAS THAT ARE SUSCEPTABLE TO FLOODING AT A FREQUENCY OF MORE THAN 1:30 YEARS RECURRENCE. THE KIOSK FACILITY SHOULD BE DESIGNED FOR INUNDATION. THE FINISHED
SLAB LEVEL SHOULD BE POSITIONED ABOVE THE 1:100 YEARS FLOOD LEVEL. ALL ELECTRICAL CONTROL EQUIPMENT SHALL BE WATER RESISTANT AND POSITIONED ABOVE THE 1:200 YEAR FLOOD LEVEL.
17. ALL DIMENSIONS ARE MINIMUM DIMENSIONS AND MAY VARY TO SUIT THE KIOSK REQUIREMENT.
SLOPED ROOF
MIN.1200
HIGH LEVEL VENTILATION
MIN. 300
ON OTHER SIDE
MIN. 1800
REMOVABLE
MIN. 1200
WATER - TIGHT
CAP ON PVC DUCT
450
150
150
450mm THICK 600 75mm THICK 600 1500
CONCRETE
CONCRETE
PLINTH
BLINDING SLOW BEND
GRADE C25/ 30
GRADE C12/15
PVC DUCTING WITH
75mm THICK DRAW - CORD
CONCRETE
CROSS SECTION BLINDING CROSS SECTION
GRADE C12/15
(WET KIOSK) (TELEMETRY KIOSK)
HEAVY DUTY
MIN. 600 STEEL HINGES MIN. 1200
TELEMETRY
KIOSK
WET KIOSK
MIN. 1800
RECESS
MIN. 1200
DOUBLE
DOORS
150 150
150 150
450
450
150
150
900
1500
450mm THICK 450mm THICK
CONCRETE 75mm THICK 75mm THICK
CONCRETE
PLINTH CONCRETE CONCRETE
PLINTH
GRADE C25/ 30 BLINDING BLINDING
GRADE C25/ 30
GRADE C12/15 GRADE C12/15
FRONT ELEVATION
FRONT ELEVATION (CONTROL KIOSK)
(WET KIOSK) 150 MIN. 1200 150
MIN. 1200
REMOVABLE
WATER - TIGHT
300
MIN. 600
POWER IN
PLAN DUCT
REFER TO
STD-WW-19 FOR
NOTE: PLAN DUCT CHAMBER DETAILS
ALL KIOSK DIMENSIONS ARE MINIMUM DIMENSIONS & MAY
VARY TO SUIT THE KIOSK REQUIREMENT.
WET KIOSK CONTROL KIOSK
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
KIOSK TYPE 1 PUMPING STATION
2 11/'17 JMC TOC Updated note 9 MOD
1 08/'16 JMC TOC Added note 5 (kiosk doors) MOD AND WET KIOSK STD-WW- 30 2
0 09/'15 JMC TOC Initial Issue SL (Sheet 1 of 2)
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
2. CONTROL KIOSK TO BE CONSTRUCTED FROM 215mm THICK CONCRETE BLOCKS IN ACCORDANCE WITH IS EN 771-3, WITH SMOOTH RENDER FINISH INTERNALLY AND EXTERNALLY. WET KIOSK TO BE CONSTRUCTED FROM THERMOSETTING U.V. &
WEATHER RESISTANT PLASTIC POWDER COATED & HOT DIPPED GALVANISED MILD STEEL PLATE (MINIMUM 4mm THICK) TO BS EN 1461. ALTERNATIVE MATERIAL, STAINLESS STEEL IN HARSH ENVIRONMENTS, NON-METALLIC (GRP, POLYESTER, ETC.)
MAY BE ALLOWED FOR WET KIOSK SUBJECT TO AGREEMENT WITH IRISH WATER.
3. KIOSK TO HAVE SINGLE OR DOUBLE STEEL/GRP DOORS WITH MULTIPLE LOCKS TO LPS 1175 SR4 OR EN 1627. MINIMUM DOUBLE LOCKS WITH BOLTS THAT ENGAGE INTO THE SILL & HEADER AS WELL AS BETWEEN THE TWO LEAVES OR LEAF &
FRAME. LEADING EDGE OF LEAVES TO HAVE EITHER REBATED EDGES OR FITTED WITH ASTRAGALS.
4. COLOUR TO BE HOLLY GREEN BS 4800 14 C39. INTERIOR FINISH TO BE WHITE UNLESS APPROVED BY IRISH WATER.
5. THE QUALITY OF KIOSK CONSTRUCTION SHALL ENSURE THAT THE FOLLOWING IS ACHIEVED:
A) A THERMAL TRANSMITTANCE OF 1.5W PER m²K.
B) A FIRE RESISTANCE (RETENTION OF STABILITY, INTEGRITY AND INSULATION), EQUIVALENT TO CLASS 2 OF BS 476, WHEN TESTED IN ACCORDANCE WITH BS 476 FOR A PERIOD EXCEEDING 30 MINUTES.
C) AN IP RATING OF IP65 OR EQUIVALENT.
6. THE DEVELOPER SHALL BE RESPONSIBLE FOR THE ULTIMATE SIZING OF THE KIOSK TO ENSURE ADEQUATE SPACE REQUIREMENTS.
7. CABLE DUCTING TO BE IN ACCORDANCE WITH BS 4660 AND BS EN 1401.
8. ELECTRICAL REQUIREMENTS TO BE IN ACCORDANCE WITH ESB SPECIFICATION.
9. ALL EXPOSED PIPEWORK TO BE ADEQUATELY INSULATED WITH PIPE LAGGING.
10. ALL CONCRETE TO BE IN ACCORDANCE WITH IS EN 206.
11. WATER TIGHT SEALS ARE TO BE PROVIDED WHERE DUCTING ENTERS DUCT CHAMBERS AND KIOSKS. ALL DUCTING TO BE INSTALLED WITH DRAW CORDS.
12. THE KIOSK SHALL NOT BE LOCATED IN AREAS THAT ARE SUSCEPTABLE TO FLOODING AT A FREQUENCY OF MORE THAN 1:30 YEARS RECURRENCE. THE KIOSK FACILITY SHOULD BE DESIGNED FOR INUNDATION. THE FINISHED SLAB LEVEL SHOULD
BE POSITIONED ABOVE THE 1:100 YEAR FLOOD LEVEL. ALL ELECTRICAL CONTROL EQUIPMENT SHALL BE WATER RESISTANT AND POSITIONED ABOVE THE 1:200 YEAR FLOOD LEVEL.
13. ALL DIMENSIONS ARE MINIMUM DIMENSIONS AND MAY VARY TO SUIT THE KIOSK REQUIREMENT.
150mm REINFORCED
1800
CONCRETE ROOF SLAB
TO GRADE C30/37
WITH WEATHER PROOF
ASPHALT FINISH
2400
LOW LEVEL VENTILATION
300 (LOUVRED GRILLE)
REMOVABLE
WATER - TIGHT 150 150
CAP ON PVC DUCT
450
1200
150
150 150
600 2100
450
SLOW BEND
150
GALVANISED DOORS TO BS
729
1200
150 150
150 150
450
450
150
900
150
450mm THICK
CONCRETE 2100
450mm THICK 75mm THICK PLINTH 75mm THICK
CONCRETE CONCRETE GRADE C25/ 30 CONCRETE
PLINTH BLINDING BLINDING
GRADE C25/ 30 GRADE C12/15 FRONT ELEVATION GRADE C12/15
(CONTROL KIOSK)
FRONT ELEVATION 215 215
900
300
2100
600
1585
600
REMOVABLE
WATER - TIGHT
CAP ON PVC DUCT
PLAN
POWER IN
DUCT
REFER TO
NOTE: STD-WW-19 FOR
ALL KIOSK DIMENSIONS ARE MINIMUM DIMENSIONS & MAY
VARY TO SUIT THE KIOSK REQUIREMENT.
PLAN DUCT CHAMBER DETAILS
4000mm
1:40 FALL
75mm THICKNESS OF
10mm SINGLE SIZED CROSS SECTION
AGGREGATE GEOTEXTILE
WEED BARRIER OF MACADAM SURFACE
400mm 75mm
CLAUSE 804
PERMEABLE AREA
4000mm
1:40 FALL
CROSS SECTION
CONCRETE SLAB
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
1 11/'17 JMC TOC Updated notes 2 & 3 MOD HARDSTANDING AREA PUMPING STATION STD-WW- 32 1
0 09/'15 JMC TOC Initial Issue SL (PERMEABLE AND IMPERMEABLE)
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
510
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
470
3. LAMP STANDARD TO BE REVIEWED BY IRISH WATER.
LAMP STANDARD
SHAFT
100
305
762
75 BLINDING
ARMOURED CABLING TO DUCT
600 100mm DIA. T.PIECE 100mm DIA. DUCT
SECTION SECTION
600 300
LAMP BOLLARD
CONCRETE GRADE C30/37
300
600
600 x 450 CABLE JUNCTION BOX MIN. 100 DIA. CABLE DUCT
(SIMILAR TO DUCT CHAMBER
DETAIL ON DRG. No. STD-WW-19)
PLAN
PLAN
LAMP STANDARD LAMP BOLLARD
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
1 11/'17 JMC TOC Updated notes 2 & 3 MOD LAMP BOLLARD & LAMP STANDARD STD-WW- 33 1
0 09/'15 JMC TOC Initial Issue SL
No. Date Drn Chk Description App
IW-CDS-5030-01 Rev. 03 December 2017
1. ALL DIMENSIONS ARE IN MILLIMETRES (mm) UNLESS NOTED OTHERWISE.
7.600
1200
800
CONCRETE C30/37
900
VENT DETAIL
REFER TO INDEX SHEET FOR NOTES REGARDING DESIGN RESPONSIBILITY & RISK ASSESSMENT
SCALE DATE
STANDARD DETAILS - WASTEWATER NOT TO SCALE SEPT. 2015
TITLE DRAWING No. REV
STD-WW-06 RESTRICTIONS ON WASTEWATER INFRASTRUCTURE WORKS ADJACENT TO Revised to suit ILI recommendations 2 Drawing revised
TREES
STD-WW-06A RESTRICTIONS ON NEW TREES/SHRUBS PLANTING ADJACENT TO SEWERS 0 New Drawing
STD-WW-07 TRENCH BACKFILL & BEDDING Updated & added Notes 1 Drawing revised
STD-WW-08 CONCRETE BED, HAUNCH & SURROUND TO WASTEWATER PIPES 0 No change
STD-WW-09 BLOCKWORK MANHOLE (<450mm DIA.) Added rocker pipe table Updated & added Notes 2 Drawing revised
STD-WW-10 PRE-CAST CONCRETE MANHOLE Added rocker pipe table & deep Updated & added Notes 2 Drawing revised
manhole detail
STD-WW-11 IN-SITU CONCRETE MANHOLE Added rocker pipe table & deep Updated & added Notes 2 Drawing revised
manhole detail
STD-WW-12 BACKDROP MANHOLES Updated notes 2 Drawing revised
STD-WW-13 PRIVATE SIDE INSPECTION CHAMBER Updated notes 2 Drawing revised
STD-WW-14 THRUST BLOCKS FOR RISING MAINS Anti-torque support note & thrust flange Note 6 updated 1 Drawing revised
added
STD-WW-15 SCOUR VALVE CHAMBER (FOUL RISING MAIN <200mm DIA.) Revised & added notes 2 Drawing revised
STD-WW-16 SLUICE VALVE DETAILS FOR RISING MAINS DUCTILE IRON (D.I.) PIPE (<200mm Revised & added notes 3 Drawing revised
DIA.) (Sheet 1 of 2)
STD-WW-17 SLUICE VALVE DETAILS FOR RISING MAINS POLYETHYLENE (P.E.) PIPE Revised & added notes 2 Drawing revised
(<200mm DIA.) (Sheet 2 of 2)
STD-WW-18 AIR VALVE CHAMBER (FOUL RISING MAIN <200mm DIA.) Revised & added notes 2 Drawing revised
STD-WW-19 DUCT CHAMBER Revised notes 2 Drawing revised
STD-WW-20 EMERGENCY OVERFLOW STRUCTURE Notes revised 1 Drawing revised
STD-WW-21 TYPICAL DITCH/STREAM CROSSING FOR GRAVITY MAIN (Sheet 1 of 2) Updated pipe depth dimension 1 Drawing revised
STD-WW-22 TYPICAL DITCH/STREAM CROSSING FOR RISING MAIN (Sheet 2 of 2) Updated pipe depth dimension Note 10 revised 1 Drawing revised
STD-WW-23 TYPICAL BRIDGE CROSSING FOR RISING MAIN (Sheet 1 of 2) Notes 5 & 14 revised 1 Drawing revised
STD-WW-24 TYPICAL BRIDGE CROSSING FOR RISING MAIN (Sheet 2 of 2) Updated pipe depth dimension Revised notes 12 & 14 1 Drawing revised
STD-WW-25 SECURITY GATE & FENCING Fencing table updated 2 Drawing revised
STD-WW-26 INDICATIVE PUMPING STATION LAYOUT 0 No change
STD-WW-27 FLOW METER CHAMBER (FOUL RISING MAIN <200mm DIA.) Revised & added notes 2 Drawing revised
STD-WW-28 INDICATIVE SUBMERSIBLE PUMPING STATION Revised notes 2,4,9 & 11 Revised notes 2 Drawing revised
STD-WW-28A INDICATIVE PRE-CAST CONCRETE SUBMERSIBLE PUMPING STATION Revised notes 2,4,9 & 11 Revised notes 1 Drawing revised
STD-WW-29 RISING MAIN DISCHARGE MANHOLE Added rocker pipe table Updated & added Notes 2 Drawing revised
STD-WW-30 KIOSK TYPE 1 PUMPING STATION & WET KIOSK (Sheet 1 of 2) Updated note 9 2 Drawing revised
STD-WW-31 KIOSK TYPE 2 + 3 PUMPING STATION & WET KIOSK (Sheet 2 of 2) Updated note 6 2 Drawing revised
STD-WW-32 HARDSTANDING AREA PUMPING STATION (PERMEABLE & IMPERMEABLE) Updated notes 2 & 3 1 Drawing revised
STD-WW-33 LAMP BOLLARD & LAMP STANDARD Updated notes 2 & 3 1 Drawing revised
STD-WW-34 VENT STACK Updated note 2 1 Drawing revised
/ INDEX SHEET Inclusion of STD-WW-06A Drawing revisions updated Nov 2017 Drawing revisions updated
/ Design Risk Assessment for Wastewater Standard Details Inclusion of STD-WW-06A General Amendments v4.01 Document revised