Air Change Rates in typical Rooms and
Buildings
The table below indicates air change rates (air changes per hour) in common types of rooms and
buildings.
Note! - be aware that it may be necessary to calculate required supply air based on no. of
persons in the room or building. More information about required supply air per person can be
found here.
Air Change Rate
Building / Room -n-
(1/h)
Auditoriums 8 - 15
Bakeries 20 - 30
Banks 4 - 10
Barber Shops 6 - 10
Bars 20 - 30
Beauty Shops 6 - 10
Boiler rooms 15 - 20
Bowling Alleys 10 - 15
Cafeterias 12 - 15
Churches 8 - 15
Classrooms 6 - 20
Club rooms 12
Clubhouses 20 - 30
Air Change Rate
Building / Room -n-
(1/h)
Cocktail Lounges 20 - 30
Computer Rooms 15 - 20
Court Houses 4 - 10
Dental Centers 8 - 12
Department Stores 6 - 10
Dress Shops 6 - 10
Drug Shops 6 - 10
Fire Stations 4 - 10
Foundries 15 - 20
Galvanizing plants 20 - 30
Air Change Rate
Building / Room -n-
(1/h)
Garages repair 20 - 30
Jewelry shops 6 - 10
Kitchens 15 - 60
Laundries 10 - 15
Libraries, public 4
Luncheonettes 12 -15
Nightclubs 20 - 30
Machine shops 6 - 12
Malls 6 - 10
Medical Centers 8 - 12
Medical Clinics 8 - 12
Medical Offices 8 - 12
Air Change Rate
Building / Room -n-
(1/h)
Mills, paper 15 - 20
Municipal Buildings 4 - 10
Museums 12 -15
Offices, public 3
Offices, private 4
Pig houses 6 - 10
Police Stations 4 - 10
Post Offices 4 - 10
Poultry houses 6 - 10
Precision Manufacturing 10 - 50
Pump rooms 5
Residences 1-2
Restaurants 8 - 12
Air Change Rate
Building / Room -n-
(1/h)
Retail 6 - 10
School Classrooms 4 - 12
Shoe Shops 6 - 10
Shopping Centers 6 - 10
Shops, machine 5
Shops, paint 15 - 20
Shops, woodworking 5
Substation, electric 5 - 10
Supermarkets 4 - 10
Swimming pools 20 - 30
Town Halls 4 - 10
Taverns 20 - 30
Theaters 8 - 15
Transformer rooms 10 - 30
Warehouses 2
Air Change Rate
Building / Room -n-
(1/h)
Warehouses 6 - 30
Fresh air supply - make up air - to a room based on the table above can be calculated as
q=nV (1)
where
= 4000 m3/h
1000
Room Volume (m3, ft3)
calculate!
nm = 60 / n (2)
where