Professional Documents
Culture Documents
Novel Protection Schema For A Radial Microgrid System
Novel Protection Schema For A Radial Microgrid System
Quito, Ecuador
Abstract—The improved use of renewable power The arrangement of DER near to a consumption point, to
generation and the coordinated connection with electrical electrical loads and to storage devices at low or medium
networks and loads bring a new concept, the microgrids. In voltage, operating as a small network, is referred to a
general, a microgrid can operate in both grid connected mode microgrid [2]. A structure of a microgrid is shown in Figure
and islanding mode. Ensuring the continuity of protection in 1. The advantages of a microgrid are: low transmission
both operation modes is a great technical challenge. Dealing losses, local power supply, reduced operation cost, and local
with different short circuit currents level depending on the reliability improvement. However, due to the fact that the
operation mode as well as ensuring selectivity and sensitivity distribution system is being transformed from a passive to an
are the issues of the proposed protection scheme. The present
active network, some technical challenges in terms of
work presents a microgrid protection scheme for a three bus-
bar radial microgrid which includes energy storage and a
control, management and protection have arisen [3].
static compensator (STATCOM). Protection strategy is based Microgrid protection is perhaps the most challenging
on the implementation of bi-directional overcurrent relays and task. The microgrid should be able to operate in a non-
includes over- and under-voltage and frequency relays as autonomous way, when interconnected to the grid, and in an
back-up protection. The main restriction is perhaps a autonomous way, when disconnected from the main grid [4].
limitation in normal working at 80% of the rated current of In the first scenario, the protection should act selectively,
the converter-based generator, leaving the 20% remaining to isolating a small portion of the microgrid until the fault is
overcurrent detection. In the other hand, an impedance
corrected. While in the second case, the protection system
measurement method is used to perform the islanding
protection. Results show that the protection scheme detect
must quickly isolate the microgrid from the main grid,
effectively the islanding condition and also isolate three-phase allowing operation as an islanding system, ensuring a
faults applied in each bus-bar. continuous supply [5]. In all cases, the electrical protections
must switch as fast as possible to prevent the transients.
Keywords— Microgrid protection, fault analysis, However, electrical protection design in an active
distributed generation distribution system is not as simple as a passive one.
Bidirectional currents can flow through the protection
I. INTRODUCTION elements during normal working, but in a fault, further
Since the early years of the use of electricity, several complexity arises once islanding occurs since the high short
forms of power generation have been developed to supply circuit current levels provided by utility grid are not supplied
the global demand. The dependence on fossil fuels and anymore [6].
further demand for energy, not only electrical, has been Although intentional islanding has some benefits, i.e.
linked to growing carbon dioxide emissions [1]. The impact ensuring continuity of supply when disturbances occur in the
on the environment has been widely debated and has main grid, unintentional islanding can cause many problems
motivated many countries to engage in the development of in terms of safety, grounding, power quality, voltage,
alternatives clean energy. In the case of power generation, frequency interference and frequency stability, thereby
for instance from fossil fuels or nuclear power, the wasted resulting in instantaneous reclosing [7], [8]. Therefore, the
by-products generated are not environmentally friendly. protection system should be able to protect the microgrid
Thus, the renewable generation has become more important against islanding by sensing the disconnection or absence of
in the recent years. Usually, the meaning of the term the main grid and ensure a safe reclosing [9].
“renewable energy sources” is related to solar photovoltaic
energy, the solar thermal energy, the wind energy, the fuel In order to guarantee continuous operation of the
cells and the hydraulic energy, which have a reduced adverse microgrid, a number of alternating solutions has been
impact on the environment. However, the use of renewable proposed to face the possible protection problems due to
generation implies the migration from traditional centralized external faults. One of them is the Adaptive Protection
generation to the implementation of distributed energy Scheme which is based on the dynamic modification of the
resources (DER). relays settings depending on the operation mode of the
microgrid that is grid connected or islanding. The principle
of differential current between two distant points has also
been used in Differential Protection Schemes but the main other hand, the reactive average compensator STATCOM
issue is perhaps the high dependence in the communication model (SH1) has been designed by means of an inner current
networks and the way to improve its reliability. Another loop and an outer PI voltage loop to control the reactive
scheme, like Voltage Based Protection, uses the Park power injected at BUS-3.
transform to change the three-phase voltages into the d-q
frame being the sensitivity to small voltage changes the
major difficulty to deal with. Finally, the ability of
communication in protection relays has also been considered
to propose a Communication-Assisted Protection Scheme in
which centralized, distributed and decentralized
communication networks are used but it considers some
technical features that are not available in modern protection
devices. [10]
As can be seen, some of the actual protection schemes
are communication dependant. The aim of this paper is to
present a strategy to protect a radial microgrid against short
circuit events in the grid connected mode and islanding mode
with a minimum communication needs. As a further Fig. 1. Microgrid scheme with protection relays.
protection against unsafe reclosing, islanding detection will
be included in the design. Finally, the proposed protection TABLE I. SYSTEM PARAMETERS
scheme will be evaluated using a model developed in System
Matlab®. System Quantities Values Values
Quantities
System Frequency 50 Hz Base Power 20 MVA
II. SYSTEM TOPOLOGY
Battery
In general, distribution systems are connected following Base Voltage 22 KV sourced
a radial structure. Loop close feeders could be present, but inverter DER2
normally are in open mode and only change to closed mode Base Impedance
24.2 Rated voltage 22 KV
(Xbase)
to give an alternative path to avoid a faulty section.
Therefore, a radial microgrid shown in Figure 1 is preserved Transformer T1 Rated Power 5 MVA
and used as case of study for the present work. Short circuit
Primary Voltage 110 KV (L-L) Xbase
impedance Xsc
A. System description Secondary Voltage 22 KV (L-L) STATCOM
The considered microgrid is supplied from the main grid Rated Power 20 MVA Rated voltage 22 KV
of 110 KV by means of a feeder line of 2km and connected Rated short circuit
to a transformer (T1) to decrease the voltage into a 400 KW Rated Power 3 MVA
power ǻPkt
distribution level of 22 KV. A circuit breaker CB0 has been Rated short circuit Short circuit
16.20% Xbase
included to disconnect the main source and simulate voltage ǻVkt impedance Xsc
islanding. The microgrid is formed by three bus-bars (BUS Connection type ǻ-Y11g Load 1
1-3), in which are linked electrical loads (Load 1-3). A 0.1153+j0.00148
5MVA synchronous generator (DER1) is connected at BUS- Feeder impedance Rated Power 4 MVA
/Km
1. A 5MVA converter interfaced with battery source (DER2) Feeder 1 long 2 Km Power Factor 0.92
is connected at BUS-2 and a 5MVA static shunt compensator
STATCOM (SH1) is connected at BUS-3 to compensate the Feeder 2 long 2 Km Load 2
voltage dip and to improve the stability of the system. The Feeder 3 long 5 Km Rated Power 1.5 MVA
power of the DERs selected in the function of the entire
Synchronous
microgrid can operate alone, in case of islanding mode. Full generator DER1
Power Factor 0.95
parameters of the microgrid elements are given in Table I.
Rated voltage 22 KV Load 2
B. Model design in MatLab® Rated Power 5 MVA Rated Power 2 MVA
The model was performed with special emphasis on the Short circuit
0.2 Xbase Power Factor 0.85
short circuit contribution of each element of the microgrid, impedance Xsc
in case of faults. Acceptable active power, reactive power
and voltage levels in the microgrid bus-bars were also III. PROTECTION SCHEME
considered in the design model and to test and to validate the In general, a microgrid protection should operate
proposed solutions, different scenarios were considered. effectively in the grid connected mode, separating the faulty
The parameters of the main grid, distribution transformer section when an electrical fault exterior to the system occurs.
and constant impedance loads were set according to the However, the main criterion of the protection operation is
values stated in Table I. The DER1 is a 480V synchronous when the microgrid changes the operation to islanding mode.
generator connected to a transformer T2 (ǻ/Y-480V/22KV), The operation philosophy recommended by IEEE 1547 in
while the operation of the DER2 was emulated using an ideal case of islanding consists of: detect it in maximum 2s and
480V three phase source followed by a transformer T3 (ǻ/Y- then separate the microgrid from the main grid and shutting
480V/22KV). In both, DER1 and DER2, the resistance and down their DERs, when a fault is detected inside of it.
reactance values were carefully set to match the appropriate However, a microgrid would be improved if it can operate in
short circuit current contribution on one hand, and on the both operation modes: in faults mode and islanding mode.
2017 IEEE PES Innovative Smart Grid Technologies Conference - Latin America (ISGT Latin America). Quito, Ecuador
A. Islanding protection time taken to act main protection), the islanding protection
Islanding protection scheme is required inter alia to avoid system acts, being a back-up of the microgrid protection.
an out of phase connection. Once the loss of the mains
condition is detected, the Islanding Protection Relay (IPR)
should disconnect the microgrid from the mains by means of
CB1. Then, if the main grid is again present, the appropriate
microgrid control could synchronise with the grid and re-
close CB1 safely.
The loss of mains detection is performed by the
impedance measurement at a specific harmonic of voltage
and current transients [11].
Fig. 2. Impedance measurement circuit at POM for ݊ order harmonic. Fig. 4. Estimated impedance waveform at 750Hz with fault at BUS-1.
a storage supply and capable of supplying more power than the maximum load current (ܫ௫ǡǡௗ ሻand 0.9 times the
required by Load-2 and Load-3, the maximum current minimum fault current has been usedሺ݂ܫǡǡௗ ሻ. The
supplied in normal working is limited to 80% (0.20pu) of substantial variation of the current fault between the two
their rated value, thus allowing a margin of 0.05pu to detect operation modes suggests the use of a very inverse time
faults. Is important to emphasise that this limitation does not characteristic curve.
affect the normal operation of the DER-2, as this action will
only limit in the rare case when DERs feed the main grid for C. Voltage and frequency protection
the case of all microgrid loads being disconnected. The voltage and frequency protections (VFR) are located
independently in each bus-bar and in the DER, working both
TABLE II. CURRENT THROUGH CB1, CB2 AND CB3. together with the overcurrent protection. In fact, the voltage
Current Current and frequency protections act as back-up of the overcurrent
Circuit Parameter Parameter protection. The voltage and frequency protections are
Breaker (pu) (pu)
especially helpful to trip CB-DER2 and CB-SH1, as for both
ܫ௫ଵி 0.37 ܫ௫ଵோ 0.50
an overcurrent is not possible. In addition, the protection was
CB1
݂ܫଵி 3.86 ݂ܫଵோ 1.28 performed by using definite time characteristics, taking into
ܫ௫ଶி 0.17 ܫ௫ଶோ 0.20 account a safety margin of േͳͲΨ of the nominal voltage
CB2 ሺܸ ሻ, and േʹΨ of the nominal frequency (݂ ). The
݂ܫଶி 1.29 ݂ܫଶோ 0.25 protection time was graded to avoid the disconnection of two
ܫ௫ଷி 0.1 ܫ௫ଷோ N/A adjacent circuit breakers. It’s important to emphasise that to
CB3 avoid mis-operation of overcurrent relays, the voltage or
݂ܫଷி 0.25 ݂ܫଶோ 0.15
frequency protection cannot work before the microgrid
overcurrent protection. Therefore, the protection time would
start after the maximum operation time of OCRs (i.e. 1s).
The required protection relay needs to operate two
Following these guidelines, a grading time of 0.3s starting
different settings; both depend on the fault direction.
from the 1rst was used. The operation curves for voltage and
Therefore, the most suitable protection device is a numerical
frequency protections are shown in Figure 5.
relay. It is important to mention that under the scheme of the
Figure 1, between relays, is not necessary to use
communication.
In accordance with IEC60255, the normalised operation
of the IDMT relays follows (2):
ܥ (2)
ݐൌ ή ܶܵܯ
ܫఈ
ቀ ቁ െͳ
ܫ௦
After that, a three-phase fault is applied to each bus-bar at The importance of back-up relays is evidenced when the
the instant ݐൌ ͲǤͷ ݏto observe their respective response. fault is applied in BUS-2. As shown in Figure 11, OCR3
does not work due to the fault current provided by SH1
becomes extinguishing and decreasing below their pick-up
value. This time, VFR3 acts at last instance. Then the
persistent low voltage present in BUS-2 causes that DER2
stops supplying fault current at ݐൌ ʹ ݏwhen CB-DER2 is
opened by the signal of VFR-DER2.