E5CSZ
Note: Modules are available with a black case. Add the suffix “-B” to models with a black case.
Terminal Cover
Model
E53-COV10
Specifications
■ Ratings
Supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC/VDC, 50/60 Hz
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 5 VA 3 VA/2 W
Sensor input Multi-input (thermocouple/platinum resistance thermometer) type: K, J, L, Pt100
Control Relay output SPST-NO, 250 VAC, 3A (resistive load)
output
Voltage output (for driving the SSR) 12 VDC, 21 mA (with short-circuit protection circuit)
Control method ON/OFF or 2-PID (with auto-tuning)
Alarm output SPST-NO, 250 VAC, 1A (resistive load)
Setting method Digital setting using front panel keys
Indication method 3.5 digit, 7-segment digital display (character height: 13.5 mm) and deviation indicators
Other functions • Setting change prohibit (key protection)
• Input shift
• Temperature unit change (°C/°F)
• Direct/reverse operation
• Temperature range, Sensor switching (K/J/L, Pt100)
• Switching is performed between a thermocouple and platinum resistance thermometer for multi-input models.
• Control period switching
• 8-mode alarm output
• Sensor error detection
Ambient temperature −10 to 55°C (with no condensation or icing)
Ambient humidity 25% to 85%
Storage temperature −25 to 65°C (with no condensation or icing)
Hysteresis (for ON/OFF control) 0.1% FS for multi-input (thermocouple/platinum resistance thermometer) models
Proportional band (P) 1 to 999°C (automatic adjustment using auto-tuning/self-tuning)
Integral time (I) 1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning
Derivative time (D) 1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Alarm output range Absolute-value alarm: Same as the control range
Other: 0% to 100% FS
Alarm hysteresis: 0.2°C or °F (fixed)
Control period 2/20 s
Sampling period 500 ms
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
Vibration Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
resistance
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions
Shock resistance Malfunction 100 m/s2 min., 3 times each in 6 directions
Destruction 300 m/s2 min., 3 times each in 6 directions
Life expectancy Electrical 100,000 operations min. (relay output models)
Weight Approx. 120 g (Controller only)
Degree of protection Front panel: Equivalent to IP50; Rear case: IP20; Terminals: IP00
Memory protection EEPROM (non-volatile memory) (number of writes: 1,000,000)
EMC EMI Radiated: EN 55011 Group 1 Class A
EMI Conducted: EN 55011 Group 1 Class A
ESD Immunity: EN 61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Radiated Electromagnetic Field Immunity: EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)
10 V/m (900 MHz pulse modulated)
Conducted Disturbance Immunity: EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2)
Noise Immunity (First Transient Burst Noise): EN 61000-4-4
Burst Immunity: 2 kV power-line (level 3), 1 kV I/O signal-line (level 3)
Surge Immunity: EN 61000-4-5: Power line: Normal mode 1 kV; Common mode 2 kV
Output line (relay output): Normal mode 1 kV; Common mode 2 kV
Voltage Dip/Interrupting Immunity: EN 61000-4-11 0.5 cycle, 100% (rated voltage)
Approved standards UL 61010C-1 (listing)
CSA C22.2 No.1010-1
Conformed standards EN 61326, EN 61010-1, IEC 61010-1
VDE 0106 Part 100 (finger protection), when the terminal cover is mounted.
300
100
50
30
10
5
E5CSZ
3 250 VAC, 30 VDC
(resistive load)
cosφ = 1
1
0 1 2 3 4 5 6
Switching current (A)
2 3
(selected
2 3
700
4 5 6 using switch) 600
500 400
400
300 199.9 200
(Default setting: 0) 200 99
100
0
0.0 0 0
−100
−99 −99
Setting number 0 1 2 3 4 The shaded value indicates the default setting status.
Minimum setting unit 1°C 0.1°C 1°C Do not set the temperature range switch to between No. 5 and No. 9.
1 1 6
12 VDC,
21 mA
2 2 7
Alarm output 1 (See note 3.)
A
3 3 8
B
4 4 9 100 to 240 VAC, 50/60 Hz
(24 VAC/VDC)
B (See note 2.)
5 5 10
Thermocouple/
platinum resistance thermometer multi-input
Note: 1. The voltage output (12 VDC, 21 mA) is not electrically isolated from the internal circuits. When using a grounding thermocouple, do not
connect output terminals 1 or 2 to ground. Otherwise, unwanted current paths will cause measurement errors.
2. Models with 100 to 240 VAC and 24 VAC/VDC are separate. Models using 24 VDC have no polarity.
3. The number of alarm outputs (none or 1) depends on the model.
Nomenclature
E5CSZ Models with Terminal Blocks
Output indicator
Deviation indicators Temperature display
The indicator lights when the PV is greater than The display switches each time the
the SP and the indicator lights when the PV is Key is pressed.
less than the SP. The indicator (green) lights
when the deviation is less than 0.25% FS. These
indicators flash during ST (self-tuning)/AT (auto- Output indicator
tuning). Lights when the control output is ON.
Mode indicators
Mode Key
When the power is turned ON, normally the Up Key
display will use the display items in the following Pressing the Up Key increases the
order each time the Mode Key is pressed. SP/alarm value display. Keeping the Up
E5CSZ
Power ON Key pressed continues to increase the
display value. When the internal protect
switch is ON, press the Up Key while
PV
holding down the Lock Release Key.
Press the Key.
SP
Press the Key. Down Key
Alarm value 1
Lock Release Key Pressing the Down Key decreases the
Press the Key.
This item is not displayed when
SP/alarm value display. Keeping the Down
Input shift value
the Control Mode Switch 4 is OFF. When the protect switch is ON, the set Key pressed continues to decrease the
Press the Key. value can be changed by pressing the Up display value. When the internal protect
and Down Keys while holding down the switch is ON, press the Down Key while
Lock Release Key. holding down the Lock Release Key.
20 min.
(3) P X 1 2 3 4 5 6
INIT switch
0.4 2.0 (See note 2.)
(2)
(1) Protect switch
2. Insert the tool in the gap between the front panel and rear case,
and pull out the front panel slightly. Grip the front panel and pull
out fully. Be sure not to impose excessive force on the panel.
Note: 1. The alarm mode switch is not provided on models without an alarm.
2. The INIT switch is always OFF during normal operation.
7 8
Use the control mode switches ( ) to change the
2 3
4 5 6
1 2 3 4 5 6
control mode. (All switches are OFF for the default settings.) the alarm mode. (The default is 2).
Upper-limit
alarm Upper-limit
alarm
SP
SP
Lower-limit
alarm Lower-limit
Alarm ON alarm
output OFF Alarm ON
output OFF
Note: Turn OFF the power before changing the DIP switch settings on the E5CSZ. Each of the switch settings will be enabled after the power is
turned ON.
For details on the position of the temperature range switch, control mode switches, and alarm mode switch, refer to page 6.
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
Switch 1 OFF: ON/OFF control
Control output ON
Control output ON
OFF
OFF SP
SP
PID Control
Turn ON switch 1 to use PID control.
ON
1 2 3 4 5 6
Switch 1 ON: PID control
1. Set the control period. 2. Set direct/reverse operation for the output.
Performing Control via Relay Output, External Relay, or Performing Heating Control for Heaters
Conductor Switch 3: OFF
Switch 2: OFF (control period: 20 s)
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
Output level
1 2 3 4 5 6 1 2 3 4 5 6
Output level
Control output ON
OFF 100%
2s 0%
SP
U D
Press for
AT execution in progress at least 2 s.
ON
1 2 3 4 5 6
Note: The control range for multi-input (thermocouple/platinum resistance thermometer) models is −40 to +40°F of each temperature range.
5. Protect Switch
ON
Protect Switch
P X 1 2 3 4 5 6
When the protect switch is ON, Up Key and Down Key operations are prohibited to prevent setting mistakes.
Adapter
Tightening screw
Tightening screw
Panel
Note: The resistance value for platinum resistance thermometers is 100 Ω at 0°C and 140 Ω at 100°C.
E5CST-@@@ E5CSZ-@@@@-@
1 2 3 1 2 3 4 5
■ Display
Previous model E5CSZ
SP AL AL
■ Functions
The control outputs for relay outputs have been changed from SPDT (single-pole, double-throw) to SPST-NO (single-pole, single-throw, normally
open) contacts.
The control method has been changed to 2-PID control.
An auto-tuning (AT) function has been added.
The deviation display flashes during self-tuning (ST) and auto-tuning (AT).
The control calculation period has been improved from 2 s to 0.5 s.
■ External Dimensions
The depth has been shortened from 100 mm to 76 mm.
B
4 4 9
100 to 240 VAC,
1 2 3 4 5 50/60 Hz
B (24 VAC/VDC)
Thermocouple ALARM 5 5 10
input 250 VAC, 1 A
(Resistive load)
B Platinum resistance Thermocouple
A B thermometer input input
Platinum resistance
thermometer input
Multi-input (thermocouple/platinum resistance thermometer)
ON ON
1 2 3 4 5 6 1 2 3 4 5 6
7 8
2 3
4 5 6
Function Selection 4
Alarm Lower-limit Set Alarm type Alarm output operation
X
Modes ON ON value
OFF
SP 0, 9 Alarm function OFF OFF
Upper-limit Upper- and lower- X X
X ON
ON OFF 1 limit OFF
OFF SP
SP
Upper-limit ON
X
2
OFF
SP
Lower-limit ON
X
3
OFF
SP
Lower-limit with X
ON
7 standby sequence
OFF
(See note 2.) SP
Absolute-value ON
Y
8 upper-limit OFF
0
9 0 1
Temperature Range Switch
7 8
2 3
4 5 6
Function selection 5 6
Temperature KJ J: 0 to 300°C ON ON Set Temperature Range
Range value
K: 0 to 999°C OFF ON
K: 0 to 500°C 0 Control Mode K: 0 to 1,300°C/−99 to 1,999°F
ON OFF
Switch 5: OFF
1 K: 0.0 to 199.9°C/0.0 to 199.9°F
K: 0 to 300°C OFF OFF
2 J: −99 to 850°C/−99 to 1,500°F
P --- ON ON
3 J: 0.0 to 199.9°C/0.0 to 199.9°F
Pt100: 0 to 300°C OFF ON
4 L: −99 to 850°C/−99 to 1,500°F
Pt100: 0.0 to 99.0°C ON OFF
0 Control Mode Pt100: −99 to 850°C/−99 to 1,500°F
Pt100: 0.0 to 50.0°C OFF OFF
Switch 5: ON
1 Pt100: 0.0 to 199.9°C/0.0 to 199.9°F
2 Pt100: −99 to 99°C/−99 to 99°F
3 Pt100: 0 to 200°C/0 to 200°F
4 Pt100: 0 to 400°C/0 to 400°F
■ Controller
E5CSZ Panel Cutout Dimensions
84
48 × 48 6 78 45+0.6
0
L
45+0.6
0 45+0.6
0
44.8×44.8
60 min. L = (48 × N−2.5)+10
z Mounting side-by-side
E5CSZ (group mounting of N Controllers)
58
E5CSZ
z Tightening
48 screws
7.5 76.5
°C
22
92A -4
-488B
z
B
9.1
Never disassemble, modify, or repair the product or touch 1. The product is designed for indoor use only. Do not use the
any of the internal parts. Minor electric shock, fire, or product outdoors or in any of the following locations.
malfunction may occasionally occur. • Places directly subject to heat radiated from heating equipment.
CAUTION - Risk of Fire and Electric Shock • Places subject to splashing liquid or oil atmosphere.
a) This product is UL listed as Open Type Process • Places subject to direct sunlight.
Control Equipment. It must be mounted in an • Places subject to dust or corrosive gas (in particular, sulfide gas
enclosure that does not allow fire to escape externally. and ammonia gas).
b) More than one disconnect switch may be required to
de-energize the equipment before servicing the • Places subject to intense temperature change.
product. • Places subject to icing and condensation.
c) Signal inputs are SELV, limited energy. (See note 1.) • Places subject to vibration and large shocks.
d) Caution: To reduce the risk of fire or electric shock, do
2. Use and store the product within the rated temperature and
not interconnect the outputs of different Class
humidity ranges.
2 circuits. (See note 2.)
Group-mounting two or more Temperature Controllers, or
If the output relays are used past their life expectancy, mounting Temperature Controllers above each other may cause
contact fusing or burning may occasionally occur. Always heat to build up inside the Temperature Controllers, which will
consider the application conditions and use the output shorten their service life. In such a case, use forced cooling by
relays within their rated load and electrical life fans or other means of air ventilation to cool down the
expectancy. The life expectancy of output relays varies Temperature Controllers.
considerably with the output load and switching 3. To allow heat to escape, do not block the area around the product.
conditions. Do not block the ventilation holes on the product.
Loose screws may occasionally result in fire. 4. Use the specified size (M3.5, width of 7.2 mm or less) crimped
Tighten terminal screws to the specified torque of 0.74 to terminals for wiring. To connect bare wires to the terminal block,
0.90 N·m. use copper braided or solid wires with a gage of AWG24 to
AWG18 (equal to a cross-sectional area of 0.205 to 0.832 mm2).
Unexpected operation may result in equipment damage
(The stripping length is 5 to 6 mm.) Up to two wires of the same
or accidents if the settings are not appropriate for the
size and type, or two crimp terminals can be inserted into a single
controlled system. Set the Temperature Controller as
terminal.
follows:
5. Be sure to wire properly with correct polarity of terminals. Do not
• Set the parameters of the Temperature Controller so
wire any of the I/O terminals incorrectly.
that they are appropriate for the controlled system.
6. Do not wire the terminals that are not used.
• Turn the power supply to the Temperature Controller
OFF before changing any switch setting. Switch settings 7. The voltage output (control output) is not electrically isolated from
are read only when the power supply is turned ON. the internal circuits. When using a grounded temperature sensor,
do not connect any of the control output terminals to ground.
• Make sure that the INIT switch in the control mode
Otherwise unwanted current paths will cause measurement
switches is turned OFF before operating the
errors.
Temperature Controller.
8. To avoid inductive noise, keep the wiring for the Temperature
A malfunction in the Temperature Controller may Controller's terminal block away from power cables carrying high
occasionally make control operations impossible or voltages or large currents. Also, do not wire power lines together
prevent alarm outputs, resulting in property damage. with or parallel to Temperature Controller wiring. Using shielded
To maintain safety in the event of malfunction of the cables and using separate conduits or ducts is recommended.
Temperature Controller, take appropriate safety Attach a surge suppressor or noise filter to peripheral devices that
measures, such as installing a monitoring device on a generate noise (in particular, motors, transformers, solenoids,
separate line. magnetic coils or other equipment that have an inductance
Faulty terminal contact or decreased waterproofing component).
capability may result in a fire or equipment malfunction. When a noise filter is used at the power supply, first check the
When inserting the Temperature Controller into the rear voltage or current, and attach the noise filter as close as possible
case after setting the switches, check the watertight to the temperature controller.
packing and make sure that the top and bottom hooks are Allow as much space as possible between the Temperature
locked securely in place. Controller and devices that generate powerful high frequencies
(high-frequency welders, high-frequency sewing machines, etc.)
or surge.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS,
OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED,
INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE
MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of
products in the customer's application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will
be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON
PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR
SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a
warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application
requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with
your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
Cat. No. H141-E1-01 In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company