Professional Documents
Culture Documents
Figure 49: AC Method For Testing Transformer Polarities: POL H X 1 2 POL H X 1 2
Figure 49: AC Method For Testing Transformer Polarities: POL H X 1 2 POL H X 1 2
For the voltmeter, when VPOL = VH - VX the transformer functions with subtractive
polarity and terminals A and B would be labeled “X1 to X2,” respectively. Conversely,
when VPOL = VH + VX the transformer has additive polarity and terminals B and A would
be labeled “X1 to X2,” respectively as polarity terminals are diagonally opposite each
other.
The AC Polarity test method can be conveniently made during the Transformer Ratio
test. The methodology used to check ratio include the Voltage method and the
Transformer Turns Ratio (TTR) test set. The test is used to check nameplate voltage
values for the range of taps on the transformer.
The circuit for making ratio and polarity tests of a two-winding transformer is shown in
Fig. 50.
Figure 50: Ratio and Polarity Voltmeter Method For Two-Winding Transformers
Test evaluations are aided by pre-calculating the expected test voltages and filling out the
data sheets ahead of time.
Because induced voltage from nearby current-carrying bus or lines could modify
measurements, make low-resistance connections directly to transformer bushing
terminals and don’t coil up excess potential lead length; lay excessive leads side by side,
oriented at 90° with induction sources.
The lower voltage winding should be excited, in most cases, to some multiple of its
rating. For example, if the transformer in Fig. 50 is rated 115.5 kV to 7.2 kV, energize the
low-voltage winding to 7.2 V, then measure voltage on the high-voltage winding. The
high side should be 1/1000 of its rating, or 115.5 V. The voltmeter, VPOL, will read the
difference -- 108.3 V -- for subtractive transformers.
If the high side has a tap changer, hold the 7.2 V constant on the low-voltage winding and
read the new high-side voltage for each tap position. These voltages may be compared
directly with the nameplate values.
WARNING!
Remember, if transformer terminals are accessible or if bussing is connected to the
transformer terminals, all safety procedures of this transformer section as well as
Section 2 must be followed.
1. High to Low: Excite the low-voltage winding, Y1 to Y2 = EL. When the low-
voltage windings have additional taps (Y1, Y2, Y3, Y4), measure all taps on low-
voltage winding. (Example: Y1, to Y2, Y1to Y3, Y1to Y4). Measure high-side (H1to
H0) voltage throughout its tap-changer range, EH. Ratio = EH/EL.
2. Medium to Low: Excite low voltage winding, Y1to Y2 = EL. Measure medium
voltage, XH to X2/X0, throughout its tap-changer range, EM. Ratio = EM/EL
The Transformer Turns Ratio (TTR) method compares the test transformer ratio with an
adjustable-ratio standard transformer by using a null balance detector to determine when
the standard transformer ratio is the same as the test transformer. During test procedures
transformer polarity is determined by comparison with the standard transformer (See Fig.
52, below).
Figure 52: TTR Method for Testing the Transformer Turns Ratio