Professional Documents
Culture Documents
Analysis of Split Inductor Neutral Point Clamped Multilevel Inverter
Analysis of Split Inductor Neutral Point Clamped Multilevel Inverter
Analysis of Split Inductor Neutral Point Clamped Multilevel Inverter
Abstract -The emerging trends in the application inductor neutral point clamped multilevel inverter avoids the
ofrenewable energy source increase day by day, due to the usage of transformer for connecting the inverter with grid
generation of energy without polluting the environment is system .Topologies without a transformer generally have
essential .The applications of Multilevel Inverter (MLI) lower cost, size, and weight than topologies with transformers.
with high power medium voltage system is feasible because The main disadvantage is the connection of the PV array to
of their improved performance than two-level inverters. the grid without galvanic isolation, which raises the leakage
Among various type of multi-level inverters, neutral point current through the parasitic capacitance of the PV array. Due
clamped multi-level (NPC-MLI) is suitable for a to this capacitance and depending on the inverter topology and
transfomerless photovoltaic (PV) grid connected system. the switching strategy, fluctuations of the potential between
The main advantage of using transfomerless Split the PV array and the ground can appear. These fluctuations
Inductor MLI (SI-MLI) is to eliminate the leakage current inject a capacitive leakage current, and this current can cause
and shoot through possibility and they maintain the grid current distortion, losses in the system, and safety
common mode voltage constant. The proposed SI-NPC- problems and furthermore, the in-grid current harmonics and
MLI-HCC topology guarantees for no shoot- through losses are increased .
possibility and also maintains low voltage total harmonic In transformerless PV systems that use the connection
distortion (THD) and current total harmonic distortion between the neutral of the grid and the central point of the dc
(THD). This report presents the analysis of the proposed link, the leakage currents have low values because the
technique with the conventional technique. potential between the PV array and the ground is constant.
Transformerless SI-NPC-MLI for grid connected PV system
for single phase was proposed .There is large voltage stress on
Keywords –Grid Connected system ,Hysteresis current loop the power devices. In order to solve the aforesaid problems,
(HCC),Neutral point Clamped multilevel inverter (NPC- the multilevel leg structure was introduced. For controlling the
MLI), Transformerless Split inductor inverter, hysteresis current control applied.
Hysteresis current control (HCC) strategy for three-phase
I.INTRODUCTION neutral-point (NP)-clamped inverters was disused. And
parameters for choosing the fixed bandwidth values are grid
Photovoltaic (PV) power generation is a reliable and voltage, PV voltage, switching frequency and inductances.
economical source of electricity in rural areas and plays an Based on the single phase SI-NPC-MLI structure, approached
significant role in the development of distributed electric for three phase SI-NPCTLI system using PI controller for
power systems. Solar energy can be exploited in two major tuning the reference currents. Achieved the leakage current,
ways. Firstly, the captured heat can be used as solar thermal low voltage stress on the power device using Transformerless
energy, with applications in space heating. Another alternative grid-connected inverter with high reliability and avoid shoot
is the conversion of incident solar radiation to electrical through problems as well. Simulation results of this proposed
energy, which is the most usable form of energy. This can be system analyzed using MATLAB SIMULINK
achieved with the help of solar photovoltaic cells [1] or with
concentrating solar power plants. The grid-connected PV
system does not require a battery because the grid can store
the power generated by the PV array. Transformerless split
Fig 2. I-V characteristics of a solar panel
II.PV ARRAY AND MPPTALGORITHM
A PV array consists of several photovoltaic cells in series A. Perturb & Observe Algorithm
and parallel connections. Series connections are responsible
for increasing the voltage of the module whereas the parallel Perturb & Observe (P&O) is the simplest method. In
connection is responsible for increasing the current in the this we use only one sensor, that is the voltage sensor, to sense
array. Typically a solar cell can be modeled by a current the PV array voltage and so the cost of implementation is less
source and an inverted diode connected in parallel to it. It has and hence easy to implement. The time complexity of this
its own series and parallel resistance. Series resistance is due algorithm is very less but on reaching very close to the MPP it
to hindrance in the path of flow of electrons from n to p doesn’t stop at the MPP and keeps on perturbing on both the
junction and parallel resistance is due to the leakage current. directions. When this happens the algorithm has reached very
close to the MPP and we can set an appropriate error limit or
can use a wait function which ends up increasing the time
complexity of the algorithm.
The Perturb & Observe algorithm states that when the
operating voltage of the PV panel is perturbed by a small
increment, if the resultant change in power ΔP is positive
(ΔP>0), then it change to shift in the direction of MPP and it
keep on perturbing in the same direction. If ΔP is negative
(ΔP<0), it leaves away from the direction of MPP and the sign
of perturbation supplied has to be changed. The flowchart for
Fig 1. Single diode model of a PV cell P&O algorithm is shown in Fig 3.
In this model we consider a current source (I) along In [4] a situation where the irradiance changes rapidly, the
with a diode and series resistance (Rs). The shunt resistance MPP also moves on the right hand side of the curve. The
(RSH) in parallel is very high, has a negligible effect and can algorithm takes it as a change due to perturbation and in the
be neglected. next iteration it changes the direction of perturbation and
The output current from the photovoltaic array is hence goes away from the MPP.
I = Isc – Id (1)
(2)
(4)
In order to ensure the correct multilevel operation, Grid Voltage (Vg) 200 V
the control system has to fulfill two tasks. It must generate the
correct voltage vector and hence, the correct multilevel Grid Frequency (f) 50 HZ
waveform. At the same time, it must maintain the same
voltage across the two capacitors for reducing the capacitor SI – NPC (L) 4 MH
balancing problem and evade of shoot through problems.
DC Bus Capacitance (C) 100 micro farad
A.Analysis of the hysteresis band (h)
Inverter Switching Frequency (f) 10KHZ
The hysteresis current control can achieve accurate Temperature (T) 40 degree
tracking to the inductor current. In order to ensure the zero
inductor current before the zero crossing of the grid voltage,
the high frequency switching signals must be stopped at the
time xπ, and the inductor current may be forced to zero by the B. Model of SI-NPC-MLI for Grid Connected System
grid voltage. Hysteresis current control, which is a nonlinear
control method, possesses high performance,
simplerealization circuit, high stability, inherent current-
limiting capability, and fast dynamic response hysteresis band
real-time regulation and the hysteresis band.(h)
Fig 10. Simulink model of SI-NPC- Fig 13. Output voltage waveform
MLI E.Output Waveform for Various Parameters Grid Voltage Waveform
PV Array Voltage