Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO.

2, MAY 2013 2035

Adaptive Load Shedding Based on Combined


Frequency and Voltage Stability Assessment Using
Synchrophasor Measurements
Junjie Tang, Graduate Student Member, IEEE, Junqi Liu, Graduate Student Member, IEEE,
Ferdinanda Ponci, Senior Member, IEEE, and Antonello Monti, Senior Member, IEEE

Abstract—Under frequency load shedding (UFLS) and under However, the traditional load shedding schemes are not ca-
voltage load shedding (UVLS) are attracting more attention, as pable of dealing with combined instabilities, as discussed in
large disturbances occur more frequently than in the past. Usually, [2] and [3]. Since the action of UFLS usually only considers
these two schemes work independently from each other, and are
not designed in an integrated way to exploit their combined effect the frequency information, it may have unanticipated, adverse
on load shedding. Besides, reactive power is seldom considered consequences on the voltage. A similar issue affects the con-
in the load shedding process. To fill this gap, we propose in this ventional UVLS which uses only local voltage magnitude
paper a new centralized, adaptive load shedding algorithm, which information at the individual buses. Another disadvantage of
uses both voltage and frequency information provided by phasor the conventional methods is that they simply follow a preset
measurement units (PMUs). The main contribution of the new
method is the consideration of reactive power together with active rule, such as shedding a fixed percentage of loads when fre-
power in the load shedding strategy. Therefore, this method ad- quency is out of the normal range. This type of rule lacks the
dresses the combined voltage and frequency stability issues better flexibility to execute load shedding actions fit for the different
than the independent approaches. The new method is tested on the type of instabilities.
IEEE 39-Bus system, in order to compare it with other methods. Research work about adaptive UFLS was introduced in
Simulation results show that, after large disturbance, this method
can bring the system back to a new stable steady state that is [4]–[7] in order to improve the conventional load shedding
better from the point of view of frequency and voltage stability, schemes. However, in these approaches, still only the fre-
and loadability. quency information is used in the load shedding process. An
Index Terms—Adaptive load shedding scheme, phasor measure- improvement has been proposed in [8] and [9], where voltage
ment units (PMUs), power system stability, synchrophasor, under dependent load modeling has been taken into account for the
frequency load shedding, under voltage load shedding. active power imbalance estimation. Also in this case, though,
the voltage information is not exploited for the load shedding
strategy. Furthermore, some researchers [10]–[13] have pro-
I. INTRODUCTION posed combinational load shedding methods based on adaptive

M OSTLY as a consequence of the deregulated electricity UFLS, in which the distribution of load shedding is determined
markets and the growth of electrical energy consump- using the voltage magnitude information. All these combina-
tion, power systems are now often operated close to their sta- tional load shedding methods go in the direction of addressing
bility limits. In case of large disturbances, such as generators the voltage stability issue in adaptive UFLS. However, the
tripping and faults on transmission lines leading to cascading existing methods for combinational load shedding still exclude
faults [1], the resulting active and reactive power imbalance can controlled reactive power from the direct participation in load
eventually lead to simultaneous large frequency and voltage de- shedding. Instead, we believe that the contribution of resources
viation, as well as instability. Thus, there is a higher risk that the and equipment capable of reactive power support and control
overall system may collapse. is essential for the voltage stability [14], [15].
Conventionally, load shedding schemes—under frequency With the diffusion of wide-area monitoring and control sys-
load shedding (UFLS) and under voltage load shedding tems (WAMCS) [16]–[19] based on phasor measurement units
(UVLS), are designed independently and they constitute the (PMUs), the power system stability issues can be addressed
last line of defense against frequency and voltage instability. more effectively. PMUs can provide synchronized measure-
ments, which include the magnitude and phase angle of voltages
and currents, frequency and rate of change of frequency [20].
Manuscript received May 01, 2012; revised May 18, 2012, September 20,
2012, and January 11, 2013; accepted January 14, 2013. Date of publication These measured data may support the tracking of dynamic phe-
March 07, 2013; date of current version April 18, 2013. Paper no. TPWRS- nomena and provide sufficient information for both frequency
00452-2012.
and voltage stability assessment. Moreover, the phase angle
The authors are with the Institute for Automation of Complex Power
Systems, E.ON Energy Research Center, RWTH Aachen University, Aachen, measurements provided by PMUs are proven in principle to
Germany (e-mail: jtang@eonerc.rwth-aachen.de; jliu@eonerc.rwth-aachen.de; facilitate more accurate and early voltage instability detection
fponci@eonerc.rwth-aachen.de; amonti@eonerc.rwth-aachen.de).
[21]–[24]. Nevertheless, they have not been exploited yet in
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. existing load shedding methods. In this paper, synchrophasor
Digital Object Identifier 10.1109/TPWRS.2013.2241794 measurements are used to enable more advanced, adaptive load

0885-8950/$31.00 © 2013 IEEE


2036 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 2, MAY 2013

shedding on the basis of both frequency and voltage stability The structure of this paper is organized as follows: the role
indices. of synchrophasors in implementing the proposed adaptive
In the conventional methods for distribution of load shedding, load shedding scheme, and the corresponding algorithms for
the initial load of each load bus is considered as a starting point obtaining the information required in load shedding are de-
for allocation. Hence, all the load buses are involved in sharing scribed in Section II. The conventional adaptive load shedding
the total power imbalance without selection. This is unpractical, is presented in Section III, while Section IV introduces the
especially for complex power systems with a large number of load shedding method newly proposed, in particular the load
load buses. Moreover, according to the knowledge of the au- shedding distribution determination; test system and platform
thors, power flow tracing is a reasonable choice for the selec- for the assessment of the proposed method are introduced
tion of a subset of all load buses in the load shedding distribu- in Section V, and Section VI presents experimental results
tion for general use. In [25] and [26], power flow tracing is pro- based on real time simulation and provides explanations and
comments. Section VII summarizes the conclusions.
posed in a load shedding scheme for the faults originating from
lines tripping, and they are proven to work effectively. In this II. SYNCHROPHASOR FOR LOAD SHEDDING
work, we consider the case of generators tripping. By means of
the power flow tracing, we can accurately determine the corre- A. PMUs, Synchrophasor and WAMCS
sponding proportional power of each load bus that is supplied PMUs, instruments providing so-called synchronized phasor
by the lost generators or lines. Usually, the buses in the vicinity or synchrophasor measurements have been widely deployed in
of tripping elements are the most sensitive to such kind of faults. power systems in the last decade [27], mostly in high voltage
This fact leads to load bus selection, and eventually to a reduc- transmission networks [18].
tion of the load busses involved in load shedding. In the standard [28], the synchrophasor is defined as a
In this paper, we propose a new adaptive load shedding complex number representation of either a voltage or a current,
method that considers frequency and voltage stability assess- at the fundamental frequency, using a standard time reference.
ment simultaneously. Such adaptive method is organized in The synchrophasor representation of a sinusoidal signal
three main steps: is the complex value given by
1) determination of a trigger for activating the load shedding
procedure; (1)
2) estimation of total power imbalance for the whole system;
3) distribution of the total power imbalance to individual load where is the root-mean-square (rms) value of the signal
bus. , and is its instantaneous phase angle that is referred to a
The proposed adaptive load shedding method should be ap- common reference time (UTC, Universal Coordinated Time).
plied using both frequency and voltage information at each step, Both values can be measured directly by PMUs [17].
especially in the third step which yields the final load shedding WAMCS is a central platform that may use synchrophasor
action to be implemented. First, a global voltage stability index measurements gathered from a wide area for the purpose
and the frequency information for the equivalent inertial center of centralized monitoring and control, such as for assessing
are utilized jointly for the trigger determination. In the second and maintaining stability [16]–[19]. The time-stamped syn-
step, we apply a low-order system frequency response (SFR) chrophasor data are calculated by the PMUs at high rate and
model [4] combined with the voltage dependent load models [9], with high accuracy [20]. Hence they are very effective for
to obtain the overall active power mismatch and hence the total tracking the dynamic evolution in the power system operation,
amount of reactive power to be shed. Finally, we use both the especially in critical conditions, such as the occurrence of
frequency and voltage information in the third step, for simulta- oscillations and large disturbances [19]. Large disturbances
neous active and reactive load shedding distribution. In the ac- are caused mainly by lines or generators tripping, whose
tive load shedding distribution process, the frequency measure- connection/disconnection status monitoring can be supported
by PMUs as in [10]. Therefore, synchrophasor measurements
ments are used together with the active power estimates pro-
facilitate global awareness of the system. This is beneficial for
vided by tracing power flow. While for the reactive power load
the stability assessment and load shedding.
shedding distribution, it requires the voltage information com-
bined with reactive power estimates obtained also from tracing B. Role of Synchrophasor Measurements in the Proposed
power flow. In this way, the appropriate amount of active and Load Shedding Scheme
reactive power to be shed at the selected buses can be deter- Synchrophasor measurements have enabled new appli-
mined simultaneously. Furthermore, the conventional methods cations, including combinational load shedding using both
have been augmented with reactive power, global voltage sta- frequency and voltage information [19]. While in traditional
bility analysis and load bus selection for load shedding. Thus, supervisory control and data acquisition (SCADA) systems,
the new approach can enhance the recovered steady state with generally only the non-synchronized magnitude measurements
respect to frequency stability, voltage stability and loadability, of the signals are received directly from Remote Terminal
while also ensuring a good transient behavior, for the same total Unit (RTU), which are designed for lower rate and accuracy.
active power curtailment, compared to the existing load shed- Furthermore, the phase angle has to be estimated via power
ding methods. flow calculation, which is a time consuming process. Instead,
TANG et al.: ADAPTIVE LOAD SHEDDING BASED ON COMBINED FREQUENCY AND VOLTAGE STABILITY ASSESSMENT 2037

TABLE I where
PHASOR MEASUREMENTS FOR DIFFERENT • : right eigenvector matrix of ;
ISSUES AND STEPS OF LOAD SHEDDING
• : left eigenvector matrix of ;
• : diagonal eigenvalue matrix of ;
• : th column of ;
• : th row of ;
• : th eigenvalue of and the corresponding mode.
The corresponding th modal voltage variation is

(7)

If , the th modal voltage collapses. Correspondingly,


the minimum eigenvalue stands for the mode that is the
most prone to collapse, and thus it can be used as an indicator
for the voltage stability of the whole system [29].
Moreover, V-Q sensitivity at bus can be computed [29] by
using the phase angles available directly as PMU measure-
ments, the monitoring in power systems can be significantly
improved [20], especially for centralized applications such as (8)
power flow analysis and systematic voltage stability assess-
ment. In summary, the WAMCS system and PMUs provide the
environment for implementing UVLS and UFLS together in where is the th element of , while is the th ele-
the same platform, thus facilitating the realization of adaptive ment of .
combinational load shedding. A positive value of indicates that the relationship be-
In the proposed load shedding scheme, the phasor measure- tween the change of voltage and the change of reactive power
ments are used in each step of load shedding procedure, as is stable at bus , and the voltage is more sensitive to reactive
shown in Table I. power variation as increases. A negative value of
represents an unstable operating condition [29].
C. Voltage Stability Assessment Based on Modal Analysis The indices for voltage stability assessment based on modal
Modal analysis based on the Jacobian matrix in (2) is an ef- analysis are used in this paper as follows:
ficient analytical method for global voltage stability assessment 1) is applied in the load shedding trigger determination
[29]–[31]: from a global perspective; also an evaluation index for dif-
ferent methods comparison in the recovered steady state
(2) after load shedding;
2) is applied in the reactive power load shedding dis-
It is assumed in this paper that the Jacobian matrix is calcu- tribution.
lated by directly using the measured magnitude and phase angle
values of the voltage from PMUs. D. Power Flow Tracing Method for Load Shedding
In order to extract the relationship between reactive power Distribution
and voltage magnitude, is a usual assumption to obtain Originally, power flow tracing is a method to determine the
the following simplified relationship as [29], [30]: proportional usage of lines and generators by the power con-
sumers, and then the results will act as the reference for charging
in the electricity market. As a mature technology, now power
(3) flow tracing has been widely applied in the study of the power
system analysis, including load shedding. This method is based
So, the relationship can also be expressed as
on power flow results which can also be calculated using voltage
(4) magnitude and phase angle measurements supplied directly by
PMUs. The so-called proportional sharing principle, as men-
In practice, instead of calculating the directly, a decom- tioned in [32] and [33], is the core of the power flow tracing
position method is usually applied, according to (5): method, which lays foundation for the power allocations. Basic
power flow tracing algorithms are generally classified as up-
(5) stream-looking algorithm and downstream-looking algorithm
So (4) can be transformed to [32], both with the same computational burden. The only dif-
ference lies in the way to apportion the line loss to the side of
loads or generators. The downstream-looking algorithm is ap-
plied in this paper to trace the power of each load bus received
(6) from each line and generator, and its main process is described
as follows [33].
2038 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 2, MAY 2013

According to the principle that the inflow equals the outflow [5], [10], [34]. A local method to activate the trigger by consid-
at any bus, the outflow of bus can be defined as ering both voltage and frequency jointly at each bus has been
proposed in [2] and [3]. The details of each trigger used in this
(9) paper are introduced in Section IV-A.

B. Power Imbalance Estimation


where is the set of buses supplied directly by bus , which is
defined as downstream buses of bus ; is the active power As an important feature of adaptive load shedding method,
flow from bus to bus , is the total active power load at the total power imbalance should be estimated adaptively ac-
bus , and is the active power loss of line connecting cording to different disturbances [5]. The estimation method is
bus and bus . based on a low-order system frequency response (SFR) model
A downstream distribution matrix is defined with corre- [4] which is applied to estimate the active power deficit of the
sponding entries according to th generator as shown in (14). The initial rate of change of fre-
quency required in the calculation of (14) can be obtained from
PMUs. These data are expected to be sent to control center, so
(10)
that the active power imbalance of the th generator can
be estimated as soon as the disturbance occurs by
The active power contribution made by the generator at the
th bus to active power load of the th bus is denoted as , (14)
which can be determined as
where
(11)
• : inertia constant of the th generator;
• : rated apparent power (MVA) of the th generator;
where and represent the unit column vector where the th
• : rated system frequency (50 Hz in this paper);
or th element equals one and the others are zeros; is the
• : frequency of the th generator;
active power supplied by the generator at the th bus, while
• : mechanical power of the th generator;
is the total active power consumed at the th bus.
• : electrical power of the th generator.
Correspondingly, the contribution from the active power flow
Adding the individual estimated active power deficits of the
of line to the active power load of the th bus is
generators in the power system, we can estimate the total active
calculated as
power imbalance :
(12)
(15)
where is the active power flow from bus to bus .
Similarly, the reactive power flow tracing can also be defined. where is the total number of generators.
Therefore, the obtained tracing active and reactive power from Combining the two (14) and (15), together with the frequency
the generators and lines to load buses provide guidance for de- for the equivalent inertial center
ciding the load shedding distribution in terms of power. All in as defined in [5], a new equation can be obtained as
all

(16)

(13) where

• , the rate of change


of frequency for the equivalent inertial center;
where • , a constant value.
, : total active and reactive power at
C. Existing Methods for Load Shedding Distribution
the th load bus received from the tripping generators and
lines before the disturbance, calculated by means of power After estimating the total power imbalance, this step focuses
flow tracing approach. on determining the exact shedding amount of each load bus.
Conventional load shedding distribution uses the information
III. DESCRIPTION OF THE EXISTING LOAD SHEDDING PROCESS of [6] or frequency change [7] at each load bus, to-
gether with the initial loading condition. Considering that the
A. Trigger for Load Shedding large disturbance may cause the value of of load buses to
The trigger is a signal that starts the load shedding action. be unreliable in the process of load shedding distribution [34],
As the first step of conventional load shedding, trigger is al- is usually selected as the representative frequency informa-
ways based on frequency or voltage information independently tion used in load shedding distribution.
TANG et al.: ADAPTIVE LOAD SHEDDING BASED ON COMBINED FREQUENCY AND VOLTAGE STABILITY ASSESSMENT 2039

The amount of active power load to be shed at the th load Therefore, depending on the fault type, any of the triggers
bus, denoted as , is given according to [7], by may exceed the individual threshold thus initiating the load
shedding procedure.
(17)
B. Improved Power Imbalance Estimation
where In the classic SFR model, only inertia constant of generator
: frequency deviation at the th load bus compared to and frequency information are considered. However, as sug-
the rated frequency (50 Hz in this paper); gested in IEEE standard for UFLS [34], the load model with
: amount of active power load at the th bus before voltage and frequency dependence should also be included in
disturbance; the design for UFLS in order to achieve accurate active power
: total number of load buses. imbalance estimation. Since the voltage variation is always
In this method for load shedding distribution, a load bus with much faster and larger than the change of frequency [9], only
heavier initial load and a larger frequency deviation ends up the voltage dependence of load model as in (20), is applied in
with a larger share of load curtailment. the load shedding scheme in this paper:
Besides, there is another group of methods that utilize the
voltage information in load shedding distribution. In [11], local
voltage stability index called VSRI and voltage deviation are (20)
applied for small and large disturbance, respectively. As large
disturbance is assumed in this paper, only voltage deviation is
taken into consideration as suggested in [11]: (21)

(18) where
• : the current total active and reactive power load of
: voltage deviation at the th load bus compared to all the load buses;
the voltage before the disturbance. • : the current active and reactive power load of
While in [12], voltage deviation and index as defined the th load bus;
in (8), are used in allocating the total load curtailment as • : the initial active and reactive power load of
the th load bus before the disturbance;
• : the current voltage magnitude of the th load bus after
(19) the disturbance;
• : the initial voltage magnitude of the th load bus be-
fore the disturbance;
However, the reactive power is not involved in the calculation • : factor depicting the active and reactive power de-
of (19). Moreover, the information used in (19) are not based on pendence of the load on voltage deviations, which are set
the synchrophasor measurements. Thus, there is no guarantee to 1 and 2, respectively, as introduced in [9];
on the accuracy and speed for application. • : total number of load buses.
Based on this load model, the method proposed in [9] is
adopted in this paper to improve active power imbalance
IV. PROPOSED METHOD FOR LOAD SHEDDING estimation. The total active power imbalance of all the gen-
erators considering the voltage dependent load modeling,
In the proposed adaptive combinational load shedding is defined as
method, both voltage and frequency information are used in all
the three main steps, as mentioned in Section I.
(22)
A. Triggering for Load Shedding

In this work, the use of global triggers is proposed. Therefore, where is the total active power imbalance of all the gen-
we consider simultaneously , and as the triggers erators based on the classic SFR model, neglecting the voltage
with corresponding thresholds: dependence and frequency dependence of the load, as defined
• : the minimum eigenvalue of the Jacobian matrix in (15).
smaller than zero; By means of the comprehensive model introduced in this sec-
• : out of the normal frequency range [49.5, 50.5] Hz; tion, a more accurate and rational total active power imbalance
• : the rate of change of frequency in the abnormal can be estimated. Therefore, in (17), (18) and (19) are re-
range of . As summarized in the IEEE placed with for the tests in this paper.
UFLS standard [34], total amount of shedding load ranges Furthermore, under the assumption that the power factor be-
from 5% to 20%, combining with (16) the values of tween the total active power deficit and reactive
can be calculated. power deficit is identical to the one between
2040 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 2, MAY 2013

total active power load and reactive power load be- at each load bus can be carried out separately in theory. How-
fore load shedding, once is estimated by (22), ever, the situation is totally different in practice: load shedding
we propose to calculate as follows: is usually operated according to which leads to the cor-
responding reactive power curtailment . It means that the
(23) controllability of reactive power is not taken into account. In
simulation, there is always an implicit assumption that, if a load
is cut off, this leads to both active and reactive power curtail-
C. New Method for Load Shedding Distribution ment, and the ratio is decided by the power factor of their initial
load before disturbance as shown in (26):
This section focuses on a proposal to improve the load shed-
ding distribution method, and constitutes the main contribution
(26)
of this paper. Since the same total power imbalance is possible
to shed at different locations of load buses, the process may lead
to different new steady states after load shedding. These steady Therefore, there is a mismatch between , as determined
states may also not achieve system stability [15]. From this point by reactive power load shedding, and , caused by the cur-
of view, load shedding distribution is crucial for the effect of the tailment action only according to the active power. This differ-
load shedding scheme in general. ence, though, can be compensated by the reactive power com-
Although the existing methods as mentioned in (17), (18) and pensating devices such as the static compensator (STATCOM),
(19) could be valid solutions for the distribution of load shed- static VAR compensator (SVC), switching capacitor banks and
ding, there are still two major challenges needed to be tackled: so on. Moreover, the calculated amount of reactive power to
1) reactive power is not considered in the load shedding dis- be shed in the proposed method can be distributed as an addi-
tribution: this may lead to a deficient load shedding distri- tional reference signal to the local reactive power compensation
bution, thus reducing the effect of load shedding; sources like switching capacitor banks. It can also be regarded
2) voltage stability issue is not addressed jointly with reac- as a kind of coordinated reactive power compensation from the
tive power: there is no guarantee of voltage stability, and point of view of the overall system during the load shedding.
the separation of voltage and reactive power may provide D. New Indices for Evaluating the Effect of Load Shedding
fallacious information to load shedding distribution, thus on Loadability
weakening the effect of load shedding.
Considering these two points, a new process for the load Due to the load model in (20) and the improved power imbal-
shedding distribution is proposed here. The core idea of the ance estimation in (22) applied in this paper, three new indices
proposed method is to consider the active and reactive power are selected as metric for evaluating the effect of load shedding.
jointly, in the determination of load shedding distribution. To The indices are defined as follows:
this end, two indices, the load shedding distribution factor for • : the total active power loss of the whole net-
active power (LSDFP) and load shedding distribution factor for work in the recovered steady state after load shedding;
reactive power (LSDFQ) for the load buses, are defined. LSDFP • : the total active power load in the recovered
and LSDFQ can be obtained by (24), which is proportional to steady state after load shedding;
the total active and reactive power imbalance, respectively, as • : the total reactive power load in the recovered
shown in (25). As seen in (24), information about frequency and steady state after load shedding.
active power are included in LSDFP, while voltage and reactive Notice that and , do not simply equal the
power information are calculated together for LSDFQ. How- initial total load minus the total power imbalance. Since the load
ever, in the load shedding distribution methods previously men- modeling in the form of voltage dependence is applied in this
tioned, as in (17), (18) and (19), only the LSDFP is needed. As paper, in (27) and in (28) are determined as
another improvement, the initial load is replaced by the tracing the amount of load shedding and voltage of each load bus to-
power flow, to select more effective thus less load buses into gether in the recovered steady state. Essentially, and
shedding processing. So, in summary are closely dependent to the allocation of load shed-
ding:

(24)
(27)
(25)

where
• : frequency deviation to the rated frequency (50 Hz (28)
in this paper) of the th load bus; where:
• : sensitivity of voltage variation to reactive power of • : the initial voltage magnitude of the th load bus
the th load bus. after load shedding;
Afterwards, and are determined according to • : voltage magnitude of the th load bus in the
(24) and (25), and then active and reactive power load shedding steady state after load shedding.
TANG et al.: ADAPTIVE LOAD SHEDDING BASED ON COMBINED FREQUENCY AND VOLTAGE STABILITY ASSESSMENT 2041

Fig. 2. Configuration of the testing platform.

machines are used for generator modeling, with the IEEE Type
Fig. 1. Topology of modified IEEE 39-Bus system. 1 Excitation System and IEEE Type 1 Governor/Turbine con-
trol models. The ratios of the step-up transformers are chosen
TABLE II by 13.8/345 kV and its wire style is lagging . The trans-
THE DESCRIPTION ABOUT MODIFIED IEEE 39-BUS SYSTEM mission lines are modeled with ideal RLC components, and re-
alistic transmission line models are used for connecting the sub-
systems modeled in three different racks. For each load bus, as
mentioned in (20), the exponential coefficient load model (only
considering voltage dependence) is adopted, whose active and
reactive power varies dynamically as voltage changes in run-
time. According to the standard [28], the reporting rate of PMUs
V. TEST SYSTEM AND TESTING PLATFORM 25 Hz is an available option and is selected in the subsequent
simulation, which means synchrophasor measurements are col-
A. Test Case lected from PMUs every 40 ms and all the analysis are required
As a typical transmission network with multiple generators, to complete within such time interval.
IEEE 39-Bus test system (New England network) [35] is se-
lected as an example in this paper. Seen from Fig. 1, a small C. Testing Platform
modification is to divide bus 39 into bus 39 with a load and bus As shown in Fig. 2, the testing platform constitutes of two
40 located with a generator, which are connected by a transmis- aspects: power system simulation in RTDS and analysis in
sion line with low impedance, while the small load in bus 31 MATLAB [37]. The synchrophasor measurements used for
is neglected. A short summary of the network characteristics is load shedding are collected from the PMU components of
given in Table II. Two assumptions are made for the PMUs: RTDS. First, a collapse process without any load shedding
1) full network observability is ensured by the PMUs located action is recorded. The saved data is imported into MATLAB
in this system; for the off-line computation, such as and for the
2) PMUs are able to provide the complete information about equivalent inertial center, power imbalance estimation, tracing
each bus involved in the load shedding process. power flow and , indices and
about the voltage stability, and the amount of load curtailment
B. Modeling in RTDS Simulation distributed to each individual load bus. According to the results
The power network in Fig. 1 is simulated in Real Time Dig- provided by MATLAB, the load shedding scheme can be drawn
ital Simulator (RTDS) [36]. RTDS is a powerful platform which up and implemented back into the RTDS simulation for test,
performs real time simulation of power systems by a combina- hence the corresponding data is recorded and sent back to
tion of customized software and hardware, with a fixed time- MATLAB again, to check the effect of the load shedding.
step of 50 (or less for specific schemes). The reason for this
choice lies in that RTDS simulates the full dynamic behavior, D. Time Burden in the Centralized Application
essential for the load shedding research. In addition, this im- For the centralized application as proposed in this paper, there
plementation is ready for the extension of our proposed load are two main challenges related to time: communication delay
shedding method to on-line operation, for the real-time control by transmitting PMU measurements to the control center and
research and test with hardware in the loop techniques. calculation time for central analysis based on the Jacobian ma-
In the RTDS simulation, the rated frequency of the system is trix. For the latter, as for computing the minimum eigenvalue
50 Hz, while the reference voltage and the reference power are of Q-V Jacobian and power flow tracing, no iteration process
chosen by 345 kV and 100 MVA, respectively. The synchronous is needed, since the magnitude and phase angle of voltage are
2042 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 2, MAY 2013

TABLE III
TIME BURDEN CAUSED BY DIFFERENT ISSUES

TABLE IV
CLASSIFICATION OF METHODS FOR LOAD SHEDDING

Fig. 3. Observation for the system collapse process without load shedding.

steady condition before the disturbance occurs. Therefore, the


tripping of them leads to an active power deficit accompanied
by a reactive power deficit in the test scenario.
The evolution of the test condition is recorded for 30 s. In sim-
M1: corresponds to existing distribution method as defined in (17); ulation the disturbance occurs at 0.3 s. The voltage magnitude of
M2: corresponds to existing distribution method as defined in (18);
each bus immediately undergoes a slight fluctuation, sustained
M3: corresponds to existing distribution method as defined in (19);
M4: corresponds to the distribution method as mainly defined in (24) and for approximately 7 s, then falls into severe oscillation, as shown
(25), proposed in this paper. in part (a) of Fig. 3. Part (b) to part (d) of Fig. 3 are zoomed in
to concentrate on the transient process after disturbance, and the
directly provided by PMUs, instead of being calculated conven- red dashed lines denote the threshold for each trigger as men-
tionally by iterative power flow or state estimation. Therefore, tioned in Section IV-A. According to the global voltage stability
the computing time is very low. assessment with the minimum eigenvalue as discussed in
As for the communication delay of PMUs, this can vary from Section II-C, voltage collapse is determined at about 7.4 s as
milliseconds to seconds [28]. However, the latency for detecting shown in part (b). Seen from part (c), the rate of change of the
voltage instability and frequency instability is acceptable in the frequency immediately presents a sudden glitch at 0.04 s
range of 1 s to 30 s and 0.25 s to 5 s, respectively, according to after disturbance. This transient highly depends on the dynamic
the survey to the TSOs and research facilities in Nordic Region response of generators with excitation and governor control,
[38]. Therefore, a load shedding procedure that can react within loads and other dynamic devices as described in [5], while part
such time range, which may make the time issues not critical. (d) indicates the value of frequency changes slowly and moves
For addressing the time issues more clearly, the expected time out of normal frequency range at 2.44 s, hence starting to fre-
burden of the main operations are listed in Table III. For the quency oscillation. Therefore, this disturbance causes voltage
analysis part, all the results about computation time are obtained and frequency instability simultaneously, but the trigger is firstly
with MATLAB 2010b operating in the PC environment of Intel activated by the change of . Since no load shedding ac-
Core 2 Quad CPU Q8400 at 2.66 GHz. tion is taken, eventually all the generators are out of step and the
system falls into serious oscillation.
VI. TESTING RESULTS AND DISCUSSION
C. LSDFP and LSDFQ in Load Shedding Methods
A. Classification of Load Shedding Methods As defined in Table IV, LSDFP of methods M1, M2 M3 and
According to the distribution of load shedding, four load M4 together with LSDFQ of method M4 are shown in Fig. 4.
shedding methods are summarized here and denoted as M1, Fig. 4 shows that LSDFP of M1, M2 and M3 yield different
M2, M3 and M4 in Table IV. The common point is that they effects even for a same bus, while the total amount of load
have the same first and second step in the load shedding process. curtailment is shared uniformly by each load bus. For M4, the
All the information needed in each load shedding distribution LSDFP and LSDFQ of each bus are different, which demon-
method is also included in Table IV. The subsequent tests are strates active power and reactive power have different properties
carried out for comparison purpose. for sharing the respective total load curtailment. If we ignore the
LSDFQ or just simply assume that they are identical, this may
B. System Collapse Without Load Shedding lead to an inaccurate load shedding distribution, thus bringing
The simultaneous tripping of generator 3 and transmission to a less effective load shedding scheme, according to the fol-
line (5, 6) is assumed in this test scenario. The generator and lowing test results. Also notice that not all the load buses are
transmission line play a significant role in the system, based involved into load shedding in M4, which instead concentrates
on the large respective generation and transmission capacity in the burden on few load buses in vicinity of the tripping generator
TANG et al.: ADAPTIVE LOAD SHEDDING BASED ON COMBINED FREQUENCY AND VOLTAGE STABILITY ASSESSMENT 2043

Fig. 4. Load shedding distribution factor of each method.


Fig. 6. Minimum eigenvalue of each method in the load shedding process.

Fig. 5. Mean voltage of all the buses in the load shedding process.
Fig. 7. of each method in the load shedding process.

and transmission line, for instance bus 4, 7, 8 and 12. The critical
difference lies in the fact that power flow tracing method is only
applied in M4. Therefore, this result reveals the main advantage
of power flow tracing when applied in load shedding distribu-
tion: it can contribute to focus on some load buses to narrow
the sharing scale among the load buses, instead of dividing total
power imbalance uniformly to each load bus, according to the
information such as the initial load before disturbance.

D. Comparison of Transient Behavior of Different Load


Shedding Methods
Since the same disturbance is applied to test all load shedding
methods, and as all the methods obtain as de-
fined in (22), the total active power imbalance is identical for all
methods. As observed from the results, the system can always Fig. 8. of each method in the load shedding process.
escape from collapse, and stay at different new steady states de-
pending on the chosen methods for load shedding distribution.
The whole process of load shedding with different methods is Figs. 6–8 report the comparisons of , and for
reported from Figs. 5–8. all the four methods: during the process from steady state before
As shown in Fig. 5, the mean voltage of all the buses of the disturbance to the system recovery. In Fig. 6, of M4 is
four methods have similar behavior presenting a fast and large always higher than the others in positive ranges, even during the
drop when disturbance occurs and settling at a new value after short oscillation, which means that M4 keeps the system voltage
a short oscillation thanks to load shedding actions. This result more stable all the time. Fig. 7 is about the recovering of the
indicates that all the methods are effective to prevent system frequency for the equivalent inertial center . It shows that the
from collapsing, and are able to move it into a new steady state amplitude of the oscillation of M4 is the smallest. Seen from
after load shedding. Fig. 8, the difference of is minimal among the methods,
2044 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 2, MAY 2013

TABLE V TABLE VI
COMPARISON AMONG LOAD SHEDDING METHODS COMPARISON AMONG LOAD SHEDDING METHODS
DURING THE TRANSIENT PROCESS IN FREQUENCY AND VOLTAGE

which means this index is weakly impacted by the load shedding


TABLE VII
distribution method. COMPARISON AMONG LOAD SHEDDING METHODS IN POWER
To quantify the results during the transient process, the
maximum deviation of and the maximum deviation of
mean voltage of all load buses during the transient
process, and the time for the and to re-settle to a new
steady-state value are also used as significant indices. Refer-
ring to the definitions for maximum deviation and oscillation
duration for rotor speed in [40], we applied them to the analysis
of the transient process of voltage and frequency oscillation in
this paper. The oscillation duration is defined as

(29) E. Comparison of Recovered Steady State in Aspect of Voltage


and Frequency
where is the time when the fault occurs, which is 0.3 s in our
test; while is the time when the system reaches a To compare the effective of different load shedding methods,
new steady state after load shedding. Normally, is some evaluation indices are needed to distinguish the charac-
determined by the change of , which is the value of or teristics of the new steady state after disturbance and the corre-
at time point , once it is sufficient small in a continuous sponding action of load curtailment. Including the steady states
period of time, as defined in the following: before disturbance and after load shedding with four methods,
five aspects are considered.
First, the frequency for the equivalent inertial center of
the system and the indices of voltages of all the load buses are
(30)
compared as shown in Table VI. There is only a minor difference
where is set as 0.04 s corresponding to the reporting rate of in among the methods, which indicates that the frequency
PMUs. The value of depends on the analysis objective, that of the system in new steady state is mainly determined by the
is chosen for while is used in in total amount of load shedding, considering that active power
this paper. imbalance is identical for all the methods. In terms of higher
The maximum deviation of and are defined as , M4 is able to bring the system into a new steady state
with more stable voltage, for the same total load to be shed.
(31) Moreover, it indicates that the best voltage profile in M4 is kept
in the new steady state, regardless of the mean and minimum
where is the value of at the time point voltage of all the load buses.
.
The test results can be found in Table V. These indicate that F. Comparison of Recovered Steady State in Aspect of
the maximum deviation of caused by M4 is the smallest, but Loadability
the corresponding oscillation duration is the longest. This is be- In Table VII, three new indices as defined in Section IV-C are
cause of the best loadability of M4 as shown in the next subsec- used for evaluating the test results.
tion, which is not beneficial to damping the oscillation of fre- As it can be seen from Table VII, M4 achieves the least total
quency. While M4 does not experience the largest voltage oscil- active power loss of network in the new steady state, although
lation in the transient process, voltage recovers fastest to the new the new steady state is only a temporary period which is usually
steady state with the highest magnitude. Hence, the voltage sta- not sustained for a long time. Interesting comparison informa-
bility issue is well addressed by considering the reactive power tion are provided by and , which are not in-
and voltage as a pair individually in the process of load shed- cluded in previous reasearch work. In this comparison, the effect
ding distribution. of M4 is the best since both active and reactive power loading
TANG et al.: ADAPTIVE LOAD SHEDDING BASED ON COMBINED FREQUENCY AND VOLTAGE STABILITY ASSESSMENT 2045

Fig. 9. of method M4 with different time delays in the load shedding Fig. 10. of method M4 with different time delays in the load shedding
process. process.

is kept at a higher level than the others. The larger values of TABLE VIII
COMPARISON AMONG LOAD SHEDDING METHODS IN FREQUENCY
and indicate the loadability in recovery con- AND VOLTAGE—IN CONDITION OF TWO GENERATORS TRIPPING
dition is better after shedding identical total amount of load. The
reason can be understood from two aspects:
• in all the four methods compared in our paper, total amount
of load shedding is identical owing to the same disturbance
and same method for total active power imbalance esti-
mation. Therefore, the total load before load shedding and
total load curtailment of all the methods are identical, but
the total power loading after load shedding is different de-
pending on the load shedding distribution methods. The
critical reason lies in the load model of voltage dependence
[9] applied in the analysis and simulation in this work,
more realistic for real power system and also suggested by
the IEEE standard [34]. This decides that larger voltage TABLE IX
magnitude leading to larger power consumption, thus the COMPARISON AMONG LOAD SHEDDING METHODS IN POWER—IN CONDITION
OF TWO GENERATORS TRIPPING
better loadability;
• total load after load shedding closely depends on the
voltage profiles. The better voltage profiles are achieved
by taking into consideration the index together with
reactive power in the step that yields the distribution of
load shedding. Therefore, M4 ensures the best loadability
after load shedding, thanks to the better voltage profiles
at individual load buses. This is achieved by means of the
load shedding distribution that integrates reactive power
compensation.
In summary, the proposed method M4 exhibits the best per-
formance in relation to steady state after load shedding from the H. Test Results in Condition of Simultaneous Tripping of Two
point of view of each proposed index. Generators
To show the applicability of the proposed methods, another
G. Impact of Time Delay Caused by Communication on Load test scenario is studied. In this scenario, the disturbance caused
Shedding Results by tripping of generator 5 and generator 6 simultaneously is
In Table III, the time delay in synchrophasor transmission is assumed. The capacities of some generators are adjusted to
the biggest challenge for load shedding. To better investigate allow for the system collapse in this fault condition. Similarly
this aspect, we have run a sensitivity test to check its impact, to the previous test results, all the load shedding methods
setting different values of time delay in the RTDS simulation. can maintain the stability of the system after disturbance and
As shown in Figs. 9 and 10, as time delay increases, the max- bring the system into a new steady state. In addition, similar
imum deviation of and during the oscillation becomes conclusions can be obtained from Tables VIII and IX, that the
larger. For this test case, the limit of impact from the time delay M4 is still the most effective method at strengthening the new
is between 2 s and 4 s, beyond which the load shedding proce- steady state after executing the same total amount of active
dure may fail. power curtailment.
2046 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 2, MAY 2013

VII. CONCLUSIONS [13] K. Mollah and N. C.-K. Nair, “Coordinated strategy for under-voltage
and under-frequency load shedding,” in Proc. 2010 20th Australasian
To overcome the disadvantages of the existing adaptive Universities Power Engineering Conf. (AUPEC), Dec. 2010, pp. 1–6.
combinational load shedding methods, a load shedding scheme [14] W. Qin, P. Wang, X. Han, and X. Du, “Reactive power aspects in re-
liability assessment of power systems,” IEEE Trans. Power Syst., vol.
based on a new load shedding distribution method, using 26, no. 1, pp. 85–92, Feb. 2011.
combined frequency and voltage stability assessment, is pro- [15] C. M. Affonso, L. C. P. da Silva, F. G. M. Lima, and S. Soares, “MW
posed in this work. The synchrophasor measurements are and MVar management on supply and demand side for meeting voltage
stability margin criteria,” IEEE Trans. Power Syst., vol. 19, no. 3, pp.
used throughout the proposed load shedding process. As an 1538–1545, Aug. 2004.
innovation of this paper, reactive power is used directly into [16] D. Karlsson, M. Hemmingsson, and S. Lindahl, “Wide area system
the reactive power load shedding distribution together with monitoring and control-terminology, phenomena, and solution imple-
mentation strategies,” IEEE Power and Energy Mag., vol. 2, no. 5, pp.
active power load shedding distribution, to address the voltage 68–76, Sep.–Oct. 2004.
stability issue directly and more effectively in the load shed- [17] J. De La Ree, V. Centeno, J. S. Thorp, and A. G. Phadke, “Synchro-
ding process. Also, modal analysis is chosen to address the nized phasor measurement applications in power systems,” IEEE
Trans. Smart Grid, vol. 1, no. 1, pp. 20–27, Jun. 2010.
voltage stability issue more accurately, via a sophisticated and [18] X. Xie, Y. Xin, J. Xiao, J. Wu, and Y. Han, “WAMS applications in
global algorithm, which particularly benefits from phase angle Chinese power systems,” IEEE Power and Energy Mag., vol. 4, no. 1,
measurements of the PMUs. Moreover, the power flow tracing pp. 54–63, Jan.–Feb. 2006.
[19] M. Zima, M. Larsson, P. Korba, C. Rehtanz, and G. Andersson,
algorithm is applied in the load shedding distribution, to select “Design aspects for wide-area monitoring and control systems,” Proc.
the more effective load buses and thus reducing the number IEEE, vol. 93, no. 5, pp. 980–996, May 2005.
of load buses for sharing the total power imbalance. The test [20] A. G. Phadke and J. S. Thorp, Synchronized Phasor Measurements and
results indicate that the improvements on load shedding distri- Their Applications. New York, NY, USA: Springer, 2008.
[21] M. Glavic and T. Van Cutsem, “Wide-area detection of voltage in-
bution of load shedding method can enhance the new steady stability from synchronized phasor measurements. Part I: Principle,”
state of power systems in view of frequency stability, voltage IEEE Trans. Power Syst., vol. 24, no. 3, pp. 1408–1416, Aug. 2009.
stability and loadability, also with a good transient behavior, [22] M. Glavic and T. Van Cutsem, “Wide-area detection of voltage insta-
bility from synchronized phasor measurements. Part II: Simulation re-
when encountering the large disturbances. Thus, for the load sults,” IEEE Trans. Power Syst., vol. 24, no. 3, pp. 1417–1425, Aug.
shedding in practical application, there is a new choice to 2009.
protect the system safely and efficiently. [23] Y. Wang, I. R. Pordanjani, W. Li, W. Xu, T. Chen, E. Vaahedi, and
J. Gurney, “Voltage stability monitoring based on the concept of cou-
pled single-port circuit,” IEEE Trans. Power Syst., vol. 26, no. 4, pp.
REFERENCES 2154–2163, Nov. 2011.
[24] B. Milosevic and M. Begovic, “Voltage-stability protection and con-
[1] P. Kundur et al., IEEE/CIGRE Joint Task Force on Stability Terms trol using a wide-area network of phasor measurements,” IEEE Trans.
and Definitions, “Definition and classification of power system sta- Power Syst., vol. 18, no. 1, pp. 121–127, Feb. 2003.
bility ,” IEEE Trans. Power Systems, vol. 19, no. 3, pp. 1387–1401, [25] R. Niu, Y. Zeng, M. Cheng, and X. Wang, “Study on load-shedding
Aug. 2004. model based on improved power flow tracing method in power system
[2] A. P. Ghaleh, M. Sanaye-Pasand, and A. Saffarian, “Power system risk assessment,” in Proc. 2011 4th Int. Conf. Electric Utility Deregu-
stability enhancement using a new combinational load-shedding algo- lation and Restructuring and Power Technologies (DRPT), Jul. 2011,
rithm,” IET Gen., Transm., Distrib., vol. 5, no. 5, pp. 551–560, May pp. 45–50.
2011. [26] Y. Zhao, N. Zhou, J. Zhou, K. Xie, Y. Liu, and J. Kuang, “A heuristic
[3] A. Saffarian and M. Sanaye-Pasand, “Enhancement of power system approach to local load shedding scheme for reliability assessment of
stability using adaptive combinational load shedding methods,” IEEE bulk power systems,” in Proc. 2005 IEEE/PES Transmission and Dis-
Trans. Power Syst., vol. 26, no. 3, pp. 1010–1020, Aug. 2011. tribution Conf. Exhib.: Asia and Pacific, 2005, pp. 1–5.
[4] P. M. Anderson and M. Mirheydar, “An adaptive method for setting [27] A. G. Phadke and R. M. de Moraes, “The wide world of wide-area
underfrequency load shedding relays,” IEEE Trans. Power Syst., vol. measurement,” IEEE Power and Energy Mag., vol. 6, no. 5, pp. 52–65,
7, no. 2, pp. 647–655, May 1992. Sep.–Oct. 2008.
[5] V. V. Terzija, “Adaptive underfrequency load shedding based on the [28] IEEE Standard for Synchrophasor Measurements for Power Systems,
magnitude of the disturbance estimation,” IEEE Trans. Power Syst., IEEE Std. C37.118.1-2011 (Revision of IEEE Std C37.118-2005), Dec.
vol. 21, no. 3, pp. 1260–1266, Aug. 2006. 2011.
[6] A. V. Kulkarni, W. Gao, and J. Ning, “Study of power system [29] P. Kundur, Power System Stability and Control. New York, NY,
load shedding scheme based on dynamic simulation,” in Proc. 2010 USA: McGraw-Hill, 1994.
IEEE PES Transmission and Distribution Conf. Expo., Apr. 2010, [30] B. Gao, G. K. Morison, and P. Kundur, “Voltage stability evaluation
pp. 1–7. using modal analysis,” IEEE Trans. Power Syst., vol. 7, no. 4, pp.
[7] Z. Zhong, “Power systems frequency dynamic monitoring system de- 1529–1542, Nov. 1992.
sign and applications,” PhD. dissertation, Dept. Elect. Comput. Eng., [31] G. K. Morison, B. Gao, and P. Kundur, “Voltage stability analysis using
Virginia Polytechnic Institute and State Univ., Blacksburg, VA, USA, static and dynamic approaches,” IEEE Trans. Power Syst., vol. 8, no.
Jul. 2005. 3, pp. 1159–1171, Aug. 1993.
[8] U. Rudez and R. Mihalic, “Monitoring the first frequency derivative [32] J. Bialek, “Topological generation and load distribution factors for sup-
to improve adaptive underfrequency load-shedding schemes,” IEEE plement charge allocation in transmission open access,” IEEE Trans.
Trans. Power Syst., vol. 26, no. 2, pp. 839–846, May 2011. Power Syst., vol. 12, no. 3, pp. 1185–1193, Aug. 1997.
[9] U. Rudez and R. Mihalic, “Analysis of underfrequency load shedding [33] B. Zhang, S. Chen, and Z. Yan, Advanced Analysis for Power Network,
using a frequency gradient,” IEEE Trans. Power Del., vol. 26, no. 2, 2nd ed. Beijing, China: Tsinghua Univ. Press, 2007.
pp. 565–575, Apr. 2011. [34] IEEE Guide for the Application of Protective Relays Used for Ab-
[10] H. Seyedi and M. Sanaye-Pasand, “New centralised adaptive load- normal Frequency Load Shedding and Restoration, IEEE Std. C37.
shedding algorithms to mitigate power system blackouts,” IET Gen., 117-2007, Aug. 2007.
Transm., Distrib., vol. 3, no. 1, pp. 99–114, Jan. 2009. [35] M. A. Pai, Energy Function Analysis for Power System Stability.
[11] K. Seethalekshmi, S. N. Singh, and S. C. Srivastava, “A synchrophasor Boston, MA, USA: Kluwer, 1989.
assisted frequency and voltage stability based load shedding scheme [36] “RTDS Manual Set,” RTDS Technologies, Inc., 2005.
for self-healing of power system,” IEEE Trans. Smart Grid, vol. 2, no. [37] “MATLAB User’s Guide,” MathWorks, Inc., 1995.
2, pp. 221–230, Jun. 2011. [38] M. Chenine, K. Zhu, and L. Nordstrom, “Survey on priorities and com-
[12] D. Prasetijo, W. R. Lachs, and D. Sutanto, “A new load shedding munication requirements for PMU-based applications in the Nordic re-
scheme for limiting underfrequency,” IEEE Trans. Power Syst., vol. 9, gion,” in Proc. 2009 IEEE Bucharest PowerTech, Jun.–Jul. 2008, pp.
no. 3, pp. 1371–1378, Aug. 1994. 1–8.
TANG et al.: ADAPTIVE LOAD SHEDDING BASED ON COMBINED FREQUENCY AND VOLTAGE STABILITY ASSESSMENT 2047

[39] M. Chenine and L. Nordstrom, “Modeling and simulation of wide-area Ferdinanda Ponci (M’00–SM’08) received the
communication for centralized PMU-based applications,” IEEE Trans. Ph.D. degree in electrical engineering from Politec-
Power Del., vol. 26, no. 3, pp. 1372–1380, Jul. 2011. nico di Milano, Milano, Italy, in 2002.
[40] M. Reza, “Stability analysis of transmission systems with high penetra- In 2003 she joined the Department of Electrical
tion of distributed generation,” Ph.D. dissertation, electrical engineer, Engineering at the University of South Carolina,
Delft Univ. Technol., Delft, The Netherlands, Dec. 2006. Columbia, SC, USA, as an Assistant Professor. In
2008 she was tenured and promoted to Associate
Professor. In 2009 she joined the E.ON Energy
research Center-Institute for Automation of Com-
Junjie Tang (GS’10) was born in Chongqing, China, plex Power Systems at RWTH Aachen University,
in 1984. He received the B.S. and M.S degrees from Aachen, Germany, where she is currently an apl.
China Agricultural University, China, in 2007 and Professor. Her research activity is focused on agent based applications in
2010, respectively. He is currently pursuing the Ph.D. monitoring and energy management, distributed state estimation, and modeling
degree in the Institute for Automation of Complex and simulation of uncertain systems.
Power Systems of the E.ON Energy Research Center
at RWTH Aachen University, Aachen, Germany.
His research interests include power system
wide-area monitoring, synchronized phasor mea-
surement, power system stability and power system Antonello Monti (M’94–SM’02) received the M.S.
state estimation. and Ph.D. degrees in electrical engineering from Po-
litecnico di Milano, Milano, Italy, in 1989 and 1994,
respectively.
From 1990 to 1994, he was with the research
Junqi Liu (GS’10) received the M.Sc. degree from laboratory of Ansaldo Industria of Milan, designing
the Technische Universität München, München, Ger- the digital control of a large power drives. In 1995,
many, in 2009. He is currently a research associate he joined the Department of Electrical Engineering,
and is pursuing the Ph.D. degree in the Institute for Politecnico di Milano as an Assistant Professor.
Automation of Complex Power Systems of the E.ON From 2000 to 2008, he was an Associate Professor
Energy Research Center at RWTH Aachen Univer- and then a Full Professor with the Department of
sity, Aachen, Germany. Electrical Engineering, University of South Carolina, Columbia, SC, USA. He
His research interests include advanced measure- is currently the Director of the Institute for Automation of Complex Power
ment, control and optimization techniques for next Systems, E.ON Energy Research Center, RWTH Aachen University, Aachen,
generation power systems. Germany.

You might also like