Professional Documents
Culture Documents
Adaptive Load Shedding Based On Combined
Adaptive Load Shedding Based On Combined
Abstract—Under frequency load shedding (UFLS) and under However, the traditional load shedding schemes are not ca-
voltage load shedding (UVLS) are attracting more attention, as pable of dealing with combined instabilities, as discussed in
large disturbances occur more frequently than in the past. Usually, [2] and [3]. Since the action of UFLS usually only considers
these two schemes work independently from each other, and are
not designed in an integrated way to exploit their combined effect the frequency information, it may have unanticipated, adverse
on load shedding. Besides, reactive power is seldom considered consequences on the voltage. A similar issue affects the con-
in the load shedding process. To fill this gap, we propose in this ventional UVLS which uses only local voltage magnitude
paper a new centralized, adaptive load shedding algorithm, which information at the individual buses. Another disadvantage of
uses both voltage and frequency information provided by phasor the conventional methods is that they simply follow a preset
measurement units (PMUs). The main contribution of the new
method is the consideration of reactive power together with active rule, such as shedding a fixed percentage of loads when fre-
power in the load shedding strategy. Therefore, this method ad- quency is out of the normal range. This type of rule lacks the
dresses the combined voltage and frequency stability issues better flexibility to execute load shedding actions fit for the different
than the independent approaches. The new method is tested on the type of instabilities.
IEEE 39-Bus system, in order to compare it with other methods. Research work about adaptive UFLS was introduced in
Simulation results show that, after large disturbance, this method
can bring the system back to a new stable steady state that is [4]–[7] in order to improve the conventional load shedding
better from the point of view of frequency and voltage stability, schemes. However, in these approaches, still only the fre-
and loadability. quency information is used in the load shedding process. An
Index Terms—Adaptive load shedding scheme, phasor measure- improvement has been proposed in [8] and [9], where voltage
ment units (PMUs), power system stability, synchrophasor, under dependent load modeling has been taken into account for the
frequency load shedding, under voltage load shedding. active power imbalance estimation. Also in this case, though,
the voltage information is not exploited for the load shedding
strategy. Furthermore, some researchers [10]–[13] have pro-
I. INTRODUCTION posed combinational load shedding methods based on adaptive
M OSTLY as a consequence of the deregulated electricity UFLS, in which the distribution of load shedding is determined
markets and the growth of electrical energy consump- using the voltage magnitude information. All these combina-
tion, power systems are now often operated close to their sta- tional load shedding methods go in the direction of addressing
bility limits. In case of large disturbances, such as generators the voltage stability issue in adaptive UFLS. However, the
tripping and faults on transmission lines leading to cascading existing methods for combinational load shedding still exclude
faults [1], the resulting active and reactive power imbalance can controlled reactive power from the direct participation in load
eventually lead to simultaneous large frequency and voltage de- shedding. Instead, we believe that the contribution of resources
viation, as well as instability. Thus, there is a higher risk that the and equipment capable of reactive power support and control
overall system may collapse. is essential for the voltage stability [14], [15].
Conventionally, load shedding schemes—under frequency With the diffusion of wide-area monitoring and control sys-
load shedding (UFLS) and under voltage load shedding tems (WAMCS) [16]–[19] based on phasor measurement units
(UVLS), are designed independently and they constitute the (PMUs), the power system stability issues can be addressed
last line of defense against frequency and voltage instability. more effectively. PMUs can provide synchronized measure-
ments, which include the magnitude and phase angle of voltages
and currents, frequency and rate of change of frequency [20].
Manuscript received May 01, 2012; revised May 18, 2012, September 20,
2012, and January 11, 2013; accepted January 14, 2013. Date of publication These measured data may support the tracking of dynamic phe-
March 07, 2013; date of current version April 18, 2013. Paper no. TPWRS- nomena and provide sufficient information for both frequency
00452-2012.
and voltage stability assessment. Moreover, the phase angle
The authors are with the Institute for Automation of Complex Power
Systems, E.ON Energy Research Center, RWTH Aachen University, Aachen, measurements provided by PMUs are proven in principle to
Germany (e-mail: jtang@eonerc.rwth-aachen.de; jliu@eonerc.rwth-aachen.de; facilitate more accurate and early voltage instability detection
fponci@eonerc.rwth-aachen.de; amonti@eonerc.rwth-aachen.de).
[21]–[24]. Nevertheless, they have not been exploited yet in
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. existing load shedding methods. In this paper, synchrophasor
Digital Object Identifier 10.1109/TPWRS.2013.2241794 measurements are used to enable more advanced, adaptive load
shedding on the basis of both frequency and voltage stability The structure of this paper is organized as follows: the role
indices. of synchrophasors in implementing the proposed adaptive
In the conventional methods for distribution of load shedding, load shedding scheme, and the corresponding algorithms for
the initial load of each load bus is considered as a starting point obtaining the information required in load shedding are de-
for allocation. Hence, all the load buses are involved in sharing scribed in Section II. The conventional adaptive load shedding
the total power imbalance without selection. This is unpractical, is presented in Section III, while Section IV introduces the
especially for complex power systems with a large number of load shedding method newly proposed, in particular the load
load buses. Moreover, according to the knowledge of the au- shedding distribution determination; test system and platform
thors, power flow tracing is a reasonable choice for the selec- for the assessment of the proposed method are introduced
tion of a subset of all load buses in the load shedding distribu- in Section V, and Section VI presents experimental results
tion for general use. In [25] and [26], power flow tracing is pro- based on real time simulation and provides explanations and
comments. Section VII summarizes the conclusions.
posed in a load shedding scheme for the faults originating from
lines tripping, and they are proven to work effectively. In this II. SYNCHROPHASOR FOR LOAD SHEDDING
work, we consider the case of generators tripping. By means of
the power flow tracing, we can accurately determine the corre- A. PMUs, Synchrophasor and WAMCS
sponding proportional power of each load bus that is supplied PMUs, instruments providing so-called synchronized phasor
by the lost generators or lines. Usually, the buses in the vicinity or synchrophasor measurements have been widely deployed in
of tripping elements are the most sensitive to such kind of faults. power systems in the last decade [27], mostly in high voltage
This fact leads to load bus selection, and eventually to a reduc- transmission networks [18].
tion of the load busses involved in load shedding. In the standard [28], the synchrophasor is defined as a
In this paper, we propose a new adaptive load shedding complex number representation of either a voltage or a current,
method that considers frequency and voltage stability assess- at the fundamental frequency, using a standard time reference.
ment simultaneously. Such adaptive method is organized in The synchrophasor representation of a sinusoidal signal
three main steps: is the complex value given by
1) determination of a trigger for activating the load shedding
procedure; (1)
2) estimation of total power imbalance for the whole system;
3) distribution of the total power imbalance to individual load where is the root-mean-square (rms) value of the signal
bus. , and is its instantaneous phase angle that is referred to a
The proposed adaptive load shedding method should be ap- common reference time (UTC, Universal Coordinated Time).
plied using both frequency and voltage information at each step, Both values can be measured directly by PMUs [17].
especially in the third step which yields the final load shedding WAMCS is a central platform that may use synchrophasor
action to be implemented. First, a global voltage stability index measurements gathered from a wide area for the purpose
and the frequency information for the equivalent inertial center of centralized monitoring and control, such as for assessing
are utilized jointly for the trigger determination. In the second and maintaining stability [16]–[19]. The time-stamped syn-
step, we apply a low-order system frequency response (SFR) chrophasor data are calculated by the PMUs at high rate and
model [4] combined with the voltage dependent load models [9], with high accuracy [20]. Hence they are very effective for
to obtain the overall active power mismatch and hence the total tracking the dynamic evolution in the power system operation,
amount of reactive power to be shed. Finally, we use both the especially in critical conditions, such as the occurrence of
frequency and voltage information in the third step, for simulta- oscillations and large disturbances [19]. Large disturbances
neous active and reactive load shedding distribution. In the ac- are caused mainly by lines or generators tripping, whose
tive load shedding distribution process, the frequency measure- connection/disconnection status monitoring can be supported
by PMUs as in [10]. Therefore, synchrophasor measurements
ments are used together with the active power estimates pro-
facilitate global awareness of the system. This is beneficial for
vided by tracing power flow. While for the reactive power load
the stability assessment and load shedding.
shedding distribution, it requires the voltage information com-
bined with reactive power estimates obtained also from tracing B. Role of Synchrophasor Measurements in the Proposed
power flow. In this way, the appropriate amount of active and Load Shedding Scheme
reactive power to be shed at the selected buses can be deter- Synchrophasor measurements have enabled new appli-
mined simultaneously. Furthermore, the conventional methods cations, including combinational load shedding using both
have been augmented with reactive power, global voltage sta- frequency and voltage information [19]. While in traditional
bility analysis and load bus selection for load shedding. Thus, supervisory control and data acquisition (SCADA) systems,
the new approach can enhance the recovered steady state with generally only the non-synchronized magnitude measurements
respect to frequency stability, voltage stability and loadability, of the signals are received directly from Remote Terminal
while also ensuring a good transient behavior, for the same total Unit (RTU), which are designed for lower rate and accuracy.
active power curtailment, compared to the existing load shed- Furthermore, the phase angle has to be estimated via power
ding methods. flow calculation, which is a time consuming process. Instead,
TANG et al.: ADAPTIVE LOAD SHEDDING BASED ON COMBINED FREQUENCY AND VOLTAGE STABILITY ASSESSMENT 2037
TABLE I where
PHASOR MEASUREMENTS FOR DIFFERENT • : right eigenvector matrix of ;
ISSUES AND STEPS OF LOAD SHEDDING
• : left eigenvector matrix of ;
• : diagonal eigenvalue matrix of ;
• : th column of ;
• : th row of ;
• : th eigenvalue of and the corresponding mode.
The corresponding th modal voltage variation is
(7)
According to the principle that the inflow equals the outflow [5], [10], [34]. A local method to activate the trigger by consid-
at any bus, the outflow of bus can be defined as ering both voltage and frequency jointly at each bus has been
proposed in [2] and [3]. The details of each trigger used in this
(9) paper are introduced in Section IV-A.
(16)
(13) where
The amount of active power load to be shed at the th load Therefore, depending on the fault type, any of the triggers
bus, denoted as , is given according to [7], by may exceed the individual threshold thus initiating the load
shedding procedure.
(17)
B. Improved Power Imbalance Estimation
where In the classic SFR model, only inertia constant of generator
: frequency deviation at the th load bus compared to and frequency information are considered. However, as sug-
the rated frequency (50 Hz in this paper); gested in IEEE standard for UFLS [34], the load model with
: amount of active power load at the th bus before voltage and frequency dependence should also be included in
disturbance; the design for UFLS in order to achieve accurate active power
: total number of load buses. imbalance estimation. Since the voltage variation is always
In this method for load shedding distribution, a load bus with much faster and larger than the change of frequency [9], only
heavier initial load and a larger frequency deviation ends up the voltage dependence of load model as in (20), is applied in
with a larger share of load curtailment. the load shedding scheme in this paper:
Besides, there is another group of methods that utilize the
voltage information in load shedding distribution. In [11], local
voltage stability index called VSRI and voltage deviation are (20)
applied for small and large disturbance, respectively. As large
disturbance is assumed in this paper, only voltage deviation is
taken into consideration as suggested in [11]: (21)
(18) where
• : the current total active and reactive power load of
: voltage deviation at the th load bus compared to all the load buses;
the voltage before the disturbance. • : the current active and reactive power load of
While in [12], voltage deviation and index as defined the th load bus;
in (8), are used in allocating the total load curtailment as • : the initial active and reactive power load of
the th load bus before the disturbance;
• : the current voltage magnitude of the th load bus after
(19) the disturbance;
• : the initial voltage magnitude of the th load bus be-
fore the disturbance;
However, the reactive power is not involved in the calculation • : factor depicting the active and reactive power de-
of (19). Moreover, the information used in (19) are not based on pendence of the load on voltage deviations, which are set
the synchrophasor measurements. Thus, there is no guarantee to 1 and 2, respectively, as introduced in [9];
on the accuracy and speed for application. • : total number of load buses.
Based on this load model, the method proposed in [9] is
adopted in this paper to improve active power imbalance
IV. PROPOSED METHOD FOR LOAD SHEDDING estimation. The total active power imbalance of all the gen-
erators considering the voltage dependent load modeling,
In the proposed adaptive combinational load shedding is defined as
method, both voltage and frequency information are used in all
the three main steps, as mentioned in Section I.
(22)
A. Triggering for Load Shedding
In this work, the use of global triggers is proposed. Therefore, where is the total active power imbalance of all the gen-
we consider simultaneously , and as the triggers erators based on the classic SFR model, neglecting the voltage
with corresponding thresholds: dependence and frequency dependence of the load, as defined
• : the minimum eigenvalue of the Jacobian matrix in (15).
smaller than zero; By means of the comprehensive model introduced in this sec-
• : out of the normal frequency range [49.5, 50.5] Hz; tion, a more accurate and rational total active power imbalance
• : the rate of change of frequency in the abnormal can be estimated. Therefore, in (17), (18) and (19) are re-
range of . As summarized in the IEEE placed with for the tests in this paper.
UFLS standard [34], total amount of shedding load ranges Furthermore, under the assumption that the power factor be-
from 5% to 20%, combining with (16) the values of tween the total active power deficit and reactive
can be calculated. power deficit is identical to the one between
2040 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 2, MAY 2013
total active power load and reactive power load be- at each load bus can be carried out separately in theory. How-
fore load shedding, once is estimated by (22), ever, the situation is totally different in practice: load shedding
we propose to calculate as follows: is usually operated according to which leads to the cor-
responding reactive power curtailment . It means that the
(23) controllability of reactive power is not taken into account. In
simulation, there is always an implicit assumption that, if a load
is cut off, this leads to both active and reactive power curtail-
C. New Method for Load Shedding Distribution ment, and the ratio is decided by the power factor of their initial
load before disturbance as shown in (26):
This section focuses on a proposal to improve the load shed-
ding distribution method, and constitutes the main contribution
(26)
of this paper. Since the same total power imbalance is possible
to shed at different locations of load buses, the process may lead
to different new steady states after load shedding. These steady Therefore, there is a mismatch between , as determined
states may also not achieve system stability [15]. From this point by reactive power load shedding, and , caused by the cur-
of view, load shedding distribution is crucial for the effect of the tailment action only according to the active power. This differ-
load shedding scheme in general. ence, though, can be compensated by the reactive power com-
Although the existing methods as mentioned in (17), (18) and pensating devices such as the static compensator (STATCOM),
(19) could be valid solutions for the distribution of load shed- static VAR compensator (SVC), switching capacitor banks and
ding, there are still two major challenges needed to be tackled: so on. Moreover, the calculated amount of reactive power to
1) reactive power is not considered in the load shedding dis- be shed in the proposed method can be distributed as an addi-
tribution: this may lead to a deficient load shedding distri- tional reference signal to the local reactive power compensation
bution, thus reducing the effect of load shedding; sources like switching capacitor banks. It can also be regarded
2) voltage stability issue is not addressed jointly with reac- as a kind of coordinated reactive power compensation from the
tive power: there is no guarantee of voltage stability, and point of view of the overall system during the load shedding.
the separation of voltage and reactive power may provide D. New Indices for Evaluating the Effect of Load Shedding
fallacious information to load shedding distribution, thus on Loadability
weakening the effect of load shedding.
Considering these two points, a new process for the load Due to the load model in (20) and the improved power imbal-
shedding distribution is proposed here. The core idea of the ance estimation in (22) applied in this paper, three new indices
proposed method is to consider the active and reactive power are selected as metric for evaluating the effect of load shedding.
jointly, in the determination of load shedding distribution. To The indices are defined as follows:
this end, two indices, the load shedding distribution factor for • : the total active power loss of the whole net-
active power (LSDFP) and load shedding distribution factor for work in the recovered steady state after load shedding;
reactive power (LSDFQ) for the load buses, are defined. LSDFP • : the total active power load in the recovered
and LSDFQ can be obtained by (24), which is proportional to steady state after load shedding;
the total active and reactive power imbalance, respectively, as • : the total reactive power load in the recovered
shown in (25). As seen in (24), information about frequency and steady state after load shedding.
active power are included in LSDFP, while voltage and reactive Notice that and , do not simply equal the
power information are calculated together for LSDFQ. How- initial total load minus the total power imbalance. Since the load
ever, in the load shedding distribution methods previously men- modeling in the form of voltage dependence is applied in this
tioned, as in (17), (18) and (19), only the LSDFP is needed. As paper, in (27) and in (28) are determined as
another improvement, the initial load is replaced by the tracing the amount of load shedding and voltage of each load bus to-
power flow, to select more effective thus less load buses into gether in the recovered steady state. Essentially, and
shedding processing. So, in summary are closely dependent to the allocation of load shed-
ding:
(24)
(27)
(25)
where
• : frequency deviation to the rated frequency (50 Hz (28)
in this paper) of the th load bus; where:
• : sensitivity of voltage variation to reactive power of • : the initial voltage magnitude of the th load bus
the th load bus. after load shedding;
Afterwards, and are determined according to • : voltage magnitude of the th load bus in the
(24) and (25), and then active and reactive power load shedding steady state after load shedding.
TANG et al.: ADAPTIVE LOAD SHEDDING BASED ON COMBINED FREQUENCY AND VOLTAGE STABILITY ASSESSMENT 2041
machines are used for generator modeling, with the IEEE Type
Fig. 1. Topology of modified IEEE 39-Bus system. 1 Excitation System and IEEE Type 1 Governor/Turbine con-
trol models. The ratios of the step-up transformers are chosen
TABLE II by 13.8/345 kV and its wire style is lagging . The trans-
THE DESCRIPTION ABOUT MODIFIED IEEE 39-BUS SYSTEM mission lines are modeled with ideal RLC components, and re-
alistic transmission line models are used for connecting the sub-
systems modeled in three different racks. For each load bus, as
mentioned in (20), the exponential coefficient load model (only
considering voltage dependence) is adopted, whose active and
reactive power varies dynamically as voltage changes in run-
time. According to the standard [28], the reporting rate of PMUs
V. TEST SYSTEM AND TESTING PLATFORM 25 Hz is an available option and is selected in the subsequent
simulation, which means synchrophasor measurements are col-
A. Test Case lected from PMUs every 40 ms and all the analysis are required
As a typical transmission network with multiple generators, to complete within such time interval.
IEEE 39-Bus test system (New England network) [35] is se-
lected as an example in this paper. Seen from Fig. 1, a small C. Testing Platform
modification is to divide bus 39 into bus 39 with a load and bus As shown in Fig. 2, the testing platform constitutes of two
40 located with a generator, which are connected by a transmis- aspects: power system simulation in RTDS and analysis in
sion line with low impedance, while the small load in bus 31 MATLAB [37]. The synchrophasor measurements used for
is neglected. A short summary of the network characteristics is load shedding are collected from the PMU components of
given in Table II. Two assumptions are made for the PMUs: RTDS. First, a collapse process without any load shedding
1) full network observability is ensured by the PMUs located action is recorded. The saved data is imported into MATLAB
in this system; for the off-line computation, such as and for the
2) PMUs are able to provide the complete information about equivalent inertial center, power imbalance estimation, tracing
each bus involved in the load shedding process. power flow and , indices and
about the voltage stability, and the amount of load curtailment
B. Modeling in RTDS Simulation distributed to each individual load bus. According to the results
The power network in Fig. 1 is simulated in Real Time Dig- provided by MATLAB, the load shedding scheme can be drawn
ital Simulator (RTDS) [36]. RTDS is a powerful platform which up and implemented back into the RTDS simulation for test,
performs real time simulation of power systems by a combina- hence the corresponding data is recorded and sent back to
tion of customized software and hardware, with a fixed time- MATLAB again, to check the effect of the load shedding.
step of 50 (or less for specific schemes). The reason for this
choice lies in that RTDS simulates the full dynamic behavior, D. Time Burden in the Centralized Application
essential for the load shedding research. In addition, this im- For the centralized application as proposed in this paper, there
plementation is ready for the extension of our proposed load are two main challenges related to time: communication delay
shedding method to on-line operation, for the real-time control by transmitting PMU measurements to the control center and
research and test with hardware in the loop techniques. calculation time for central analysis based on the Jacobian ma-
In the RTDS simulation, the rated frequency of the system is trix. For the latter, as for computing the minimum eigenvalue
50 Hz, while the reference voltage and the reference power are of Q-V Jacobian and power flow tracing, no iteration process
chosen by 345 kV and 100 MVA, respectively. The synchronous is needed, since the magnitude and phase angle of voltage are
2042 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 2, MAY 2013
TABLE III
TIME BURDEN CAUSED BY DIFFERENT ISSUES
TABLE IV
CLASSIFICATION OF METHODS FOR LOAD SHEDDING
Fig. 3. Observation for the system collapse process without load shedding.
Fig. 5. Mean voltage of all the buses in the load shedding process.
Fig. 7. of each method in the load shedding process.
and transmission line, for instance bus 4, 7, 8 and 12. The critical
difference lies in the fact that power flow tracing method is only
applied in M4. Therefore, this result reveals the main advantage
of power flow tracing when applied in load shedding distribu-
tion: it can contribute to focus on some load buses to narrow
the sharing scale among the load buses, instead of dividing total
power imbalance uniformly to each load bus, according to the
information such as the initial load before disturbance.
TABLE V TABLE VI
COMPARISON AMONG LOAD SHEDDING METHODS COMPARISON AMONG LOAD SHEDDING METHODS
DURING THE TRANSIENT PROCESS IN FREQUENCY AND VOLTAGE
Fig. 9. of method M4 with different time delays in the load shedding Fig. 10. of method M4 with different time delays in the load shedding
process. process.
is kept at a higher level than the others. The larger values of TABLE VIII
COMPARISON AMONG LOAD SHEDDING METHODS IN FREQUENCY
and indicate the loadability in recovery con- AND VOLTAGE—IN CONDITION OF TWO GENERATORS TRIPPING
dition is better after shedding identical total amount of load. The
reason can be understood from two aspects:
• in all the four methods compared in our paper, total amount
of load shedding is identical owing to the same disturbance
and same method for total active power imbalance esti-
mation. Therefore, the total load before load shedding and
total load curtailment of all the methods are identical, but
the total power loading after load shedding is different de-
pending on the load shedding distribution methods. The
critical reason lies in the load model of voltage dependence
[9] applied in the analysis and simulation in this work,
more realistic for real power system and also suggested by
the IEEE standard [34]. This decides that larger voltage TABLE IX
magnitude leading to larger power consumption, thus the COMPARISON AMONG LOAD SHEDDING METHODS IN POWER—IN CONDITION
OF TWO GENERATORS TRIPPING
better loadability;
• total load after load shedding closely depends on the
voltage profiles. The better voltage profiles are achieved
by taking into consideration the index together with
reactive power in the step that yields the distribution of
load shedding. Therefore, M4 ensures the best loadability
after load shedding, thanks to the better voltage profiles
at individual load buses. This is achieved by means of the
load shedding distribution that integrates reactive power
compensation.
In summary, the proposed method M4 exhibits the best per-
formance in relation to steady state after load shedding from the H. Test Results in Condition of Simultaneous Tripping of Two
point of view of each proposed index. Generators
To show the applicability of the proposed methods, another
G. Impact of Time Delay Caused by Communication on Load test scenario is studied. In this scenario, the disturbance caused
Shedding Results by tripping of generator 5 and generator 6 simultaneously is
In Table III, the time delay in synchrophasor transmission is assumed. The capacities of some generators are adjusted to
the biggest challenge for load shedding. To better investigate allow for the system collapse in this fault condition. Similarly
this aspect, we have run a sensitivity test to check its impact, to the previous test results, all the load shedding methods
setting different values of time delay in the RTDS simulation. can maintain the stability of the system after disturbance and
As shown in Figs. 9 and 10, as time delay increases, the max- bring the system into a new steady state. In addition, similar
imum deviation of and during the oscillation becomes conclusions can be obtained from Tables VIII and IX, that the
larger. For this test case, the limit of impact from the time delay M4 is still the most effective method at strengthening the new
is between 2 s and 4 s, beyond which the load shedding proce- steady state after executing the same total amount of active
dure may fail. power curtailment.
2046 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 28, NO. 2, MAY 2013
VII. CONCLUSIONS [13] K. Mollah and N. C.-K. Nair, “Coordinated strategy for under-voltage
and under-frequency load shedding,” in Proc. 2010 20th Australasian
To overcome the disadvantages of the existing adaptive Universities Power Engineering Conf. (AUPEC), Dec. 2010, pp. 1–6.
combinational load shedding methods, a load shedding scheme [14] W. Qin, P. Wang, X. Han, and X. Du, “Reactive power aspects in re-
liability assessment of power systems,” IEEE Trans. Power Syst., vol.
based on a new load shedding distribution method, using 26, no. 1, pp. 85–92, Feb. 2011.
combined frequency and voltage stability assessment, is pro- [15] C. M. Affonso, L. C. P. da Silva, F. G. M. Lima, and S. Soares, “MW
posed in this work. The synchrophasor measurements are and MVar management on supply and demand side for meeting voltage
stability margin criteria,” IEEE Trans. Power Syst., vol. 19, no. 3, pp.
used throughout the proposed load shedding process. As an 1538–1545, Aug. 2004.
innovation of this paper, reactive power is used directly into [16] D. Karlsson, M. Hemmingsson, and S. Lindahl, “Wide area system
the reactive power load shedding distribution together with monitoring and control-terminology, phenomena, and solution imple-
mentation strategies,” IEEE Power and Energy Mag., vol. 2, no. 5, pp.
active power load shedding distribution, to address the voltage 68–76, Sep.–Oct. 2004.
stability issue directly and more effectively in the load shed- [17] J. De La Ree, V. Centeno, J. S. Thorp, and A. G. Phadke, “Synchro-
ding process. Also, modal analysis is chosen to address the nized phasor measurement applications in power systems,” IEEE
Trans. Smart Grid, vol. 1, no. 1, pp. 20–27, Jun. 2010.
voltage stability issue more accurately, via a sophisticated and [18] X. Xie, Y. Xin, J. Xiao, J. Wu, and Y. Han, “WAMS applications in
global algorithm, which particularly benefits from phase angle Chinese power systems,” IEEE Power and Energy Mag., vol. 4, no. 1,
measurements of the PMUs. Moreover, the power flow tracing pp. 54–63, Jan.–Feb. 2006.
[19] M. Zima, M. Larsson, P. Korba, C. Rehtanz, and G. Andersson,
algorithm is applied in the load shedding distribution, to select “Design aspects for wide-area monitoring and control systems,” Proc.
the more effective load buses and thus reducing the number IEEE, vol. 93, no. 5, pp. 980–996, May 2005.
of load buses for sharing the total power imbalance. The test [20] A. G. Phadke and J. S. Thorp, Synchronized Phasor Measurements and
results indicate that the improvements on load shedding distri- Their Applications. New York, NY, USA: Springer, 2008.
[21] M. Glavic and T. Van Cutsem, “Wide-area detection of voltage in-
bution of load shedding method can enhance the new steady stability from synchronized phasor measurements. Part I: Principle,”
state of power systems in view of frequency stability, voltage IEEE Trans. Power Syst., vol. 24, no. 3, pp. 1408–1416, Aug. 2009.
stability and loadability, also with a good transient behavior, [22] M. Glavic and T. Van Cutsem, “Wide-area detection of voltage insta-
bility from synchronized phasor measurements. Part II: Simulation re-
when encountering the large disturbances. Thus, for the load sults,” IEEE Trans. Power Syst., vol. 24, no. 3, pp. 1417–1425, Aug.
shedding in practical application, there is a new choice to 2009.
protect the system safely and efficiently. [23] Y. Wang, I. R. Pordanjani, W. Li, W. Xu, T. Chen, E. Vaahedi, and
J. Gurney, “Voltage stability monitoring based on the concept of cou-
pled single-port circuit,” IEEE Trans. Power Syst., vol. 26, no. 4, pp.
REFERENCES 2154–2163, Nov. 2011.
[24] B. Milosevic and M. Begovic, “Voltage-stability protection and con-
[1] P. Kundur et al., IEEE/CIGRE Joint Task Force on Stability Terms trol using a wide-area network of phasor measurements,” IEEE Trans.
and Definitions, “Definition and classification of power system sta- Power Syst., vol. 18, no. 1, pp. 121–127, Feb. 2003.
bility ,” IEEE Trans. Power Systems, vol. 19, no. 3, pp. 1387–1401, [25] R. Niu, Y. Zeng, M. Cheng, and X. Wang, “Study on load-shedding
Aug. 2004. model based on improved power flow tracing method in power system
[2] A. P. Ghaleh, M. Sanaye-Pasand, and A. Saffarian, “Power system risk assessment,” in Proc. 2011 4th Int. Conf. Electric Utility Deregu-
stability enhancement using a new combinational load-shedding algo- lation and Restructuring and Power Technologies (DRPT), Jul. 2011,
rithm,” IET Gen., Transm., Distrib., vol. 5, no. 5, pp. 551–560, May pp. 45–50.
2011. [26] Y. Zhao, N. Zhou, J. Zhou, K. Xie, Y. Liu, and J. Kuang, “A heuristic
[3] A. Saffarian and M. Sanaye-Pasand, “Enhancement of power system approach to local load shedding scheme for reliability assessment of
stability using adaptive combinational load shedding methods,” IEEE bulk power systems,” in Proc. 2005 IEEE/PES Transmission and Dis-
Trans. Power Syst., vol. 26, no. 3, pp. 1010–1020, Aug. 2011. tribution Conf. Exhib.: Asia and Pacific, 2005, pp. 1–5.
[4] P. M. Anderson and M. Mirheydar, “An adaptive method for setting [27] A. G. Phadke and R. M. de Moraes, “The wide world of wide-area
underfrequency load shedding relays,” IEEE Trans. Power Syst., vol. measurement,” IEEE Power and Energy Mag., vol. 6, no. 5, pp. 52–65,
7, no. 2, pp. 647–655, May 1992. Sep.–Oct. 2008.
[5] V. V. Terzija, “Adaptive underfrequency load shedding based on the [28] IEEE Standard for Synchrophasor Measurements for Power Systems,
magnitude of the disturbance estimation,” IEEE Trans. Power Syst., IEEE Std. C37.118.1-2011 (Revision of IEEE Std C37.118-2005), Dec.
vol. 21, no. 3, pp. 1260–1266, Aug. 2006. 2011.
[6] A. V. Kulkarni, W. Gao, and J. Ning, “Study of power system [29] P. Kundur, Power System Stability and Control. New York, NY,
load shedding scheme based on dynamic simulation,” in Proc. 2010 USA: McGraw-Hill, 1994.
IEEE PES Transmission and Distribution Conf. Expo., Apr. 2010, [30] B. Gao, G. K. Morison, and P. Kundur, “Voltage stability evaluation
pp. 1–7. using modal analysis,” IEEE Trans. Power Syst., vol. 7, no. 4, pp.
[7] Z. Zhong, “Power systems frequency dynamic monitoring system de- 1529–1542, Nov. 1992.
sign and applications,” PhD. dissertation, Dept. Elect. Comput. Eng., [31] G. K. Morison, B. Gao, and P. Kundur, “Voltage stability analysis using
Virginia Polytechnic Institute and State Univ., Blacksburg, VA, USA, static and dynamic approaches,” IEEE Trans. Power Syst., vol. 8, no.
Jul. 2005. 3, pp. 1159–1171, Aug. 1993.
[8] U. Rudez and R. Mihalic, “Monitoring the first frequency derivative [32] J. Bialek, “Topological generation and load distribution factors for sup-
to improve adaptive underfrequency load-shedding schemes,” IEEE plement charge allocation in transmission open access,” IEEE Trans.
Trans. Power Syst., vol. 26, no. 2, pp. 839–846, May 2011. Power Syst., vol. 12, no. 3, pp. 1185–1193, Aug. 1997.
[9] U. Rudez and R. Mihalic, “Analysis of underfrequency load shedding [33] B. Zhang, S. Chen, and Z. Yan, Advanced Analysis for Power Network,
using a frequency gradient,” IEEE Trans. Power Del., vol. 26, no. 2, 2nd ed. Beijing, China: Tsinghua Univ. Press, 2007.
pp. 565–575, Apr. 2011. [34] IEEE Guide for the Application of Protective Relays Used for Ab-
[10] H. Seyedi and M. Sanaye-Pasand, “New centralised adaptive load- normal Frequency Load Shedding and Restoration, IEEE Std. C37.
shedding algorithms to mitigate power system blackouts,” IET Gen., 117-2007, Aug. 2007.
Transm., Distrib., vol. 3, no. 1, pp. 99–114, Jan. 2009. [35] M. A. Pai, Energy Function Analysis for Power System Stability.
[11] K. Seethalekshmi, S. N. Singh, and S. C. Srivastava, “A synchrophasor Boston, MA, USA: Kluwer, 1989.
assisted frequency and voltage stability based load shedding scheme [36] “RTDS Manual Set,” RTDS Technologies, Inc., 2005.
for self-healing of power system,” IEEE Trans. Smart Grid, vol. 2, no. [37] “MATLAB User’s Guide,” MathWorks, Inc., 1995.
2, pp. 221–230, Jun. 2011. [38] M. Chenine, K. Zhu, and L. Nordstrom, “Survey on priorities and com-
[12] D. Prasetijo, W. R. Lachs, and D. Sutanto, “A new load shedding munication requirements for PMU-based applications in the Nordic re-
scheme for limiting underfrequency,” IEEE Trans. Power Syst., vol. 9, gion,” in Proc. 2009 IEEE Bucharest PowerTech, Jun.–Jul. 2008, pp.
no. 3, pp. 1371–1378, Aug. 1994. 1–8.
TANG et al.: ADAPTIVE LOAD SHEDDING BASED ON COMBINED FREQUENCY AND VOLTAGE STABILITY ASSESSMENT 2047
[39] M. Chenine and L. Nordstrom, “Modeling and simulation of wide-area Ferdinanda Ponci (M’00–SM’08) received the
communication for centralized PMU-based applications,” IEEE Trans. Ph.D. degree in electrical engineering from Politec-
Power Del., vol. 26, no. 3, pp. 1372–1380, Jul. 2011. nico di Milano, Milano, Italy, in 2002.
[40] M. Reza, “Stability analysis of transmission systems with high penetra- In 2003 she joined the Department of Electrical
tion of distributed generation,” Ph.D. dissertation, electrical engineer, Engineering at the University of South Carolina,
Delft Univ. Technol., Delft, The Netherlands, Dec. 2006. Columbia, SC, USA, as an Assistant Professor. In
2008 she was tenured and promoted to Associate
Professor. In 2009 she joined the E.ON Energy
research Center-Institute for Automation of Com-
Junjie Tang (GS’10) was born in Chongqing, China, plex Power Systems at RWTH Aachen University,
in 1984. He received the B.S. and M.S degrees from Aachen, Germany, where she is currently an apl.
China Agricultural University, China, in 2007 and Professor. Her research activity is focused on agent based applications in
2010, respectively. He is currently pursuing the Ph.D. monitoring and energy management, distributed state estimation, and modeling
degree in the Institute for Automation of Complex and simulation of uncertain systems.
Power Systems of the E.ON Energy Research Center
at RWTH Aachen University, Aachen, Germany.
His research interests include power system
wide-area monitoring, synchronized phasor mea-
surement, power system stability and power system Antonello Monti (M’94–SM’02) received the M.S.
state estimation. and Ph.D. degrees in electrical engineering from Po-
litecnico di Milano, Milano, Italy, in 1989 and 1994,
respectively.
From 1990 to 1994, he was with the research
Junqi Liu (GS’10) received the M.Sc. degree from laboratory of Ansaldo Industria of Milan, designing
the Technische Universität München, München, Ger- the digital control of a large power drives. In 1995,
many, in 2009. He is currently a research associate he joined the Department of Electrical Engineering,
and is pursuing the Ph.D. degree in the Institute for Politecnico di Milano as an Assistant Professor.
Automation of Complex Power Systems of the E.ON From 2000 to 2008, he was an Associate Professor
Energy Research Center at RWTH Aachen Univer- and then a Full Professor with the Department of
sity, Aachen, Germany. Electrical Engineering, University of South Carolina, Columbia, SC, USA. He
His research interests include advanced measure- is currently the Director of the Institute for Automation of Complex Power
ment, control and optimization techniques for next Systems, E.ON Energy Research Center, RWTH Aachen University, Aachen,
generation power systems. Germany.