The document details the megger test results for the 18kV excitation cables at Kariba South Power Station Unit 4 during its commissioning. The test measured insulation resistance between phases and earth, with results ranging from 2.4 to 6 GΩ over 1 minute, indicating good insulation for the cables. The document was produced by M Chibowora for the commissioning tests on Unit 4.
The document details the megger test results for the 18kV excitation cables at Kariba South Power Station Unit 4 during its commissioning. The test measured insulation resistance between phases and earth, with results ranging from 2.4 to 6 GΩ over 1 minute, indicating good insulation for the cables. The document was produced by M Chibowora for the commissioning tests on Unit 4.
The document details the megger test results for the 18kV excitation cables at Kariba South Power Station Unit 4 during its commissioning. The test measured insulation resistance between phases and earth, with results ranging from 2.4 to 6 GΩ over 1 minute, indicating good insulation for the cables. The document was produced by M Chibowora for the commissioning tests on Unit 4.