Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 11

code 1-ground 2-1st.

floor
NAME OF PROJECT : MINIATURE CIRCUIT BREAKERS (MCB) : BREAKING 10 KA AT 415V , 50ºC (BS 3871 PART1)
LOCATION: - RESIDUAL CURRENT CIRCUIT BREAKER (RCCB) :EARTH LEAKAG (30mA,20ms) , BREKING 3KA (BS 4293,3871 PART 1)
DB REF: CODE - - CONTACTORS AND DIGITALTIMERS( BS 775/IEC 158.1): CONTACTORS(240V,50HZ,1PH,16A),TIMER(240V,50HZ,16A RESISTIVE,2.5A INDU
FED FROM:
MOUNTING: SURFACE MOUNTED
NEUTRAL CONNECTION BAR : THE NUMBER OF CABLE TERMINATIONS = THE NUMBER OF INDIVIDUAL CIRCUITS (THE TERMINATIONS SHALL BE OF A SIZE
SUFFICIENT TO LARGEST SIZE CABLE IT IS USED ON AN OUTGOING CIRCUITS)
EARTH CONNECTION BAR : THE NUMBER OF CABLE TERMINATIONS = THE NUMBER OF INDIVIDUAL CIRCUITS (A CABLE CONNECTION BOARD SHALL BE
‫القاصي للستشارات الهندسيه‬
MADE FROM THE EARTH BAR TO THE CABLE GLAND OF THE INCOMING CABLE)
*HEIGHT NOT LESS THAN 1200mm FROM FINISHED FLOOR LEVEL TO BOTTOM OF THE D.B. AND MAIN ISOLATORE : 63 A TP & N ISOLATOR (BS 5420)
MAXIMUM HEIGHT OF THIS D.B. SHALL BE 2200 mm
6 WAYS TP & N INCOMING CABLE : - -
CKT CIRCUIT BREAKER CABLE LOADE LOAD IN WATTS
NO. CONTROL LOCATION
REF A ELCB TYPE SIZE mm2 TYPE LIGHTS W/P LIGHTS FAN R.M.S UNIT CHANDLER
UNIT
CHANDLER
E.W.H UNIT A/C/TONE A/C UNIT COOKER UNIT PUMP UNIT R Y
R - - - - - - - 0 0 0
1 Y - - - - - - - 0 0 0
B - - - - - - - 0 0
R - - - - - - - 0 0 0
2 Y - - - - - - - 0 0 0
B - - - - - - - 0 0
R - - - - - - - 0 0 0
3 Y - - - - - - - 0 0 0
B - - - - - - - 0 0
R - - - - - - - 0 0 0
4 Y - - - - - - - 0 0 0
B - - - - - - - 0 0
R - - - - - - - 0 0 0
5 Y - - - - - - - 0 0 0
B - - - - - - - 0 0
R - - - - - - - 0 0 0
6 Y - - - - - - - 0 0 0
B - - - - - - - 0 0
R - - - - - - - 0 0 0
7 Y - - - - - - - 0 0 0
B - - - - - - - 0 0
R - - - - - - - 0 0 0
8 Y - - - - - - - 0 0 0
B - - - - - - - 0 0
R - - - - - - - 0 0 0
9 Y - - - - - - - 0 0 0
B - - - - - - - 0 0
R - - - - - - - 0 0 0
10 Y - - - - - - - 0 0 0
B - - - - - - - 0 0
R - - - - - - - 0 0 0
11 Y - - - - - - - 0 0 0
B - - - - - - - 0 0
R - - - - - - - 0 0 0
12 Y - - - - - - - 0 0 0
B - - - - - - - 0 0
C - CONTROL ON/OFF FROM MAIN SWITCH IN CONTROL ROOM PHASE LOAD 0 0
PH - PHOTO CELL MODULE WITH MANUAL OVERRIDE SWITCH TOTAL CONNECTED LOAD 0
ABBREVIATIONS: D - 10A THYRISTOR FIRED DIMMING MODULE TOTAL NO. TOTAL TOTAL TOTA
E - EMERGENCY LIGHT LIGHTS W/P
NO. NO. NO. UNIT TOTAL CH. E.W.H TOTAL A/C COOKER PUMP TOTAL
LIGHTS FAN R.M.S
0 0 0 0 0 0 0 0 0 0 0
‫القاصي للس‬
LOAD IN WATTS

0
0
0

TOTAL
0
NAME OF PROJECT : MINIATURE CIRCUIT BREAKERS (MCB) : BREAKING 10 KA AT 415V , 50ºC (BS 3871 PART1)
LOCATION: - RESIDUAL CURRENT CIRCUIT BREAKER (RCCB) :EARTH LEAKAG (30mA,20ms) , BREKING 3KA (BS 4293,3871 PART 1)
DB REF: CODE - - CONTACTORS AND DIGITALTIMERS( BS 775/IEC 158.1): CONTACTORS(240V,50HZ,1PH,16A),TIMER(240V,50HZ,16A RESISTIVE,2.5A INDUCTIVE)
FED FROM:
MOUNTING: SURFACE MOUNTED
NEUTRAL CONNECTION BAR : THE NUMBER OF CABLE TERMINATIONS = THE NUMBER OF INDIVIDUAL CIRCUITS (THE TERMINATIONS SHALL BE OF A SIZE SUFFICIENT
TO LARGEST SIZE CABLE IT IS USED ON AN OUTGOING CIRCUITS)
EARTH CONNECTION BAR : THE NUMBER OF CABLE TERMINATIONS = THE NUMBER OF INDIVIDUAL CIRCUITS (A CABLE CONNECTION BOARD SHALL BE MADE FROM
‫القاصي للستشارات الهندسيه‬
THE EARTH BAR TO THE CABLE GLAND OF THE INCOMING CABLE)
*HEIGHT NOT LESS THAN 1200mm FROM FINISHED FLOOR LEVEL TO BOTTOM OF THE D.B. AND MAIN ISOLATORE : 63 A TP & N ISOLATOR (BS 5420)
MAXIMUM HEIGHT OF THIS D.B. SHALL BE 2200 mm
INCOMING CABLE : 0 -
CKT REF CIRCUIT BREAKER CABLE LOADE LOAD IN WATTS
CONTROL LOCATION UNIT
A ELCB TYPE SIZE mm2 TYPE LIGHTS W/P LIGHTS FAN R.M.S UNIT CHANDLER CHANDLER
E.W.H UNIT A/C/TONE A/C UNIT COOKER UNIT PUMP UNIT

1 - - - - - - - 0 0 0
2 - - - - - - - 0 0 0
3 - - - - - - - 0 0 0
4 - - - - - - - 0 0 0
5 - - - - - - - 0 0 0
6 - - - - - - - 0 0 0
7 - - - - - - - 0 0 0
8 - - - - - - - 0 0 0
9 - - - - - - - 0 0 0
10 - - - - - - - 0 0 0
11 - - - - - - - 0 0 0
12 - - - - - - - 0 0 0
C - CONTROL ON/OFF FROM MAIN SWITCH IN CONTROL ROOM PHASE LOAD
0
PH - PHOTO CELL MODULE WITH MANUAL OVERRIDE SWITCH TOTAL CONNECTED LOAD
ABBREVIATIONS: D - 10A THYRISTOR FIRED DIMMING MODULE TOTAL NO. TOTAL TOTAL TOTA

E - EMERGENCY LIGHT LIGHTS W/P


NO.
LIGHTS
NO.
FAN
NO.
R.M.S
UNIT TOTAL CH. E.W.H TOTAL A/C COOKER PUMP TOTAL
0 0 0 0 0 0 0 0 0 0 0
M.S.B REF LOCATION TYPE

1
2
3
4
5
6
7
8
9
1 10
11
12

LOCATION TYPE

TOTAL A/C TOTAL

TOTAL CONNECTE
MAXIMUM DEMAND
TOTAL CONNECT
MAXIMUM DEMA
%K
2C X 10mm2 + 1C X 10mm2
2C X 16mm2 + 1C X 16mm2
2C X 25mm2 + 1C X16mm2
4C X 16mm2 + 1C X 16mm2
4C X 25mm2 + 1C X 16mm2
4C X 35mm2 + 1C X 16mm2
4C X 50mm2 + 1C X 25mm2
4C X 70mm2 + 1C X 35mm2
4C X 95mm2 + 1C X 50mm2
4C X 120mm2 + 1C X 70mm2
4C X 150mm2 + 1C X 70mm2
4C X 185mm2 + 1C X 95mm2
4C X 240mm2 + 1C X 120mm2
4C X 300mm2 + 1C X 150mm2
4C X 400mm2 + 1C X 240mm2
ELECTRIC LOAD CURRENT LOAD
MCCB
REF CABLE
C.L C.L

ELECTRIC LOAD CURRENT LOAD


MCCB
REF CABLE
C.L M.L C.L M.L

0 0 0 0

TOTAL W/H GENRAL LOAD

L CONNECTED LOAD IN KW (C.L)


MUM DEMAND LOAD IN KW (M.L)
AL CONNECTED LOAD IN KVA
XIMUM DEMAND LOAD IN KVA
% KVA
2 + 1C X 10mm2
2 + 1C X 16mm2
2 + 1C X16mm2
2 + 1C X 16mm2 4C X 10mm2 + 1C X 10mm3
2 + 1C X 16mm2
2 + 1C X 16mm2
2 + 1C X 25mm2
2 + 1C X 35mm2
2 + 1C X 50mm2
2 + 1C X 70mm2
2 + 1C X 70mm2
2 + 1C X 95mm2
2 + 1C X 120mm2
2 + 1C X 150mm2
2 + 1C X 240mm2
BRANCH CABLE
CABLE TYPE LENGTH V.D

MAIN CABLE
CABLE TYPE LENGTH V.D

GENRAL LOAD TOTAL LOAD


0
0
0
0
0
0
V.D

V.D