Professional Documents
Culture Documents
Daikin Wall Mounted
Daikin Wall Mounted
SECRET
INTERNAL USE
PUBLIC
Topic Page
1) Refrigerant Circuit Diagram 3
2) Control Module 10
4) Control Algorithm 23
Page 2
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Refrigerant Circuit Diagram
FTV15/20/25/35/50/60AXV14 - RV15/20/25/35/50/60AXV14 (Cooling)
Page 3
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Refrigerant Circuit Diagram
1.1 Compressor
Description
Port 1 = C= White wire= compressor relay
Port 2 = S= Red wire= compressor capacitor (live)
Rotary
Port 3= R= Blue wire= compressor capacitor (neutral) Page 4
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Refrigerant Circuit Diagram
1.2 Expansion Device
Page 5
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Refrigerant Circuit Diagram
1.3 Heat Exchanger
Page 6
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Refrigerant Circuit Diagram
1.3.2 Condensor coil
• All condenser coil consists of single row except for FTV35 which is 2
rows coil
• All coils are tested against by Nitrogen holding at 609 psig and highly
precise Helium leak test at 235 psig.
Page 7
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Refrigerant Circuit Diagram
1.4 Motor
Motor
Stepping Induction
Eg: Swing motor in Wall Mounted
Page 8
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Refrigerant Circuit Diagram
1.4.1 Indoor Fan Motor
Page 9
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Refrigerant Circuit Diagram
Silicon Controlled Rectifier (SCR) Motor
A silicon-controlled rectifier (or semiconductor-controlled rectifier) is used
to control the voltage peak along with time.
There is a Hall Sensor in the control circuit to detect the RPM of motor rotor and
feedback to main control module PCB
Page 10
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Refrigerant Circuit Diagram
1.4.2 Indoor Stepping Motor
Page 11
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Refrigerant Circuit Diagram
1.4.3 Outdoor Fan Motor
• Type: Permanent Split
Model Type Connection
RV15/20/25 6P 1PH 230V
Capacitor 2.0uF/440V
Index of protection: IP44
Page 12
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Control Module
2.1 Indoor Printed circuit board ( PCB)
• Type: WMJ01B ( applicable for FTV15/20/25/35)
ID coil sensor
Cool/Heat
Timer
Sleep
Tact Switch
PCB software version for manual
On/Off Unit
PCB hardware version Wired controller (optional)
Page 13
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Control Module
• Type: WMJ02B ( applicable for FTV50/60)
ID coil sensor
OD coil sensor
Cool/Heat
Timer
Sleep
Tact Switch
for manual
On/Off Unit
PCB software version
ON/OFF
Swing Fan motor Speed
Mode Selection
Turbo Function
Sleep mode Temperature Setting : Up or Down
Quiet mode
BRC52A62
Page 15
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
3. Handset
3. 2 Wired Handset (optional)
Swing Control
Quiet Mode
Turbo Mode
Mode Selection
Temperature selection
Delay Timer*
On/Off Timer** Sleep Mode
On/Off Button
Fan speed selection
Real Time Clock, RTC
(Enable/disable)
Page 16
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
3. Handset
3.2 Wired Handset (Optional) Indoor
Page 18
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
3. Handset
Page 19
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
3. Handset
Press and hold Timer ON/OFF key for 3 seconds to go into timer setting mode.
(Icon ON 1 or OFF 1 will blink)
NOTE : Each timer (Timer 1 ON or Timer 1 OFF or Timer 2 ON or Timer 2 OFF) will only be set
separately after all 7 steps, if there is no key operation for 5 seconds during setting the timer, it will
automatically exits from setting mode and no changes will be made.
Page 20
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
3. Handset
Page 21
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
3. Handset
Press RTC key one time will activate RTC setting mode. Day will blink.
Press UP or DOWN to select the day.
Press RTC again to confirm the day.
NOTE : RTC will only be set after all 7 steps, if there is no key operation for 5 seconds during setting
the RTC, it will automatically exits from setting mode and no changes will be made on the setting.
Page 22
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
3. Handset
Page 24
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
Page 25
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.1 Cool Mode
• Compressor will cut in if Tr – Ts > 0.5˚C
• Compressor will cut out if Tr < Ts – 1.0˚C
• For manual speed, the indoor fan will run as per user set speed.
• For Auto Fan speed, the indoor fan speed will run as follows:
Page 26
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.2 Cold Start
• Cold start if: Unit restart 2 hours after it has stopped OR during power-on reset
start
• For the first 12 minutes of DRY mode, unit will run under COOL mode with Auto
Fan Speed for 12 minutes OR run Until Tr < Ts – 1°C
• After the first 12 minutes, DRY mode will run either Zone A, B, C or D depending
on temperature condition.
Page 27
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.3 Dry Mode
ZONE A : if Tr - Ts > 2 o C
ON
Compressor
OFF
ON
Low Fan
OFF
Page 28
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.3 Dry Mode
ON
Compressor
OFF
8 min 4 min
ON
Low Fan
OFF
12 Minutes
30 sec 30 sec
Page 29
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.3 Dry Mode
ON
Compressor
OFF
6 min 6 min
ON
Low Fan
OFF
12 Minutes
30 sec 30 sec
Page 30
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.3 Dry Mode
ON
Compressor
OFF
12 Minutes
ON
Low Fan
OFF
30 sec
Page 31
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.4 Sleep Function
• SLEEP function is only available for COOL, HEAT, and AUTO modes.
• Pressing ON/OFF will deactivate/clear the sleep function.
• Function can be set from wired or wireless controller.
• Under SLEEP function, temperature will increase or decrease from the set
temperature with time depending on the mode.
Page 32
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.4 Sleep Function
• Under COOLING mode, temperature will be increased to Tset + 2˚C over time.
Tr 0 1/2 1 2
Hours since sleep set
Ts+2
Ts+1
Ts+1/2
Ts t (hr)
Page 33
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.4 Sleep Function
• Under HEATING mode, temperature will be reduced progressively until
Tset – 3˚C over time.
Page 34
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
• When Quiet function is activate, indoor fan will force to run at low fan speed.
• Any change of fan speed will deactivate this function.
Page 35
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.7 Indoor Fan Control
• Indoor fan speeds are LOW, MEDIUM, HIGH, QUIET, TURBO or AUTO FAN in
COOL mode.
• In FAN mode, only LOW , MEDIUM, QUIET, TURBO and HIGH speed are
available.
Cooling Mode
- Outdoor fan will run when compressor has cut in
Page 36
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.10 Power Up Settings
Page 37
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.10 Power Up Settings
ON/OFF status
Key lock
(for wired control)
• When there is no feedback from ID fan, unit will wait for 10 sec
• After 10 sec, counter in the software will increase by one
• Then LED will start blinking to indicate error of the unit while the compressor and
OD fan are allowed to on depend on thermostat cycle
• If there is no fan speed feedback error continue for another 30 sec, compressor
and OD fan will be forced off
• LED will continue blinking and louver is allowed to operate
Page 39
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.12 Compressor Protection
(a) 3 minutes Minimum OFF time
• Compressor can only cut in after a minimum period of 3 minutes from
the time it cuts off
(b) Compressor Random Restart
• With memory backup selection, compressor cut in 0-64 seconds
randomly after power up again
• Compressor cut in is subjected to thermostat cut in mode
(c) Compressor Minimum Run Time
• Compressor can only cut out after minimum 150 seconds of running in
current mode
•
Compressor can cut out at any time if system is switched to other
modes or other protection sequences
(d) Compressor Internal Overload Protector
ON
Comp & OD Fan OFF
1oC for 1 minute
&
Compressor run > 10 minutes
• Once ID Coil Temp reached 10˚C and above for at least 1 min.
OFF
10oC for 1 minute
• ID = Indoor
• OD = Outdoor
Page 41
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
4. Control Algorithm
4.14 Gas Leak
• Gas leak is declared if ID coil temperature is ≥ 24°C in cooling cycle
• System will check the gas leak mode if compressor run time of 30 minutes is
achieved
• If these condition is met, the system will reconfirm ID coil temperature for 5
minutes in cool mode before declaring gas leak mode
Question?
Page 43
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
Installation
Prepared by
Yeoh Hooi Ling
Technical Engineer
Global UP Marketing Department
Page 44
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC Overview
Topic Page
1) Outline and Dimensions
1.1 R32 Refrigerant 46
1.2 Indoor 48
1.3 Outdoor 50
2) Installation
2.1 Indoor 58
Page 45
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Special care for R32 refrigerant
Storage
• R32 is, according to the General High Pressure Gas Safety Regulation, not a
flammable gas. Likewise other high-pressure gases, R32 should be preserved and
stored in accordance with the standards established by laws and regulations.
(Cool, dark place that is well-ventilated, with a temperature of 40ºC or lower;
Implementation of fall-prevention devices, etc.)
Page 46
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Tools compatibility between R22, R410A and R32 system
*1: When using an R22 type for R32 & R410A, use with a reverse flow preventive adapter.
*2: CFC recovery systems can be shared if they have been certified by the manufacturers to be supporting the relevant CFCs.
*3: R22 recovery cylinder’s pressure capacity: FC1 to FC3 can be used. R32 & R410A recovery cylinder’s pressure capacity:
Only FC3 can be used and shared, but not to be used to recover (charged with) a mixture of R32 & R410A.
*4: Even if a detector supports R22, if the detector does not support HFC (R32, R410A), it cannot be shared.
Page 47
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1.Outline and Dimensions
1.1 Indoor
1.1.1 Wall Mounted
Page 48
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1.Outline and Dimensions
1.1.2 Wall Mounted
Page 49
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1.Outline and Dimensions
1.1.3 Wall Mounted
Page 50
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1.Outline and Dimensions
1.2 Outdoor
Page 51
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1.Outline and Dimensions
1.2 Outdoor
Page 52
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1.Outline and Dimensions
1.2 Outdoor
Page 53
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Special care for R32 refrigerant
Storage
• R32 is, according to the General High Pressure Gas Safety Regulation, not a
flammable gas. Likewise other high-pressure gases, R32 should be preserved and
stored in accordance with the standards established by laws and regulations.
(Cool, dark place that is well-ventilated, with a temperature of 40ºC or lower;
Implementation of fall-prevention devices, etc.)
Page 54
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.1 General Clearance
2.1.1 Wall Mounted
• Key highlights for Indoor Installation:
Page 55
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.1.3 Outdoor
Page 56
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.1.3 Outdoor
Page 57
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2 Procedure
2.2.1 Wall Mounted
2.2.1.1 Mounting Bracket Installation
Page 58
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2 Procedure
2.2.1 Wall Mounted
2.2.1.1 Mounting Bracket Installation
Page 59
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.1.2 Refrigerant piping routing
• Confirm the piping route and bend the pipe accordingly to the correct direction
- Right/Left side piping
- Right/Left bottom piping
- Right/Left back piping
Page 60
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.1.3 Wall mounted hanging
• Ensure that the unit is hooked at the top of the mounting plate.
Page 61
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.2 Refrigerant Piping Installation
2.2.2.1 Piping insulation
Page 62
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.2 Refrigerant Piping Installation
Flare Nut
Page 63
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.2.1 Flare joint connection
Page 64
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Page 65
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.2.2 Purging process
• Before installing the piping to the flare nut, purging is necessary.
Step 1 Step 2
(70psi)
Remark: Do not conduct brazing by supplying other gas such as oxygen and etc
Page 67
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Method of connection
Copper tube
adaptor for N2
replacement
Pressure
regulator
Page 68
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Piping with
Piping without N2
N2 replacement
replacement
Page 69
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Brazing work should be carried out such that the final result is either downwards or
sideways. Upwards direction should be avoided. N2 replacement method is a MUST.
Page 70
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
The IMPORTANT POINTS about Brazing work is the pre-heating of the copper pipes. 80%
of the work is for pre-heating & 20% is for brazing.
Color of the flame : light blue Color of the flame : light red Color of the flame : light pink
copper pipes : reddish black copper pipes: reddish black copper pipes: orange yellow
Temp. of the copper pipes : Temp. of the copper pipes : Temp. of the copper pipes :
around 600~700℃ around 750~850℃ around 850~1000℃
Page 71
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Page 72
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Brazing equipment
Page 74
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
Installation Procedure
Special cautions dealing with R32 unit
Page 75
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Example:
FTV25AXV14 & RV25AXV14 with 19.0m piping length, is installed with 4 L-joint and
1 trap bend.
Equivalent liquid piping length = 19.0m + (4 x 0.18)m + (1 x 1.3)m = 21.02 m
Page 76
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.2.4 Piping condition
Page 77
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Pipe Storage
Page 78
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
• Problem :
– Moisture, dust, sand ect…
can enter the pipe
– Pipes can be crushed by stepping
onto them
• Recommendation :
– Seal the pipes
– Store pipes on a stand
Page 79
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.2.5 Drain Hose Installation
Page 80
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Page 81
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.2.6 Power Supply Connection
Page 82
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Page 83
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Page 84
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Page 85
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Page 86
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
Incorrect power supply wiring connection at terminal block
Evaporator
Coil
Assembly
Control Box
Joint
Page 87
Wire
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.2.7 Unit and mounting plate installation
• Unit is clipped at the bottom to the mounting plate to ensure the unit is
mounted properly.
Page 88
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.2.8 Vacuuming
• Except for the outdoor unit which is pre-charged with refrigerant, the
indoor unit and the refrigerant connection pipes must be vacuumed to
remove moisture that remains in the refrigerant piping.
Page 89
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.2.9 Charging
For charging R32, following equipment is required:
Flammable gas Gas under pressure No smoking Wear gloves Wear eye
protection
• Weighing Scale
Remark: Leak detector is not considered liable after some time. Also, leak detector should be placed
on the ground because this is were R32 will accumulate.
Under ASHRAE 34 and draft ISO 817, R32 is a slightly flammable gas
Page 91
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
• Before starting the charging, the hoses from the manifold must be vacuumed to
prevent moisture or non-condensables from entering the unit.
• To make sure the correct amount of R32 is charged, a weighing scale is required.
F-gas regulation: for all
refrigerants, a logging should
be done. We need to indicate
how much refrigerant we
removed from the cylinder
and in which unit it was
charged.
Step 4: Open the gas cylinder and low pressure charging valve.
Step 5: When the required refrigerant quantity is pumped into the unit, close
the low pressure side and the gas cylinder valve.
Step 6: Disconnect the service hose from service port. Put back the service
port cap.
• As for R32, it can be charge either in gas form or liquid form as R32 comes
from one component property.
Page 94
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.2.10 Piping Insulation
Page 95
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Installation
2.2.2.11 Leak Test
Page 96
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
Question?
Page 97
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
Topic Page
1) Fault Diagnosis
1.1 Error Code 3
1.2 Components 18
2) Servicing
2.1 Indoor 28
2.1.1 Floor Standing 30
2.1.2 Wall Mounted 71
2.2 Outdoor 98
Page 99
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.1 Error Code
Page 100
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.2 Error Code
Page 101
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.1 Error Code
E1 : Room Sensor Open or Short E2 : Indoor Coil Sensor Open or Short
E3 : Outdoor Coil Sensor Open
Check the Room Sensor
connector/Indoor Coil Sensor connector
Yes
Disconnected or loose? Reconnect
No
Check sensor wire
condition
Yes
Broken/Loose out Repair or replace wire
Page 102
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.1 Error Code
E1 : Room Sensor Open or Short
E2 : Indoor Coil Sensor Open or Short
E3 : Outdoor Coil Sensor Open
No
Check resistance value
*refer to resistance-
temperature table
No
Within specification? Replace Room
Sensor/ID/OD Coil
Sensor
Yes
Replace PCB
Page 103
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1) Fault Diagnosis
1.1 Error Code
Resistance – Temperature Characteristics (spec 10kΩat 25 ⁰C)
Page 104
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.1 Error Code
E4 : Compressor Overload Protection/Indoor Coil Sensor
Short/Outdoor coil sensor short
Check the compressor
Running ampere
normal? No
Refer to technical Replace compressor
manual or sticker serial
no.
Yes
Page 105
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.1 Error Code
E4 : Compressor Overload Protection/Indoor Coil Sensor
Short/Outdoor coil sensor short
No
Within acceptable Replace ID Coil Sensor
range?
Yes
No
Fan motor running? Further inspection on
fan motor fault
Yes
Page 106
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.1 Error Code
E4 : Compressor Overload Protection/Indoor Coil Sensor
Short/Outdoor coil sensor short
Yes
Yes
Any obstacles? Remove obstacles
No
Within acceptable No
range? Replace compressor
Yes
Replace PCB
Page 108
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
E4 : Compressor Overload Protection/Indoor Coil Sensor
Short/Outdoor coil sensor short
Page 109
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.1 Error Code
E5 : Gas Leak
Check indoor coil temperature
Yes
No
Check system pressure Within acceptable Change indoor
range? coil sensor
Remark: Refer to resistance- temperature
table in page 96
Yes
Within acceptable Yes
range? (low side: 100- Change PCB
130psig)
No
Page 110
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.1 Error Code
E5 : Gas Leak
No
Yes
Leaking? Repair leak spot and
top up refrigerant
No Remark: Refer to Leak test under Installation
Replace PCB
Page 111
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.1 Error Code
E8 : Hardware Error (Tact Switch Pin Short):
Yes
Jam? (unable to press) Replace tact switch
pin
No
Replace PCB
Page 112
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.1 Error Code
E9 : No feedback from Indoor fan
Check the feedback fan cable and fan
motor cable condition
Yes
Disconnected or loose? Reconnect
No
Check fan motor condition Remark: Refer SCR fan motor troubleshooting
steps
No
Okay? Replace fan motor
Yes
Replace PCB
Page 113
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.2 Component Troubleshooting
1.2.1 Compressor
Wiring connection is No
Reconnect the wiring
correct?
Yes
Check the terminal wire
No
Burnt?
Yes
Page 114
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
Yes No
Is the compressor
shorted?
Is the running ampere No
Yes If the reading is OL, it
value tally with the
represents OPEN
running ampere value
meaning the
in the technical
compressor is not
manual?
shorted.
Replace Replace
compressor compressor
No Yes
Page 115
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
No Yes
Yes
Wiring connection is No
Reconnect the wiring
correct?
Yes
Check on the physical appearance
No
Page 118
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
Silicon Controlled
Permanent Split motor No No Rectified motor
Check on fan motor short body. Check fan motor continuity. Using
Using a multimeter, touch the black multimeter, use the probe to touch
probe to any connection terminal and Live(L) & Neutral(N)
red probe to the body of fan motor.
Yes
Any ‘peep’ sound?
Replace fan
motor
No
Page 119
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
No
No
Check on fan motor winding. Check on fan motor winding.
Using a multimeter, touch the black
and red probes to two terminals
simultaneously.
For three phase fan motor, note the
resistance for terminal R-S, R-T, S-T
should be close to one another. No
Within specification?
Replace Fan
Motor
No
Page 122
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.2 Component Troubleshooting
1.2.3 Swing Motor
Wiring connection is No
Reconnect the wiring
correct?
Yes
Check on the physical appearance
No
Page 123
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
No
Is the winding No
resistance for each Replace swing motor
phase 200Ω ±7% ?
Yes
1 RED (Common)
2 ORANGE
3 YELLOW
4 PINK
5 BLUE
Page 124
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
1. Fault Diagnosis
1.2 Component Troubleshooting
1.2.3 Control Module PCB
Items which can be inspected at site:
Item Inspection Action Photo
Physical Check if there is any Replace component on
Appearance component lifted, PCB and reconnect the
broken, burnt, or cable
cable loosen
Capacitor Measure the Compare value to
capacitance using a capacitor specification. If
multimeter out of range, replace
capacitor
Fuse Check on continuity If no continuity, replace
fuse
Page 125
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2 Wall Mounted Exploded View
Page 126
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2 Wall Mounted Exploded View
No Item No Item
1 Assy. Chasis 19 Fan Motor
2 Assy Air Discharge Housing 20 Blower
3 Assy Louver 21 Fan Bush
4 Assy Mounting Plate 22 Motor Mounting Plate 1
5 Drain Hose 23 Motor Mounting Plate 2
6 Drain Pan 24 Motor Cover
7 Service Cover 25 Air Swing Motor
8 Shield Plate
9 Assy Front Grille
10 Front Panel
11 Front Grille
12 Air Filter
13 Air Filter, Photocatalyst
14 Air Filter, Bio
15 Dust Collecting Element Frame
16 Assy Indoor Coil
17 Assy Control Box
18 Control Box Cover
Page 127
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
Note : For all the actions below, kindly ensure the electrical power is turned OFF
2.1.2.1 Air Filter
Step 2: Filter is slotted onto the front grille. Lift up the filter to remove it.
Note : It is advisable to clean the filter regularly (recommended every two weeks
Page 128
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.2 Unit Casing / Front Grille
FTV 50/60
FTV 15/20/25/35
Step 1: Pull out the front panel cover and the louver.
Screw
Page 130
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.2 Unit Casing / Front Grille
Page 131
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.2 Unit Casing / Front Grille
Page 133
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.3 Control Box
Control box is slotted in at the end of the chassis or bottom frame and only
attached by a screw.
Page 134
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
Step 7: Remove the quick connectors for coil sensor, fan feedback cable, fan
motor cable, and swing motor cable from the PCB. PCB able to slot
out as shown in below figure.
Fan Motor
Swing Motor
Fan feedback
Coil sensor
Page 135
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.3 Control Box
Step 8: Remove the earth cable attached to the coil surface by a screw.
Step 9: Remove the screw indicated below to detach the entire control box.
Page 136
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.4 Coil Sensor
Step 1: Pull out the front panel cover.
Step 2: Remove no. screws indicated.
Step 3: Remove the service cover.
Coil sensor
Page 137
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.4 Coil Sensor
Step 8: Remove the coil sensor from the u-bend indicated.
Page 138
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.5 Swing Motor
Step 1: Pull out the front panel cover.
Step 2: Remove no. screws indicated.
Step 3: Remove the service cover.
Swing Motor
Page 139
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.5 Swing Motor
Step 8: Swing motor can be removed by removing the screw indicated below.
Page 140
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.6 Drain Pan
Step 1: Pull out the front panel cover.
Step 2: Remove no. screws indicated.
Step 3: Remove the service cover.
Step 7: Remove the quick connectors for coil sensor, fan feedback cable, fan
motor cable, and swing motor cable from the PCB.
Step 8: Remove the earth cable attached to the coil surface by a screw.
Step 9: Remove the screw indicated below to detach the entire control box.
Page 141
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.6 Drain Pan
Drain Pan is attached to the unit using two hook.
Step 10: Remove both hook on the left and right of the unit to remove the drain pan.
Unit - LEFT
Unit - RIGHT
Step 7: Remove the quick connectors for coil sensor, fan feedback cable, fan
motor cable, and swing motor cable from the PCB.
Step 8: Remove the earth cable attached to the coil surface by a screw.
Step 9: Remove the screw indicated below to detach the entire control box.
Page 143
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.7 Coil
Step 10: Remove both hook on the left and right of the unit to remove the drain pan.
Step 11: Unscrew the two screws on the fan motor cover.
Page 144
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.7 Coil
Step 12: Unscrew the screw located at the left hand side of the coil
Page 145
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.7 Coil
Step 13: Slot out the coil from the chassis/bottom frame and clip before removing it.
Page 146
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.7 Coil
After removing the coil, we can access the fan motor and the blower.
Blower
Fan Motor
Page 147
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.8 Fan Motor and Blower
Step 1: Pull out the front panel cover.
Step 2: Remove no. screws indicated.
Step 3: Remove the service cover.
Step 7: Remove the quick connectors for coil sensor, fan feedback cable, fan
motor cable, and swing motor cable from the PCB.
Step 8: Remove the earth cable attached to the coil surface by a screw.
Step 9: Remove the screw indicated below to detach the entire control box.
Page 148
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.8 Fan Motor and Blower
Step 10: Remove both hook on the left and right of the unit to remove the drain
pan.
Step 11: Unscrew the two screws on the fan motor cover.
Step 12: Unscrew the screw located at the left hand side of the coil
Step 13: Slot out the coil from the chassis/bottom frame and clip before removing it.
Page 149
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.8 Fan Motor and Blower
Fan Motor and Blower can be removed simultaneously by removing a screw.
Step 14: Remove the screw that attach the fan motor shaft to the blower
Page 150
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.9 Louver
Step 1: Open up the louver.
Page 151
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.1.2.9 Louver
Step 2: Slightly bend the louver to detach the louver from the hook.
Page 152
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2 Outdoor
RV50/60
RV15/20/25
RV35
Page 153
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.1 Electrical Components (Control Box)
Step 1: Remove 2 screw from terminal cover. Terminal cover can be remove by slot up
from service panel. Wiring can be carried out to terminal block.
RV15/20/25
Page 154
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.1 Electrical Components (Control Box)
Step 1: Remove 1 screw from terminal cover . Terminal cover can be remove by slot up
from service panel. Wiring can be carried out to terminal block.
RV35
Page 155
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.1 Electrical Components (Control Box)
Step 1: Remove 1 screw from terminal cover and slot up from service panel. Wiring can be
carried out to terminal block.
RV50/60
Page 156
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.1 Electrical Components (Control Box)
Step 2: Remove 2 screws from left side top panel, 3 screws from right side top
panel and 1 screw from back side top panel. Remove top panel.
Fan motor
capacitor
Compressor
capacitor
Fan motor
capacitor
Compressor
capacitor
Fan motor
capacitor
Compressor
capacitor
RV50/60 Page 159
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.2 Compressor
Step 1: Remove 2 screw from terminal cover and pull it out from service panel.
Wiring can be carried out to terminal block.
Step 2: Remove 2 screws from left side top panel, 3 screws from right side top panel
and 1 screw from back side top panel.
Step 3: Remove 10 screws from front panel and service panel as indicated below.
RV15/20/25
Page 160
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.2 Compressor
Step 4: Pump down the system/recover refrigerant.
Step 5: Remove power wiring connection from the compressor terminal.
Step 6: Unbraze the compressor suction and discharge copper pipe.
Step 7: Remove 3 compressor nut and washer.
Discharge pipe
Suction pipe
Compressor nut
and washer
RV15/20/25
Page 161
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.2 Compressor
Step 1: Remove 1 screw from terminal cover and pull it out from service panel.
Wiring can be carried out to terminal block.
Step 2: Remove 2 screws from left side top panel and 1 screws from right side top
Step 3: Remove 10 screws from front panel and service panel as indicated below.
RV35
Page 162
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.2 Compressor
Step 4: Pump down the system/recover refrigerant.
Step 5: Remove power wiring connection from the compressor terminal.
Step 6: Unbraze the compressor suction and discharge copper pipe.
Step 7: Remove 3 compressor nut and washer.
Discharge pipe
Suction pipe
Compressor nut
and washer
RV35
Page 163
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.2 Compressor
Step 1: Remove 1 screw from terminal cover and pull it out from service panel.
Wiring can be carried out to terminal block.
Step 2: Remove 2 screws from front side top panel, 3 screws from right side top
panel, 3 screws from back top panel and 2 screws from left side top panel.
Step 3: Remove 9 screws from front panel and service panel as indicated below.
RV50/60
Page 164
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.2 Compressor
Step 4: Pump down the system/recover refrigerant.
Step 5: Remove power wiring connection from the compressor terminal.
Step 6: Unbraze the compressor suction and discharge copper pipe.
Step 7: Remove 3 compressor nut and washer.
Suction pipe
Discharge pipe
Compressor nut
and washer
RV50/60
Page 165
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.3 Capillary Tube
Step 1: Remove 2 screw from terminal cover and pull it out from service panel. Wiring
can be carried out to terminal block.
Step 2: Remove 2 screws from left side top panel, 3 screws from right side top panel
and 1 screw from back side top panel.
Step 3: Remove 10 screws from front panel and service panel as indicated below.
(refer model RV15/20/25)
Step 4: Pump down the system/recover refrigerant.
Step 5: Unbraze capillary tube
Capillary tube
RV15/20/25
Page 166
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.3 Capillary Tube
Step 1: Remove 2 screw from terminal cover and pull it out from service panel. Wiring
can be carried out to terminal block.
Step 2: Remove 2 screws from left side top panel, 3 screws from right side top panel
and 1 screw from back side top panel.
Step 3: Remove 10 screws from front panel and service panel as indicated below.
(refer model 35)
Step 4: Pump down the system/recover refrigerant.
Step 5: Unbraze capillary tube
Capillary tube
RV35
Page 167
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.3 Capillary Tube
Step 1: Remove 2 screw from terminal cover and pull it out from service panel. Wiring
can be carried out to terminal block.
Step 2: Remove 2 screws from left side top panel, 3 screws from right side top panel
and 1 screw from back side top panel.
Step 3: Remove 9 screws from front panel and service panel as indicated below.
(refer model 50/60)
Step 4: Pump down the system/recover refrigerant.
Step 5: Unbraze capillary tube
Capillary tube
RV50/60
Page 168
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.4 Coil
Step 1: Remove 2 screw from terminal cover and pull it out from service panel. Wiring
can be carried out to terminal block.
Step 2: Remove 2 screws from left side top panel, 3 screws from right side top panel and
1 screw from back side top panel.
Step 3: Remove 10 screws from front panel and service panel as indicated below.
(refer model RV15/20/25)
Step 4: Pump down the system/recover refrigerant.
Step 5: Unbraze the condenser coil inlet and coil outlet copper pipe to remove the coil
RV35
Page 170
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.4 Coil
Step 1: Remove 2 screw from terminal cover and pull it out from service panel. Wiring
can be carried out to terminal block.
Step 2: Remove 2 screws from left side top panel, 3 screws from right side top panel and
1 screw from back side top panel.
Step 3: Remove 9 screws from front panel and service panel as indicated below.
(refer model 50/60)
Step 4: Pump down the system/recover refrigerant.
Step 5: Unbraze the condenser coil inlet and coil outlet copper pipe to remove the coil
RV50/60
Page 171
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.6 Fan Guard
Step 1: Remove 4 screws which attach the coil guard to the front panel.
Page 172
TOP SECRET DAIKIN
SECRET
INTERNAL USE
PUBLIC
2. Servicing
2.2.7 Propeller Fan
Step 1: Remove 4 screws which attach the coil guard to the front panel.
Step 2 : Remove the nut attached to the body of the fan.
Step 3 : Fan can be removed by pulling the fan horizontally out.
Fan motor
capacitor
Fan motor
(purple color=live)
Step 5 : Remove 4 screws indicated below to remove the fan motor from the bracket.
Question?
Page 176