ELECTRICAL RESEARCH AND DEVELOPMENT ASSOCIATION

(Accredited by the National Accreditation Board forTestlng and Calibration Laboratories, Govt. of India)
ERDA Road, Makarpura Industrial Estate, Vadodara-390 010, India.
EPABX : +91 (0265) 2642942,2642964,2642377,3043128/29/30/31/33

Certificate No. : T-0071


Fax :+91 (0265)2638382
E-mail: erda@erda.org
Web : http://www.erda.org

TEST REPORT
Sheet 1 of 4
NAME & ADDRESS OF CUSTOMER TEST REPORT NO. : LSWG/937
DATE: 22/03/2013
ABB LIMITED
CUSTOMER REF. NO. DATED
PP-HV DISCONNECTOR,
Nil 11/03/2013
MANEJA WORKS, MANEJA,
DATE OF SAMPLE DATE OF
VADODARA - 390013
RECEIPT TESTING
GUJARAT
INDIA 11/03/2013 12/03/2013 to
14/03/2013
SAMPLE DESCRIPTION SAMPLE IDENTIFICATION

72.5 kV, 1600A HORIZONTAL ERDA sample code no. :


CENTRE BREAK DISCONNECTOR LSWGW001010826/01
No. of poles : One
Type designation: SDF72.5
Rated voltage 72.5 kV
Rated current 1600 Amp
Serial No. : 3600024535-10-001
Rated frequency 50/60 Hz
Rated power frequency withstand voltage:
Manufacturer's name:
Phase to earth : 165 kV
M/s. ASS Limited, Vadodara
Across isolating distances: 175 kV
Rated impulse withstand voltage:
Drawing No. : As per list of drawing no.
Phase to earth : 375 kV
1HYD990402-002 (Rev. A) (Sh. No.1)
Across isolating distances: 440 kV
[Total 4 sheets]
Rated short time withstand current
& its duration : 40 kA rms for 3 see.
Quantity (tested) : 01 No.
TEST DETAILS TEST SPECIFICATION
1) Temperature rise tests (CI. No. 6.5) IEC 62271-102 : 2012
IEC 62271-1 : 2011

ENCLOSURE: 1) Photograph no. 1010826/01/ A


2) Drawing Nos. As per list of drawing no. 1HYD990402-002
(Rev. A) (Sh. No.1) [Total 4 sheets]

TEST WITNESSED BY : i) Mr. Arabinda Shattacherjee,


ii) Mr. Darshan Trivedi of M/s. ASS Limited, Vadodara.

REMARKS: Sample conforms to the requirement of the standard for

s:
temperature-rise test.

P~BV Che~ Approved By


Note: 1. This report relates only to the particular sample received by ERDA in good condition at ERDA.
2. This report can not be reproduced in part under any circumstances.
3. Publication of this report requires prior permission in writing from director, ERDA.
4. Only the tests asked for by the customer have been carried out.
5. In case of any dispute, Vadodara will be the exclusive jurisdiction & shall be construed as
where the cause has arised.
Caution: ERDA is not responsible for the authenticity of photocopied or reproduced test reports.
ERDA provides support to customers for verification of the authenticity of test reports issue
by ERDA.

.,