Professional Documents
Culture Documents
ENI - Well Testing Service Technical Specification
ENI - Well Testing Service Technical Specification
1
Eni S.p.A.
DEPARTMENT ACTIVITY' DEPT. TYPE
E&P Division OF 38
STAP A 1 SS 1728
TITLE
DISTRIBUTION LIST
ARCO
RIAP
TEPE
TEOP
GEOP
APGI
Working Group
E. Beretta TEOP
G. Petronio TEOP
G. Albasi ARCO
L. Pilia ARCO
E. Incecchi ARCO
P. Magarini STAP
A. Parmigiani STAP
INDEX
1. SCOPE................................................................................................................................ 5
3. RESPONSIBILITIES........................................................................................................... 6
4. DEFINITIONS ..................................................................................................................... 6
7. DOCUMENTATION .......................................................................................................... 32
1. SCOPE
The scope of this specification is to define personnel, down hole and surface equipment
minimum requirements for DST, Surface Equipment, Bottom Hole Data Acquisition
Service and Sampling Service.
2. APPLICABLE DOCUMENTS
The service provided shall comply with the following documents:
• STAP M1M 4001 Procedures to determine the Wire Line (Slick and
Electrical) material suitable to the operating
environment.
• ENI AGIP 310520 SG22 (*) Integrated HSE-QR Requirements for Drilling,
Completion and Exploration Services.
• EN 60079-10 Electrical Apparatus for Explosive Gas
Atmospheres Part 10 (if not otherwise stated in
the Project Specification).
• PED 97/23/CE Pressure Equipment Directive (for
European activities and if not otherwise stated in
the Project Specification).
• API RP 1004 Bottom Loading and Vapour Recovery for MC-306
& DOT-406 Tank Motor Vehicles
• API RP7G Recommended Practice for Drill Stem Design and
Operating Limits.
• ASME Sez. VIII Div 1& 2 Rules of construction of pressure vessel. (IF NOT
otherwise stated in project specification – see also
PED Directive).
• API STD 2000 Venting Atmospheric and Low Pressure Storage
Tanks.
• ISO 11960 Specification for Casing and Tubing.
• ISO 11961 Drill pipe with well-on tool joint.
• API SPEC 5D Specification for Drill Pipe.
• API SPEC 7 Specification for Rotary Drilling Equipment.
• API RP 44 Sampling Petroleum Reservoir Fluids.
• NACE Std MR0175 Standard Material Requirements - Sulphide Stress
Cracking Resistant Metallic Materials for Oil field
Equipment.
• ISO 10432 Down-hole equipment - Subsurface safety valve
equipment.
• ISO 10423 Wellhead and Christmas Tree.
• ISO 14310 Packers and Bridge Plugs.
NOTE: If in the document it is indicated an ISO standard that is not yet issued, then the
corresponding latest edition of the API specification shall be used. All documents are
intended as the latest revision unless specified otherwise.
The document ENI AGIP 310520 SG22, marked with (*), can be replaced by equivalent
document issued by Affiliated Companies and included in the PROJECT
SPECIFICATION.
SPEO IDENTIFICATION CODE PAG 6 OF 38
Eni S.p.A.
E&P Division REVISION
STAP-A-1-SS-1728 0 1
3. RESPONSIBILITIES
The CONTRACTOR is responsible for the compliance with the requirements set forth in
this specification and with applicable laws and regulations.
Nothing in this specification shall relieve the CONTRACTOR of the responsibility for
performing, in addition to the requirements of this specification, such analysis, tests,
standard inspections and other activities those he considers necessary to ensure that
the product, and workmanship are satisfactory for the service intended, or as may be
required by common usage or good practice.
Modification to the requirements of this specification may be proposed by the
CONTRACTOR during the bidding phase, providing they are submitted to Company for
approval, with the support of proper documentation.
3.1 HSE-QR
All the activities shall be carried out with minimum impact on the environment and
maximum care of health and safety of all concerned, directly or indirectly, with the
activities.
4. DEFINITIONS
The service includes the supply of all equipment, vehicles, personnel, technical
assistance and documentation necessary to carry out Well Testing operations with
Bottom Hole and Surface Well Testing technology at our sites on land and off shore.
The Well testing services are grouped in 4 categories:
PERSONNEL
The number and the qualification of Contractor personnel shall be defined according to
the program.
The Contractor shall provide for all the personnel detailed Professional Curriculum
indicating background, training and specific experience.
During the whole period of contract validity before the employ of personnel not included
in the bidding documents the Contractor shall send Professional Curriculum to the
Company for acceptance.
The Well Test team composition working on our wells will be approved by our District
Well Area Superintendent at the moment of the call and will be formed by professional
specialists.
The CONTRACTOR shall all time be responsible for ensuring that the personnel
provided to perform the services are appropriately qualified, hold valid certifications , are
adequately trained including “training for handling of acid and solvent”, and that the
validity of such qualifications, certifications and training are maintained throughout the
Contract Period.
In addition, for the personnel working at rig site, the following courses are requested:
Survival at Sea
All personnel working on an offshore rig, must attend a specific “survival at sea” training
course. This course shall be held at training centres recognised by the Company.
Fire Fighting
All personnel must receive training in Basic Fire Fighting.
First Aid
All personnel must receive basic training in First Aid technique.
The personnel shall be fully aknowledged of the applicable procedures and operating
instructions and must be able to speak, read and write the language indicated in the
“Personnel Qualification Card”.
The Contractor shall provide to Company the professional curricula for all personnel he
intends to use, indicating background, training and work experience.
During the period of applicability of the contract, before any operative personnel are
replaced, the Contractor shall send updated Professional Curriculum (a) to the Company
of said substitute(s).
5.1.1.2 EQUIPMENT
GENERAL
• The equipment shall be for sour service environment.
• The equipment selection shall be made in a way to maintain safety conditions
inside the well during the whole well testing period.
• All components shall be designed to be easy and safely handled on deck and rig
floor.
• The equipment shall be equipped with means to check for and safely release any
internal pressure build-up caused by down hole use or pressure testing.
• All down hole tools shall be “FULL BORE” type and internal profiles without
sharp edges.
• For equipment to be used into 7” casing, the minimum I.D. shall be not less than
2.25”.
5.1.1.2.9 JAR
• Shall be Hydraulic type.
• Shall be possible to repeat the jarring operation as much time as needed.
SPEO IDENTIFICATION CODE PAG 10 OF 38
Eni S.p.A.
E&P Division REVISION
STAP-A-1-SS-1728 0 1
5.1.1.2.10 CROSSOVERS
All the crossovers necessary to connect the required DOWN HOLE TESTING TOOLS to
the COMPANY tubing test string
5.1.2.2 EQUIPMENT
• Sub sea tree shall be able to cut coiled tubing with 7/16” logging cable inside.
• The Control hose bundle shall be one single length without intermediate
connections or splicing.
• Sub sea tree shall allow a chemical injection and the Control hose bundle shall
integrally include one injection line equipped with double check valves.
• A Remote Station to operate an emergency sub sea tree shut-in shall be
provided.
• Shall be possible to unlatch the sub sea tree under tension, however shall be no
possible to accidentally unlatch while running in hole.
• In case of hydraulic power lack, a mechanical back-up releasing system to
operate the sub sea tree shall be provided.
• In water depth greater than 300 meters, an additional device to offer a faster
response should be provided.
• In case of loss of hydraulic control, shall be possible to kill the well by pumping
from above.
5.1.2.2.5 CROSSOVERS
All the crossovers necessary to connect the required DOWN HOLE TESTING TOOLS to
the COMPANY tubing test string
SPEO IDENTIFICATION CODE PAG 12 OF 38
Eni S.p.A.
E&P Division REVISION
STAP-A-1-SS-1728 0 1
5.2.1 PERSONNEL
The presence of a Well Testing Supervisor at well site is mandatory in case of oil test
with two separation steps and oil storage.
5.2.1.3 OPERATOR
• Experience: not less than 4 (four) years of well test job; must have carried out
well test operations on gas wells, sour gas wells and oil wells with STHP up to
10000 psi.
• Education: not below Vocational School Diploma.
• Specialisation Courses: basic well test.
5.2.1.4 HELPER
• Experience: not required
• Education: not below secondary school.
• Specialisation Courses: basic well test.
5.2.2 EQUIPMENT
The surface equipment shall be able to receive high pressure well fluid, perform 3 phase
separation of the fluid and accurately measure the individual flow stream.
Produced water and hydrocarbon shall be disposed off without spill to ground or sea.
Contractor shall provide all the equipment needed and adequate to carry out the service,
including radio headset (adequate to the work area, zone 1, 2) for the main personnel
involved in the operation. All the equipment must be H2S service. The equipment shall
be designed to ensure safety operations and shall be certified in accordance with the
laws and regulations applicable in the Country where the operations will be performed.
The main equipments that can be used for the service are described below.
SPEO IDENTIFICATION CODE PAG 13 OF 38
Eni S.p.A.
E&P Division REVISION
STAP-A-1-SS-1728 0 1
• Control console including air driven pump, hydraulic tank, storage reels with air
hoses and hydraulic hoses for actuators.
• Control system shall be equipped with minimum two remote stations for
emergency closure and shall be possible to interface it with rig’s or plant’s
Emergency Shut Down (ESD/PSD) system.
• On request the Control system shall include a control console for emergency
closure of Tubing Safety Valve (inside BOP) or of a SCSSV (in case of
completed well). Shall be possible to interface it with rig’s or plant’s Emergency
Shut Down (ESD/PSD) system.
5.2.2.5 HEATER
• Shall be arranged with an internal heating source, composed by a combustion
chamber, in contact but hydraulically separated with the vessel.
• Bleeding off coils for the purpose of changing choke shall be possible through
isolation valves.
• The choke box shall be manufactured to receive both fixed choke and adjustable
choke. The adjustable choke assembly shall have pressure capabilities for the
purpose of testing high pressure coil tubing.
• Shall be equipped with a temperature control system regulating the internal
heating source
• Shall be equipped with pressure and temperature sensors up and down stream
of choke.
• Shall be equipped with by-pass line with double valve arrangement together with
isolation valves on inlet and outlet of coils.
• The internal heating source shall have burners able to be fed on diesel or gas
from the well. The pilot light must be fed by an independent source.
• The starter for both pilot light and burners shall be electric. The electric circuit
shall be explosion proof.
• Shall be equipped with gas detector and combustion control device, in order to
prevent the starting of burners in presence of gas inside the combustion
chamber. Shall be provided with fan in order to flow the combustion chamber.
• Shall have a minimum of two coils with interconnection by means of a choke box
either submerged inside the vessel or by an external connection.
• For Well Testing on Oil well a heater without choke box could be requested.
boiler. By preference this detection shall be sampled from the main vessel before
the gas is allowed to enter into the condensate system.
• If the secondary coil has a lower pressure rating than the primary coil and or the
down stream valve, the coil shall be equipped with a pressure relief device.
• The steam inlet shall be equipped with a non return valve.
• The Heat Exchanger shall have a minimum of two coils with interconnection by
means of a choke box either submerged inside the vessel or by an external
connection.
• For Well Testing on Oil well a Heat Exchanger without choke box could be
requested.
5.2.2.8 COOLER
• The cooler shall be arranged with an external cooling source, preferably water.
• The cooler shall have coils with a surface contact area enable to cool the
designed flow rate.
• Shall be equipped with a temperature control system regulating the external
cooling source based on the required well fluid discharge temperature.
• Shall be equipped with pressure and temperature sensors up and down stream.
• Shall be equipped with by pass line with double valve arrangement together with
isolation valves on inlet and outlet of coils.
• The flow control instruments shall be operated with either air or gas.
• Shall have a trim suitable for the required service.
5.2.2.19 PIPING
The PIPING includes all the low pressure pipes used down stream the choke manifold
or down stream the choke inside the heater / heat exchanger (if the pressure drop is
obtained in the heater / heat exchanger) to connect all the CONTRACTOR’S
equipment.
All the piping shall have a trim and diameter suitable for the required service
5.2.2.24 BOOM
• The modular type is the preferred option.
• It is used mainly in offshore application to move the burner as far as possible
from the platform border.
• The length of the boom shall be accepted by the rig contractor.
• It must provide to carry out the oil, gas and water pipes and the electric lines
from the platform to the burner.
Type B
• Connection ‘4" API Coupler’ as per API RP1004.
• A dedicated line for recovering of vapour as per API RP1004 can also be
required.
In case of special requirement refer to the Laboratory for Analysis at Rig Site included in
the section “Sampling Service”
SPEO IDENTIFICATION CODE PAG 21 OF 38
Eni S.p.A.
E&P Division REVISION
STAP-A-1-SS-1728 0 1
5.3.1 PERSONNEL
5.3.1.4 HELPER
• Experience: not required
• Education: not below secondary school.
• Specialisation Courses: basic well test.
5.3.2 EQUIPMENT
The bottom hole data acquisition equipment shall be able to allow the real time reading
of bottom hole data during the flowing and the build up periods of the well test. It shall be
able to perform PLT logs and all the other bottom hole acquisitions needed during the
well test operation. Contractor on request shall provide a computer system with bottom
hole data evaluation and well test interpretation software.
Contractor shall provide all the equipment needed and adequate to carry out the service.
All the equipment must be H2S service. The design of equipment shall ensure safety
operations.
The main equipments that can be used for the service are described below.
SPEO IDENTIFICATION CODE PAG 22 OF 38
Eni S.p.A.
E&P Division REVISION
STAP-A-1-SS-1728 0 1
5.3.2.4 BOP
• Shall perform the closure on the wire line cable with two series of rams at least.
• For HPHT application shall have four series of rams.
• Only BOP with wire shaped rams are allowed.
• BOP control shall be hydraulic and manual type.
• It shall be equipped with equalizing valve.
• Bottom connection shall be flange type or equivalent metal to metal connection.
• The hydraulic control pump must be equipped, downstream of the fluid end with
a check valve + “T” + bleed off valve of suitable W.P.
SPEO IDENTIFICATION CODE PAG 23 OF 38
Eni S.p.A.
E&P Division REVISION
STAP-A-1-SS-1728 0 1
• The connection between pipe and quick union must be of integral or welded
type.
• Threaded type connection shall be approved at tender and only for equipment
below 10000 psi WP.
• In the lower section the lubricator shall be equipped with at least 1/2" NPT hole
to allow pressure bleed off.
• The Lubricator pressure bleeding off shall be carried out using n° 1 bleed off
valve for W.P. up to 5000 psi, and n° 2 bleed off valves for W.P.> 5000 psi. On
the Lubricator bleed off point a wear joint shall be applied.
5.4.1 PERSONNEL
Contractor shall provide all the equipment needed and adequate to carry out the service.
All the equipment must be H2S service. The equipment shall be designed to ensure
safety operations and shall be certified in accordance with the laws and regulations
applicable in the Country where the operations will be performed.
The service shall include the transfer of the fluid recovered from the bottom sampler into
a Sampling Bottle.
The main equipments to be used for the service are described below.
The “Transfer Bench” will be used to transfer the fluid sampled at bottom hole into a
Sampling Bottle.
SPEO IDENTIFICATION CODE PAG 26 OF 38
Eni S.p.A.
E&P Division REVISION
STAP-A-1-SS-1728 0 1
The main equipments to be used for the service are described below.
Contractor shall provide oil, gas and water sampling bottles for surface sampling.
The bottle shall be:
• H2S/CO2 service.
• Mercury-free type.
• Positive Displacement Type , Conventional or Single Phase
• Complying with IATA regulation.
• Shall have adequate W.P (refer to Project Specification)
• There shall be provisions for checking opening pressure of the bottle chamber
and saturation pressure (due point or bubble point) of the collected fluid before
transportation.
The bottle shall always be accompanied by proper testing certification in accordance to
the reference standard.
The main Sampling Bottles types that Contractor shall be able to provide are:
Wellhead Single Phase 600 cc W.P. as per Project Specification
Wellhead Conventional 600 cc W.P. as per Project Specification
Separator Oil 600 cc W.P. 200 bar
Separator Gas 20 l W.P. 200 bar
Separator Water 600 cc W.P. 200 bar
Atmospheric Water Glass/plastic
Atmospheric Crude Oil Tin 25l
6. EQUIPMENT TESTS
All surface and lubricator equipment as minimum requirement shall undergo a cyclical
series of checks. A guideline for type of test and frequency is defined in section 6.1 and
6.2 . Modifications to the frequency and to the reference specifications can be proposed
by Contractor during the bidding phase (see chapter 3). The modifications must be
approved by Company.
All surface and lubricator equipment shall be accompanied by the certificate of the last
hydraulic test as well as the last non destructive test which they have undergone.
All surface and lubricator equipment shall be marked with an identification code
including, beside component identification, a nameplate allowing determination of the
working pressure, type of material and service.-
The Contractor is responsible for the keeping of a test logbook and of the compliance
with the procedure listed hereunder.
6.1.9.5 Pressure test of bypass manifold according to point 6.2.2 before and after every
job.-
6.1.10 Heater, Cooler and Heat Exchanger
6.1.10.1 Visual inspection according to point 6.2.1 every 12 months.-
6.1.10.2 Pressure test according to point 6.2.2 every 12 months.-
6.1.10.3 Pressure test of bypass manifold according to point 6.2.2 before and after every
job.-
6.1.10.4 Magnetic/Ultrasonic inspection on the coils, Magnetic and eventually Liquid
Penetrant inspection on the connections, Ultrasonic inspection on weldings;
according to point 6.2.4 every 24 months.-
6.1.10.5 Inspection of combustion chamber, burners, electric supply devices, fuel supply
lines, temperature control devices, vessel, all test every year, drawing up a
maintenance data sheet to be kept by Contractor.
6.1.11 Choke Manifold 5000 to 15000 psi WP.-
6.1.11.1 Visual inspection according to point 6.2.1 every 12 months.-
6.1.11.2 Pressure test according to point 6.2.2 before every job and at least every 12
months.-
6.1.11.3 Magnetic/Ultrasonic inspection on the body, Magnetic and eventually Liquid
Penetrant inspection on the threading, Ultrasonic inspection on weldings;
according to point 6.2.4 every 24 months.-
6.1.12 Flexible Flow lines, Piping and Data Header
6.1.12.1 Visual inspection according to point 6.2.1 every 12 months.-
6.1.12.2 Pressure test according to point 6.2.2 every 12 months.-
6.1.12.3 Magnetic/Ultrasonic inspection on the body, Magnetic and eventually Liquid
Penetrant inspection on the threading, Ultrasonic inspection on weldings;
according to point 6.2.4 every 24 months.-
6.1.13 Gas Diverter and Oil Manifold
6.1.13.1 Visual inspection according to point 6.2.1 every 12 months.-
6.1.13.2 Pressure test according to point 6.2.2 before every job and at least every 12
months.-
6.1.13.3 Magnetic/Ultrasonic inspection on the body, Magnetic and eventually Liquid
Penetrant inspection on the threading, Ultrasonic inspection on weldings;
according to point 6.2.4 every 24 months.-
SPEO IDENTIFICATION CODE PAG 30 OF 38
Eni S.p.A.
E&P Division REVISION
STAP-A-1-SS-1728 0 1
6.2.3.6 Draw up the “NDT Test Pressure BOP Report” for each component examined,
to be kept by the Contractor.-
6.2.4 Magnetic Examination – Magnetic particle examination - Ultrasonic
examination - Liquid Penetrant examination.
6.2.4.1 The test must be performed by qualified inspection companies.
6.2.4.2 The test must be performed in according to the written procedure available for
Company verification. The procedures must be in compliance with the
requirements of EN/ISO standard.
6.2.4.3 Draw up the “NDT Magnetic/Ultrasonic Examination Report” for each
component checked, enclose with it the report of the company performing the test;
this report will be kept by the Contractor.-
6.2.5 Hardness Test.-
6.2.5.1 A hardness test of the must be included in each item documentation.-
6.2.5.2 Surface equipment for standard service must have a minimum hardness of 200
Brinnell for material with 80000 psi minimum yield; a hardness between 290
Brinnell (30 Rockwell C) and 341 Brinnell (36 Rockwell C) for material with
110000 psi minimum yield.
6.2.5.3 Surface equipment for H2S service must have a hardness not above 22
Rockwell C.
6.2.6 Thickness inspection
6.2.6.1 Thickness inspection on vessel to look for inside corrosion points with special
attention rear the inlet and outlet of the produced fluid
6.2.6.2 Draw up the “NDT Thickness Inspection Report” for each component
examined, to be kept by the Contractor.-
6.2.7 Internal inspection
6.2.7.1 Internal inspection on vessel to check for inside condition, cleaning of walls and
separation improvement device, removing on debris, scales and rust.
6.2.7.2 Draw up the “NDT Internal Inspection Report” for each component examined,
to be kept by the Contractor'.-
SPEO IDENTIFICATION CODE PAG 32 OF 38
Eni S.p.A.
E&P Division REVISION
STAP-A-1-SS-1728 0 1
7. DOCUMENTATION
Standardisation of the file format of the data recorded during well testing
*************************************************************************************************
The release of ASCII files containing the following information is generally required:
a. a few heading lines - information notes, numerical values of quantities not depending on time;
b. lines relevant to the required numerical values recorded as a function of time.
Each line, either relevant to information data or recorded values, must be concluded by a carriage
return (<CR>). The recorded values must always be reported starting from a defined line number. As
far as the information data are concerned, it should be noted that a well-defined meaning is
associated to each line: shouldn’t the information be available, the line must be left empty, and a
<CR> typed.
The last line of the file should contain the last values recorded, and not special characters or
indicators of end of file. A <CR> is always necessary.
NOTE: the use of <CR> or <CR><LF> as the line ender is absolutely indifferent.
The following pages present details concerning the file format for the in-hole recordings - point 1:
bottom hole recordings (PRESSURE AND TEMPERATURE HISTORY FILES) - and surface
recordings - point 2 (SURFACE DATA FILES - TEST TREND) -.
As far as the system of units is concerned, note that in all cases the recorded values are implicitly
referred to pre-arranged units, which can be reported in one of the file heading lines for information
purposes only.
History files must contain the pressure and temperature values recorded by the tool in the well. If
pressure and temperature profiles have been carried out, the values recorded during the run-in hole
and pull-out of hole operations must be also included.
<from line 1 to line 21: the description of the line content can occupy the first 24 positions;
the corresponding value must be specified from position 25 on, without length limit;
the line must NOT contain <tab>, but spaces > only
REVISION
38
<from line 22 to line 25: notes, if any, can be specified from position 1 on, without length limits;
line 26 must be empty - containing a <CR> only ->
line 1---------------------------------------------------------------<CR>
22 xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx.....(Note)
23 xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx.....(Note)
24 xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx.....(Note)
Eni S.p.A.
25 xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx.....(Note)
26
E&P Division
SPEO
<from line 27 on: data must be organised into 5 columns, the first 4 must have a fixed length. The last column, to be
used for notes, must start from position 66 and doesn’t have length limit; it does not contain <CR>, except the one
indicating the end of the line. If there are no notes, the <CR> at the end of the line MUST be typed after position
65.
This is valid also when no temperature values have been recorded; the line must NOT contain <tab>, but only spaces.
There are no limits on the number of decimals for the recorded numerical values.
Lines 27 and 28 must always contain the description of the variables and the reference measurement units and are not
considered as containing data; the recorded values start from line 29.
REVISION
38
SPEO IDENTIFICATION CODE PAG 36 OF 38
Eni S.p.A.
E&P Division REVISION
STAP-A-1-SS-1728 0 1
Surface data files must contain values of the significant variables as a function of time, i.e.
pressure, temperature, flow rates, and fluid properties, recorded by tools/equipment located at
surface, notes, and a set of pressure and temperature data downhole recorded (based on variable
sampling time intervals, coinciding with the monitorings at well head).
Herebelow are the variables which have been identified, together with their relevant units and the
order according to which they must be reported inside the file:
<from line 1 to line 9 : the description of the line content can occupy the first 24 positions;
the corresponding value must be specified from position 25 on, without length limits;
Eni S.p.A.
<from line 10 to line 13: notes, if any, can be specified from position 1 on,without length limits;
line 14 must be empty - it contains only a <CR>
STAP-A-1-SS-1728
line 1--------------------------------------------------------------<CR>
IDENTIFICATION CODE
10 xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx.....(Note)
11 xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx.....(Note)
12 xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx.....(Note)
0
13 xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx.....(Note)
14.....xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx (Note)
1
PAG
37
OF
REVISION
38
DATA ROWS>
Eni S.p.A.
<FROM LINE 15 ON: THE DATA MUST BE REPORTED IN THE ORDER ALREADY DESCRIBED IN THE PREVIOUS PAGE, STARTING
FROM POSITION 1, AND SEPARATED BY “ ; “
E&P Division
IF A VALUE IS LACKING, “ ; “ MUST BE TYPED IN ANY CASE TO ALLOW THE CORRECT IDENTIFICATION OF THE NEXT VALUE
UNLESS IT IS THE LAST DATA OF THE LIST- THE REMARKS WHICH MUST CONTAIN NEITHER “ ; “ NOR <CR>, EXCEPT THE ONE
SPEO
LINES MUST NOT BE BROKEN; THERE IS NO LIMIT ON THE NUMBER OF DECIMALS OF THE NUMERICAL VALUES.
LINES 15 AND 16 MUST ALWAYS CONTAIN THE DESCRIPTION OF THE VARIABLE AND REFERENCE UNIT AND ARE NOT CONSIDERED
AS CONTAINING DATA; THE RECORDED VALUES START FROM LINE 17.
1--------------------------------------------------------------------------------------------------------------------<CR>
DATE TIME;ELAPSED;CHOKE;BHP;BHT;................(THE VARIABLES MUST BE REPORTED; 26 COLUMNS ARE NORMALLY EXPECTED SEPARATED BY “ ; “)
MM/DD/YYYY HH:MM;MIN;INCH;KG/CM2 REL.;°C;.......(THE UNITS OF EACH VARIABLE MUST BE ALL REPORTED; 26 COLUMNS ARE NORMALLY EXPECTED SEPARATED BY “ ; “)
01/01/0001 00:00;0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;XXXXX.....
01/01/0001 00:00;0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;0.0;XXXXX.........
STAP-A-1-SS-1728
IDENTIFICATION CODE
0
1
PAG
38
OF
REVISION
38