Air System Sizing Summary for 1.

SUBESTACION
Project Name: SUBESTACION ECOPLAZA 04/26/2019
Prepared by: AT CONSULTORES 11:38AM

Air System Information


Air System Name 1. SUBESTACION Number of zones 1
Equipment Class UNDEF Floor Area 283.0 ft²
Air System Type SZCAV Location Lima, Peru

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.8 Tons Load occurs at Feb 2100
Total coil load 58.0 MBH OA DB / WB 79.3 / 73.2 °F
Sensible coil load 58.0 MBH Entering DB / WB 75.3 / 46.1 °F
Coil CFM at Feb 2100 2730 CFM Leaving DB / WB 55.6 / 35.9 °F
Max block CFM 2730 CFM Coil ADP 53.4 °F
Sum of peak zone CFM 2730 CFM Bypass Factor 0.100
Sensible heat ratio 1.000 Resulting RH 0 %
ft²/Ton 58.5 Design supply temp. 55.0 °F
BTU/(hr·ft²) 205.0 Zone T-stat Check 1 of 1 OK
Water flow @ 10.0 °F rise 11.61 gpm Max zone temperature deviation 0.0 °F

Supply Fan Sizing Data


Actual max CFM 2730 CFM Fan motor BHP 0.22 BHP
Standard CFM 2726 CFM Fan motor kW 0.18 kW
Actual max CFM/ft² 9.65 CFM/ft² Fan static 0.30 in wg

Outdoor Ventilation Air Data


Design airflow CFM 0 CFM CFM/person 0.00 CFM/person
CFM/ft² 0.00 CFM/ft²

Hourly Analysis Program v5.01 Page 1 of 2


Air System Design Load Summary for 1. SUBESTACION
Project Name: SUBESTACION ECOPLAZA 04/26/2019
Prepared by: AT CONSULTORES 11:38AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Feb 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.3 °F / 73.2 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 149 ft² 1547 - 149 ft² 873 -
Roof Transmission 283 ft² 2604 - 283 ft² 1103 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 730 ft² 1806 - 730 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 509 W 1738 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 50840 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 58535 0 - 1975 0
Zone Conditioning - 57405 0 - 491 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2730 CFM 0 - 2730 CFM 0 -
Ventilation Load 0 CFM 0 0 0 CFM 0 0
Supply Fan Load 2730 CFM 607 - 2730 CFM -607 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 58012 0 - -116 0
Central Cooling Coil - 58012 0 - 0 0
>> Total Conditioning - 58012 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v5.01 Page 2 of 2