The document calculates the heat load for an area that is 15 meters by 29.8 meters. It sums the BTUs from the area size, three sets of doors, five people, equipment, and lights. The total heat load is approximately 175,028 BTUs. This equates to a required cooling capacity of 14.586 tons. With a 10% addition, the recommended tonnage is 17 tons.
The document calculates the heat load for an area that is 15 meters by 29.8 meters. It sums the BTUs from the area size, three sets of doors, five people, equipment, and lights. The total heat load is approximately 175,028 BTUs. This equates to a required cooling capacity of 14.586 tons. With a 10% addition, the recommended tonnage is 17 tons.
The document calculates the heat load for an area that is 15 meters by 29.8 meters. It sums the BTUs from the area size, three sets of doors, five people, equipment, and lights. The total heat load is approximately 175,028 BTUs. This equates to a required cooling capacity of 14.586 tons. With a 10% addition, the recommended tonnage is 17 tons.
1 Area BTU 15 x 29.8 Mtr 49.2 x 97.74 Ft.x 31.25 150275.25
2 DOOR - A 3+2NOS. 3x2=6 x 868=5208 2x2=4 x 164=656 5864 3 DOOR - B 1+1 NOS 2 x 868 = 1736 2 x 164= 328 2064 4 DOOR - C 1+1 NOS 2.05 x 868=1779.4 2.05 x 164=336.2 2115.6 5 No. Person 5 Nos 5 x 600 = 3000 3000 6 Equipment Watts Transformer 16 + 16 = 32 KW = 40 KVA Up to 150 KVA - 50 Watts- 50 x 3.4 = 170 85 % - 170 x 85 = 9860 9860 5+5+6+30+16 = 62 KW 77.5 KVA - 50 x 3.4 = 170 5% - 170 x 5 = 85 850 Total Light Watts Watts x 4.25 Approximately 1000 1000 Total Heat BTU 175028.85 Total Heat Cooling BTU/ Cooling 175028.85/12000 14.586 Capacity