KPONG GENERATING STATION RETROFIT PROJECT


04 AS build documentation 2/4/2019 NB
Index Modification Date Prepared Checked
TITLE:

CAUSE&EFFECT
Fire extinquishing control panels
FECP 01&02&03&04
Client VRA Prepared by 2/18/2016 HILL Filename
Plant KPONG Checked Index / Date Filedate
Project N° H110.120036 Approved Department 04 4/4/2019 SHEET
= +

HAV
Internal N° 614636-004
DOC N° E344700-5000-10-042-0104
Approved By

PROJECT
Checked Approved

6/25/2019
1 OF 4
System released 03.01.113
Summary fault 03.01.111
Solenoid valve YV1101

2nd alarm main alarm


Fire Alarm 03.01.112

Common Panel Alarm Indicaton


Common Panel Fault Indicaton
Flash light H1102
Sounder H1101
CAUSE/EFECT
FECP1 Generator unit 1

OUTPUT

Trouble relay
MR-2306-R6
Alarm relay

indicaton
Relay2

Panel
Sig 1

Sig 2

Sig 3
Zone el.no. Description
1 1 Detector FC1101 / Smoke detector X X X 2ZDD 2ZDD X
1 2 Detector FC1102 / Smoke detector X X X 2ZDD 2ZDD X
1 3 Detector FC1103 / Smoke detector X X X 2ZDD 2ZDD X
1 4 Detector FC1104 / Smoke detector X X X 2ZDD 2ZDD X
2 2 Detector FC1105 / Heat detector X X X 2ZDD 2ZDD X
2 3 Detector FC1106 / Heat detector X X X 2ZDD 2ZDD X
2 4 Detector FC1107 / Heat detector X X X 2ZDD 2ZDD X
2 5 Detector FC1108 / Heat detector X X X 2ZDD 2ZDD X
2 1 Generator protecton signal 87G X X X 2ZDD 2ZDD X
3 3 Alarm pressure switch X ** X
4 4 Gate valve water supply line X X
4 4 Motor driven gate valve X X
5 5 Abort Signal K63 ABR 1101 (Generator protecton) B X
5 5 Abort switch AB1102 (Control room) B X
6 6 Manual release pull staton S1101 (Unit 1 door) X X X X X X
7 7 Manual release pull staton S1102 (Control room) X X X X X X

Note:
1. If 2ZDD (two zone actvated 1&2) Solenoid valve will actvated after 60 sec delay
2. If Manual release pull staton is actvated, solenoid valve will be actvated after 30 sec delay

3. If Manual release pull staton is actvated, abort switch is overrided (can not abort system release sequence). Acording to UL
standard
4. ** ONLY after expired release tmer discharge releay will be aqctvated
System released 03.01.116
Summary fault 03.01.114
Solenoid valve YV1201

2nd alarm main alarm


Fire Alarm 03.01.115

Common Panel Alarm Indicaton


Common Panel Fault Indicaton
Flash light H1202
Sounder H1201
CAUSE/EFECT
FECP2 Generator unit 2

OUTPUT

Trouble relay
MR-2306-R6
Alarm relay

indicaton
Relay2

Panel
Sig 1

Sig 2

Sig 3
Zone el.no. Description
1 1 Detector FC1201 / Smoke detector X X X 2ZDD 2ZDD X
1 2 Detector FC1202 / Smoke detector X X X 2ZDD 2ZDD X
1 3 Detector FC1203 / Smoke detector X X X 2ZDD 2ZDD X
1 4 Detector FC1204 / Smoke detector X X X 2ZDD 2ZDD X
2 2 Detector FC1205 / Heat detector X X X 2ZDD 2ZDD X
2 3 Detector FC1206 / Heat detector X X X 2ZDD 2ZDD X
2 4 Detector FC1207 / Heat detector X X X 2ZDD 2ZDD X
2 5 Detector FC1208 / Heat detector X X X 2ZDD 2ZDD X
2 1 Generator protecton signal 87G X X X 2ZDD 2ZDD X
3 3 Alarm pressure switch X ** X
4 4 Gate valve water supply line X X
4 4 Motor driven gate valve X X
5 5 Abort Signal K63 ABR 1201 (Generator protecton) B X
5 5 Abort switch AB1202 (Control room) B X
6 6 Manual release pull staton S1201 (Unit 1 door) X X X X X X
7 7 Manual release pull staton S1202 (Control room) X X X X X X

Note:
1. If 2ZDD (two zone actvated 1&2) Solenoid valve will actvated after 60 sec delay
2. If Manual release pull staton is actvated, solenoid valve will be actvated after 30 sec delay

3. If Manual release pull staton is actvated, abort switch is overrided (can not abort system release sequence). Acording to UL
standard
4. ** ONLY after expired release tmer discharge releay will be aqctvated
System released 03.01.145
Summary fault 03.01.143
Solenoid valve YV1301

2nd alarm main alarm


Fire Alarm 03.01.144

Common Panel Alarm Indicaton


Common Panel Fault Indicaton
Flash light H1302
Sounder H1301
CAUSE/EFECT
FECP3 Generator unit 3

OUTPUT

Trouble relay
MR-2306-R6
Alarm relay

indicaton
Relay2

Panel
Sig 1

Sig 2

Sig 3
Zone el.no. Description
1 1 Detector FC1301 / Smoke detector X X X 2ZDD 2ZDD X
1 2 Detector FC1302 / Smoke detector X X X 2ZDD 2ZDD X
1 3 Detector FC1303 / Smoke detector X X X 2ZDD 2ZDD X
1 4 Detector FC1304 / Smoke detector X X X 2ZDD 2ZDD X
2 2 Detector FC1305 / Heat detector X X X 2ZDD 2ZDD X
2 3 Detector FC1306 / Heat detector X X X 2ZDD 2ZDD X
2 4 Detector FC1307 / Heat detector X X X 2ZDD 2ZDD X
2 5 Detector FC1308 / Heat detector X X X 2ZDD 2ZDD X
2 1 Generator protecton signal 87G X X X 2ZDD 2ZDD X
3 3 Alarm pressure switch X ** X
4 4 Gate valve water supply line X X
4 4 Motor driven gate valve X X
5 5 Abort Signal K63 ABR 1301 (Generator protecton) B X
5 5 Abort switch AB1302 (Control room) B X
6 6 Manual release pull staton S1301 (Unit 1 door) X X X X X X
7 7 Manual release pull staton S1302 (Control room) X X X X X X

Note:
1. If 2ZDD (two zone actvated 1&2) Solenoid valve will actvated after 60 sec delay
2. If Manual release pull staton is actvated, solenoid valve will be actvated after 30 sec delay
3. If Manual release pull staton is actvated, abort switch is overrided (can not abort system release sequence). Acording to UL
standard
4. ** ONLY after expired release tmer discharge releay will be aqctvated
System released 03.01.148
Summary fault 03.01.146
Solenoid valve YV1401

2nd alarm main alarm


Fire Alarm 03.01.147

Common Panel Alarm Indicaton


Common Panel Fault Indicaton
Flash light H1402
Sounder H1401
CAUSE/EFECT
FECP4 Generator unit 4

OUTPUT

Trouble relay
MR-2306-R6
Alarm relay

indicaton
Relay2

Panel
Sig 1

Sig 2

Sig 3
Zone el.no. Description
1 1 Detector FC1401 / Smoke detector X X X 2ZDD 2ZDD X
1 2 Detector FC1402 / Smoke detector X X X 2ZDD 2ZDD X
1 3 Detector FC1403 / Smoke detector X X X 2ZDD 2ZDD X
1 4 Detector FC1404 / Smoke detector X X X 2ZDD 2ZDD X
2 2 Detector FC1405 / Heat detector X X X 2ZDD 2ZDD X
2 3 Detector FC1406 / Heat detector X X X 2ZDD 2ZDD X
2 4 Detector FC1407 / Heat detector X X X 2ZDD 2ZDD X
2 5 Detector FC1408 / Heat detector X X X 2ZDD 2ZDD X
2 1 Generator protecton signal 87G X X X 2ZDD 2ZDD X
3 3 Alarm pressure switch X ** X
4 4 Gate valve water supply line X X
4 4 Motor driven gate valve X X
5 5 Abort Signal K63 ABR 1401 (Generator protecton) B X
5 5 Abort switch AB1402 (Control room) B X
6 6 Manual release pull staton S1401 (Unit 1 door) X X X X X X
7 7 Manual release pull staton S1402 (Control room) X X X X X X

Note:
1. If 2ZDD (two zone actvated 1&2) Solenoid valve will actvated after 60 sec delay
2. If Manual release pull staton is actvated, solenoid valve will be actvated after 30 sec delay
3. If Manual release pull staton is actvated, abort switch is overrided (can not abort system release sequence ). Acording to UL
standard
4. ** ONLY after expired release tmer discharge releay will be aqctvated