Vvio12a en M b005
Vvio12a en M b005
VIO 12AC / AD
RTD AND mA OUTPUT / INPUT MODULES
User manual
Table of Contents VIO 12A
Table of Contents
1 General .................................................................................... 4
2 Layout ..................................................................................... 5
2.1 VIO 12AA RTD input module ............................................. 5
2.2 VIO 12AB RTD input module ............................................. 6
2.3 VIO 12AC & VIO 12AD RTD input and mA input/output
modules ...................................................................................... 7
3 Operation ................................................................................ 8
4 Application ............................................................................ 11
4.1 VIO 12AA ......................................................................... 11
4.2 VIO 12AB ......................................................................... 14
4.3 VIO 12AC & VIO 12AD .................................................... 15
4.4 Communication Settings .................................................. 20
5 Connections.......................................................................... 23
5.1 RTDs ................................................................................ 23
5.2 mA inputs / -outputs connections ..................................... 24
6 Configurations ...................................................................... 25
6.1 Connecting VAMP relay to PC ......................................... 25
6.2 Relay settings .................................................................. 25
6.2.1 Protocol configuration .............................................. 26
6.2.2 External I/O configuration ........................................ 26
6.2.3 External analog inputs ............................................. 28
6.2.4 External analog Outputs .......................................... 30
6.2.5 Troubleshooting ....................................................... 32
6.3 VIO 12AA settings ............................................................ 32
6.3.1 RTDinput protocol .................................................... 32
6.3.2 Modbus RTU protocol .............................................. 32
6.4 VIO 12AB settings ............................................................ 33
6.4.1 RTDinput protocol .................................................... 33
6.5 VIO 12AC & VIO 12AD settings ....................................... 33
6.5.1 Modbus RTU protocol .............................................. 33
6.5.2 RTDinput protocol .................................................... 33
7 Technical data ...................................................................... 34
7.1 General ............................................................................ 34
7.1.1 RTD inputs ............................................................... 34
7.1.2 mA inputs ................................................................. 34
7.1.3 mA outputs............................................................... 35
7.1.4 PTC input ................................................................. 35
7.2 Connections ..................................................................... 35
7.2.1 Measuring circuitry ................................................... 35
7.2.2 Auxiliary voltage ....................................................... 36
7.2.3 Glass fiber connection ............................................. 36
7.2.4 RS-232 connection .................................................. 36
7.2.5 RS-485 connection .................................................. 36
7.3 Tests and environmental conditions ................................. 37
7.3.1 Disturbance tests ..................................................... 37
7.3.2 Test voltage ............................................................. 37
7.3.3 Environmental conditions ......................................... 37
7.3.4 Casing...................................................................... 38
2 VVIO12A/EN M/B005
VIO 12A Table of Contents
VVIO12A/EN M/B005 3
2.1 VIO 12AA RTD input modules 1 General VIO 12A
1 General
1. Measures as many as 12 RTD resistances
2. Measuring accuracy ±0,3Ω
3. Supported RTD types:
Pt100
Ni100
Ni120
Cu10
4. Communications:
VIO 12AA:
ST-type glass fiber (only TX)
RS-232 (can only be used with VAMP40)
VIO 12AB:
RS-485
4 VVIO12A/EN M/B005
VIO 12A Layout 2.1 VIO 12AA RTD input module
2 Layout
1. Metal enclosure
2. Glass fiber Tx communication
3. RS-232 communication (can only be used with VAMP40)
4. RTD inputs (12 channels, 3-wire connection + shield / channel)
5. Power connector and PE connection
6. DIN Rail mounting
VVIO12A/EN M/B005 5
2.2 VIO 12AB RTD input modules 2 Layout VIO 12A
1. Metal enclosure
2. RS-485 communication (including Termination switch)
3. Address DIP Switch
4. RTD inputs (12 channels, 3-wire connection + shield / channel)
5. Power connector and PE connection
6. DIN Rail mounting
6 VVIO12A/EN M/B005
VIO 12A Layout 2.3 VIO 12AC & VIO 12AD RTD input
and mA input/output modules
Figure 2.3-1 VIO 12AC / VIO 12AD RTD input module layout
1. Metal enclosure
2. Glass fiber Rx communication
3. Glass fiber Tx communication
4. RS-232 communication (can only be used with VAMP40)
5. RS-485 communication (including termination switch)
6. Address DIP switch
7. RTD inputs (12 channels, 3-wire connection + shield / channel)
8. Power connector and PE connection
9. PTC input (2-wire connection)
10. Four mA inputs / four mA outputs (2-wire connection /channel)
11. DIN Rail mounting
VVIO12A/EN M/B005 7
2.3 VIO 12AC & VIO 12AD RTD input 3 Operation VIO 12A
and mA input/output moduless
3 Operation
VIO 12A supports two different External I/O protocols:
RTDinput (Figure 3-1)
Modbus RTU (Figure 3-2).
RTDinput protocol
(one-way communication) Single fiber
Function
Measure the resistances of RTD sensors and send results via
RTDinput protocol.
8 VVIO12A/EN M/B005
VIO 12A Operation 2.3 VIO 12AC & VIO 12AD RTD input
and mA input/output modules
Modbus RTU
(two-way communication) Two fibers, RS-485, RS-232
mAin3 * mAout3 *
mAin4 * mAout4 *
:
:
*Only VIO 12AC and VIO 12AD
RTD12
Function
Measure the resistances of RTD sensors and send results via
Modbus RTU.
Measure analog inputs (mA and PTC) and send results via
Modbus RTU. (Only VIO 12AC and VIO 12AD).
Provide analog outputs (mA). (Only VIO 12AC and VIO 12AD)
VVIO12A/EN M/B005 9
2.3 VIO 12AC & VIO 12AD RTD input 3 Operation VIO 12A
and mA input/output moduless
10 VVIO12A/EN M/B005
VIO 12A Application 4.1 VIO 12AA
4 Application
This chapter deals with the different ways to use VIO 12A and
VAMP accessories with VAMP relays.
VIO 12AA
VIO 12AA assembled onto the
fiber Tx wall or DIN-RAIL
VVIO12A/EN M/B005 11
4.1 VIO 12AAs 4 Application VIO 12A
VIO 12AA
assembled onto the
fiber Tx wall or DIN-RAIL
* Refer to the Table 4.1-1 for compatible VAMP relays and fiber
optic modules
** For detailed mounting instructions, refer to the User Manual of
the particular fiber optic module
Table 4.1-1 shows fiber optic modules that can be used with
VAMP relays in one-way glass fiber application.
12 VVIO12A/EN M/B005
VIO 12A Application 4.1 VIO 12AA
RS-232 application:
VVIO12A/EN M/B005 13
4.2 VIO 12ABs 4 Application VIO 12A
RS-485 communication
module mounted to the
VAMP relay‟s serial port *
Table 4.2-1 shows RS-485 modules that can be used with VAMP
relays in RS-485 application.
14 VVIO12A/EN M/B005
VIO 12A Application 4.3 VIO 12AC & VIO 12AD
RJ-45 cable
VVIO12A/EN M/B005 15
4.3 VIO 12AC & VIO 12ADs 4 Application VIO 12A
16 VVIO12A/EN M/B005
VIO 12A Application 4.3 VIO 12AC & VIO 12AD
* Refer to the Table 4.3-1 for compatible VAMP relays and fiber
optic modules
** For detailed mounting instructions, refer to the User Manual of
the particular fiber optic module
Table 4.3-1 shows fiber optic modules that can be used with
VAMP relays in two-way glass fiber application.
VCM_Fibre GG 257
VVIO12A/EN M/B005 17
4.3 VIO 12AC & VIO 12ADs 4 Application VIO 12A
RS-232 application:
18 VVIO12A/EN M/B005
VIO 12A Application 4.3 VIO 12AC & VIO 12AD
RS-485
application:
RS-485 communication module
mounted to the VAMP relay‟s serial
port *
Table 4.3-2 shows RS-485 modules that can be used with VAMP
relays in RS-485 application.
VSE 004 40
VSE 005-1 40
VVIO12A/EN M/B005 19
4.4 Communication Settingss 4 Application VIO 12A
LE T A
VIO- Module
Switch 12AA 12AB 12AC/AD
LE* X
T X X
A X X
Table 4.4-1 DIP Switches in VIO 12
Notes:
*) LE switch is divided into two parts, LE:1 and LE:2
**) “X” stands for: available in VIO module.
***) The switch position is ON when the switch is turned DOWNWARDS.
20 VVIO12A/EN M/B005
VIO 12A Application 4.4 Communication Settings
Position Function :
VIO’s optical fiber communication setup.
ON Light is on when there is no data being sent.
OFF Light is off when there is no data being sent.
Position Function :
Selection of the termination resistor of 120 ohms
for the RS-485 interface.
ON Resistor is selected
OFF Resistor is not selected
A. Address Switch
The address switch is meant for selecting the slave address for
the VIO module.
Position Function :
Assignment of slave address for the VIO module.
ON Selected single address bit is set to 1.
OFF Selected single address bit is set to 0.
VVIO12A/EN M/B005 21
4.4 Communication Settingss 4 Application VIO 12A
Example:
The address switch represents the VIO-12‟s address in its binary
notation.
Address Switch
OFF
ON
1 2 3 4 5 6 7 8
Note:
RTDinput protocol
By setting VIO 12AB/AC/AD module‟s address to „0‟ it is possible
to use RTDinput protocol to send RTD measurements to the relay.
Please note that mA outputs and inputs can not be used via
RTDinput protocol
22 VVIO12A/EN M/B005
VIO 12A Connections 5.1 RTDs
5 Connections
5.1 RTDs
RTD connections are equal in all versions of VIO 12A. Figure
5.1-1 shows the proper way to connect RTDs.
Cable type:
Shielded non-paired control and instrumentation cable (e.g.
Belden 8771)
VVIO12A/EN M/B005 23
5.2 mA inputs / -outputs 5 Connections VIO 12A
connectionss
mA inputs mA outputs
Figure 5.2-1 VIO 12AC / VIO 12AD mA input and mA output connection cables
Cable type:
Shielded non-paired control and instrumentation cable (e.g.
Belden 8771).
PTC connections +-
PTC input
Cable type:
Shielded non-paired control and instrumentation cable (e.g.
Belden 8771).
24 VVIO12A/EN M/B005
VIO 12A Configurations 6.1 Connecting VAMP relay to PC
6 Configurations
This chapter describes the configurations required to correctly set
up VAMP relay and VIO 12A module.
Figure 6.1-1 Connecting cable VX003 to the relay’s front port for the External
I/O settings of the relay.
VVIO12A/EN M/B005 25
6.2 Relay settingss 6 Configurations VIO 12A
Parity * Even
26 VVIO12A/EN M/B005
VIO 12A Configurations 6.2 Relay settings
Parity * Even
Parameter Value(s)
AI Enabled On / Off
VVIO12A/EN M/B005 27
6.2 Relay settingss 6 Configurations VIO 12A
Refer to the Table 6.2.3-1 for the proper values to the parameters
“AI Enabled”, “AI Unit”, “AI Slave Address”, “AI Modbus Address”,
“AI Register Type” and “AI Signed”.
Scalings
Also in the external analog inputs –menu give proper values to
parameters “AI Offset”, “x1”, “x2”, “y1” and “y2”. Refer to the Table
6.2.3-2 for proper values of the particular RTD.
AI Offset X1 Y1 X2 Y2
28 VVIO12A/EN M/B005
VIO 12A Configurations 6.2 Relay settings
Registers
Modbus register Properties
VVIO12A/EN M/B005 29
6.2 Relay settingss 6 Configurations VIO 12A
30 VVIO12A/EN M/B005
VIO 12A Configurations 6.2 Relay settings
318
319
320
321
Ao Register
HoldingR Holding register Only available option.
type
Typical value
Minimum value which is
ModBus Min Refer to note sent to the VIO‟s mA Min = 0
ModBus register.
ModBus Min = 0
Typical value:
Maximum value which
Modbus Max is sent to the VIO‟s mA Max = 20
ModBus
ModBus Max = 20000
It increments itself if either Ao
AO Counter 0… Error counter for AO Slave Address or Ao Register
Address are not set correctly
VVIO12A/EN M/B005 31
6.3 VIO 12AA settingss 6 Configurations VIO 12A
6.2.5 Troubleshooting
If an RTD sensor is disconnected, VAMPSET displays a value of -
200ºC in the External Analog Inputs –menus respective sensor
channel.
32 VVIO12A/EN M/B005
VIO 12A Configurations 6.4 VIO 12AB settings
Note: When implementing the connection between VIO 12AB and VAMP
relay with RS-485 via RTDinput protocol it needs to be taken into
consideration that no other modules can be connected to the RS-
485 bus.
Note: When implementing the connection between VIO 12AC / VIO 12AD
and VAMP relay with RS-485 via RTDinput protocol it needs to be
taken into consideration that no other modules can be connected
to the RS-485 bus. Please note that mA outputs and inputs can not
be used via RTDinput protocol
VVIO12A/EN M/B005 33
7.1 Generals 7 Technical data VIO 12A
7 Technical data
7.1 General
RTD inputs 12
7.1.2 mA inputs
VIO 12AC VIO 12AD
mA inputs 4
Input range 0 – 25 mA
34 VVIO12A/EN M/B005
VIO 12A Technical data 7.2 Connections
7.1.3 mA outputs
VIO 12AC VIO 12AD
mA outputs 4
Output range 0 – 25 mA
PTC inputs 1
7.2 Connections
2
Maximum wire resistance 50 Ω per lead (corresponds to 2000m at 0,75 mm
copper wire)
Terminal block Phoenix MSTB or equivalent
2
Maximum wire dimensions 2,5 mm (13-14 AWG)
VVIO12A/EN M/B005 35
7.2 Connectionss 7 Technical data VIO 12A
36 VVIO12A/EN M/B005
VIO 12A Technical data 7.3 Tests and environmental
conditions
VVIO12A/EN M/B005 37
7.3 Tests and environmental 7 Technical data VIO 12A
conditionss
7.3.4 Casing
VIO 12AA VIO 12AB VIO 12AC VIO 12AD
Weight About 1 kg
38 VVIO12A/EN M/B005
VIO 12A Construction and mounting 8.1 DIN-RAIL mounting
VVIO12A/EN M/B005 39
8.2 Wall mountings 8 Construction and mounting VIO 12A
40 VVIO12A/EN M/B005
VIO 12A Construction and mounting 8.3 VAMP 40 mounting
VVIO12A/EN M/B005 41
9 Order information VIO 12A
9 Order information
When order, please state:
Type designation:
VIO 12AA, VIO 12AB, VIO 12AC or VIO 12AD
Quantity:
42 VVIO12A/EN M/B005
VVIO12A/EN M/B005
Customers Care Center
http://www.schneider-electric.com/ccc
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication version: VVIO/EN M/B005 02/2013