DESIGN CALCULATION FOR CW PUMP HOUSE

Basic Input:-
Grade of concrete M30
Grade of r/f Fe500
EL of Bottom of sump (CW Pump) -9.50
EL of Bottom of sump (ACW Pump) -5.10
EL of Bottom of raft (CW Pump) -10.70
EL of Bottom of raft (ACW Pump) -6.30
EL of finished Ground Level (FGL) -0.50
C/C distance between Piers (CW Pump) 5.40
THK of raft (CW Pump) 1.20
THK of raft (ACW Pump) 1.20
THK of pier 1.00
THK of back wall 1.00

Stability against Uplift


Case-I: Construction up to FFL

Uplift pressure due to water @ bottom of raft (CW Pump) pu = 10.20


So, total uplift in a CW Sump Panel (5.4X14.25M2) Pu = 784.89
Vertical load due to raft +back wall and pier Pv = 672.975

FOS 0.771672
M

M
M
M
M
M

T/m2
T
T