Project: Geotechnical investigation for proposed construction of 400KV GIS line Bays Extension(JSW

Energy Pvt Ltd) at Bellary district of KARNATAKA.

SBC CALCULATIONS FOR INDUSTRIAL BUILDING

Foundation strata: Silty Sandy Gravel


Structures INDUSTRIAL BUILDING
Reference Borehole BH-1 BH-1 BH-1 BH-1
Bed Level/Ground Level 476.490 476.490 476.780 476.780
Scour Level/Undisturbed GL 476.490 476.490 476.780 476.780
FGL 477.058 477.058 477.058 477.058
Foundation Level -0.932 -1.432 -2.222 -2.722
Thickness of overburden soil, m 0.932 1.432 2.222 2.722
Depth of excavation required, m 0.932 1.432 2.222 2.722
Width of foundation, m 2.00 2.00 2.00 2.000
SPT value of the soil in the zone of influence 18 22 16 20
Angle of Internal friction, Degrees 31 31 30 31
Unit weight of over-burden soil, kN/Cu.m. 18.00 18.00 18.00 18.000
Length of foundation, m 2.00 2.00 2.00 2.00
Shear strength of soil, kN/Sq.m. 0 0 0 0
Bearing capacity factor Nc 33.34 33.34 30.14 33.336
Bearing capacity factor Nq 21.38 21.38 18.40 21.380
Bearing capacity factor Ny 27.53 27.53 22.40 27.526
Depth factor, dc 1.16 1.25 1.38 1.48
Depth factor, dq 1.08 1.13 1.19 1.24
Depth factor, dy 1.08 1.13 1.19 1.24
Shape Factor, sc 1.20 1.20 1.20 1.20
Shape Factor, sq 1.20 1.20 1.20 1.20
Shape Factor, sy 0.60 0.60 0.60 0.60
Inclination Factor, ic 1.00 1.00 1.00 1.00
Inclination Factor, iq 1.00 1.00 1.00 1.00
Inclination Factor, iy 1.00 1.00 1.00 1.00
Water Table Correction Factor, w 0.50 0.50 0.50 0.50
Ultimate Bearing Capacity, UBC1, kN/Sq.m. 0.00 0.00 0.00 0.00
Ultimate Bearing Capacity, UBC2, kN/sq.m. 207.05 331.11 468.02 693.08
Ultimate Bearing Capacity, UBC3, kN/Sq.m. 71.50 74.42 64.11 81.95
Ultimate Bearing Capacity, UBC, kN/Sq.m. 278.55 405.53 532.13 775.03
SBC with a factor of safety of 2.5, kN/Sq.m. 111.42 162.21 212.85 310.01

This capacity is vetrified based on settlement criteria and calculations are provided
below.

Bearing Capacity Calculations


Project: Geotechnical investigation for proposed construction of 400KV GIS line Bays Extension(JSW
Energy Pvt Ltd) at Bellary district of KARNATAKA.

SBC CALCULATIONS FOR INDUSTRIAL BUILDING

Allowable SBC on the basis of Settlements are estimated in the following pages.
Foundation Strata = Silty Sandy Gravel
Ground Level = 476.780
Foundation Level = -0.932 RL
Depth Below Scour Level = 477.712 m
Minimum Dimension of Foundation = 2.00 m
Depth Correction Factor = 0.5006
Design SPT (Corrected as per IS: 2131) = 18
Refer Fig. No. 9 of IS:8009 (Part I) - 1976 =
For unit pressure, settlement = 12 mm
Water Table Correction Factor = 0.5
Depth Correction Factor =
0.5006
Rigidity Correction Factor = 0.8
Estimated Settlement after applying all factors =
9.6121 mm
Permissible Settlement = 25 mm
2
Allowable Pressure from settlements considerations =2.601 kg/cm
2
= 260 kN/m
2
SBC on shear failure criteria 162.21 kN/m
=
Hence, Allowable SBC = 150 kN/m2
Allowable SBC on the basis of Settlements are estimated in the following pages.
Foundation Strata = Silty Sandy Gravel
Ground Level = 476.780
Foundation Level = -2.772 RL
Depth Below Scour Level = 479.552 m
Minimum Dimension of Foundation = 2.00 m
Depth Correction Factor = 0.5006
Design SPT (Corrected as per IS: 2131) = 18
Refer Fig. No. 9 of IS:8009 (Part I) - 1976 =
For unit pressure, settlement = 12 mm
Water Table Correction Factor = 0.5
Depth Correction Factor = 0.5006
Rigidity Correction Factor = 0.8
Estimated Settlement after applying all factors = 9.612 mm
Permissible Settlement = 25 mm
Allowable Pressure from settlements considerations = 2.601 kg/cm2
= 260 kN/m2
SBC on shear failure criteria = 310.01 kN/m2
Hence, Allowable SBC = 250 kN/m2

Bearing Capacity Calculations