Rev. No.: 08
Dated: Aug/2017 EQUIPMENT / PIPING THICKNESS MEASUREMENT SHEET
SMP / WI No.: SMP-INSP-051
INSPECTION DEPARTMENT
Page: 1 of 1
Drowing/Sketch Thickness Thickness Reading
Orig. Remark(s)
Measurement (mm)
N 25-AIH-8232137-RE31O Location *
Thk.
(mm) 0 90 180 270 N E S W
(TMLs)
1-2ӯ 2.9
2-2ӯ 2.9
3-2ӯ 2.9
7
4-2ӯ 2.9
5-2ӯ 2.9
6-2ӯ 2.9
LINE # 25-AIH-8232155-RE31O
7-2ӯ 2.9
South of TE-8204
5
6

1 Thickness Gauge S.R. No. : GE DM5E (S/N: 1309726)


Insulation - No Calibration date : 23-DEC-2018
Scaffolding- 1 Probe # and Frequency : DK-537 - 5 MHz (S/N: 1835/58)
Applicable Procedure : PK SHEM 7.05 & SMP-INSP-051
Criteria for passing Inspection : API 570
Eqpt. / Piping Material : A-106 GRB
Corrosion Allowance (mm) : 1.2 mm
Corrosion Rate (mm / Year) : -
Remaining Life (Year) : -
Surface Temperature (ºC) : AMBIENT
Condition of Piping : Satisfactory X Unsatisfactory
Classification: Internal Use :
Recommendation (if any)

Plant : VCM – UNIT 82 Description : NEAR TE-8204 Inspector(s) : ADAM Date : 06/06/2019
Eqpt / Line No. : 25-AIH-8232155-RE31O Service : AIH KARTIK