Professional Documents
Culture Documents
Tech Note Dehumidification and The Psychrometric Chart Technical Bulletin DA103
Tech Note Dehumidification and The Psychrometric Chart Technical Bulletin DA103
1978
Technical Bulletin 3
49
14.5 CU. FT.
170
45
44
The curve forming the top edge of the chart is called the
43
160
B)
80
150
(B
140
moisture added could not be absorbed and would remain in a
75
130
PY
36
AL
TH
35
120
EN
The sweeping curved lines that follow the saturation curve are
34
RH
33
70
110
RH
31
100
30
RH
65
70
We 90
tB
28
26
RH
60
25
Te
mp 80
24
60
t RH e ra
y
di
%
23
e i
50 tur
rv m es 70
22
Cu55 Hu RH
21
on ve
%
40
ti i
lat
18
60
20
a
Figure 1 ur0 Re
17
at 5
19
S RH
16
% 50
30
15
45
14
12
40
40 RH
11
13
20%
10
12
35 30
9
30
8
25 H
10% R 20
7
0
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105
12.5 CU. FT. 13.0 CU. FT. DRY BULB °F 13.5 CU. FT. 14.0 CU. FT.
As the air temperature increases, its total volume increases This is important to understand because water damage
and decreases on reduction of temperature. Pressure has the occurs at an absolute humidity concentration regardless of its
opposite effect. As pressure increases volume decreases. relative humidity. This is known as the constant Dew Point
Temperature.
Water, however, is not compressible. Therefore given a specific
amount, it will always occupy the same amount of volume. S ENSIBLE AND LATENT HEATING AND COOLING
Figure 2 illustrates how this applies to the psychrometric
There are four types of energy changes when heat of moisture
chart. As moisture laden air is heated or cooled the air volume
is added or removed. Sensible heat occurs when heat is
changes but the moisture does not. Thus there is a change in
added without the addition or reduction of moisture. Sensible
relative humidity, without a change in actual water content.
cooling is the reverse. Latent heat, also known as humidification,
is the addition of moisture without changing the dry bulb tem-
perature. Latent cooling or dehumidification is the removal of
moisture. Figure 3 shows how these are displayed on the chart.
49
14.5 CU. FT.
48
85 90 95 100 105
180
47
92°F
46
70°F 78°F 44
45 170
43
160
B)
80
42
/L
TU
41
150
(B
40
N
IO
AT
39
140
R
TU
38
80% RH
SA
75
60% RH
37
AT
130
40% RH
Y
36
A LP
TH
35
120
EN
34
80
RH
33
70
%
90
110
60
RH
31
%
80
100
30
RH
%
88 GR.
29
65
70
90
28
26
RH
60
25
80
24
60
RH
%
23
50
70
%
22
Figure 2 55
RH
40
21
%
40
18
60
20
17
50
19
RH
16
% 50
30
15
45
14
12
40
40 RH
11
13
20%
10
12
35 30
9
30
8
25 H
10% R 20
7
10
0
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105
12.5 CU. FT. 13.0 CU. FT. DRY BULB °F 13.5 CU. FT. 14.0 CU. FT.
TECHNICAL BULLETIN 3
Dehumidification and the Psychrometric Chart
Rarely will these occur as shown but will rather be a mixture By obtaining the starting and finishing grains per pound, the
of them. A refrigerant dehumidification system is a combination amount of moisture to be removed can be calculated. The
of sensible and latent cooling and sensible heating. First the amount of moisture to be removed is the difference between
system cools the air to reduce the dry bulb temperature to the these two values known as GR.
dew point. Then latent cooling reduces the absolute humidity
and finally the air is reheated increasing its dry bulb temperature. Figure 5 shows how a dehumidification system was sized. The
Figure 4 graphs this process. ambient design was 91°F dry bulb and 78°F wet bulb. The
desired indoor value was 80°F dry bulb and 50% relative
D EHUMIDIFIER SIZING humidity. The outside ambient has a moisture content of 124
grains and the indoor design has 78 grains. Thus the required
To properly apply a dehumidification system, the amount of moisture removal rate is 124-78 = 46 grains per pound of dry air.
moisture to be removed must be calculated. For most applications
the only information available is the dry bulb and relative
humidity or dry bulb and wet bulb temperatures. The psy-
chrometric chart is used to plot these two values by finding
their intersection and then following the horizontal line to the
right to determine the moisture content in grains per pound.
49
14.5 CU. FT.
48
85 90 95 100 105
180
47
46
170
45
44
43
160
B)
80
42
/L
TU
41
150
(B
40
N
Figure 3
IO
AT
39
140
R
TU
38
SA
C
75
37
AT
B. Sensible Cooling
TH
35
120
EN
34
C. Humidification B A
RH
33
70
%
90
110
D. Dehumidification
RH
31
%
80
100
30
RH
%
29
65
70
90
28
26
RH
D
%
27
60
25
80
24
60
RH
%
23
50
70
22
55
RH
21
%
40
18
60
20
17
50
19
RH
16
% 50
30
15
45
14
12
40
40 RH
11
13
20%
10
12
35 30
9
30
8
25 H
10% R 20
7
10
0
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105
12.5 CU. FT. 13.0 CU. FT. DRY BULB °F 13.5 CU. FT. 14.0 CU. FT.
Figure 4
49
14.5 CU. FT.
48
85 90 95 100 105
180
47
46
170
45
44
43
160
B)
80
42
/L
TU
41
150
(B
QL = Latent Cooling A-C
40
N
TIO
39
RA
140
TU
38
SA
75
37
AT
130
PY
WB = Specific Humidity C (supply air)
36
AL
TH
QL
35
120
EN
34
T = Total Temperature Rise B-D
RH
33
70
%
90
110
QT
RH
A Entering Air WA
31
%
80
100
30
RH
%
29
65
70
QS
90
28
26
RH
%
27
60
25
80 ∆GR
24
60
RH
%
23
50
70
22
55
RH D
21
%
40
18
60
20
B C Reheated WB
17
50
% 50
30
Evaporator
15
45
Coil
14
12
40
40 RH
11
13
20%
10
12
35 30
9
30
8
25
10% RH 20
7
10
0
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105
12.5 CU. FT. 13.0 CU. FT. DRY BULB °F 13.5 CU. FT. 14.0 CU. FT.
∆T
49
14.5 CU. FT.
48
85 90 95 100 105
180
47
Figure 5 46
170
45
44
43
160
B)
80
42
/L
150
(B
40
N
TIO
39
7000
RA
140
TU
38
SA
75
37
AT
130
PY
91°F DB/78°F WB WA
36
AL
TH
4.5 = Constant
35
120
EN
34
RH
33
70
110
RH
∆GR
31
%
80
GR = WA-WB 100
30
RH
%
29
65
70
RH
%
27
60
25
%
50 80
24
60
H
%
R 80°F DB WB
50
23
70
22
55
RH
21
%
40
18
60
20
17
50
19
RH
16
% 50
30
15
45
14
12
40
40 RH
11
13
20%
10
12
35 30
9
30
8
25
10% RH 20
7
10
0
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105
12.5 CU. FT. 13.0 CU. FT. DRY BULB °F 13.5 CU. FT. 14.0 CU. FT.
103 2019/01